Escolar Documentos
Profissional Documentos
Cultura Documentos
UMJ29000 Issue 2
Page 1 of 26
Section 1 Introduction
1.1
WinGPS Software
This software is used to commission a Regulo installation on a Pilot Operated PRV.
In addition, all other Technolog GSM Data loggers can be programmed by using
WinGPS, allowing diagnostic tools to monitor GSM communications to and from the
data logger.
1.2
100mH2O or 200mH2O
0.001 - 0.100m3/hr (cum/hr) or 1 - 100 l/s
Outlet Pressure
Inlet Pressure
Flow Pulse Significance
Diagnostics:
100m
200m
3
0.001m
Battery
Pump
Exhaust Valve
Inlet Valve
We do not supply configuration files with editable values because this would affect the
correct display scaling on the Regulo Display Panel.
UMJ29000 Issue 2
Page 2 of 26
WinGPS Setup
2.1.1
2.1.2
Tools
Shortcut to the Profile Editor
Options for setting the comms,
File directories,
Diagnostic tools etc.
Help
Information about the version,
Contents, index etc.
UMJ29000 Issue 2
Page 3 of 26
2.1.3
2.1.4
Configure Regulo
UMJ29000 Issue 2
Page 4 of 26
b.
c.
UMJ29000 Issue 2
Page 5 of 26
2.2
General
Logger:
Displays the Logger type, Serial Number
and Memory size of the logger
Recording:
Status: STANDBY / LOGGING
Mode: Can be adjusted, rotating store or
store until full, prior to starting
Clock
The Logger can be synchronised with the
Computer by selecting Set Clock
Notepad
Displays current configuration
The notepad details can be edited
Any notepad changes made must be saved
otherwise they will not be written back to the
logger.
Each Data logger should be given a unique
PMAC ID ranging from 0001 to 65535
2.3
Channels
All channels can be selected individually
to display live inputs.
If no channels are selected but the Live
Input is pressed, all channels, excluding
Pump, Exhaust and Inlet Valves will
display their live input readings.
For Outlet and Inlet pressures, the
transducer offsets must be zeroed whilst
the transducers are not pressurised.
To perform this, highlight one channel,
select live input, edit value to remove
offset.
Other channels are not editable from this
page.
UMJ29000 Issue 2
Page 6 of 26
2.4
Remote Communications
2.4.1
2.4.2
Bearer:
Indicates different
Communications
modes
of
GSM
Retry mode:
Single sequence or Repeat every 2 hours
Should remain at Single Sequence
UMJ29000 Issue 2
Page 7 of 26
2.4.3
SMS Messages:
Message Reserve: *Unlimited *
Total Messages sent: Increment on usage
Update: *Unlimited*
* For Non-UK SIM Cards this should always
indicate Unlimited *
2.4.4
Modem
Modem always on to receive alarms &
commands - must be selected only when
used for Closed Loop Control.
30
30
secs
UMJ29000 Issue 2
Page 8 of 26
2.6
2.6.1
Status:
STANDBY / CONTROLLING
Mode:
Fixed Pressure
Daily Profile 1
Daily Profile 2
Flow Profile
Closed Loop
Start Control
Turn control OFF / ON
Edit Profile
For Time & Flow Profile Editing
Status
Timeout screens for Low Points (Cello CP)
Timeout, Pump Timeout and Inlet/Exhaust
Valve Timeouts
UMJ29000 Issue 2
Page 9 of 26
2.6.2
Settings PRV
Target Pressure:
Required pressure for Regulo to achieve
Threshold:
Tolerance between achieved pressure and
the required target pressure
Averaging:
Time between comparing the current outlet
pressure with required target pressure,
adjustment may be necessary to cater for
hydraulic nature of various pressure
management schemes
(For initial commissioning this may be
reduced to 1 second)..
Vmax:
Maximum allowed PRV Outlet pressure value
Vmin:
Minimum allowed PRV Outlet pressure value
2.6.3
UMJ29000 Issue 2
Page 10 of 26
2.6.4
Required Pressure:
Control manifold pressure necessary to perform
change to outlet pressure range between Vmax &
Vmin.
Threshold:
Tolerance of applied control pressure to the required
control pressure
Pump timeout:
Maximum permissible time allowed for pump operation
when no adjustment made to control pressure
Full scale:
Maximum allowed Manifold control pressure units
Valve Parameters:
Set at maximum, see appendix on control parameters
2.7
2.7.1
Fixed Pressure
Fixed pressure is typically used during Regulo
commissioning or Closed Loop Control
Status:
Controlling (Control Started)
Mode:
Select Fixed Pressure mode
Vmax / Vmin:
Create operating range for control of Pressure Reducing
Valve (PRV)
Target Pressure:
Set target values for outlet pressure
Threshold:
Adjust to acceptable control tolerance
(0.5M for 100M / 1M for 200M ranges)
Averaging:
Typically set to 1 second for commissioning
UMJ29000 Issue 2
Page 11 of 26
2.7.2
Time Profile
Selected after initial commissioning to facilitate
adjustment to the PRV downstream pressure according
to specific times of the day or days of the week
Status:
Controlling (Control Started)
Mode:
Select Daily Profile 1
(Options of Daily Profile 1 or 2)
Editing of Profiles See Section 2.8
Vmax / Vmin:
Create PRV operating range for the
time profile
Target Pressure:
Select initial pressure for time period
Threshold:
Adjust to acceptable control tolerance
Averaging:
Adjust sample period to 5 seconds
UMJ29000 Issue 2
Page 12 of 26
2.7.3
Flow Profile
Typically used, after commissioning, to
compensate for frictional losses (Headloss)
within a distribution network
Status:
Controlling (Control Started)
Mode:
Select flow Profile
Editing of Profiles See Section 2.8
Vmax / Vmin:
Create PRV operating range for editing the time profile
Target Pressure:
Select starting pressure pressure for flow modulation
Threshold:
Adjust to acceptable control tolerance
Averaging:
Adjust sample period to 5 seconds
1 pulse =
Scale factor is determined from the pulse significance from the meter output
Calculate
Create Straight line (linear) or Curve profile (Headloss Compensation)
UMJ29000 Issue 2
Page 13 of 26
2.7.4
Closed Loop
Before Control
After Control
Threshold
Threshold
Cello
CP
Cello
CP
UMJ29000 Issue 2
Page 14 of 26
2.8
Profile Editor
2.8.1
Concept
The Control Profile Editor provides a graphical editing environment for working with pressure control profiles for
Regulo, including Modulo.
Multiple profiles can be opened and edited within an MDI (Multiple Document Interface) window similar to the way
Word, Excel, etc display multiple documents. Profiles can be read directly from a local logger or file for editing and
then saved back to the logger or a file.
2.8.2
Profiles
Flow
Flow verse Pressure relationship. Pressures are defined for each of 256 bands of flow. The size of each
flow band varies: small bands at low flows increasing to large bands at high flows. The active part of the
profile, where the pressure transitions from low to high, is normally located in a small number of bands
approximately 2/3 of the way into the profile.
Profile size (in bytes) = 256
Daily
Time verse Pressure relationship over 24 hours, with changes of pressure at an Interval specified in
minutes or hours (1 min 2 hours).
Profile size (in bytes) = 1440 / Interval x 2 (two profiles)
Weekly
Time verse Pressure relationship over 7 days, with changes of pressure at an Interval specified in
minutes or hours (1 min 2 hours).
Profile size (in bytes) = 10080 / Interval
For time profiles (Daily or Weekly) the Interval determines the size of the profile and whether it is
compatible with certain loggers and their configurations (see below).
The Interval normally remains fixed but a tool is available (Tools > Change Interval) to change a
profiles Interval if required.
Modulo supports 1 Flow and 2 Daily profiles, with Intervals in the range 6 mins 2 hours.
Regulo supports 1 Flow and either 2 Daily profiles or 1 Weekly profile, with Intervals in the range 1 min
to 2 hours. Regulo needs to be specially configured for Weekly profiles with intervals <20 minutes, or
Daily profiles with intervals <6 minutes.
2.8.3
The Editor may be started from within WinGPS using either the Tools>Edit Control Profile menu item, or the Edit
Profile button on the Pressure Control Tab. The main WinGPS window remains available for interaction with a logger
while the Editor window is open.
By default the editor will present a blank window where new profiles can be created or old ones opened.
If the editor is started while WinGPS is communicating with a logger then the currently active profile held in the logger
(Flow, Daily 1, Daily 2 or Weekly) will be automatically read and presented in a profile sub-window.
In the case of a Daily 1 or Daily 2 profile being active, both Daily profiles will be read into separate windows. If no
profile is active (e.g. Fixed Pressure mode) the user will be prompted to choose which profile(s) to read.
If profiles are read automatically then communication with the logger will be disconnected after reading, unless the
logger is controlling in which case communication will be maintained so that live markers can be displayed.
(See 2.8.4 Graph, Live Outlet Marker).
In most cases only the default active profile will be required for editing, but any profiles held in the logger may be read
using the File>Read from Logger menu option.
Each profile sub-window may be freely sized, minimised or maximised and it will re-annotate accordingly. The subwindows can also be selected and arranged using the Windows menu option.
UMJ29000 Issue 2
Page 15 of 26
Graph
The graph area of a profile window is automatically annotated with time/flow on the horizontal axis and pressure on
the vertical axis. Various tools are available (see 7. Tool Bar) to zoom in and out of profile data, move the graph area,
and edit the profile.
The following lines/markers may be visible on the graph:
Profile
Original Profile
Horizontal lines indicating the maximum and minimum PRV pressure as defined in the pressure
control settings for a logger.
These lines are enabled by default if theyre available (when reading profiles directly from a
logger or LGR file).
They are for information only and do not restrict the editing of the profile.
For profiles read directly from a logger, the Max & Min will change dynamically if the settings
are edited in the Pressure Control Tab of WinGPS.
May be turned on or off using View > Show PRV VMax & VMin
Horizontal lines on flow profiles indicating the maximum and minimum pressure values as
defined in Edit > Flow Properties.
These lines are enabled by default.
May be turned on or off using View > Show Network PMax & PMin
Vertical lines on flow profiles indicating the maximum and minimum flow values as defined in
Edit > Flow Properties
These lines are enabled by default if theyre available:
Fmax line shown if Fmax>0, and Fmin line shown if Fmin>0.
May be turned on or off using View > Show Network Fmax & Fmin
Overlay Data
Time verse Pressure data (time profile) or Flow verse Pressure data (flow profile) from loggers
in the network. See Tools > Overlay Data and Tools > Create Profile from Data.
May be turned on or off using View > Show Overlay Data
Live Outlet Marker. Shows the live Outlet pressure at the current loggers time or flow. For the
marker to be visible and updated WinGPS needs to be communicating with a logger that is
controlling and the Channels Tab or Pressure Control Tab must be displayed.
May be turned on or off using View > Show Live Outlet
The colours for each line may be changed using the options in the View > Line Colours menu.
2.8.5
The status line at the bottom of a profile window displays the following information:
Cursor location
Range
Interval
Profile Properties
For flow profiles, clicking on this area will activate Edit > Flow Profile Properties
UMJ29000 Issue 2
Page 16 of 26
2.8.6
File
New
Open
Close
Closes currently selected profile window. If the profile has been changed since it was
last saved then it will be queried for saving.
Save
Saves currently selected profile back to its original source (file or logger).
Save will be disabled for new profiles (source unknown).
Save As
Save To Logger
Exit
Exits the editor. Any profiles that have been changed since they were last saved will
be queried for saving before exiting. (Same as File>Close for each profile)
UMJ29000 Issue 2
Page 17 of 26
Edit
Undo
Undo editing operations. The number of possible times to undo is shown in the menu.
e.g. Undo (4) to a maximum of 5.
Undo will be disabled, if no undo available.
Copy
Do not use the Windows Clipboard so a copied profile is not available outside of the
editor and will be lost when the editor is closed.
Paste
Pastes a previously copied profile or profile section into the currently selected profile.
The menu will show what is available to paste: Paste Flow, Paste Flow Range,
Paste Day, Paste Week, or Paste Time Range.
Paste will be disabled if there is nothing to paste, or if the copied profile is not
compatible with the current profile.
By default any copied whole profile (Flow/Daily/Weekly) will be pasted to the whole of
the current profile. Pasting a Daily profile onto a Weekly profile will align the profile
with the day that the cursor is on.
If a range was copied (Paste Time Range, Paste Flow Range), the range will be
pasted from the start of the graph, or the position the cursor is at if using the Paste
option in the R-Click Context Menu.
If a range is selected prior to pasting, the copied profile will be placed into the selected
range, replicating and/or truncating as necessary to fill the range. For example, with a
Weekly profile and a Day ready to paste, selecting the whole week as a range and
then pasting the Day into it will replicate the day for all days of the week.
Table of Values
Opens a separate window with a table of the profile values, either Flow verse
Pressure or Time verse Pressure.
The position in the table that is first presented for editing is either the first value on the
graph or the first value in a selected range.
Pressure values can edited by selecting the value of interest and then changing the
value in the edit box, either by typing, clicking the up/down arrows, or using the mouse
scroll wheel. Cursor Up/Down, Page Up/Down, Home and End keys allow the table to
be navigated in addition to the normal scroll bar on the right hand side.
When a value is changed in the table the row will be highlighted in red and the profile
graph will immediately show the new value.
Click the Save button to keep changes, or Cancel to discard.
Change Interval
From Edit Control Profiles,
Tools, Change Interval
UMJ29000 Issue 2
Page 18 of 26
Show or hide the Original Profile line on the graph (see Graph)
Show or hide the horizontal PRV Max & Min lines on the graph (see Graph).
Only enabled when PRV Max & Min available.
Show or hide the vertical max & min flow lines on the graph.
Only enabled for Flow profiles.
Show or hide the live Outlet marker on the graph (see Graph).
Line Colours
Sub-menu to change the colours for each of the lines. New colours will be
automatically saved by the Editor and used for future sessions. The Restore
Defaults option restores the default line colours.
Tools
Overlay Data
Change Interval
Converts a time profiles interval from one value to another if more or less
time resolution is needed. The conversion will inevitably change the shape of
the profile to a greater or lesser degree. The compatibility restrictions
concerning loggers and configurations will apply with the new Interval.
(See 2.8.2 Profiles). Smoothing..
Converts a profiles pressure range from one value to another. This may be
used when exchanging transducers (e.g. 200m to 100m), or to convert from
one unit to another (e.g. 100m to 9.8Bar). If the different ranges have
different units then a conversion factor may be specified to allow conversion
between the units.
Window
Arrange
When there are multiple profile windows this sub-menu provides a quick way
to arrange windows alongside each other (Tile Horizontal and Tile Vertical),
or cascade them (Cascade).
Profiles
Each profile window has a menu item that can be selected to change focus to
that window. The currently selected window is shown with a check mark.
UMJ29000 Issue 2
Page 19 of 26
2.8.7
Tool Bar
Resets the graph scaling and annotation to show the complete time/flow range and the
complete pressure range.
Expands the pressure axis by a round number step to magnify the data. The maximum
expansion is when 1 division = pressure resolution.
If the pressure data does not overflow the top or bottom of the graph prior to expansion then
the expansion will be around the vertical mid-point of the data, which saves hunting for the
data after expansion. Otherwise, expansion will be around the mid-point of the pressure axis.
Compresses the pressure axis by a round number step to reduce the data. The maximum
compression is when the pressure axis shows 0 full scale pressure.
Magnifies the time/flow axis by a round number step to magnify the data. The maximum
expansion for time profiles is when 1 division = 1 minute, and for flow profiles it is 1 division =
smallest flow band.
For time profiles expansion will be around the mid-point of the time axis, and for flow profiles it
will be around the mid-point of a region visible on the graph where the pressure changes
(normally low to high).
If a range is selected then the graph will be expanded to show the selected range.
Compresses the time/flow axis by a round number step to reduce the data. The maximum
compression is when the time/flow axis shows the whole profile.
UMJ29000 Issue 2
Page 20 of 26
2.8.8
Right-clicking on the graph produces a menu that contains most of the Toolbar navigation and mode buttons,
together with the Copy and Paste items from the main Edit menu.
Using the Paste option on this menu is valuable because it allows the cursor to be accurately placed on the graph
prior to pasting (e.g. Day onto Week, or Range onto a graph). Ctrl+V will allow the same flexibility.
2.8.9
Dragging an LGR file from another application (e.g. Windows Explorer) and dropping it into the Profile Editor window
will cause the file to be opened as if it had been selected in File > Open.
UMJ29000 Issue 2
Page 21 of 26
Section 3
3.1
UMJ29000 Issue 2
Page 22 of 26
3.2
Fitting of the Pilot Bias chamber should be done with the PRV bypassed.
However if this is not possible the following steps can be taken with care.
This should be carried out by a competent engineer and should be completed quickly and at a time
where changes in flow demand are likely to be small.
UMJ29000 Issue 2
Page 23 of 26
UMJ29000 Issue 2
Page 24 of 26
10. Finally very slowly open the top cover isolating tap.
Monitor the outlet pressure all the time and make sure
it does not change.
Remove the pressure gauge from the system.
UMJ29000 Issue 2
Page 25 of 26
3.3
3.4
The Regulo has a magnetically triggered display as part of its standard design.
A programmable sequence activated by short touch, steps automatically:
Regulo -> Version number.
A Fixed sequence activated by long touch, steps manually:
Inlet, Outlet and Target -> Flow, Outlet and Target -> Status, Date and Time.
UMJ29000 Issue 2
Page 26 of 26