Você está na página 1de 44

7100 Series Fire Alarm

Control Field Configuration


Program Setup Guide for
Windows
Document 9021-60554
01/13/2010
Rev:
P/N 9021-60554:A

A
ECN 10-006

Fire Alarm System Limitations


While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm systemtypically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capabilitycan provide early warning of a developing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System
Smoke Detectors, which are made available at no charge to all
installing dealers. These documents can be found at http://
www.systemsensor.com/html/applicat.html. A study by the
Federal Emergency Management Agency (an agency of the
United States government) indicated that smoke detectors
may not go off in as many as 35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or smoke from a developing fire
may not reach the sensing chambers of smoke detectors
because:

Barriers such as closed or partially closed doors, walls, or


chimneys may inhibit particle or smoke flow.

Smoke particles may become cold, stratify, and not reach


the ceiling or upper walls where detectors are located.

Smoke particles may be blown away from detectors by air


outlets.

Smoke particles may be drawn into air returns before


reaching the detector.

The amount of smoke present may be insufficient to alarm


smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).

Heat detectors do not sense particles of combustion and


alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:

Strobes can, under certain circumstances, cause seizures


in people with conditions such as epilepsy.

Studies have shown that certain people, even when they


hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.

In rare instances, the sounding of a warning device can


cause temporary or permanent hearing loss.

A fire alarm system will not operate without any electrical


power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Limit-C1-2-2007

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49
C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27 C/60-80 F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may


operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005

FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.

Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.

Gamewell-FCI, SmartScan, and E3 Series are registered trademarks of Honeywell International Inc. Echelon is a registered trademark and
LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are
registered trademarks of the Microsoft Corporation.
2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
(2010) with express permission from Adobe Systems Incorporated.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Table of Contents

Table of Contents
Section 1 ................................................................................................................................... 7
1.1: Introduction....................................................................................................................................................7
1.2: Methods to Configure the FCP-7100 Program ..............................................................................................8
1.2.1: General Output Lists............................................................................................................................8
1.2.2: Input and Output Groups .....................................................................................................................8
1.2.3: Conditional Action Maps (CAMs) ......................................................................................................8
1.3: Program Requirements ..................................................................................................................................9
1.3.1: Hardware .............................................................................................................................................9
1.3.2: Software...............................................................................................................................................9
1.3.3: Memory ...............................................................................................................................................9
1.4: Installation ...................................................................................................................................................10
1.4.1: USB Flash Drive Format ...................................................................................................................10
1.4.2: Internet Download .............................................................................................................................11
1.5: Starting the FCP-7100 .................................................................................................................................12
1.5.1: Welcome to FCP-7100 Project Wizard .............................................................................................12
1.5.2: Creating a New Project File...............................................................................................................13
1.5.3: System Password ..............................................................................................................................14
1.5.4: Opening Project Files ........................................................................................................................15
1.5.5: FCP-7100 Import Screen ...................................................................................................................16
1.5.6: FCP-7100 Main Menu Screen ...........................................................................................................17
1.6: Online Help System .....................................................................................................................................18
1.6.1: Overview ...........................................................................................................................................18
1.6.2: Entering the Online Help System ......................................................................................................19
1.6.3: Online Help Contents ........................................................................................................................19
1.6.4: Context Sensitive Online Help ..........................................................................................................19
1.6.5: System Status Map Online Help........................................................................................................20

Section 2 ................................................................................................................................. 21
2.1: Creating a Configuration File ......................................................................................................................21
2.2: Global Parameters........................................................................................................................................22
2.2.1: Program Globals Parameters .............................................................................................................22
2.2.2: Program Globals Miscellaneous Screen ............................................................................................23
2.3: Program Device Types.................................................................................................................................24
2.3.1: Defining SLC Devices.......................................................................................................................24
2.3.2: Assigning Output Devices to the General Output List ......................................................................25
2.4: Program Input Groups .................................................................................................................................26
2.4.1: Using Program Input Groups.............................................................................................................26
2.5: Program Output Groups...............................................................................................................................27
2.5.1: Program Output Groups Menus.........................................................................................................27
2.6: Program Cross Zones...................................................................................................................................28
2.6.1: Program Cross Zone Settings ............................................................................................................29
2.6.2: Defining Cross Zone Settings............................................................................................................29
2.6.3: Entering Labels..................................................................................................................................30
2.7: View General Output Lists ..........................................................................................................................31
2.7.1: View General Output List Screens ....................................................................................................31
2.8: FCP-7100 Options .......................................................................................................................................32
2.8.1: FCP-7100 Options Screen .................................................................................................................32

Section 3 ................................................................................................................................. 33
3.1: Conditional Action Maps (CAMs) ..............................................................................................................33
3.1.1: System Status Map (SSM).................................................................................................................33
3.1.2: Input Groups ......................................................................................................................................33
3.1.3: Output Groups ...................................................................................................................................34
3.1.4: CAM Logic Expressions ...................................................................................................................34
3.2: CAM Logic Operators .................................................................................................................................35
7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Table of Contents

3.2.1: AND (&) Gate ...................................................................................................................................35


3.2.2: OR (|) Gate.........................................................................................................................................35
3.2.3: Exclusive OR (XOR) (^) Gate...........................................................................................................35
3.2.4: NOT (~) Gate.....................................................................................................................................36
3.2.5: Parentheses ........................................................................................................................................36
3.2.6: Using the CAM Operators Menu.......................................................................................................37

Section 4 ................................................................................................................................. 38
4.1: Downloading the Project Files.....................................................................................................................38
4.1.1: Verifying the Password......................................................................................................................39
4.2: Printing the Project Files..............................................................................................................................40

Index ........................................................................................................................................ 42

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Section 1
1.1 Introduction
The Gamewell-FCI, 7100 Series Fire Alarm Control panel is a multiprocessor-based configurable
system. To program the 7100 Series System, a software program named, 7100 Series Field Configuration Program (FCP-7100), is provided with the system. The FCP-7100 Program allows users to
create, edit, print and download custom configuration programming files to the 7100 Series System. It also offers users full-featured programming and simplifies the structuring of the 7100 Series
System program configuration. Configurations may be generated offline or off-site, then, downloaded to the 7100 Series System.
By building a FCP-7100 program configuration, the 7100 Series System can provide the following
features.
Optimize sensitivity of the sensors for the time of days, nights, week-ends and holidays.
Record recent fire alarm incidents and performance in the System Event History Log.
Program output devices to activate when an event triggers a fire alarm device.
To create an FCP-7100 program, do the following in sequence:
1. Select a project file name. (See Section 1.5.4)
2.

Use the default settings or define custom global parameters for the program.
(See Section 2.2.1)

3.

Program device types and Input/Output Groups for each address. (See Section 2.3.1)

4.

Enter labels and modify the default settings for the Loop devices. (See Section 2.6.3)

5.

Define and program Input/Output Groups and Cross Zone Settings. (See Section 2.4.1,
Section 2.5.1 and Section 2.6.2)

6.

Download the configuration project file to the 7100 Series System. (See Section 4.1)

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Methods to Configure the FCP-7100 Program

1.2 Methods to Configure the FCP-7100 Program


You can use the FCP-7100 Program to configure the 7100 Series System by implementing input-tooutput relationships to respond to the system conditions.
For example, when a smoke detector (sensor-input device) goes into alarm, it displays on the 7100
Series fire alarm control panel. In the background, control modules (output devices) assigned to the
Input Group (that includes the same sensors), responds to the event (for example, triggering
elevator recall). If the alarm occurs during the day, the control module activates the panel to turn on
the General Outputs defined as a Day Alarm on the General Output List. This action then causes
the strobes or horns to go into alarm.
The input devices control the output devices using any of the following three methods:

General Output Lists

Input and Output Groups

Conditional Action Maps (CAMs)

1.2.1 General Output Lists


A General Output List is a method that allows you to define the response of each system output
device to the panels current condition or event. Each output device may be programmed to
activate under any combination of events or conditions. Output devices or modules (for
example, AOM-2Rs and AOM-2Ss) or built-in output devices, such as the Notification
Appliance Circuits (NAC circuits), can be programmed to activate under any of the following
events on a General Output List.
Day Alarm
Supervisory
Night Alarm
Walk Test/Drill
Trouble
Pre-Alarm Action
For example, if the Notification Appliance Circuits are linked to the Day Alarm and Night
Alarm events on the General Output List, the NACs will automatically activate upon an alarm
occurring during the scheduled day or night hours.
For additional information on output devices, refer to Section 2.3.2.

1.2.2 Input and Output Groups


Input and Output Groups is a method you can use to assign all individual input and output
devices in the 7100 Series program to one or more groups. An activation of any input device,
assigned to a group, automatically activates all output devices also assigned to that group.
For example, 10 sensors on SLC 1 could be assigned to Input Group 1, and 10 AOMs on SLC
1 could be assigned to Output Group 1. All output devices in Output Group 1 will activate
when Input Group 1 is triggered once any of its member sensors or AMMs are activated.
For additional information on input and output groups, refer to Section 3.1.2 and Section 3.1.3.

1.2.3 Conditional Action Maps (CAMs)


The Conditional Action Maps (CAMs) use information defined in the System Status Map
(SSM) to process logical results. A CAM is a collection of logic operations that takes input
from bit addresses in the System Status Map (SSM). The bit address numbers are referred to as
Groups throughout the FCP-7100 program.
Output devices on the 7100 Series fire alarm control panel can be assigned to a CAM
Controlled Output Group to enable full Boolean logic control. In this case, the output state
(active or inactive) is solely controlled by the CAM expression written for the selected output
group.
For additional information on Conditional Action Maps (CAMs), refer to Section 3.1.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Program Requirements

1.3 Program Requirements


This section describes the hardware, software and memory criteria required for the FCP-7100
Series Configuration Program for Microsoft Windows.

1.3.1 Hardware
The following list the hardware required for the FCP-7100 Program used with Microsoft Windows.

Pentium IV processor

Super VGA graphics card. (A screen resolution of 1024x768 or greater is recommended)

Microsoft compatible mouse or pointing device supported by Microsoft Windows

Windows-compatible printer (required for printing reports only)

RS-232 serial port

NOTE: Use the KeySpan model USA-19HS USB-to-Serial adapter if a built-in RS-232 port is not
available. For additional information, See the Technical Bulletin T08.2.

One available USB 2.0 port


(Two USB 2.0 ports are required if you use a USB-to-Serial adapter).

1.3.2 Software
The following list the software required for the FCP-7100 Program used with Microsoft
Windows.

An installed copy of Microsoft Windows 2000 or later.


(Windows XP recommended).

1.3.3 Memory
The following list the criteria required for the memory.

A minimum of 60 megabytes of hard disk space must be available for the installation of the
FCP-7100 Program.

The system must have at least 512 megabytes of RAM or at least the minimum of RAM
required by the installed version of Microsoft Windows (whichever is greater).

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Installation

1.4 Installation
Use the Installation Program to copy the required files to the hard disk and configure the computer.
There are two (2) installation formats available:

USB Flash Drive

Internet download

NOTE: Before you install this software, you must request Administrative privileges. Contact your
system administrator for assistance if needed.

1.4.1 USB Flash Drive Format


The following steps describe how to use the USB Flash Drive installation format.
1.

Connect the USB Flash Drive format (supplied by Gamewell-FCI) to an available USB port.

2.

Click on Start and select My Computer.

3.

Depending on the version of Windows installed on your PC, do one of the following:
Windows 2000
Double-click on the My Computer icon on the Desktop.
Windows XP
Click on the Start menu, and then click on My Computer.

4.

In the My Computer window, select one of the following icons and double-click the icon. No
matter which icon is present, the disk label appears as, GW-FCI_7100.

Figure 1.4.1.1 FCP-7100 USB


Flash Drive Icon
5.

Figure 1.4.1.2 FCP-7100 USB


Flash Drive Icon

Double-click on the menu.exe file.

NOTE: If the Hide File Extensions For Known File Types option is enabled in the Windows
Explorer, this file is labeled, menu.

6.

When the menu appears, select FCP-7100 as shown in Figure 1.4.1.3.

Figure 1.4.1.3 FCP-7100 Screen


7.

10

The Program Wizard appears and prompts you through the installation process.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Installation

1.4.2 Internet Download


The following steps describe how to use the Internet Download installation format.
1.

Access the Gamewell-FCI web site: http://www.gamewell-fci.com.

2.

Click the ESD Login link that appears below the Quick Links Section on the left side of the
screen.

3.

Click the Gamewell-FCI ESD Login link.

4.

Enter your user name, password and click OK.

5.

On the Engineered Systems Distributor screen, click Downloads.

6.

Click Software link.

7.

To begin the download, move the cursor below the 7100 Standalone FCP category and click
the link that appears below the Download column next to V7.00.16.
Depending on how you set your web browser settings, a File Download prompt may appear.
You can use any of the following options to select where the installer should be saved.
a.
b.

If the File Download prompt appears, select the Desktop so that you can quickly access
the file.
If no File Download prompt appears, then look at your web browsers settings to
determine where the system saves downloaded files.

8.

Unzip the FCP7100Setup-7.00.16.zip file.

9.

To run the installer, double-click the FCP7100Setup-7.00.16.exe file.

10. The Program Wizard appears and you can select the prompts to install.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

11

Starting the FCP-7100

1.5 Starting the FCP-7100


To start the FCP-7100 Program, you can select any of the following options.
Double-click on the FCP-7100 icon on the desktop.
Use the Start Menu, and select the following:
Programs (All Programs on Windows XP)//
Gamewell-FCI, FCP-7100 V7.00.16 folder
FCP-7100 V7.00.16 icon
.

NOTE: Use the FCP-7100 installer to choose where the programs Start Menu icons
should be placed. The Start Menu location above is the suggested default location that
is used by the Installer.

1.5.1 Welcome to FCP-7100 Project Wizard


The first time you access the FCP-7100 V7.00.16 program from your PC, the Welcome to FCP7100 Wizard appears. On this screen, you can select the folder to which you want to save or store
the new project files. The FCP-7100 has a project backup feature, when you open a project, a
system prompt appears and offers to backup a project. This feature also uses this location to store
the project file .
NOTE: To change the backup default setting, in the FCP-7100 Main screen, from the
Options Menu, select FCP-7100 Options.
1.
2.

3.

When you open the FCP-7100 Program, the Welcome to FCP-7100 screen appears.
The FCP-7100 Program displays a folder called, FCP-7100 Projects. The folder is located in
the current users My Documents folder. If you do not change the folder location, this folder
will be used by default to store new project files.
The user can select a location on either the computers hard drive or the network drive.
Since this location is used to store all project backups, it is recommended that this location be
always available. To select a different location, you can do either of the following:

4.

a. Enter the path to the selected location.


b. Use the Browse button to select the location to a Windows Explorer screen.
After you select the location to store the project file, click the <Next> button.

Figure 1.5.1.1 illustrates the Welcome to FCP-7100 screen and the Location selection field.

Step 1: Click the Browse


button to select the
location that you want
to store the project file.

Figure 1.5.1.1

12

Welcome to FCP-7100 Wizard

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Starting the FCP-7100

1.5.2 Creating a New Project File


To create a new FCP-7100 project file or database, select the New option from the File menu. A
New FCP-7100 Project Wizard screen appears.

Figure 1.5.2.1 FCP-7100 Project Wizard Screen


1.

On the FCP-7100 Project Wizard screen, enter a project name of no more than sixty-four (64)
characters in the Enter name of project: field.

2.

The FCP-7100 prompts the user for new projects to be saved in a default folder, which if it is
not changed by the user, is the FCP-7100 Projects folder located in the current users My
Documents folder.

NOTE: If you do not change this setting, the default folder, FCP-7100 Projects folder located in
the current users My Documents folder appears.

3.

To select a different location, click the Browse button.

4.

To continue once the project name is selected, click the Next> button.

5.

The FCP-7100 Program prompts the user to select a Level 4 password for this project. The
Level 4 password cannot be any of the system default passwords.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

13

Starting the FCP-7100

1.5.3 System Password


Before you create the project, the FCP-7100 Project Wizard screen appears.
1.

Enter a Level 4 Password for the new project.

2.

To create the new project, click the Finish button.

NOTE: Gamewell-FCI recommends you record the Level 4 Password, so that you can enter the
password in the Program Globals Access Code Screen. Before you download the program, you
must enter the Level 4 Password on the Access Code Screen. (See Section 4.1.1).

Figure 1.5.3.1 illustrates the System Password section of the FCP-700 Project Wizard screen.
.

Step 1: Enter the Level 4


Password.

Step 2: Click the


Finish button.

Figure 1.5.3.1 FCP-7100 Project Wizard System Password Screen

14

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Starting the FCP-7100

1.5.4 Opening Project Files


You can select to open the existing project file. To open the file, do the following:
1.

From the File Menu, select Open.

2.

The Select FCP-7100 Project File screen appears.

3.

On the Select FCP-7100 Project File screen, you can select the original project file or choose to
open a project file.

4.

After you select the project file, click the Open button.

5.

The system prompts you to make a back-up copy of this project file before making any
changes. To make a back-up copy, click Yes. Otherwise, click No.

6.

If you selected Yes, a message appears indicating the following:


Project 7100 Guide.71S was successfully backed up as Back up of 7100 Guide.71S
on 1-1-2010 at 11:30 am and stored in the following location. C:\Documents &
Settings\Folder.

7.

The system stores the Back-up file in the folder selected in either the "FCP-7100" or "Welcome
to FCP-7100" screens.

Figure 1.5.4.1 illustrates the original project file and back-up project files that appear on the Select
FCP-7100 Project File screen.

Figure 1.5.4.1 Select FCP-7100 Project File Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

15

Starting the FCP-7100

1.5.5 FCP-7100 Import Screen


If you created earlier project files in earlier versions of the FCP-7100 Program, the Welcome to
FCP-7100 Project Wizard accesses the Import Projects screen. Use the FCP-7100 Import screen to
import project files from the previous project file versions of the FCP-7100 program.
After you select the project files to which you want to import, click the Finish button.
NOTE: To access the Import feature, in the FCP-7100 main screen, from the File

Menu, select Import.


Figure 1.5.5.1 illustrates the FCP-7100 Import Screen.

Figure 1.5.5.1 FCP-7100 Import Screen

16

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Starting the FCP-7100

1.5.6 FCP-7100 Main Menu Screen


After you complete the Welcome to FCP-7100 screen, the FCP-7100 Program starts, and the FCP7100 Main Menu screen appears. Figure 1.5.6.1 illustrates the FCP-7100 Main Menu screen.

Figure 1.5.6.1 FCP-7100 Main Menu Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

17

Online Help System

1.6 Online Help System


1.6.1 Overview
The FCP-7100 Program provides an Online Help System that is designed for users to either access
a quick reference online help screen or print a user-manual for the FCP-7100 Configuration
Program. You can access the online help from any screen in the FCP-7100 Program. To access the
online help from the screen, press the <F1> key. There are two options available to view the online
help.

Online Version
The online help version appears on the left side of the screen. To view the navigation tree, click
the Contents tab. Then, click the hyperlinks to access the online help topic. To search for a
topic, click the Search tab. In the Type in the words to search for field, enter the word you
want to search. Click the List Topics button and the Display button to view the online help.

Printed Version
To print the Online Help, you have the following options:
To print the selected topic or all the topics in the heading, click the Print icon on the toolbar.
From the Help Menu, select the Printable Documentation.

NOTE: To open and print the Printed version, use the Adobe Acrobat Reader.

Figure 1.6.1.1 illustrates the Online Help Contents and Search navigation screens.

Figure 1.6.1.1 Online Help Navigation Screens

18

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Online Help System

1.6.2 Entering the Online Help System


The following list the ways to access the Online Help System from the Main Menu:

Click on Help in the Main Menu. Click on the Show Help Contents Menu item.

Click on Help in the Main Menu. Click on the Printable Documentation Menu item.

To open an Adobe Acrobat version of the FCP-7100 Program help documentation, click the
Printable Documentation icon. (The Adobe Reader or a similar PDF reader software is
required).

Press the <F1> key on the keyboard.

1.6.3 Online Help Contents


The FCP-7100 Online Help System is organized into the following sections:
Section Title
General

Basic steps in creating a


7100 Configuration File
How Do I?

Main Menu Items

CAM Programming Examples

Advanced CAM Programming

Description
The General Section describes the 7100 System and
provides information about the systems general I/O
configuration concepts.
A Getting Started guide to walk new users through the
steps to start a new configuration file.
This feature provides quick reference information that
describes how to accomplish certain tasks in the
FCP-7100 Program.
This Menu is a comprehensive guide to every screen in
the FCP-7100 Program and provides information about
all available configuration options.
This Section gives examples for using Conditional
Action Map (CAM) logic to accomplish common
applications.
This Section includes information that details the use of
the low-level CAMs and describes how to access functions that are not available in the normal CAM windows.

1.6.4 Context Sensitive Online Help


To access the Online Help from a screen in the FCP-7100 System, open the appropriate entry
screen and press the <F1> key. This screen displays specific Online Help for the current screen. A
description of each programmable option for the screen appears.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

19

Online Help System

1.6.5 System Status Map Online Help


The FCP-7100 System contains a comprehensive reference list of the 7100 Series System Status
Map (SSM). Use this reference list when you write CAM expressions. To access the reference list,
select any of the following options:

Click on Help in the Main Menu. Click on the System Status Map Menu item.

In the CAM entry screen, click on the System Status Map button.

In the Advanced CAM Programming screen, from the Main Menu click on Help. Click on the
System Status Map Menu item.

Figure 1.6.5.1 illustrates the Online Help for the 7100 Series System Status Map.
.

Figure 1.6.5.1 FCP-7100 System Status Map Help Screen

20

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Section 2
2.1 Creating a Configuration File
Table 2.1.1 describes the steps required to create a typical 7100 Series Configuration File. For
additional information on all programmable options for each screen, refer to the Online Help for
that particular screen. To create a file, select the following steps in sequence.

NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

1.
2.
3.

4.

Menu
File/New
Program Globals
Parameters
Program Devices

Description
Create a new project.
From the Globals drop down Menu, select the appropriate menu
option you want to use.
From the Program Devices Menu, select the Define Device Types or
Groups.
All device types and groups can be configured in this section.
To program other sensor/module options, (for example, labels) select
the Sensors or Modules Parameters submenus.
Program Input Groups Program all input group options.
Table 2.1.1 Configuration File Screens

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

21

Global Parameters

2.2 Global Parameters


In the 7100 Series System, there are global programming options that are initialized to default settings when the project was created. Although you can use the default settings for the 7100 Series
panel configuration, you can modify the default settings to create a custom configuration. Use the
Global Parameters feature to define global parameters for the following types of system conditions,
events, and programming options.
Device Defaults
User Defined Device Types
NAC Settings
Miscellaneous Globals
Coded Patterns
Zone Code Table
Night/Weekday/Holiday Schedule
LED Annunciator Labels
Passwords
Dialer (DACT)

2.2.1 Program Globals Parameters


Table 2.2.1.1 lists the global parameters that you can define, and the screen that appears when you
select the parameters. To define Global Parameters, from the Global Parameters screen, select the
Global parameters that you want to assign to the features.
Gobal Parameter

Menu Screen

Device Defaults

Globals...Device Defaults Screen

NAC Settings

Globals...NAC Settings Screen

Coded Patterns

Coded Pattern Screen

Night/Weekend/Holiday

Night/Weekend/Holiday Screen

Password

Globals...Passwords Screen

User Defined Device Types

User Defined Device Types Screen

Miscellaneous

Globals...Miscellaneous Screen

Zone Code Table

Zone Code Table Screen

LED Annunciator Labels

LED Annunciator...Labels Screen

Dialer (DACT)

There are (3) options:

Globals DACT Test...Timing

Globals...DACT Phone Line Options

DACT Account Options

Table 2.2.1.1 Global Parameters and Screens


NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

22

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Global Parameters

2.2.2 Program Globals Miscellaneous Screen


Use the Program Globals Miscellaneous screen to select the panel-wide options that you want the
program to activate.
For example, if you want the program to activate the DACT, click the Enable DACT checkbox.
Figure 2.2.2.1 illustrates the Program Globals Miscellaneous screen with the following options
selected.

Enable DACT

Trouble Reminder

Enable Front Panel Programming

Figure 2.2.2.1 Program Globals Miscellaneous Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

23

Program Device Types

2.3 Program Device Types

Use the Program Devices Types Menu to define device types, address and input groups to link to
events that appear on the General Output List. The 7100 System is configured as either a one or two
Loop system. There are a total of 197 addresses available for programming on each Loop. The
following are the Program Device Types and the number of addresses assigned to each device type.
Sensors
Sensors are input devices. The sensor device addresses for each loop include 1-99 addresses.
Modules
There are two basic types of modules supported by the 7100 System. These types are as
follows:
Addressable Monitor Modules (AMMs)
AMMs are input devices that can be configured to provide several different system
responses, such as Alarm or Supervisory.
Addressable Output Modules (AOMs)
AOMs are output devices. These devices may be either Form-C Relay Modules or Signal
Modules which can control the NAC or Speaker circuits.
The output device addresses for each Loop include 1-98. Module address 99 on each Loop is
reserved.

2.3.1 Defining SLC Devices

To define the device types, address and input groups, do the following:
1. On the FCP-7100 screen, select the Program Devices Menu.
2. From the Program Devices Menu, select Define Device Types. You can select either Sensors or
Modules.
2.A.If you select Sensors, the Define Types...Sensors screen appears. In the Select Device
Type field, you can choose the types of sensors you want to add to a Group.
2.B. If you select Modules, the Define Types...Modules screen appears. In the Select Device
Type field, you can choose the modules you want to add to a Group.
3. In the Check Addresses to Program section, check the addresses that you want to assign to the
device type you selected in the Select Device Type field.
4. Click the Program button to assign the device types and the addresses.
5. After you click the Program button, the address numbers assigned to the device type appear in
red.
NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu..

Figure 2.3.1.1 illustrates the steps required to select a sensor and assign addresses to the device
types.
S tep 1. S elect the
device .
S tep 2. C heck the
A ddresses .

S tep 3. C lick P rogram .

Figure 2.3.1.1 Program Devices Screen


24

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Program Device Types

2.3.2 Assigning Output Devices to the General Output List


To assign the output devices to the General Output List, do the following:
1A. Module Parameters (AOMs)
1.A.1. From the Module Parameters screen, select AOMs.
1.A.2. The Program Device...AOMs screen appears. To assign General Output Lists to the
devices, click the appropriate checkbox.
1B. NAC Parameters
1.B.1. From the Program Globals...NAC Settings Menu, select Program Globals, and then
NAC Settings.
1.B.2. The NAC Settings screen appears and you can assign General Output Lists to either
NAC circuit or the Municipal Circuit.
Figure 2.3.2.1 illustrates an example of assigning events on the General Output List for AOM
output devices.
Check the Output Devices you
want to assign to the AOMs.

General Output List

Figure 2.3.2.1 AOM Parameters Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

25

Program Input Groups

2.4 Program Input Groups


Input Groups are groups of input devices (for example, pull stations) that are assigned to groups
that are intended to trigger common outputs. There are 1-99 Groups. The Input Group
configuration allows you to enable or disable the following:
General Condition responses of the inputs associated with the group.
Group cross zones and one or more LED annunciators for each input group.

2.4.1 Using Program Input Groups


To assign program input groups to cross zone functions or activate an LED function, do the
following:
1. From the Program Input Groups menu, select Group options.
2. The Group Options screen appears. This screen is divided into two sections.
1-99 Groups Section
Members Input Group Section
2.A.1-99 Groups Section
2.A.1.The 1-99 Groups Section appears on the top half of the screen.
2.A.2.On the 1-99 Groups Section, when you move the cursor over the field to which you want
to select, the row appears highlighted in gray on the top and bottom sections.
2.A.3.In the 1-99 Groups Section, on the following fields, click in the radio button to select
your option.
Group
Activate General Alarm
Activate General Supv
2.A.4.Click inside the following fields to access the drop down list and select your option.
GroupX-z
PrgLED1
PrgLED2
PrgLED3
2.B.1.Members Input Group Section
2.B.1.In the 1-99 Section, when you move the cursor to the selected Group number, the
selected Group information automatically displays in the Member Input Group section.
NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 2.4.1.1 illustrates the Program Input Groups screen.


Select Group Cross
Zone Number

Select Programmable LED for Group

Group 1-99 Section


Move the cursor to
the Group 1 field,
the row appears
highlighted in gray.

Drop-Down List

Members...Input
Group 1 Section
The same Group 1
displays highlighted
in gray.

Figure 2.4.1.1 Program Input Groups Screen


26

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Program Output Groups

2.5 Program Output Groups


Output Groups are output devices (for example, relay modules) assigned to groups that can be
programmed to activate when a panels system condition (for example, Day Alarm) is triggered.
Use the Program Output Groups Menu to define output groups for the following types of system
conditions, events, and programming options.
Timers for Output Groups/Scratchpads
CAMs for Reset Inhibit
CAMs for Output Groups
Advanced CAM Programming
CAMs for Scratchpad Locations

2.5.1 Program Output Groups Menus


Table 2.5.1.1 lists the Program Output Groups that you can define and the Menu screens that appear
for each Program Output Group.
Program Output Group
Timers for Output Groups/Scratchpads

Menu Screen
Set Timers for 7100 Output Groups And Scratchpads

CAMs for Output Groups

CAMs for 7100 Output Groups

CAMs for Scratchpad Locations

CAMs for 7100 Scratchpads

CAMs for Reset Inhibit (See Note 1)

CAMS for 7100 Reset Inhibit

*Advanced CAM Programming (See Note 2) Advanced CAM Programming

Table 2.5.1.1 Program Output Groups Menu Screens


NOTE 1:For the CAMs for Reset Inhibit to function, Firmware Version 7.1-001 or later is required.

NOTE 2:For information on the low level Advanced CAM Programming, refer to the Help Menu in
the Advanced CAM Programming screen.

Figure 2.5.1.1 illustrates an example of the CAMs for the 7100-Output Groups screen.

Figure 2.5.1.1 CAMs for 7100 Output Groups Screen


NOTE: For detailed information on CAM programming, use the Online Help. To access the
Online Help, do either of the following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

27

Program Cross Zones

2.6 Program Cross Zones


The Program Cross Zones screen allows the user to configure the twenty-five (25) cross zones in
the 7100 System. There are two types of cross zones to configure.
Group Cross Zoning
Group Cross Zoning are input groups linked directly to a cross zone. When any device in an
input group goes into alarm, that one device counts towards the cross zones trigger level. If
another smoke detector in the same input group goes into alarm, the smoke detector in that
input group will not increase the trigger count. The cross zone trigger level increases only if a
smoke detector is a member of a different input group. The trigger level is the number of inputs
required to cause the cross zone to activate.
For example, if the first detector goes into alarm, the panel displays Action. If the second
detector goes into alarm, the panel triggers the cross zone alarm.
Point Cross Zoning
Point Cross Zoning are a collection of individual points configured into a virtual cross zone
group. It provides a two-stage alarm condition. The first alarm in the virtual group initiates an
Action condition. The second alarm is triggered when the number of alarms in the virtual cross
zone group reach the pre-set trigger-level.
The following settings can be defined for each cross zone.
Cross Zone Group
Enable Multiple Point Cross Zone Activations When the
System is in Alarm
Zone Code
List View
Activate General Alarm
NOTE: For detailed information on cross zoning, use the Online Help. To access the Online
Help, do either of the following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

28

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Program Cross Zones

2.6.1 Program Cross Zone Settings


Use the Program Cross Zone Settings screen to view the cross zone settings and trigger groups you
defined in the Program Input Groups screen. Define cross zones for facility environments that
include sensitive equipment. Table 2.6.1.1 lists the Cross Zone Settings features.
Cross Zone Setting
Cross Zone Group
Zone Code
Activate General Alarm
Enable Multiple Point Cross Zone Activations When System is in Alarm
List View

Table 2.6.1.1 Program Cross Zone Settings

2.6.2 Defining Cross Zone Settings


To define Cross Zone Settings, do the following:
1. In the Sensor Parameters screen, add at least one input group to each sensor that is part of a
Group Cross Zoning.
NOTE: Although you can assign more than one sensor to the same group, multiple sensors in
the same group will count only as one alarm input toward the activation threshold. Use Group
cross zones to collect multiple group assignments into a virtual group cross zones.

2.
3.
4.

To save the configuration, close the Sensor Parameters screen.


From the Program Input Groups Menu, select Group Options.
On the Program Input Groups Options...Screen, select the Cross Zone number in the Group
XZ field for each member input group.
5. To save the selections, close the Group Options screen.
6. From the Program Cross Zones Menu, select the Configure Cross Zones.
7. On the Cross Zone Table screen, select the desired options for each virtual cross zone group.
For example, you can define Program Cross Zone Settings to appear on the screen, if you entered a
number in the GroupXZ field of the Program Input Groups...Options screen.

NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 2.6.2.1 illustrates the Cross Zone Table screen.

Figure 2.6.2.1 Cross Zone Table Screen


7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

29

Program Cross Zones

2.6.3 Entering Labels


To enter labels for each loop device, do the following.
1. From the Program Devices Menu, select the screen that includes the device type to which you
want to enter a label. You can select any of the following device types.
Sensors
Ion detectors
Photo Detectors
Thermal detectors
Modules
Addressable Output Modules (AOMs)
2.

3.

Addressable Monitor Modules (AMMs)

On the screen that includes the device type you want to enter a label, in the Description field
enter the label description.
You can enter a label description of up to 19 characters in length.
To save the information, click the Close button to close the screen.

NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 2.6.3.1 illustrates the label name entered in the Description field on the Program
Devices...AOMs screen.
Step 1: Enter the Label
Description.

Figure 2.6.3.1 Program Devices...AOMs-Label Description

30

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

View General Output Lists

2.7 View General Output Lists


The View General Output Lists Menu displays all output devices that appear on the General Output
Lists.The following events can be defined on the General Output Lists.
Alarm Day
Trouble
Alarm Night
Action
Supervisory
Walk Test

2.7.1 View General Output List Screens


The View General Output List screen displays the settings that you defined in the General Output
List in the Program Globals Menu. Table 2.7.1.1 lists the View General Output List screens.
View General Output Lists

Menu Screen

Alarm Day

General Output List-Alarm Day

Alarm Night

General Output List-Alarm Night

Supervisory

General Output List-Supervisory

Trouble

General Output List-Trouble

Action

General Output List-Action

Walk Test

General Output List-Walk Test

Table 2.7.1.1 View General Output Lists Screens and Functions


NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 2.7.1.1 illustrates a sample of the General Output List...Alarm Day screen.

Figure 2.7.1.1 General Output Lists-Alarm Day Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

31

FCP-7100 Options

2.8 FCP-7100 Options


The FCP-7100 Options screen allows you to configure the following:
New Project Locations
Project Backups

2.8.1 FCP-7100 Options Screen


Use the FCP-7100 Options screen to do the following:
Store new project files to the hard drive.
Create project files backup each time a project file is opened.
Table 2.8.1.1 lists the features on the FCP-7100 Options screen.
FCP-7100 Option Sections
New Project Locations
Backup Options
Miscellaneous

Table 2.8.1.1 FCP-7100 Options Screen


NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 2.8.1.1 illustrates the FCP-7100 Options screen.

Figure 2.8.1.1 FCP-7100 Options Screen

32

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Conditional Action Maps (CAMs)

Section 3
3.1 Conditional Action Maps (CAMs)
In the 7100 FACP System, there is a key programming feature called, CAM logic. This feature
enables the program connection between input groups (i.e., smoke detectors) and output groups
(i.e., relay switches). The input and output groups use bitmap coding based on the information
located in the System Status Map (SSM). A bitmap is a map of certain status flags, such as General
Alarm or Silenceable Outputs Active. This process is accomplished by using the Conditional
Action Map (CAM) logic. CAM logic is an optional method that allows the user to define
input/output relationships. You can also create direct input/output groups to be linked together.
A CAM is a collection of logic operations that takes input from bit addresses in the System Status
Map (SSM). The CAM modifies other System Status Map (SSM) bit addresses on the basis of the
results. The bit address numbers are referred to as Groups throughout the FCP-7100 Program.
On the 7100 Series System, Groups 125-224 are associated with the Output Group control.
For example, the true or false result of a CAM logic expression is used to control the associated
output group that can cause the physical device to turn on or off.

3.1.1 System Status Map (SSM)


The System Status Map (SSM) displays bitmaps that represent the following types of conditions or
events:

Alarm Groups
Trouble Groups
Common Mode Status
(General faults that occur with the panel)

Condition Flags
Input/Output Groups

The Input/Output Group numbers are simply aliases for the SSM bit addresses. The CAM logic on
a given panel can use any group (bit address number) in the entire SSM as part of a CAM logic
expression. For standalone 7100 Systems, all CAMs must refer to the 7100 panel as Node 0.

3.1.2 Input Groups


Input groups are alarm devices (for example, smoke detectors) that control output devices (for
example, relay controls). You can control outputs by creating General Output Lists, Input/Output
Groups or CAM controlled output groups. Each input device on the 7100 panel may be
programmed to trigger up to two local groups. In the System Status Map (SSM), these input groups
are labeled bit addresses and are assigned to the following two types of events.
Events
Alarm Bit #
Trouble Bit #

Groups
Input Group bit addresses (Group #s 1 to 99)
Input Group bit addresses (Group #s 101 to 199)

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

33

Conditional Action Maps (CAMs)

3.1.3 Output Groups


Output Groups are output devices (for example, relay controls) that are activated by an input group
(for example, pull station). Each output device may be configured to be activated by three outputs,
ten output groups or CAM controlled ouput groups. When an output group is activated by an input
group, the output group transmits an assigned System Status bit. The output groups are labeled bit
addresses and are assigned to the following two types of events
Events
Control Bit #
Trouble Bit #

Groups
Output Group bit addresses (Group #s 300 to 399)
Output Group bit addresses (Group #s 200 to 299)

NOTE: For additional information on the System Status Map (SSM), refer to the Online Help
Menu and select the System Status Map.

3.1.4 CAM Logic Expressions


A CAM logic expression consists of at least one instruction. However, a more typical CAM
expression includes several operands and one or more CAM logic operators (i.e., AND, OR, XOR,
NOT). The evaluation of these expressions is used to control the appropriate output. Each CAM
logic operator is given its own "symbol" in the FCP-7100 Program. Table 3.1.4.1 describes the
logic symbol conventions used by the FCP-7100 Program.
To add the CAM Logic Operator Symbol,
Symbol: enter the following keys
&
SHIFT-7 (standard 7)
|
SHIFT-\ (usually located above the <ENTER>
key)
NOT
~
SHIFT-` (located to the left of the 1 key)
XOR (Exclusive OR)
^
SHIFT-6 (standard 6)
Table 3.1.4.1 CAM Logic Operator Symbols
Logic Operator:
AND
OR

34

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

CAM Logic Operators

3.2 CAM Logic Operators


CAM Logic uses the following four logic operators that are labeled as follows:

AND
OR

Exclusive OR (XOR)
NOT

These operators are sometimes referred to as Gates. Gates is the term used for a hardware circuit
that performs a logic function. Section 3.2.1 thru Section 3.2.5 includes a short description of each
CAM Logic Operator.

3.2.1 AND (&) Gate


Use the AND Gate when it takes more than one input for an output to be TRUE on a CAM logic
expression.
For example, when two inputs are entered into the AND gate, the output is always FALSE (0).
However, if both inputs are TRUE (1), then the output of the AND Gate is TRUE. Table 3.2.1.1
lists a truth table for the AND gate:
A
B
A AND B
0
0
0
0
1
0
1
0
0
1
1
1
Table 3.2.1.1 AND Gate Truth Table

3.2.2 OR (|) Gate


Use the OR Gate if any one input is TRUE, then the output is TRUE on a CAM logic expression.
For example, when two inputs are entered into the OR gate, the output is always TRUE (1) unless
both inputs are FALSE (0), then the output is FALSE (0).
Table 3.2.2.1 lists the truth table for the OR gate:
A
B
A OR B
0
0
0
0
1
1
1
0
1
1
1
1
Table 3.2.2.1 OR Gate Truth Table

3.2.3 Exclusive OR (XOR) (^) Gate


Use the Exclusive Or (XOR) Gate if the inputs are the same, then the output is FALSE. To get a
TRUE output only one input can be TRUE on the CAM logic expression.
For example, when two inputs are entered into the XOR gate, the output is TRUE (1) when only
one of its inputs are TRUE (1).
Table 3.2.3.1 lists the truth table for the XOR gate:
A
B
A XOR B
0
0
0
0
1
1
1
0
1
1
1
0
Table 3.2.3.1 XOR Gate Truth Table
7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

35

CAM Logic Operators

3.2.4 NOT (~) Gate


Use the NOT Gate when you want the bit to be the opposite on the CAM logic expression. When an
input is entered into the NOT gate, the output is the opposite of that input.
For example, if the input is TRUE (1), the output is FALSE (0). If the input is FALSE (0), the
output is TRUE (1).
Table 3.2.4.1 lists the truth table for the NOT gate:
A
NOT A
0
1
1
0
Table 3.2.4.1 NOT (~) Gate Truth Table

3.2.5 Parentheses
Use parentheses to define two (2) logic operators that combine a sequence of events. Although
parentheses are not logic operators, parentheses are useful in constructing logic expressions. Use
parentheses to break down complex CAM logic expressions into manageable pieces. Parentheses
can also be used to explicitly define the order that a CAM logic expression is evaluated. For
example, Table 3.2.5.1 is an example of a CAM logic expression without parentheses and with
parentheses.
First Sample CAM Logic Expression (without Parentheses)
1st CAM Expression
with OR Gate
2nd CAM Expression AND Gate

3rd CAM Expression

N0G1|

N0G3

N0G2

&

The FCP-7100 program first evaluates the N0G2 & N0G3 terms. Then evaluates the OR
result with the N0G1 term.
Second Sample CAM Logic Expression (with Parentheses)
OR Gate
1st CAM Expression

AND Gate
(2nd CAM Expression)

3rd CAM Expression

((N0G1|
N0G2)
&
N0G3)
The FCP-7100 program first evaluates the N0G1 OR N0G2 terms. Then ANDs the output
of the first terms with the term.
Table 3.2.5.1 Parentheses Truth Table

NOTE: Gamewell-FCI recommends you use parenthese to combine a sequence of CAM Logic
Expressions.

36

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

CAM Logic Operators

3.2.6 Using the CAM Operators Menu


From the CAMs for Output Groups screen, you can use the CAM Operators Menu to add CAM
Operator symbols to the CAM Expression. To access the CAM Operators Menu, do the following:
1.

From the Program Output Groups Menu, select CAMs for Output Groups.

2.

The CAMs for Output Groups screen appears. On this screen, select the Edit CAM button.

3.

On the top of the screen, move the cursor over the word, CAM, and right-click to open the
CAM Operators Menu.

4.

From the CAM Operators Menu, select the CAM operators you want to add to build the CAM
expression.

5.

After you select the CAM Operators, the CAM symbols appear in the CAM Expression field.

6.

Click the Save button and the CAM operators automatically change to the CAM symbols.

7.

To cancel the selection, click the Cancel button and the system returns to the previous
selection.

NOTE: For detailed information, use the Online Help. To access the Online Help, do either of the
following:
Select the screen that you want to view the Online Help and press the <F1> key.
Access the Help Menu.

Figure 3.2.6.1 illustrates the steps required to access the CAM Operators Menu.

Figure 3.2.6.1 CAMs for 7100 Output Groups Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

37

Downloading the Project Files

Section 4
4.1 Downloading the Project Files
After you define the input and output devices, you can download the project files. To download the
program configurations, use an RS-232 connection between the PC/Laptop and the 7100 Series fire
alarm control panel. To download a Configuration File to the 7100 System, refer to the following
steps.
1.

Plug-in the Download cable into J3 of the 7100 System main board.

2.

From your PC desktop, access the FCP-7100 Program icon.

3.

On the FCP-7100 Program screen, from the File Menu, select the Download Panel option.

4.

The Download FCP-7100.71S screen appears.

Figure 4.1.1 illustrates the Download screen.

Figure 4.1.1 Download FCP-7100.71S Screen


5.

On the Download screen, enter the COM port to use in the Select COM Port field.
The COM port may range from COM1 to COM64.

The user may also choose to skip downloading portions of the configuration. There are two
scenarios where this feature may prove most useful:
Skipping Device Labels
If no changes have been made to the SLC device labels or the System ID label, the user may
uncheck the Download Device Labels option. The entire block of labels will not be
downloaded to the panel. This feature descreases the amount of time necessary for the
download.
Downloading only CAMs
If the user has made changes to only the panels CAM expressions, the user may uncheck
both the Download Device Labels option and the Download Configuration option. This
feature creates an extremely fast download.

38

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Downloading the Project Files

4.1.1 Verifying the Password


1.

To begin the download, click on the Download command button.

2.

For the panel to accept the download, enter the panels current Level 4 password.

NOTE: The Level 4 password is the password that is currently in the panel. The passwords that
were entered in the System Password section of the FCP-7100 Project Wizard or emtered on the
Passwords screen will take affect only upon completion of a configuration download.
(See Section 1.5.3).

3.

If you enter an invalid password, a prompt appears and you cannot download to the panel.

4.

The FCP-7100 program automatically records the date and time of the last CAM, Label and
Configuration downloads.

5.

The date and time appears in the grid in the Download window.

Figure 4.1.1.1 illustrates the Access Code screen that appears on the Download FCP-71S screen.

Figure 4.1.1.1 Access Code Screen

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

39

Printing the Project Files

4.2 Printing the Project Files


The FCP-7100 program offers the option to Print project file reports. The following list the steps
required to print project reports.
1.

To print the project file reports, from the File Menu, click on Print.

2.

The Print Reports screen appears.

3.

By default, all available reports appear for printing. However, to choose the desired reports,
click the Select checkbox next to the name of the report.

4.

A check mark in one of the checkboxes indicates that a report is selected. After you select the
reports, click the To Printer button to begin printing the reports.

NOTE: Some reports may appear to be unavailable (grayed out) if those reports do not contain
information. For example, the Sensors Report will be unavailable if no Sensors have been
assigned.

NOTE: A Windows printer must be configured properly to use this feature. In addition, the
printout will be sent to the printer that has been selected as the "default" in the Windows Control
Panel.

Figure 4.2.1.1 illustrates the Print Reports screen.

Figure 4.2.1.1 Print Reports Screen

40

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Printing the Project Files

Notes

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

41

Index
Numerics
7100 Series System 7

A
Addresses 24

C
CAM Expressions
Parentheses 36
CAM Logic Operators
AND (&) Gate 35
Exclusive OR (XOR) (^) Gate 35
NOT (~) Gate 36
OR (|) Gate 35
CAM Operators Menu 37
Conditional Action Maps (CAMs) 8
Cross Zoning
Group 28
Point 28

System Status Map 20

P
Program Device Types
Modules 24
Sensors 24
Program Output Groups 27
Program Requirements
Hardware 9
Memory 9
Software 9
Project Files
Creating Backups 15
Importing 16
Opening 15
Printing Reports 40

Devices
Input 8, 24, 26
Loop 30
Output 8, 24, 25, 27, 31

System Password 14
System Status Map
Alarm Groups 33
Common Mode Status 33
Condition Flags 33
Input/Output Groups 33
Trouble Groups 33
System Status Map (SSM) 33

FCP-7100 7
Project Backup 15

Truth Tables
AND Gate 35
NOT (~) Gate 36
OR Gate 35
XOR Gate 35

G
Gates 35
General Output List
Module Parameters 25
Global Parameters 22

U
USB Flash Drive 10

I
Input and Output Groups 8
Input Device
Monitor Modules 24

L
Labels 30

O
Online Help
Contents 19
Overview 18
42

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

Manufacturer Warranties and Limitation of Liability


Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER
INCLUDING
WITHOUT
LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replaces all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will prevent any loss
by fire or otherwise.
Warranty Claims.
Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.

Warn-HL-08-2009.fm

7100 Series Fire Alarm Control Field Configuration Program Setup Guide P/N 9021-60554:A 01/13/2010

43

Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.gamewell-fci.com

Você também pode gostar