Você está na página 1de 7

EEPB383, Semester 1 2012/2012

COLLEGE OF ENGINEERING
PUTRAJAYA CAMPUS
FINAL EXAMINATION
SEMESTER 1 2012 / 2013
PROGRAMME

: Bachelor of Electrical Power Engineering (Honours)

SUBJECT CODE

: EEPB 383

SUBJECT

: Electrical Power System II

DATE

TIME

: 2 hours

INSTRUCTIONS TO CANDIDATES:
1.

This paper contains FIVE (5) questions in SEVEN (7) pages.

2.

Answer ALL questions.

THIS QUESTION PAPER CONSISTS OF 7 PRINTED PAGES INCLUDING THIS


COVER PAGE.

Page 1 of 7

EEPB383, Semester 1 2012/2012

QUESTION 1 [15 MARKS]


Three generators are available to supply a power system peak load of 800 MW. The cost of
power production from each generator and maximum output is given.
C1 = 300 + 2.5 P1 + 0.0014 P12 RM/hr

10MW < P1 < 500 MW

C 2 = 250 + 2.3P2 + 0.0035 P22 RM/hr

10MW < P2 < 380 MW

C3 = 350 + 3.5 P3 + 0.0027 P32 RM/hr

10MW < P3 < 100 MW

a) Determine the cheapest cost of dispatch in order to meet the demand?

[7 Marks]

b) Determine the Penalty Factor for each plant if real power losses are defined as:

[6 marks]
c) Which of the three (3) generators are the most expensive and the cheapest to operate?
Support your answers with reasons.

[2 marks]

QUESTION 2 [15 MARKS]


A 100- MVA 20 kV synchronous generator is connected through a transmission line to a 100
MVA 20 kV synchronous motor. The per unit transient reactances of the generator and motor
are 0.25 and 0.20, respectively. The line reactance on the base of 100 MVA is 0.1 per unit.
The motor is taking 50 MW at 0.8 power factor leading at a terminal voltage of 20 kV. A
three-phase short circuit occurs at the generator terminals. Determine the transient currents in
each of the two machines and in the short circuit.

Page 2 of 7

[9+6 marks]

EEPB383, Semester 1 2012/2012

QUESTION 3 [25 MARKS]

j0.7

j0.2

BUS 1

j0.5

BUS 3

BUS 2

XT1=j0.2

XT2=j0.2

XG1=j0.1

XG1=j0.05

Figure 1: 3-Bus Network


Figure 1 shows a 3-Bus network with 2 generators connected to it. Based upon this, please
answer the following questions:
a) Obtain the Impedance Matrix for the network.

[6 marks]

b) A three phase fault occurred at Bus 3 with a fault impedance of j0.15 pu. Assume the
prefault voltage is 1.0 per unit. Calculate the voltage at each bus (V1, V2, V3) during fault
and short circuit current flowing through the branches (I1-2, I1-3, I2-3) in the network during
fault.

[14 marks]

c) How does Short Circuit Capacity (SCC) relate to the interrupting capacity of a Circuit
Breaker

[5 marks]

Page 3 of 7

EEPB383, Semester 1 2012/2012

QUESTION 4 [25 MARKS]


The reactance data for the power system shown in Figure 2 in per unit on a common 100
MVA base is given in Table 1 as follows:
Table1: Reactance data of power system components
Item
G1
G2
T1
T2
L1
L2

X1
0.15
0.15
0.10
0.10
0.25
0.25
1

T1

CB1

X2
0.15
0.15
0.10
0.10
0.25
0.25
L1

X0
0.05
0.05
0.10
0.10
0.35
0.35
CB2

CB5

2
CB6

T2

G1

G2
L2

CB7

CB8
CB4

CB3

Figure 2

a) Draw the positive, negative and zero sequence impedance networks for the power system.
State in your drawing the numerical values of all the impedances.
[8 marks]
b) If the breaking capacity of each of the circuit breakers used in the network is rated at 3.0
per unit on the same base (100 MVA), propose two methods/approaches to ensure that the
system operate safely for a bolted single-line to ground fault at bus 1. Please support your
answers clearly with calculations.
[17 marks]

Page 4 of 7

EEPB383, Semester 1 2012/2012

QUESTION 5 [20 MARKS]


a) A 60 Hz synchronous machine having inertia constant H= 5 MJ/MVA and a shaft axis
transient reactance X d' = 0.3 per unit is connected to an infinite bus through a purely
reactive circuit shown in Figure 3. Reactances are marked on the diagram on a common
system base.
The generator is delivering real and reactive power to infinite Bus 2 at voltage of
V = 10 per unit.
V = 10

S = 0.8 j 0.5 p.u Bus 1


XL1= j0.3

X d'

= j 0.3

Bus 2

Xt= j0.2

XL2 =j0.3
CB21

CB22

Figure 3
A three-phase fault occurred on line L2 and the fault is isolated instantaneously by the
tripping of circuit breakers CB21 and CB22 as shown in Figure 3. Determine if the
synchronous machine will remain synchronized or losses synchronism after the fault has
been cleared. Please support your answers with calculations and a graph.

[10 marks]

b) Explain why load frequency control and automatic voltage regulator for synchronous
generators are important in an interconnected power system.

END OF QUESTION PAPER

Page 5 of 7

[10 marks]

EEPB383, Semester 1 2012/2012

Formula Sheet

i
i =1 2 i
n

i
;
i =1 2 i
n

PD =

PD +
n

2
i =1

dCi
P
+ L =
dPi
Pi

H d 2
d
+
D
+ PS = 0
f 0 dt 2
dt
H d 2
= Pm Pe
f 0 dt 2
0

= 0 +

1 2

n 0

= 0

D
2

n =

e nt sin ( d t + )

e nt sin d t

f 0
HPS

f 0
H

PS

= cos 1

d = n 1 2

I a0 = I a1 = I a2 =

I a1 = I a2 =

I a0

Ea
:
Z + Z + Z 0 + 3Z f
1

Ea
:
Z + Z2 + Zf
1

Single line to ground fault

Line-Line fault

Ea Z 1 I a1
:
= 0
Z + 3Z f

Double Line to Ground Fault

Ea Z 1 I a1
:
Z2

Double Line to Ground Fault

I a2 =

Page 6 of 7

EEPB383, Semester 1 2012/2012

Ea

I a1 =
Z1 +

Z 2 Z 0 +3 Z f

Double Line to Ground Fault

Z 2 + Z 0 +3 Z f

V a 1 1
b
2
V = 1 a
V c 1 a

1 Va0

a Va1
a 2 Va2

1
1
''
E0
1
1 t d'
1
(
)
+
+

+
iasy (t ) = 2 E0 '' ' e t d + '
e
t
sin
2
sin e t a

''

X d
Xd
X d X d
Xd Xd

S pu =

S
,
SB

S
SCC = B
X kk

V pu =

new
Z pu

V
,
VB

Z old
pu

I pu =

I
,
IB

S Bnew VBold

S Bold VBnew

Z pu =

Z
,
ZB

cos c =

Pm
( max 0 ) + cos max
Pmax

cos c =

Pm ( max 0 ) + P3 max cos max P2 max cos 0


P3 max P2 max

Page 7 of 7

ZB =

(VB )2 ,
SB

IB =

SB
3VB

Você também pode gostar