PART 1 - GENERAL
1.1
GENERAL
A.
B.
IEC 60076
Power transformers
IEC 60296
Specification for New Insulating Oils for Transformers
IEC 60076-10 Measurement of transformer and reactor sound level
IEC 60137
Bushings for alternating voltages above 1kV
IEC 60076-7 Loading guide for oil-immersed Transformers
This specification
Referenced codes and standards
Acceptable alternative codes and standards
C.
D.
E.
HV: 13.8 kV OR 33 kV
LV: 400 V OR 231 V at no load
Number of phases:
Frequency:
3
60 Hz
Volume II
261210-1
SECTION 261210
G.
Documentation
1.
With the commercial offer the bidder shall send the following
documents:
a.
b.
2.
Technical datasheet
Product Catalogue
After receipt of Purchase Order, the supplier shall submit to the owner
the following documents for approval.
a.
b.
c.
d.
e.
PART 2 - PRODUCTS
2.1
Rated power: The transformer shall be designed so that they can deliver
continuously its rated current under steady loading conditions without
exceeding their temperature rise, assuming that the applied voltage is equal to
the rated voltage and that the supply is at rated frequency.
B.
C.
Transformer Oil
1.
2.
D.
Bill of Lading
Manufacturers test certificates
Core assembly
1.
The core shall be constructed of the best quality, low loss, CRGO (cold
rolled, grain oriented) electrical steel laminations insulated on both
sides. The grade of electrical steel shall be at least M4 or better.
Following documents for electrical steel to be submitted during
inspection :
Volume II
261210-2
SECTION 261210
2.
3.
4.
E.
CRGO material must be new & PRIME Grade. Second grade or used
CRGO material is not acceptable.
Laminations shall be step lap overlapped to minimise core losses and
noise.
The assembled core shall be braced in suitable steel frames that make
up the base-frame and lifting facilities for complete transformer.
1.
2)
F.
3.
95
170
2.
Volume II
261210-3
SECTION 261210
s), without damage, under service conditions, the thermal and mechanical
effects of a short circuit at the terminals of any winding in line with IEC
60076-5.
G.
+5%
+2 %
0%
-2 %
-5%
of rated voltage
of rated voltage
of rated voltage
of rated voltage
of rated voltage
H.
I.
J.
Temperature Rise: At the rated power, the transformers shall comply with the
following maximum temperature rises:
Top Oil
50 C Max.
Winding
55 C Max.
Accordingly, Hot Spot temperature shall not exceed 98 C.
K.
L.
Earthing
1.
2.
M.
261210-4
SECTION 261210
6.
7.
N.
Type of transformer
IEC codes must be stated
Manufacturers name
Serial number
Year of Manufacture
Insulation Level
Number of phases
Rated power
Rated frequency
Rated voltage
Rated currents
Vector Group
Impedance voltage at rated current
Type of Cooling
Total Mass
Temperature rise of oil & winding
PART 3 - EXECUTION
3.1
Tank
A.
Tank Fabrication
1.
c.
2.
3.
Penetrant shall be applied on all welding joints and then the joints shall
be tested for any leakage by UV (Ultra Violet) rays.
Ready assembled transformers after oil filling shall be applied 1.25
times normal operating pressure and internal pressure shall be observed
for at least 2 hours. If there should not be any pressure drop during 2
hours, the tank can be assumed leak proof.
Volume II
261210-5
SECTION 261210
B.
c.
d.
e.
f.
C.
3.2
A 1000 hour salt spray (fog) test according to ASTM B-117 and
evaluated according to ASTM D-1654, Procedure A & B.
Adhesion test according to ASTM D-3359, Method B.
Testing
A.
Routine tests
1.
2.
B.
Type and special tests: Type or special tests may be available under request,
subject to prior agreement of the supplier:
1.
Volume II
261210-6
SECTION 261210
2.
3.
3.3
Inspection
A.
The purchaser may wish to witness tests or visit factory during manufacture of
any or all items covered in this specification. Accordingly, the supplier shall
give advance notice to the Purchaser of the manufacturing and test schedule.
Volume II
261210-7