OVERVIEW OF TOPICS
13/11/2014
13/11/2014
13/11/2014
13/11/2014
13/11/2014
11
AUST STANDARDS
ESAA NENS 09:2004 / ENA NENS 09:2006
National Guidelines for Selection, Use and
Maintenance of PPE for Electrical Hazards
Applicable for Electric Utilities
Equation is based on single phase faults
3-Ph Heat Flux = 3 x 1-Ph Heat Flux
Cotton drill clothing of varying thickness/layers
Cotton can catch fire under arcing conditions !
185gsm cotton clothing for 10cal/cm2 !
12
13/11/2014
AUST STANDARDS
AS 4836 : 2011
Safe Working on or near LV Installations
Included arc flash PPE specs in 2011 edition
AUST STANDARDS
AS 4836 Testing / Fault Finding
PPE specs is based on Switchboard Rating
Up to 100A No need for Arc Flash PPE
100 400A Face Shield / Arc Flash Suit (if required)
400 1000A Face Shield necessary, AF Suit (if reqd)
13/11/2014
AUST STANDARDS
AS 3007 : 2013
Electrical Equipment in Mines and Quarries
Design shall include provisions for prevention of arc
flash / arc blast injury (Refer to AS 3439 / AS 3000)
Consideration must be given to remote switching
Clearly define arc flash levels and PPE required
For information on arc flash / arc blast protection,
refer to IEEE 1584 and NFPA 70E
15
16
13/11/2014
18
13/11/2014
19
10
13/11/2014
22
11
13/11/2014
23
12
13/11/2014
25
13
13/11/2014
27
28
14
13/11/2014
30
15
13/11/2014
HAZARD MITIGATION
Electrician awareness especially at LV boards
Most arc flash incidents are due to inadvertent
contact
Use appropriately designed equipment and tools, to
avoid possible contact with energised conductors
Use 8 or 12 cal/cm2 clothing as a minimum
Comfortable arc rated clothing is available now
Use arc rated face shield as a part electrical work
Comfortable combination helmet / face shield is
now available
32
16
13/11/2014
HAZARD MITIGATION
Ensure fast clearance for arc flash currents
(30 to 60% of bolted fault currents)
Conduct arc flash studies to establish arc
flash energy levels at switchboards
More stringent checks on O/C prot settings
Relays with two groups of protection
settings are now available Use them
Arc flash relays for high fault level boards
33
CONCLUSIONS
Be Aware of Arc Flash Hazard
415V Switchboards with high fault currents are
Dangerous
Trip Arc Flash Current Quickly - not just Bolted
Fault Current
Use Arc Rated PPE