3500/42M Proximitor*/Seismic Monitor

Bently Nevada* Asset Condition Monitoring


Description
The 3500/42M Proximitor/Seismic Monitor is a 4-channel monitor that accepts
input from proximity and seismic transducers, conditions the signal to provide
various vibrations and position measurements, and compares the conditioned
signals with user-programmable alarms. The user can program each channel of
the 3500/42M using the 3500 Rack Configuration Software to perform any of the
following functions:

Radial Vibration

Thrust Position

Differential Expansion

Eccentricity

REBAM*

Acceleration

Velocity

Shaft Absolute

Circular Acceptance Region

Note: The monitor channels are programmed in pairs and can perform up to two of these functions
at a time. Channels 1 and 2 can perform one function, while channels 3 and 4 perform another (or
the same) function.

The primary purpose of the 3500/42M monitor is to provide:


1.

Machinery protection by continuously comparing monitored parameters


against configured alarm setpoints to drive alarms.

2.

Essential machine information for both operations and maintenance


personnel.

Each channel, depending on configuration, typically conditions its input signal to


generate various parameters called static values. The user can configure Alert
setpoints for each active static value and Danger setpoints for any two of the
active static values.

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 1 of 18

Specifications
Inputs

Acceleration
and
Acceleration2
10 mV/ (m/s2) (100 mV/g).

Signal
Accepts from 1 to 4 proximity,
velocity or acceleration
transducer signals.

Velocity and
Velocity2
20 mV/ (mm/s) pk (500 mV/ (in/s)
pk), or

Input
Impedance

5.8 mV/ (mm/s) pk (145 mV/ (in/s)


pk), or

Standard I/O

4 mV/ (mm/s) pk (100 mV/ (in/s)


pk).

10 k (Proximitor and
Acceleration Inputs).
TMR I/O
The effective impedance of three
Bussed TMR I/O channels wired in
parallel to one transducer is 50
k.
Power
Consumption

Shaft Absolute,
Radial Vibration
3.94 mV/m (100 mV/mil), or
7.87 mV/m (200 mV/mil).
Shaft Absolute,
Direct
3.94 mV/m (100 mV/mil), or

7.7 Watts, typical.

Sensitivity

7.87 mV/m (200 mV/mil).


Shaft Absolute,
Velocity

Radial Vibration
3.94 mV/m (100 mV/mil), or

20 mV/ (mm/s) pk (500 mV/ (in/s)


pk), or

7.87 mV/m (200 mV/mil).

5.8 mV/ (mm/s) pk (145 mV/ (in/s)


pk), or

Thrust
3.94 mV/m (100 mV/mil), or

4 mV/ (mm/s) pk (100 mV/ (in/s)


pk).

7.87 mV/m (200 mV/mil).


Eccentricity
3.94 mV/m (100 mV/mil), or
7.87 mV/m (200 mV/mil).
Differential
Expansion

Circular
Acceptance
Region
See Radial Vibration.

Outputs
0.394 mV/m (10 mV/mil), or
0.787 mV/m (20 mV/mil).

REBAM
40 mV/m (1000 mV/mil), or

Front Panel
LEDs
OK LED
Indicates when the 3500/42M is
operating properly.

80 mV/m (2000 mV/mil).


TX/RX LED

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 2 of 18

Indicates when the 3500/42M is


communicating with other
modules in the 3500 rack.
Bypass LED
Indicates when the 3500/42M is in
Bypass Mode.

group. Each output is short-circuit


protected.
Shaft Absolute
Output
Impedance
300

Signal Conditioning

Buffered
Transducer
Outputs

Note: Specified at +25 C (+77 F) unless otherwise noted.

The front of each monitor has one


coaxial connector for each
channel. Each connector is shortcircuit protected.
Output
Impedance

Radial Vibration
Frequency
Response
Direct filter
User-programmable, single-pole,
-3db at 4 Hz to 4000 Hz or 1 Hz to
600 Hz, 1% accuracy.

550
Transducer
Power Supply

Gap filter
-24 Vdc

Recorder

-3 dB at 0.09 Hz.
Not 1X filter

+4 to +20 mA. Values are


proportional to monitor full-scale.
The monitor provides individual
recorder values for each channel.
Monitor operation is unaffected
by short circuits on recorder
outputs.
Voltage
Compliance
(current output)

60 cpm to 15.8 times running


speed. Constant Q notch filter.
Minimum rejection in stopband of
-34.9 dB.
Smax
0.125 to 15.8 times running
speed.
1X and 2X
Vector filter

0 to +12 Vdc range across load.


Load resistance is 0 to 600 .

Constant Q Filter. Minimum


rejection in stopband of -57.7 dB.

Resolution

Note: 1X & 2X Vector, Not 1X, and Smax

0.3662 A per bit

parameters are valid for machine speeds

0.25% error at room


temperature

of 60 cpm to 60,000 cpm.

0.7% error over temperature


range.

Accuracy
Direct and Gap
Exclusive of filtering, within
0.33% of full-scale typical, 1%
maximum.

Update rate 100 ms or less.


Shaft Absolute
Buffered
Outputs

1X and 2X
The Shaft Absolute I/O modules
have one output for each channel

Within 0.33% of full-scale


typical, 1% maximum.
Smax
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 3 of 18

Within 5% maximum.
Not 1X
3% for machine speeds less
than 30,000 cpm.
8.5% for machine speeds
greater than 30,000 cpm.

The following table shows the frequency ranges if a


single channel is enabled for a channel pair.
Output
Type
RMS
Peak

Without Filter, Lowor High-Pass Filter


10 to 30,000 Hz
3 to 30,000 Hz

10 to 14,500 Hz
10 to 14,500 Hz

Filter quality

Thrust and
Differential
Expansion

High-Pass
4-pole (80 dB per decade, 24 dB
per octave).

Frequency
Response

Low-Pass

Direct filter

4-pole (80 dB per decade, 24 dB


per octave).

-3 dB at 1.2 Hz.
Gap filter

Accuracy
-3 dB at 0.41 Hz.

Within 0.33% of full scale typical,


1% maximum. Exclusive of
filters.

Accuracy
Within 0.33% of full-scale
typical, 1% maximum.

Acceleration II
Frequency
Response

Eccentricity
Frequency
Response

Bias filter
-3 dB at 0.01 Hz

Direct filter
Not OK filter

-3 dB at 15.6 Hz.

-3 dB at 2400 Hz

Gap filter
1X and 2X
Vector filter

-3 dB at 0.41 Hz.
Accuracy
Within 0.33% of full-scale
typical, 1% maximum.
Acceleration
Frequency
Response
The following table shows the
frequency ranges if both channels
of a channel pair are enabled:
Output
Type

Without Filter

RMS

10 to 30,000
Hz
3 to 30,000
Hz

Peak

With Integration

Low- or
High-Pass
Filter
10 to 9,155
Hz
3 to 9,155
Hz

Valid for machine speeds of 60


cpm to 100,000 cpm.
The following table represents the frequency ranges
for the 3500/42M under different options using the
Acceleration II Channel Type.
Output
Type
RMS
Peak

Without Filter, Lowor High-Pass Filter


10 to 30,000 Hz
3 to 30,000 Hz

With Integration
10 to 20,000 Hz
10 to 20,000 Hz

With
Integration
10 to 9,155
Hz
10 to 9,155
Hz
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 4 of 18

Accuracy

Filter Quality

Within 0.33% of full scale


typical, 1% maximum. Exclusive
of filters.

High-Pass
4-pole (80 dB per decade, 24 dB
per octave).
Low-Pass
4-pole (80 dB per decade, 24 dB
per octave).

Velomitor*
Sensor
Accuracy
Full Scale 0-0.5: 3% Typical
Full Scale 0-1.0: 2% Typical

Accuracy

Full Scale 0-2.0: 1% Typical


Within 0.33% of full scale
typical, 1% maximum, exclusive
of filters.

Velocity and
Velocity II

Shaft Absolute,
Radial Vibration
Frequency
Response

Frequency
Response

Direct filter
User-programmable, 4 Hz to 4000
Hz or 1 Hz to 600 Hz.

Bias
-3dB at 0.01 Hz (Velocity II only)
Gap filter

Not OK filter

-3 dB at 0.09 Hz.

-3 dB at 40 Hz (Velocity II only)
1X Vector filter

RMS

Valid for machine speeds of 240


cpm to 60,000 cpm.

10 to 5,500 Hz, -3 dB.


Peak or
Peak-to-Peak

Accuracy
3 to 5,500 Hz, -3 dB

Direct and Gap


Within 0.33% of full-scale
typical, 1% maximum.

1X and 2X
Vector filter
Valid for machine speeds of 60 to
100,000 cpm. (Velocity II only)

1X
Within 0.33% of full-scale
typical, 1% maximum.

Filter Quality
Shaft Absolute,
Velocity

High-Pass
2-pole (40 dB per decade, 12 dB
per octave).

Frequency
Response

Low-Pass
4-pole (80 dB per decade, 24 dB
per octave).

Peak or
Peak-to-Peak
User-programmable, 1 to 4,000
Hz, -3 dB.
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 5 of 18

Programmable from 0.002 to 1.0


Hz. Selection is determined by the
Rotor filter.

Filter Quality
High-Pass
2-pole (40 dB per decade, 12 dB
per octave).
Low-Pass
2-pole (40 dB per decade, 12 dB
per octave).
1X Vector filter

1X Vector filter

The range of shaft speeds for


which the value is valid is
dependent upon the nominal
Shaft Speed the channel is
configured for. The following table
summarizes the relationship:

Constant Q Filter. Minimum


rejection in stopband of -57.7 dB.
Accuracy
Within 0.33% of full scale typical,
1% maximum. Exclusive of
filters.
Shaft Absolute
Buffered Output
Accuracy
6.0% @ 25 C
Circular
Acceptance
Region
See Radial Vibration

Nominal Shaft
Speed (Hz)

Valid Speed
Range (Hz)

10 to <126
126 to <252
252 to <504
504 to 584

0.071 to 160
0.133 to 330
0.25 to 660
0.50 to 750

Note: If a multi-event gear or speed wheel


generates the speed input, the resultant

REBAM

input signal has an upper limitation of

Frequency
Response

approximately 20 KHz.

Filter Quality

Spike

Spike high-pass
User-programmable from 0.152
to 8678 Hz.

6-pole Elliptic (155 dB per decade,


minimum). Corner frequency is 0.1 dB.

Element
User-programmable for BPFO
ranging from 0.139 to 3836 Hz.
High-pass corner is 0.8x BPFO.
Low-pass corner is 2.2x BPFO.

Element
bandpass

User programmable from 0.108 to


2221 Hz.

Rotor low-pass

8-pole Butterworth (155 dB per


decade minimum). Corner
frequency is -3 dB.

Rotor

6-pole Elliptic (155 dB per decade,


minimum). Corner frequency is 0.1 dB.

Direct
Programmable from 3.906 to 14.2
Hz. Selection is determined by
Spike and Rotor filters.

Rotor, Direct
high-pass

Gap
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 6 of 18

1-pole Butterworth (18 dB per


decade, minimum). Corner
frequency is -3 dB.
Spike, Direct
low-pass

Current shaft speed 0.95 x


(nominal shaft speed).
Switch from nominal
to higher filter set
Current shaft speed 1.1 x
(nominal shaft speed).

Corner is -0.3 dB maximum.


Gap low-pass
1-pole Butterworth (18 dB per
decade, minimum). Corner
frequency is -3 dB.
1X Amplitude
Constant Q of 16.67. Stopband
frequencies are 0.91 and 1.09
times the running speed.
Stopband attenuation is -51 dB
minimum.

Switch from higher


to nominal filter set
Current shaft speed 1.05 x
(Nominal Shaft Speed).
Shaft speed
error condition
Nominal filter set used.

Alarms
Alarm setpoints
The user can use software
configuration to set Alert levels
for each value measured by the
monitor and Danger setpoints for
any two of the values measured
by the monitor Alarms are
adjustable from 0 to 100% of fullscale for each measured value.
The exception is when the fullscale range exceeds the range of
the transducer. In this case, the
range of the transducer will limit
the setpoint. Accuracy of alarms
is to within 0.13% of the desired
value.

Accuracy
Amplitude
Within 0.33% of full scale typical,
1% maximum when input signal
is at the center frequency of the
proportional value's passband.
Phase
3 degrees error, maximum.
Channels
enabled
Certain configurations allow the
user to enable only one channel
of a channel pair. See the
discussion and graphs in the final
pages of this datasheet.
Filter tracking/
stepping
(requires a valid
speed signal)

Alarm Time
Delays
Note: Applies to Radial Vibration, Thrust, Differential Expansion,
Eccentricity, Acceleration, Velocity, Acceleration2, Velocity2,
Circular Acceptance Region, Shaft Absolute Radial Vibration

The user can program alarm


delays using software as follows:

Initial condition

Alert
Nominal filter set used.

Switch from nominal


to lower filter set

From 1 to 60 seconds in 1 second


intervals.
Danger

Current shaft speed 0.9 x


(nominal shaft speed).
Switch from lower to
nominal filter set

0.1 seconds or from 1 to 60


seconds in 0.5 second intervals.
Shaft Absolute
Velocity
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 7 of 18

The user can program Alarm


delays using software as follows:

Acceleration
Direct, defined as one of the
following:

Alert

RMS Acceleration, or

From 1 to 60 seconds in 1 second


intervals.

Peak Acceleration, or

Danger

RMS Velocity, or
From 1 to 60 seconds in 0.5
second intervals.

Peak Velocity, or
Band-pass peak Acceleration, or
Band-pass peak Velocity.
Acceleration II

REBAM

Direct, 1X Amplitude, & 2X


Amplitude; defined as one of the
following:

The user can program Alarm


delays using software as follows:
Alert

RMS Acceleration, or
From (calculated minimum value)
to 400 seconds in 1 second
intervals.

Peak Acceleration, or
RMS Velocity, or
Peak Velocity, or

Danger

Band-pass peak Acceleration, or

From (calculated minimum value)


to 400 seconds in 0.5 second
intervals.

Band-pass peak Velocity.


Additionally, 1X Phase, 2X Phase
and Bias Voltage.

Static Values
Static values are measurements used to monitor the
machine. The Proximitor/Seismic Monitor returns the
following static values:

Velocity
Direct, defined as one of the
following:

Radial Vibration

RMS Velocity, or

Direct, Gap, 1X Amplitude, 1X


Phase Lag, 2X Amplitude, 2X
Phase Lag, Not 1X Amplitude, and
Smax Amplitude.

Peak Velocity, peak-to-peak


Displacement (?), or
Band-pass peak Velocity, or

Thrust Position

Band-pass, or
Direct, Gap

Differential
Expansion

Peak-to-peak Displacement.
Velocity II

Direct, Gap
Eccentricity

Direct, 1X Amplitude, & 2X


Amplitude: defined as one of the
following:

Peak-to-peak, Gap, Direct


Minimum, Direct Maximum.

RMS Velocity, or

Spike, Element, Rotor, Direct, Gap,


1X Amplitude, 1X Phase Lag

Band-pass peak Velocity, or

REBAM

Peak Velocity (?), peak-to-peak


Displacement, or
Band-pass, or
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 8 of 18

Rmin (PWR) = 297

Peak-to-peak Displacement.
Additionally, 1X Phase, 2X Phase
and Bias Voltage.
Shaft Absolute, Radial
Vibration and Shaft
Absolute, Velocity
Direct, Gap, 1X Amplitude, 1X
Phase Lag

Channel
Parameters
(entity)
Vmax = 27.25 V
Imax = 91.8 mA
Rmin (PWR) = 297

Environmental Limits
Operating
Temperature

Circular
Acceptance
Region

When used with Internal/External


Termination I/O Module:
-30C to +65C (-22F to +150F)

Direct, Gap, 1X Amplitude, 1X


Phase Lag, 1X Circular
Acceptance Radius, 2X Amplitude,
2X Phase Lag, 2X Circular
Acceptance Radius

Barrier Parameters
The following parameters apply for both CSA-NRTL/C
and ATEX approvals.

When used with Internal Barrier


I/O Module (Internal Termination):
0C to +65C (32F to +150F)
Storage
Temperature
-40 C to +85 C (-40 F to +185
F).

Proximitor
Barrier
Circuit Parameters
Vmax (PWR) = 26.80 V
(SIG) = 14.05 V
Imax (PWR) = 112.8 mA
(SIG) = 2.82 mA
Rmin (PWR) = 237.6
(SIG) = 4985
Channel Parameters
(entity)
Vmax = 28.0 V
Imax = 115.62 mA
Rmin (PWR) = 237.6
(SIG) = 4985

Humidity
95%, noncondensing.

Compliance and Certifications


EMC
Standards:
EN 61000-6-2 Immunity for Industrial
Environments
EN 55011/CISPR 11 ISM Equipment
EN 61000-6-4 Emissions for Industrial
Environments
European Community Directives:
EMC Directive 2004/108/EC

Electrical Safety
Standards:
EN 61010-1

Seismic Barrier
Circuit
Parameters
Vmax (PWR) = 27.25 V
Imax (PWR) = 91.8 mA

European Community Directives:


2006/95/EC Low Voltage
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 9 of 18

Ex nC[nL Gc] IIC T4 Gc

Hazardous Area Approvals

T4 @ Ta = -20C to +65C

North American

(-4F to +150F)

Approval Option
(01)
When used with I/O module ordering
options with internal barriers:

Brazil
Approval Option
(02)

Ex nC [ia] IIC: Class I, Div 1


AEx nC [ia] IIC: Class 1, Zone 2/0
Groups A, B, C, D

For Selected Ordering Options


with ATEX/North American
agency approvals:
BR-Ex nC [nL] IIC
T4 @ Ta = -20 C to +65 C

T4 @ Ta = -20 C to +65 C

(-4 F to +150 F)

(-4 F to +150 F)
per drawing 138547
When used with I/O module ordering
options without internal barriers:
Ex nC [L] IIC: Class I, Div 2
AEx nC IIC: Class 1, Div 2
Groups A, B, C, D

South Africa
Approval Option
(02)

T4 @ Ta = -20 C to +65 C

For Selected Ordering Options


with ATEX/North American
agency approvals:

(-4 F to +150 F)
per drawing 149243

Ex nCAL [ia] IIC T4


Ex nCAL [L] IIC T4

ATEX

T4 @ Ta = -20 C to +65 C

Approval Option
(02)

(-4 F to +150 F)
For Selected Ordering Options
with ATEX/CSA agency
approvals:
For ATEX agency approval
ordering options with internal
barriers:

Note: When used with Internal Barrier I/O


Module, refer to specification sheet
141495-01 for approvals information.
For further certification and approvals information please visit the
following website:
www.ge-mcs.com/bently

II 3/(1) G
Ex nC[ia Ga] IIC T4 Gc
T4 @ Ta = -20C to +65C

Physical
Monitor Module
(Main Board)

(-4F to +150F)
For ATEX agency approval
ordering options without internal
barriers:
II 3/(3) G

Dimensions
(Height x Width
x Depth)
241.3 mm x 24.4 mm x 241.8 mm
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 10 of 18

External Termination Blocks


cannot be used with Internal
Termination I/O Modules.

(9.50 in x 0.96 in x 9.52 in).


Weight
0.91 kg (2.0 lb.).

When ordering I/O Modules with


External Terminations the
External Termination Blocks and
Cable must be ordered separately
for each I/O Module.

I/O Module
(non-barrier)
Dimensions
(Height x Width
x Depth)

Bussed External Termination


Blocks are to be used with TMR
I/O Modules only.

241.3 mm x 24.4 mm x 91.1 mm


(9.50 in x 0.96 in x 3.90 in).
Weight

Internal Barrier
I/O Modules
Consult the 3500 Internal Barrier
specification sheet (part number
141495-01) if the Internal Barrier
Option is selected.

0.20 kg (0.44 lb.).

Shaft Absolute

I/O Module
(barrier)

The Shaft Absolute Channel Type


requires the following (or later)
firmware and software revisions:

Dimensions
(Height x Width
x Depth)
241.3 mm x 24.4 mm x 163.1 mm

3500/42M Module Firmware


Revision B

(9.50 in x 0.96 in x 6.42 in).

3500/01 Software Version 2.61


DM2000 Software - Version 3.10.
Requires the M version of the
3500 Proximitor/Seismic Monitor.

Weight
0.46 kg (1.01 lb.).

Rack Space Requirements

REBAM

1 full-height front slot.

The REBAM channel type requires


the following (or later) firmware,
and software revisions:

1 full-height rear slot.

3500/40M Module Firmware


Revision 2.1

Monitor Module
I/O Modules

3500/01 Software Version 3.30

Ordering Information

3500/02 Software Version 2.40

General

3500/03 Software Version 1.40

The 3500/42M Module requires


the following (or later) firmware,
and software revisions:

DM2000 Software - Version 3.40.


Requires the M version of the
3500 Proximitor Monitor.

3500/01 Software Version 2.50


3500/02 Software Version 2.20
3500/03 Software Version 1.21

Acceleration II
The Acceleration II channel type
requires the following (or later)
firmware, and software revisions:
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 11 of 18

3500/42M Module Firmware


Revision 2.10
3500/01 Software Version 3.20
DM2000 Software - Version 3.30.
Requires the M version of the
3500 Proximitor Monitor.

A 04, A05, & A 06


A 07 & A 08
A 09 & A 10

Option
A 04
A 05
A 06

See Acceleration II.

B:

Proximitor Seismic Monitor


3500/42-AXX-BXX
01
02
03
04
05

06

07
08
09
10

Prox/Seismic I/O Module with


Internal Terminations
Prox/Seismic I/O Module with
External Terminations
TMR Prox/Seismic I/O Module.
I/O Module with Internal
Barriers (4 x prox./accel. ch's)
and Internal Terminations
I/O Module with Internal
Barriers (2 x prox./accl. + 2 x
channels) and Internal
Terminations
I/O Module with Internal
Barriers (4 x Velomitor
channels) and Internal
Terminations
Shaft Absolute I/O Module
with Internal Terminations
Shaft Absolute I/O Module
with External Terminations
Prox/Velom I/O Module with
Internal Terminations
Prox/Velom I/O Module with
External Terminations

Note 1: The following table shows the ordering option and


supported transducer types.

Ordering Option
A 01 & A 02
A 03

Chs 1 and 2
Prox/Accel
Prox/Accel
Velomitor sensor

Chs 3 and 4
Prox/Accel
Velomitorsensor
Velomitor sensor

Note 4: Prox/Accel and Velom are supported with the A 01 & A 02


options. However, unless a Seismoprobe* is used the appropriate
choice is the A 09 and A 10 options.

Ordering Options

I/O Module Type

Note 3: HTVS transducer is supported in A 09 and A 10 I/O


module type options.

See Acceleration II.

A:

See Note 2
X
X

Note 2: The following table shows the ordering options that are
available for Internal Barriers with this monitor.

Velocity II
Circular
Acceptance
Region

X
X

Prox/Accel

Velom

See Note 4
X
X

Seismoprobe
X

Agency Approval Option


00
None
01
CSA/NRTL/C (Class 1, Div 2)
02
ATEX/CSA (Class 1, Zone 2)

Note: Agency Approval Option B 02 is only available with Ordering


Options; A 04, A 05, A 06, and A 09.

External Termination Blocks


125808-02
Proximitor ET Block (Euro Style
Connectors).
128015-02
Proximitor ET Block (Terminal Strip
Connectors).
132242-01
Prox/Seismic Bussed TMR ET Block
(Euro Style connectors).
132234-01
Prox Seismic Bussed TMR ET Block
(Terminal Strip connectors).
128702-01
Recorder External Termination Block
(Euro Style connectors).
128710-01
Recorder External Termination Block
(Terminal Strip connectors).
140993-01
141001-01
125808-08

Shaft Absolute External Termination


Block (Euro Style connectors).
Shaft Absolute External Termination
Block (Terminal Strip).

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 12 of 18

128015-08

Proximitor/Velomitor External
Termination Block (Euro Style
connectors).
Proximitor/Velomitor External
Termination Block (Terminal Strip
connectors).

128240-01

126632-01

00530843

143489-01
135489-01

Cables
3500 Transducer (XDCR) Signal to External Termination
(ET) Block Cable
129525 -AXXXX-BXX
A:

B:

Cable Length

0005
0007
0010
0025
0050
0100
Assembly Instructions
01
02

5 feet (1.5 metres)


7 feet (2.1 metres)
10 feet (3.0 metres)
25 feet (7.6 metres)
50 feet (15.2 metres)
100 feet (30.5 metres)
Not assembled
Assembled

3500 Recorder Output to to External Termination (ET)


Block Cable
129529 -AXXXX-BXX
A:

B:

Cable Length

0005
0007
0010
0025
0050
0100
Assembly Instructions
01
02

5 feet (1.5 metres)


7 feet (2.1 metres)
10 feet (3.0 metres)
25 feet (7.6 metres)
50 feet (15.2 metres)
100 feet (30.5 metres)
Not assembled
Assembled

Spares
176449-02
128229-01

3500/42M Proximitor/Seismic Monitor


Prox/Seismic I/O Module with Internal
Terminations

135489-02

135489-03

138708-01

138700-01

00517018

140471-01

140482-01

00561941

00580434

Prox/Seismic I/O Module with External


Terminations
TMR I/O Module with External
Terminations
3500/42M Prox/Seismic I/O Module
four-pin connector shunt
3500/42M Monitor Manual
I/O Module with Internal Barriers
(Internal Terminations)
(4 x Prox/Accel).
I/O Module with Internal Barriers
(Internal Terminations)
(2 x Prox/Accel + 2 x Velomitor*)
I/O Module with Internal Barriers
(Internal Terminations)
(4 x Velomitor*)
Shaft Absolute I/O Module with
Internal Terminations
Shaft Absolute I/O Modules with
External Terminations
3500/42M Shaft Absolute I/O Module
8-pin connector shunt
Prox/Velom I/O Module with Internal
Terminations
Prox/Velom I/O Module with External
Terminations
3500/42M Prox/Velom I/O Module 10pin connector shunt
Internal I/O Module connector header,
Euro style, 8-pin. Used on I/O modules
128229-01 and 138708-01.
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 13 of 18

Internal I/O Module connector header,


Euro style, 12-pin.

00580432

00502133

Internal I/O Module connector header,


Euro style, 10-pin. Used on I/O
modules 128229-01 and 138708-01.

Graphs and Figures

1.
2.
3.
4.
5.

Status LEDs
Buffered Transducer Outputs
Prox/Seismic I/O Module with Internal Terminations
Prox/Seismic I/O Module with External Terminations
TMR I/O Module with External Terminations
Specifications and Ordering Information
Part Number 143694-01
Rev. K (06/13)
Page 14 of 18

Figure 1: Front and rear view of the Proximitor*/Seismic Monitor

1.
2.
3.
4.

Prox/Velom I/O Module, Internal Terminations


Prox/Velom I/O Module, External Terminations
Shaft Absolute I/O Module, Internal Terminations
Shaft Absolute I/O Module, External Terminations

Figure 2: Additional I/O Modules of the Proximitor/Seismic Monitor

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 15 of 18

1.
2.
3.

Barrier I/O module for connecting four Proximitor sensors.


Barrier I/O module for connecting two Proximitor sensor and two Velomitorsensor.
Barrier I/O module for connecting four Velomitor sensors.
Figure 3: Barrier I/O Modules for the Proximitor/Seismic Monitor

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 16 of 18

REBAM* Channels:
The following graphs show the maximum machine speed allowed for a monitor channel pair configured for REBAM.
The top graph assumes both channels of the channel pair are enabled. The bottom graph assumes only one channel
of a channel pair is enabled. The maximum speed is dependent on the number of rolling elements in the bearing. The
graph assumes that the rotor lowpass filter corner is set at 3.2X the shaft speed and the spike highpass filter corner is
set at 4X the element pass frequency for the outer race (BPFO).

2-C hannel C onfiguration


25000

Max R PM

20000

15000

10000

5000

0
6

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

32

34

36

38

40

N umber of E lements
Rotor

Element Pass

Spike

1-C hannel C onfiguration


40000
35000

Max R PM

30000
25000
20000
15000
10000
5000
0
6

10

12

14

16

18

20

22

24

26

28

30

N umber of Elements
Rotor

Element Pass

Spike

Specifications and Ordering Information


Part Number 143694-01
Rev. K (06/13)
Page 17 of 18

* denotes trademarks of Bently Nevada, INC., a wholly owned subsidiary of General Electric Company.
1999 2013 Bently Nevada Inc., All rights reserved.
Printed in USA. Uncontrolled when transmitted electronically.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 775.782.3611
Fax: 775.215.2873