RS485
Communication Protocol
STM250 modular inverter
Version 1.0
Date: Feb 2010
1/6
Type
: RS485
Default address : 1A
Data format
: one start bit, 8 data bits, no parity code, one stop bit;
Baud rate
: 9600.
Instruction
1.0 remote measurement
1.1 Inverter data query
Instruction format
Address
Function code
Start address
Data length
CRC verification
0xXX
0x03
0x00 00
0x00 14
CRC16
Address
Function code
Data length
Data
CRC verification
0xXX
0x03
0x14
20 Bytes
CRC16
Definition
Data length
Data format
Units
00
Input voltage
2 bytes
0.1V
01
Input frequency
2 bytes
0.1Hz
02
Output voltage
2 bytes
0.1V
03
Output frequency
2 bytes
0. 1Hz
04
DC voltage
2 bytes
0.1V
05
Output current
2 bytes
0.1A
06
Current of module 1
2 bytes
0.1A
07
Current of module 2
2 bytes
0.1A
08
Current of module 3
2 bytes
0.1A
09
Current of module 4
2 bytes
0.1A
Example:
Instruction: 1A 03 00 00 00 14 46 2E
Received data: 1A 03 14 08 EB 01 F4 08 8C 01 F4 08 8B 00 6F 00 24 00 24 00 27 00 00 1F 4E
Explanation
1A: Communication address of equipment;
03: Function code
14: Followed by 20 bytes of data (Definition as the table below)
1F 4E: CRC verification code.
2/6
Address
Definition
Data length
Data
Units
00
Input voltage
2 bytes
08EB=2283228.3V
0.1V
01
Input frequency
2 bytes
01F4=500 50.0Hz
0.1Hz
02
Output voltage
2 bytes
088C=2188218.8V
0.1V
03
Output frequency
2 bytes
0. 1Hz
04
DC voltage
2 bytes
088B=2187218.7V
0.1V
05
Output current
2 bytes
006F =111
(11.1A
0.1A
06
Current of module 1
2 bytes
0024=36
3.6A
0.1A
07
Current of module 2
2 bytes
0024=36
3.6A
0.1A
08
Current of module 3
2 bytes
0027=39
(3.9A)
0.1A
09
Current of module 4
2 bytes
0000=00
(0.0A)
0.1A
Function code
Start address
Data length
CRC verification
0xF7
0x03
0x02 00
0x00 01
CRC16
Function code
Data length
Data length
CRC verification
0xF7
0x03
0x02
Communication
address
CRC16
Note:
1> Address read out is what inverter is using right now
2> F7 is the broadcast address of inverter made by our company, of which all inverters from our
company will respond. All inverters will respond to this command and reply at same time
when receiving such query, if there are two or more inverters from our company connected
in parallel on RS485 communication bus. It may cause data conflicts on RS485 bus.
Therefore, Please ensure there is only one inverter from our company on
RS485 bus and not other equipments using the same address.
Example:
Instruction
Receiving data
: F7 03 02 00 00 01 91 24
: F7 03 02 00 0A F0 56
0A is the communication address of this inverter, and it can be used to communicate with the
machine.
3/6
Function code
Start address
Data length
CRC verification
0xXX
0x02
0x03 00
0x00 01
CRC16
Function code
Data length
Data
CRC verification
0xXX
0x02
0x02
2Bytes
CRC16
Definition
Definition
1 AC input failure
1 reserve
1 Low battery
1 reserve
1 Inverter failure
1 reserve
1 Overload
1 reserve
1 Over-temperature
1 module 4 failure
1 Inverter status
1 module 3 failure
1 Bypass status
1 module 2 failure
1 reserve
1 module 1 failure
Example:
Instruction
Receiving data
: 1A 02 03 00 00 01 BA 65
: 1A 02 02 84 08 BF 7C
4/6
Function code
Set address
Set content
CRC verification
0xXX
0x05
0x00 50
0x00 00 OR 0x00 FF
CRC16
Function code
Set address
Set content
CRC verification
0xXX
0x05
0x00 50
0x00 00 OR 0x00 FF
CRC16
Explanation:
There will be an alarm beep to remind administrator upon inverter failure. And the administrator
could turn off/on the beep alarm by sending this instruction.
Setting description:
Example:
Function code
Set address
Set content
CRC verification
0xXX
0x06
0x02 00
0x00 010x00 F6
CRC16
Function code
Set address
Set content
CRC verification
0xXX
0x06
0x02 00
0x00 010x00 F6
CRC16
Note:
1> The address range of inverter you could set is : 1~246 (0x01~0xF6).
2> Inverter will return data with original address after receiving the command of changing
communication address, and then change its communication address afterwards.
5/6
Setting new address will restart LCD or restart inverter, which may cause
power interruption. So, please make sure there is no load connected
while performing this setting.
Example:
Instruction
: 1A 06 02 00 00 0A 0B 9E
Receiving data : 1A 06 02 00 00 0A 0B 9E
0A address must be used in follow-up communication.
Function code
Data
Set content
1A
COM+0x80
CODE
CRC 16
z CODE
z COM
Example:
Instruction
Receiving data
: 1A 03 00 00 00 00 46 21
: 1A 83 03 71 36
6/6