Você está na página 1de 32

GB

HIGH PERFORMANCE GAS-FIRED WALL-MOUNTED BOILERS


OPERATING AND INSTALLATION INSTRUCTIONS

Dear Customer,
We are confident your new boiler will meet all your requirements.
All BAXI products have been designed to give you what you are looking for: good performance combined with simple
and rational use.
Please do not put away this booklet without reading it first as it contains some useful information which will help you to
operate your boiler correctly and efficiently.
Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential source of
danger.
Baxi S.p.A. declares that these models of boiler bear the CE mark in compliance with the basic
requirements of the following Directives:
- Gas Directive 90/396/EEC
- Efficiency Directive 92/42/EEC
- Electromagnetic Compatibility Directive 2004/108/EEC
- Low Voltage Directive 2006/95/EC

CONTENTS
INSTRUCTIONS FOR USERS
1. Instructions prior to installation
2. Instructions prior to commissioning
3. Commissioning the boiler
4. Adjusting CHW and DHW temperatures
5. Filling the system
6. Turning off the boiler
7. Gas conversion
8. Prolonged shutdown. Frost protection (central heating circuit)
9. Troubleshooting
10. Routine maintenance instructions

3
3
4
5
6
6
6
6
7
7

INSTRUCTIONS FOR FITTERS


11. General precautions
12. Instructions prior to installation
13. Boiler installation
14. Installation of flue and air ducts
15. Installation of flue and air ducts
16. Connecting the mains supply
17. Connecting the ambient thermostat
18. Gas conversion methods
19. Information on display
20. Parameter settings
21. Adjustment and safety devices
22. Positioning the ignition and flame-sensor electrode
23. Checking combustion parameters
24. Output/pump head performance
25. Connecting the external probe
26. Connection to an external storage boiler and three-way valve motor
27. Electrically connecting the climate controller
28. Connecting a zone heating system
29. Removing scale from the DHW circuit
30. Dismounting the water-water heat exchanger
31. Cleaning the cold water filter
32. Annual service
33. Circuit diagram
34. Illustrated wiring diagram
35. Technical specifications

8
8
9
9
10
13
13
14
15
16
18
19
19
20
20
22
22
23
24
24
24
25
26
28
32

BAXI S.p.A., a leading European manufacturer of hi-tech boilers and heating systems, has developed CSQcertified quality management (ISO 9001), environmental (ISO 14001) and health and safety (OHSAS 18001)
systems. This means that BAXI S.p.A. includes among its objectives the safeguarding of the environment, the
reliability and quality of its products, and the health and safety of its employees.
Through its organisation, the company is constantly committed to implementing and improving these aspects
in favour of customer satisfaction.

INSTRUCTIONS FOR USERS

C607504 - GB

1. INSTRUCTIONS PRIOR TO INSTALLATION


This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It must
be connected to a central heating system and to a domestic hot water supply system according to its performance and
power output.
Before having the boiler installed by a qualified service engineer, make sure the following operations are performed:
a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings
on the packaging and the rating plate on the appliance.
b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gases
from other appliances are expelled through the same flue duct, unless the latter has been specially designed to collect
exhaust gas from more than one appliance, in compliance with current laws and regulations.
c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual products of combustion may detach from the walls during operation and obstruct the flow of fumes.
d) To ensure correct operation and maintain the warranty, observe the following precautions:
1. DHW circuit
1.1. If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dispenser or an equivalent treatment system, compliant with current regulations.
1.2. Thoroughly flush the system after installation of the appliance and before use.
1.3. The materials used for the products DHW circuit comply with Directive 98/83/EC.
2. Heating circuit
2.1. new system

Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual
thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, plastic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products
are:

SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliance
with the manufacturers instructions.
2.2. existing system

Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable
proprietary products as described in section 2.1.

To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such
as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with the
manufacturers instructions.

Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.
overheating and excessive noise of the heat exchanger).
Failure to observe the above will render the guarantee null and void.

2. INSTRUCTIONS PRIOR TO COMMISSIONING


Initial lighting of the boiler must be carried out by an authorised Service Engineer who must first ensure that:
a) The rated data correspond to the supply (electricity, water and gas) data;
b) The installation complies with current laws and regulations, an excerpt of which is given in the manual intended for the
fitter.
c) The appliance is correctly connected to the power supply and earthed.
The names of the authorised Service Centres are indicated in the attached sheet. Failure to observe the above will render
the guarantee null and void.
Prior to commissioning, remove the protective plastic coating from the boiler. Do not use any tools or abrasive detergents
to do this as you may damage the painted surfaces.
The appliance is not intended to be used by persons (including children) with reduced physical, sensory or mental
capacities, or who lack experience or knowledge, unless, through the mediation of a person responsible for their
safety, they have had the benefit of supervision or of instructions on the use of the appliance.

INSTRUCTIONS FOR USERS

C607504 - GB

3. COMMISSIONING THE BOILER


To light the boiler correctly, proceed as follows:
Power the boiler;
Turn on the gas tap;
Press button
(approx. 2 seconds) to set the boiler operating mode as described in section 3.2.

NOTE: if the SUMMER

, mode is set, the boiler will only light during a DHW demand.

To set the desired CHW and DHW temperatures, press the +/- buttons as described in section 4.

WARNING

0609_2301

During initial ignition, the burner may not ignite (causing the boiler to shut down) until any air in the gas pipes is vented.
In this case, repeat the ignition procedure until gas reaches the burner. Press the RESET button ( ) for at least 2 seconds.

KEY TO SYMBOLS ON DISPLAY

TASTEN

Enable heating mode

DHW temperature settings (C)

Enable DHW mode


Heating temperature adjustment (C)

Flame present - figure 2


(power level 0 25 %)

RESET (boiler reset)

Flame modulation level - figure 2


(3 power levels)

ECO - COMFORT

Generic fault
MODE button (see section 3.2)
RESET
No water
(System pressure LOW)
Numerical signal
(Temperature, fault code, etc.)
ECO mode

Figure 1

If the optional climate controller is connected, always adjust the boiler using the climate controller. See the instructions accompanying this accessory item.

3.1 MEANING OF THE SYMBOL

Figure 2
INSTRUCTIONS FOR USERS

0603_1301

4 different boiler modulation levels may be shown during boiler


operation, as indicated in figure 2:

C607504 - GB

3.2 DESCRIPTION OF BUTTONS

(Summer - Winter - Heating only - Off)

Press this button to set the following operating modes:





SUMMER
WINTER
HEATING ONLY
OFF

. The boiler satisfies requests for DHW only while central heating is NOT
In the SUMMER mode, the display shows
enabled (ambient frost protection function active).
In the WINTER mode, the display shows
(ambient frost protection function active).

and

In the HEATING ONLY mode, the display shows


protection function active).

. The boiler satisfies requests for both DHW and central heating
. The boiler satisfies requests for central heating only (ambient frost

In the OFF mode, the display shows neither of the above two symbols
. In this mode, only the ambient frost protection function is active while requests for DHW and central heating are not satisfied.

3.3 ADDITIONAL INFORMATION


For more detailed technical information, please consult the SERVICE INSTRUCTIONS.

4. ADJUSTING CHW AND DHW TEMPERATURES


Adjust the heating flow temperature
and the DHW temperature
When the burner is lit, the control panel display shows the symbol .

, by pressing the respective +/- buttons (figure 1).

HEATING
The system must be fitted with an ambient thermostat for controlling indoor temperature.
While the boiler is operating in the heating mode, the display in figure 1 shows the flashing symbol
temperature (C) .

and the heating flow

DHW
While the boiler is operating in the DHW mode, the display in figure 1 shows the flashing symbol
and the storage boiler water
flow temperature (C).
Press P to set two different DHW temperature values, ECO and COMFORT. To modify the temperatures, proceed as follows
ECO
Press P, the display shows eco, set the required temperature by pressing +/- buttons.
COMFORT
Press P, the display shows just the temperature setting, and then +/- to set the required temperature setpoint.

NOTE: if a storage boiler is connected, during boiler operation in DHW mode, the display shows the symbol (

) and the sto-

INSTRUCTIONS FOR USERS

C607504 - GB

rage boiler flow temperature (C).

5. FILLING THE SYSTEM


IMPORTANT: Regularly check that the pressure displayed on the pressure gauge (Figure 3a) is 0.7 - 1.5 bar, with

the boiler cold. In case of overpressure, turn on the boiler drain tap. In case of insufficient temperature, turn on the boiler
filling tap (figure 3a or 3b).
Turn on the tap very slowly in order to vent the air. During this operation, the boiler must be OFF (press ( ) figure 1).

NOTE: The boiler is fitted with a hydraulic pressure gauge which prevents the boiler from working if there is no water.
If pressure drops occur frequently, have the boiler checked by an authorised Service Engineer.

180i AT - 240i - 240 Fi - 280 Fi

1.180i AT - 1.240Fi
0603_1303/CG_1791

0901_0802 / CG_1791

System filling tap


Pressure gauge

System drain tap

Figure 3a

Figure 3a

System filling tap

6. TURNING OFF THE BOILER


To turn off the boiler, disconnect the electric power supply. With the gas boiler in the OFF mode (section 3.2), the electric
circuits remain powered and the frost protection function is enabled (section 8).

7. GAS CONVERSION
The boilers can operate both on natural gas and LPG.
Any gas change must be effected by a Qualified Service Engineer.

8. PROLONGED SHUTDOWN. FROST PROTECTION


Do not drain the whole system as filling up with water again causes unnecessary and harmful scale to build up inside the
boiler and the heating elements. If the boiler is not used during winter and is therefore exposed to the danger of frost, add
some specific anti-freeze to the water in the system (e.g.: propylene glycol coupled with corrosion and scale inhibitors).
The electronic boiler management system includes a frost protection function for the heating system which, when flow
temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.
The frost protection function is enabled if:
*
*
*
*

the boiler is electrically powered;


the gas tap is open;
the system is at the correct pressure;
the boiler is not blocked.

INSTRUCTIONS FOR USERS

C607504 - GB

9. TROUBLESHOOTING

0605_1107

0605_1106

Faults are shown on the display with an error code (e.g.: E01):
The faults that can be reset by the user are indicated on the display with the symbol (figure 4).
The faults that cannot be reset by the user are indicated on the display with the symbol
(figure 4.1). To RESET the boiler,
press and hold down for at least 2 seconds.

Figure 4

Figure 4.1

CODE
DISPLAYED

TYPE OF FAULT

ACTION

E01

Ignition failure

Press

If this fault persists, call the Authorised Service Centre.

E02

Safety thermostat tripped

Press

If this fault persists, call the Authorised Service Centre.

E03

Fumes thermostat action

Call an authorised Service centre.

E04

Safety error due to frequent flame loss

Call an authorised Service centre.

E05

Flow sensor fault

Call an authorised Service centre.

E06

DHW sensor fault

Call an authorised Service centre.

E10

Hydraulic pressure switch block

Check that the pressure in the system is correct; See section


5. If this fault persists, call the Authorised Service Centre.

E11

Safety thermostat for low temperature system cuts in


(if connected)

Call an authorised Service centre.

E25

No water safety trip

Call an authorised Service centre.

E31

No connection with the climate controller

Call an authorised Service centre.

E35

Parasite flame (flame error)

Press

E51

Fumes pressure switch action during boiler operation

Call an authorised Service centre.

E52

Internal board error

Call an authorised Service centre.

E53

Fumes pressure switch action

Call an authorised Service centre.

E80

Internal climate controller error

Call an authorised Service centre.

E98

Internal board error

Call an authorised Service centre.

E99

Internal board error

Call an authorised Service centre.

If this fault persists, call the Authorised Service Centre.

10. ROUTINE MAINTENANCE INSTRUCTIONS


To keep the boiler efficient and safe, have it checked by the authorised Service Centre at the end of every operating period.
Careful servicing ensures economical operation of the system.
Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily flammable cleaners (e.g.: petrol, alcohol, and
so on). Always switch off the appliance before cleaning it (see section 6 Switching off the boiler).

INSTRUCTIONS FOR USERS

C607504 - GB

11. GENERAL PRECAUTIONS


The following notes and instructions are addressed to fitters to allow them to carry out trouble-free installation. Instructions for lighting and using the boiler are contained in the Instructions for Users section.
Moreover, the fitter must be legally qualified to install heating appliances.
Please, bear in mind the following.
This boiler can be connected to any type of double- or single-pipe convector plate, radiator or thermoconvector. Design the system sections as usual, though, bearing in mind the available flow-head at the plate, as shown in section 24.
Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential source
of danger.
Initial lighting of the boiler must be carried out by an authorised Service Engineer, as indicated on the attached sheet.
Failure to observe the above will render the guarantee null and void.

12. INSTRUCTIONS PRIOR TO INSTALLATION


This boiler has been designed to heat water to a temperature lower than boiling point at atmospheric pressure. It must
be connected to a central heating system and to a domestic hot water supply system according to its performance and
power output. Do the following before connecting the boiler:
a) Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings
on the packaging and the rating plate on the appliance.
b) Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gases
from other appliances are expelled through the same flue duct, unless the latter has been specially designed to collect
exhaust gas from more than one appliance, in compliance with current laws and regulations.
c) Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual products of combustion may detach from the walls during operation and obstruct the flow of fumes.
To ensure correct operation and maintain the warranty, observe the following precautions:
1. DHW circuit
1.1. If the water is harder than 20 F (1 F = 10 mg calcium carbonate per litre of water), install a polyphosphate dispenser or an equivalent treatment system, compliant with current regulations.
1.2. Thoroughly flush the system after installation of the appliance and before use.
1.3. The materials used for the products DHW circuit comply with Directive 98/83/EC.
2. Heating circuit
2.1. new system

Before proceeding with installation of the boiler, the system must be cleaned and flushed to eliminate residual
thread-cutting swarf, solder and any solvents, using suitable proprietary products. To avoid damaging metal, plastic and rubber parts, only use neutral cleaners, i.e. non-acid and non alkaline. Recommended cleaning products
are:

SENTINEL X300 or X400 and FERNOX Regenerator for heating circuits. Use these products in strict compliance
with the manufacturers instructions.
2.2. existing system

Before installing the boiler, drain the system and clean it to remove sludge and contaminants, using suitable
proprietary products as described in section 2.1.

To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such
as SENTINEL X100 and FERNOX Protector for heating circuits. Use these products in strict compliance with the
manufacturers instructions.

Remember that the presence of foreign bodies in the heating system can adversely affect boiler operation (e.g.
overheating and excessive noise of the heat exchanger).
Failure to observe the above will render the guarantee null and void.

WARNING

If an instantaneous (mixed) boiler is connected to a system with solar panels, the maximum temperature of the domestic
hot water entering the boiler must not exceed:
60C with flow limiting device
70C without flow limiting device

INSTRUCTIONS FOR FITTERS

C607504 - GB

13. INSTALLING THE BOILER


After deciding the exact location of the boiler, fix the template to the wall.
Connect the system to the gas and water inlets present on the lower bar of the template. Fit two G3/4 taps (flow and
return) on the central heating circuit; these taps make it possible to carry out important operations on the system without
draining it completely. If you are either installing the boiler on an existing system or replacing one, as well as the above,
fit a settling tank under the boiler on the system return line in order to collect any deposits and scale circulating in the
system after flushing. After fixing the boiler to the template, connect the flue and air ducts, supplied as accessories, as
described in the following sections.
If natural draught boilers are installed, connect them to the flue with a metal pipe resistant to normal mechanical stress,
heat, products of combustion and relative condensate.

0512_0504/CG1769

1.180 i AT - 1.240 Fi

: G 3/4 storage boiler flow - G 1/2 DHW inlet

: G 3/4 gas inlet to boiler

= BOILER WIDTH 450 =

180 i AT - 240 i - 240 Fi - 280 Fi

BOILER CONNECTION POINT

BOILER HEIGHT 780

: G 3/4 heating system flow/return

: G 3/4 heating system flow/return

: G 1/2 hot domestic water outlet/inlet

: G 3/4 gas input to boiler

0512_0503/CG1769

Figure 5

0512_0505/CG1769

14. DIMENSIONS OF BOILER


180 i AT - 240 i - 1.180 i AT

240 Fi - 280 Fi - 1.240 Fi

180i AT - 1.180i AT
240i

0606_2603

0705_0609

minimo

A = 110 mm
A = 130 mm

Figure 6

INSTRUCTIONS FOR FITTERS

C607504 - GB

15. INSTALLATION OF FLUE AND AIR DUCTS


model
240 Fi - 280 Fi - 1.240 Fi

0503_0905/CG1638

The boiler is easy and flexible to install thanks to the extensive


range of available accessories, as described below.
The boiler has been designed for connection to a vertical or horizontal coaxial flue-air duct. A splitting kit is also available if separate ducts are required.
Only accessories supplied by the appliance manufacturer
must be used for installation!

WARNING

To optimise operating safety, make sure the flue ducts are firmly
fixed to the wall with suitable brackets.
COAXIAL FLUE - AIR DUCT (CONCENTRIC)
Figure 7
0711_1901

This type of duct is used to discharge exhaust fumes and draw


combustion air both outside the building and if a LAS flue is fitted.
The 90 coaxial bend allows the boiler to be connected to a flue-air
duct in any direction as it can be rotated by 360. It can also be
used as a supplementary curve combined with a coaxial duct or a
45 curve.
If fumes are discharged outside the building, the flue-air duct must
protrude at least 18 mm from the wall to allow an aluminium weathering surround to be fitted and sealed to avoid water infiltrations.
Make sure there is a minimum upward slope towards the outside
of 1 cm per metre of duct.

Connector

Concentric
connector

A 90 curve reduces total duct length by 1 metre.


A 45 curve reduces total duct length by 0.5 metre.
Figure 8

15.1 HORIZONTAL FLUE INSTALLATION OPTIONS

L max = 4 m

0512_2001

L max = 4 m

L max = 3 m

INSTRUCTIONS FOR FITTERS

L max = 3 m

10

C607504 - GB

0512_2002

15.2 LAS FLUE DUCT INSTALLATION OPTIONS

L max = 4 m

15.3 VERTICAL FLUE INSTALLATION OPTIONS

0503_0908/CG1641

This type of installation can be carried out on either a flat or a pitched roof by fitting a flue terminal and a special weathering surround with sleeve (both available on request).

L max = 4 m

L max = 4 m

L max = 2 m

L max = 3 m

For detailed installation instructions, consult the technical data provided with the accessories.
SEPARATE FLUE AND AIR DUCTS
This type of installation makes it possible to discharge exhaust fumes both outside the building and into single flue ducts.
Comburent air can be drawn in at a different location from that of the flue terminal. The splitting kit comprises a flue duct
adaptor (100/80) and an air duct adaptor. For the air duct adaptor, fit the screws and seals previously removed from the
cap.

The 90 curve allows the boiler to be connected to a flue-air duct in any direction as it can be rotated by
360. It can also be used as a supplementary curve combined with a duct or a 45 curve.
A 90 curve reduces total duct length by 0.5
metre.
A 45 curve reduces total duct length by
0.25 metre.

Flue duct adaptor


Connector

0707_0803 / CG_1795

The first 90 curve is not included when calculating the maximum available length.

Figure 9

INSTRUCTIONS FOR FITTERS

11

C607504 - GB

0504_1806/CG_1794

15.4 DIMENSIONS OF SEPARATE OUTLETS

15.5 SEPARATE HORIZONTAL FLUE INSTALLATION OPTIONS


IMPORTANT: Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.
0503_2201/CG1643

In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.

(L1 + L2) max = 20 m

L max = 10 m

NB: For the C52 type, do not fit the flue and air duct terminals on opposite walls of the building.
The maximum length of the air duct is 10 metres. If the discharge duct is longer than 6 metres, install the condensate
collection kit, supplied as an accessory, near the boiler.

0503_0911/CG1644

15.6 SEPARATE VERTICAL FLUE INSTALLATION OPTIONS

L max = 10 m

L max = 9 m

IMPORTANT: if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct
passes through building walls.
For detailed installation instructions, consult the technical data provided with the accessories.
INSTRUCTIONS FOR FITTERS

12

C607504 - GB

16. CONNECTING THE MAINS SUPPLY


This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current
safety regulations.
Connect the boiler to a 230V single-phase earthed power supply using the supplied three-pin cable, observing correct
LIVE-NEUTRAL polarity.
Use a two-pole switch with a contact separation of at least 3 mm. When replacing the power supply cable, fit a harmonised HAR H05 VV-F 3x0.75mm2 cable with a maximum diameter of 8 mm.
Access to the power supply terminal block
disconnect the boiler from the mains power supply using the two-pole switch;
remove the two screws fixing the control panel to the boiler;
rotate the control panel;
remove the cover and access the wiring area (figure 10).
The 2A fast-blowing fuses are incorporated in the power supply terminal block (to check and/or replace the fuse, pull out
the black fuse carrier).

IMPORTANT: respect polarity L (LIVE) - N (NEUTRAL).

0512_0508/CG1770

(L) = Live (brown)


(N) = Neutral (light blue)
= Earth (yellow-green)
(1) (2) = Contact for ambient thermostat

Figure 10

WARNING

If the appliance is directly connected to an underfloor system, install a safety thermostat to prevent the latter from overheating.

17. CONNECTING THE AMBIENT THERMOSTAT


access the power supply terminal block (figure 10);
remove the jumper on terminals (1) and (2);
thread the two-wire cable through the grommet and connect it to these two terminals.

INSTRUCTIONS FOR FITTERS

13

C607504 - GB

18. GAS CONVERSION METHODS


The Technical Assistance Service can convert this boiler to natural gas (G20) or liquid gas (G31).
Carry out the following operations:
A) Replace the burner injectors
carefully pull the main burner off its seat;
replace the main burner injectors making sure to fully tighten them to prevent gas leaks. Injector diameters are specified
in table 1.
B) Change the modulator voltage
set parameter F02 according to the gas used, as described in
section 20.

Honeywell valve
Mod. VK 4105 M

C) Calibrate the pressure regulator

C1) Adjustment to nominal heat output


turn on the gas tap;
press
(Figure 1) and switch the boiler to the winter mode
(section 3.2);
turn on a hot water tap to reach a minimum 10 l/min flow rate
or ensure that maximum heating requirements are set;
remove the modulator cover;
adjust the brass screw (a) in Fig. 12 until the pressure values
shown in table 1 are obtained;
check that the boiler feeding dynamic pressure, as measured
at the inlet gas valve pressure test point (Pa) (Figure 11) is correct (37 mbar for propane gas, 20 mbar for natural gas).

0207_0406

connect the positive pressure test point of a differential pressure gauge (possibly water-operated) to the gas valve pressure test point (Pb) (Figure 11). Connect, for sealed chamber
models only, the negative pressure test point of the pressure
gauge to a T fitting in order to join the boiler adjusting outlet,
the gas valve adjusting outlet (Pc) and the pressure gauge .
(The same measurement can be carried out by connecting the
pressure gauge to the pressure test point (Pb) after removing
the sealed chamber front panel); If you measure the pressure
of burners in a different way you may obtain an altered result
in that the low pressure created in the sealed chamber by the
fan would not be taken into account.

Figure 11

0605_1701

C2) Adjustment to reduced heat output


disconnect the modulator power cable and unscrew the screw
(b) in Fig. 12 until a pressure value corresponding to reduced
heat output is achieved (see tab.1)
connect the cable again;
mount the modulator cover and seal.
C3) Final checks
mark on the data plate the type of gas and the calibration performed.

Figure 12

INSTRUCTIONS FOR FITTERS

14

C607504 - GB

TABLE OF BURNER PRESSURE AND INJECTORS

240 i

240 Fi - 1.240 Fi

280 Fi

Type of gas

G20

G31

G20

G31

G20

G31

Burner pressure (mbar*)


REDUCED POWER

2,1

6,4

3,0

5,5

2,3

4,0

Burner pressure (mbar*)


RATED POWER

8,8

28,9

12,5

25,0

13,3

23,9

Diameter of nozzles (mm)

0,87

0,5

0,82

0,52

0,82

0,55

Number of nozzles
* 1 mbar = 10,197 mm H2O
Table 1

30

34

180 i AT - 1.180 i AT

Type of gas
Burner pressure (mbar*)
REDUCED POWER
Burner pressure (mbar*)
RATED POWER
Diameter of nozzles (mm)

G20
2,9

G31
8,8

8,8

28,9

0,87

0,5

Number of nozzles
* 1 mbar = 10,197 mm H2O
Table 1

22

TABLE OF BURNER PRESSURE AND INJECTORS

240 Fi - 1.240 Fi

consumption 15 C - 1013 mbar

G20

G31

G20

G31

Rated power

2,78 m /h

2,04 kg/h

3,18 m /h

2,34 kg/h

Reduced power

1,26 m3/h

0,92 kg/h

1,26 m3/h

46,30 MJ/kg

34,02 MJ/m

p.c.i.
Table 2

34,02 MJ/m
3

0,92 kg/h
3

240 i

consumption 15 C - 1013 mbar

280 Fi

46,30 MJ/kg

180 i AT - 1.180 i AT

G20

G31

G20

G31

Rated power

2,78 m3/h

2,04 kg/h

2,05 m3/h

1,51 kg/h

Reduced power

1,26 m3/h

0,92 kg/h

1,12 m3/h

0,82 kg/h

46,30 MJ/kg

34,02 MJ/m3

46,30 MJ/kg

p.c.i.
Table 2

34,02 MJ/m
3

19. INFORMATION ON DISPLAY


To light the boiler correctly, proceed as follows:
Power the boiler.
When the gas boiler is power supplied, for approximately the first 8 seconds, the display backlighting is on. Then, it
displays the following information.
1. all symbols lit;
2. manufacturer information;
3. manufacturer information;
4. manufacturer information;
5. boiler and gas type (e.g.)
).
Die Bedeutung der angezeigten Zeichen ist folgende:

= open chamber boiler

= sealed chamber boiler;

= Natural gas used

= LPG gas used.

6. Hydraulic system;
7. Software version (two numbers x.x);

Turn on the gas tap;


Press button
(approx. 2 seconds) to set the boiler operating mode as described in section 3.2.
INSTRUCTIONS FOR FITTERS

15

C607504 - GB

19.1 OPERATING INFORMATION

Press ( ) for approx. 6 seconds. When the


function is enabled, the display shows A00
(A09) alternating with the respective value
(e.g. figure 13);

0706_1202

To display some useful information during the boiler


operation proceed as follows:

5 seconds

Press the +/- domestic hot water buttons to


display the following instantaneous information:

A00: domestic hot water temperature value (C);


A01: outside temperature (C) (with external probe
sensor connected);
A02: modulation current value (100% = 230 mA METHANE - 100% = 310 mA LPG);
A03: power range level value (%) - see parameter
F13 (section 20);
A04: temperature setpoint value (C);
A05: central heating flow temperature value (C);
A06: DHW flow value (l/min x 10);
A07: flame signal value (8-100%).
A09: pressure signal value of the flue pressure switch (Pa)

Figure 13

NOTE: display line A08 is not used


This function is active for 3 minutes. To interrupt the INFO function, press

19.2 FAULTS DISPLAY


See section 9 for error codes and anomalies description.

NOTE: the resetting operation is available only for 5 consecutive attempts, after which the gas boiler remains blocked.
To carry out a new RESET attempt, proceed as follows:

Press for approx. 2 seconds.


press for about 2 seconds, the display shows OFF;
reset the boiler operating mode as described in section 3.2.

19.3 ADDITIONAL INFORMATION


For more detailed technical information, please consult the SERVICE INSTRUCTIONS.

20. PARAMETER SETTINGS

Change parameters



To scroll the parameters press +/-.


Press +/- buttons to change the single parameter value.
Press the P button to save changes, the display shows MEM.
Press the button . to leave the function without saving, the display
shows ESC.

INSTRUCTIONS FOR FITTERS

16

0610_2504

To set the boiler parameters, press


and - ( ) together and hold down for at least 6 seconds. When the function is
activated, the display shows F01 alternated with the value of the parameter.

C607504 - GB

Factory settings

Description of parameters

180 i AT

1.180 i AT

240 i

240 Fi

F01

Types of gas boiler


30-40 = sealed chamber - 20 = atmospheric

F02

Gas used
00 = NATURAL - 01 = LPG

F03

Hydraulic system
00 = instantaneous appliance
05 = appliance with external storage boiler
08 = heating only appliance

F04

Programmable relay 1 setting


(02 = zone system - See SERVICE Instructions)

02

F05

Programmable relay 2 setting


04: fault signalling contact
05: Kitchen fan function (disabling, cooker extraction hood)
13: cool function for external conditioning system
(See SERVICE Instructions)

04

F06

External sensor programmable input setting (See SERVICE Instructions)

00

manufacturer information

00

F13

Max. heating output (0-100%)

100

F14

D.H.W. max. heating output (0-100%)

100

F15

Min. heating output (0-100%)

00

F16

Maximum temperature setpoint setting (C)


00 = 85C - 01 = 45C
CAUTION: If the appliance is directly connected to an underfloor system, install
a safety thermostat to prevent the latter from overheating

00

F17

Pump overrun time


(01-240 minutes)

03

F18

Burner ignition delay in CH mode


(00-10 minutes) - 00=10 seconds

03

F19

manufacturer information

07

F20

manufacturer information

--

F21

Anti-legionellosis function
00 = Disabled - 01 = Enabled

00

F22

manufacturer information

00

F23

Maximum DHW setpoint

60

F24

manufacturer information

35

F25

No water safety device

00

Manufacturer information (read-only parameters)

--

F30

manufacturer information

10

F31

manufacturer information

30

Diagnostics (See SERVICE Instructions)

--

F07F12

F26F29

F32F41

20

1.240 Fi
30

280 Fi
40

00 o 01

00

Final
Calibration function activation
parameter (See SERVICE Instructions)

08

00

00

08

00

WARNING: do not modify the values of the Manufacturer information parameters.

INSTRUCTIONS FOR FITTERS

17

C607504 - GB

21. ADJUSTMENT AND SAFETY DEVICES


The boiler has been designed in full compliance with European reference standards and in particular is equipped with the
following:
Air pressure switch (models 240 Fi - 1.240 Fi - 280 Fi)
This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.
In the event of one of the following faults:
the flue terminal is obstructed;
the venturi is obstructed;
the fan is blocked;
pressure switch is tripped
The boiler will stay on stand-by and the display shows error code E51 or E53 (see section 9).
Fumes thermostat (model 180 i AT - 1.180 i AT - 240 i)
This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the
burner if the flue duct is obstructed or in the event of draught failure.
In these conditions the boiler shuts down and displays error code E03 (section 9). To relight the main burner immediately,
see section 9.
It is forbidden to disable this safety device.
Safety thermostat
This device has a sensor positioned on the left section of the flue extraction hood and shuts off the gas flow to the
burner if the flue duct is obstructed or in the event of draught failure. Under such conditions the boiler is blocked and
only after the fault has been eliminated can it be ignited again.
In these conditions the boiler shuts down and displays error code E02 (section 9).
It is forbidden to disable this safety device.
Flame ionisation detector
The flame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas
failure or incomplete ignition of the burner.
In these conditions, the boiler is blocked after 3 ignition attempts. To reset normal operating conditions, ...
In these conditions the boiler shuts down and displays error code E01 (section 9).
hydraulic pressure switch
This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.
In these conditions the boiler shuts down and displays error code E01 (section 9).
Pump overrun for heating circuit
The electronically-controlled pump post-circulation function lasts 3 minutes (F17 - section 20) and is enabled, in the
heating mode, if the ambient thermostat causes the burner to go out.
Pump overrun for DHW circuit
The electronically-controlled pump post-circulation function lasts 30 seconds and is enabled, in the DHW mode, if the
probe causes the burner to go out.
Frost protection device (heating and DHW systems)
The electronic boiler management system includes a frost protection function for the heating system which, when
flow temperature falls below 5C, operates the burner until a flow temperature of 30C is reached.
Water not circulating in primary circuit (pump probably blocked)
If there is insufficient or no water circulating in the primary circuit, the boiler blocks and the error code E25 is shown on
the display (section 9).
Anti-block pump function
If no heat demand is received for 24 consecutive hours, the pump will automatically start and operate for 10 seconds.
This function is operative when the boiler is powered.
Three-way valve anti-blockage function
If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This
function is operative when the boiler is powered.
Hydraulic safety valve (heating circuit)
This device is set to 3 bar and is used for the heating circuit.

INSTRUCTIONS FOR FITTERS

18

C607504 - GB

Connect the safety valve to a drain trap. Do not use it to drain the heating circuit.
Anti-legionellosis function (model 1.180 i AT - 1.240 Fi with storage boiler)

The anti-legionellosis function is NOT enabled.


To enable this function, set parameter F21=01 (as described in section 20). When the function is enabled, the electronic
management of the boiler, at weekly intervals, heats the water contained in the storage boiler to over 60C (the function
only works if the water has never exceeded 60C in the previous 7 days).

NOTE: domestic hot water is guaranteed even if the NTC sensor develops a fault.
In this case, temperature is controlled by the flow sensor.

22. POSITIONING THE IGNITION AND FLAME-SENSOR ELECTRODE


240 Fi - 1.240 Fi - 280 Fi

0012180600

0206_0708

180 i AT - 1.180 i AT - 240 i

Figure 16

23. CHECKING COMBUSTION PARAMETERS


To measure combustion performance and the toxicity of the products of combustion, the boiler is fitted with two dedicated test points.
One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combustion products and the combustion efficiency.
The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion products
in case of coaxial pipelines.
The following parameters can be measured at the connection point on the flue gas circuit:
temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO2) concentration;
carbon monoxide (CO) concentration.
The temperature of the comburent air must be measured on the test point located on the air intake flue by inserting the
measurement sensor by about 3 cm.
For natural draught boiler models, a hole must be made in the flue gas discharge pipe at a distance from the boiler equal
to twice the inside diameter of the pipe itself.
The following parameters can be measured through this hole:
temperature of the combustion products;
oxygen (O2) or carbon dioxide (CO2) concentration;
carbon monoxide (CO) concentration.
The combustion air temperature must be measured close to the point where the air enters the boiler.
The hole, which must be made by the person in charge of operating the system when it is commissioned, must be sealed
in a way which ensures that the combustion product discharge pipe is airtight during normal operation.

INSTRUCTIONS FOR FITTERS

19

C607504 - GB

24. OUTPUT/PUMP HEAD PERFORMANCE


This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The air vent valve
incorporated in the pump allows quick venting of the heating system.

280 Fi

HEAD mH2O

HEAD mH2O

240 Fi - 1.240 Fi

FLOW l/h
Graph 1

FLOW l/h
Graph 2

0705_2101

0705_2102

HEAD mH2O

180 i AT - 1.180 i AT - 240 i

FLOW l/h
Graph 3

0705_2103

25. CONNECTING THE EXTERNAL PROBE


The boiler is prearranged for connection of an external probe (supplied as accessory). For the connection, refer to figures
below and the instructions supplied with the probe.

INSTRUCTIONS FOR FITTERS

20

C607504 - GB

models 180 i AT - 1.180 i AT - 240 i

models 240 Fi - 1.240 Fi - 280 Fi

CN 5

CN 5

0610_1301 / CG_1855

0705_2801 / CG_1941

Figure 17

Figure 17.1

0605_1604

models 1.180 i AT - 1.240 Fi

Figure 17.2

With the external probe connected, buttons +/- adjusting the heating circuit temperature ( ) (figure 1) regulate the coefficient of heat dispersion Kt (190). Charts below show the correspondence between the set value and the relative curves.
Intermediate curves can also be selected.

IMPORTANT: the maximum value of the flow temperature TM depends on the F16 parameter setting (see section
20). The maximum flow temperature may be 85 or 45C.

Graph 3

0603_0306

0603_0305

kt curves

Graph 4

TM - flow temperature
Te - external temperature

INSTRUCTIONS FOR FITTERS

21

C607504 - GB

26. CONNECTING AN EXTERNAL STORAGE BOILER


model 1.180 i AT - 1.240 Fi
CONNECTING THE STORAGE BOILER PROBE
The boiler is prearranged for connection of an external storage boiler. Hydraulically connect the storage boiler as shown in
figure. 18. Connect the NTC DHW priority probe to terminals 5-6 in the terminal block M2. The sensitive element of the NTC
probe must be inserted in the holder provided on the storage boiler. Adjust DHW temperature (35...65 C) by pressing +/-.

0702_1602

Key
UB storage boiler
UR heating unit
M three-way valve motor (accessory)
M2 connection terminal block
SB DHW priority storage boiler probe
MR heating flow
MB storage boiler flow
RR heating/storage boiler return
MOTOR

Figure 18

NOTE: Make sure parameter F03 = 05 (section 20).

27. ELECTRICAL CONNECTION OF THE CLIMATE CONTROLLER


The climate controller is not a
standard boiler component as
it is supplied as an accessory.
Open the electronic board and
connect the cable (supplied together with the two-pin terminal
board) to connector CN7 on the
boiler electronic board. Connect
the terminals of the climate controller to the two-pin terminal
board (figure 19).

0610_1302 / CG_1856

(SUPPLIED AS ACCESSORY)

CN 7

Figure 19

NOTE: for models 1.180 i AT and 1.240 Fi, connect the climate controller as described in section 28.1 (figure 20).
INSTRUCTIONS FOR FITTERS

22

C607504 - GB

28. CONNECTING A ZONE HEATING SYSTEM


28.1 CONNECTING THE RELAY BOARD

BOILER BOARD

CLIMATE CONTROLLER

0706_1203 / CG_1840

The relay board is not a standard boiler component as it is supplied as an accessory. Connect terminals 1-2-3 (common normally closed - normally open) of connector CN1 on the relay board, to the respective terminals 10-9-8 of boiler terminal
block M2 (figure 20).

RELAY BOARD ACCESSORY


RELAY 2

RELAY 1

Figure 20

28.2 CONNECTING THE ZONES

ZONE 1
ZONE 1
REMOTE CONTROL

CLIMATE CONTROLLER

ZONE 2
(AMBIENT THERMOSTAT)

ZONE 3
(AMBIENT THERMOSTAT)

ZONE N
(AMBIENT THERMOSTAT)

0709_2403 / CG_1825

Connect the contact relative to heating requests in zones that are not controlled by the climate controller in parallel to
terminals 1-2 TA on terminal block M1.
Remove the jumper.
The zone controlled by the climate controller is managed by the zone 1 solenoid, as illustrated in figure 21.

SOLENOID
ZONE 1

Figure 21

INSTRUCTIONS FOR FITTERS

23

C607504 - GB

29. REMOVING SCALE FROM THE DHW CIRCUIT


(Not contemplated in model 1.180 i AT - 1.240 Fi)
The DHW circuit can be cleaned without removing the water-water heat exchanger if the assembly is fitted with the special tap (available on request) located on the DHW outlet.
To clean, proceed as follows:
Turn off the DHW inlet tap
Drain the DHW system by turning on a hot water tap
Turn off the DHW outlet tap
Unscrew the two stopcocks
Remove the filters
If the special tap is not supplied, dismount the water-water heat exchanger, as described in the next section, and clean it separately.
Remove the scale from the seat and relative NTC sensor fitted on the DHW circuit.
To clean the exchanger and/or DHW circuit, use Cillit FFW-AL or Benckiser HF-AL.

30. DISMOUNTING THE WATER-WATER HEAT EXCHANGER


(Not contemplated in model 1.180 i AT - 1.240 Fi)
The stainless steel plate-type water-water heat exchanger is easily disassembled with a screwdriver by operating as described below:
drain the system, just the boiler if possible, through the drain tap;
drain the DHW system;
remove the two screws at the front securing the water-water heat exchanger and pull it out (figure 22).

31. CLEANING THE COLD WATER FILTER


(Not contemplated in model 1.180 i AT - 1.240 Fi)
The boiler is fitted with a cold water filter located on the hydraulic assembly. To clean, proceed as follows:
Drain the domestic hot water system.
Unscrew the nut on the flow sensor assembly (figure 22).
Pull out the flow sensor and its filter.
Remove any impurities.

IMPORTANT: when replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, not

fixing nut flow sensor

Figure 22

INSTRUCTIONS FOR FITTERS

0606_2703 / CG_1839

oil or grease.

water-water heat exchanger retaining screws

24

C607504 - GB

32. ANNUAL SERVICE


To optimise boiler efficiency, carry out the following annual controls:
check the appearance and air-tightness of the gaskets of the gas and combustion circuits;
check the state and correct position of the ignition and flame-sensing electrodes;
check the state of the burner and make sure it is firmly fixed;
check for any impurities inside the combustion chamber.
Use a vacuum cleaner to do this;
check the gas valve is correctly calibrated;
check the pressure of the heating system;
check the pressure of the expansion vessel;
check the fan works correctly;
make sure the flue and air ducts are unobstructed;
check for any impurities inside the siphon;
check the magnesium anode, where present, for boilers fitted with storage boilers.

WARNINGS

Before commencing any maintenance operations, make sure the boiler is disconnected from the power supply.
Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.

INSTRUCTIONS FOR FITTERS

25

C607504 - GB

33. CIRCUIT DIAGRAM


240 Fi - 280 Fi - 1.240 Fi
240 Fi - 280 Fi

1.240 Fi

CG_1925 / 0902_0301

0705_1804 / CG_1926

Heating
flow

DHW
Gas
outlet

DHW
inlet

Heating
return


Heating

flow

Figure 23

Key:

DHW
inlet

Heating
return

Key:

1 DHW priority sensor


2 hydraulic pressure switch
3 DHW NTC probe
4 three-way valve
5 non-return valve
6 3-way valve motor
7 gas valve
8 expansion vessel
9 flame detection electrode
10 NTC heating probe
11 safety thermostat
12 water-fumes exchanger
13 fumes conveyor
14 fan
15 concentric connector
16 air pressure switch
17 negative pressure point
18 ignition electrode
19 burner
20 pressure gauge
21 water-water plate exchanger
22 pump with air separator
23 boiler filling tap
24 boiler drain tap
25 safety valve
26 flow sensor with filter and water flow limiting device

INSTRUCTIONS FOR FITTERS

Storage
Gas
boiler
flow

1 automatic by-pass
2 hydraulic pressure switch
3 three-way valve
4 pressure gauge
5 3-way valve motor
6 gas valve
7 expansion vessel
8 flame detection electrode
9 NTC heating probe
10 safety thermostat
11 water-fumes exchanger
12 fumes conveyor
13 fan
14 concentric connector
15 air pressure switch
16 negative pressure point
17 ignition electrode
18 burner
19 automatic vent valve
20 pump with air separator
21 non-return valve
22 boiler drain tap
23 safety valve

26

C607504 - GB

180 i AT - 240 i - 1.180 i AT


180 i AT - 240 i

1.180 i AT
0705_1806 / CG_1923

CG_1924 / 0901_2902

Heating
flow

DHW
Gas
outlet

DHW
inlet

Heating
return


Heating

flow

Storage
Gas
boiler
flow

DHW
inlet

Heating
return

Figure 24

Key:

Key:

1 DHW priority sensor

1 automatic by-pass
2 hydraulic pressure switch
3 three-way valve
4 pressure gauge
5 3-way valve motor
6 gas valve
7 expansion vessel
8 ignition electrode
9 NTC heating probe
10 safety thermostat
11 water-fumes exchanger
12 fumes hood
13 fumes thermostat
14 flame detection electrode
15 burner
16 automatic vent valve
17 pump with air separator
18 non-return valve
19 boiler drain tap
20 safety valve

2 hydraulic pressure switch


3 DHW NTC probe
4 three-way valve
5 non-return valve
6 3-way valve motor
7 gas valve
8 expansion vessel
9 ignition electrode
10 NTC heating probe
11 safety thermostat
12 water-fumes exchanger
13 fumes hood
14 fumes thermostat
15 flame detection electrode
16 burner
17 pressure gauge
18 water-water plate exchanger
19 pump with air separator
20 boiler filling tap
21 boiler drain tap
22 safety valve
23 flow sensor with filter and water flow limiting device

INSTRUCTIONS FOR FITTERS

27

C607504 - GB

INSTRUCTIONS FOR FITTERS

28

THERMOSTAT

MAINS POWER
SUPPLY

FAN

IGNITION
ELECTRODE

PUMP

GAS VALVE
DETECTION
ELECTRODE

SAFETY
THERMOSTAT

NTC HEATING
PROBE

Cable colours
C = Light blue
M = Brown
N = Black
R = Red
B = White
G/V = Yellow/Green
V = Green

AIR PRESSURE
SWITCH

DHW NTC PROBE

DHW PRIORITY
SENSOR

HYDRAULIC PRESSURE
SWITCH

0711_1801 / CG_1930

34. ILLUSTRATED WIRING DIAGRAM


240 Fi - 280 Fi

C607504 - GB

INSTRUCTIONS FOR FITTERS

29

THERMOSTAT

MAINS POWER
SUPPLY

FAN

IGNITION
ELECTRODE

PUMP

GAS VALVE
DETECTION
ELECTRODE

SAFETY
THERMOSTAT

NTC HEATING
PROBE

Cable colours
C = Light blue
M = Brown
N = Black
R = Red
B = White
G/V = Yellow/Green
V = Green

AIR PRESSURE
SWITCH

DHW PRIORITY
SENSOR

HYDRAULIC
PRESSURE
SWITCH

0711_1802 / CG_1929

1.240 Fi

C607504 - GB

INSTRUCTIONS FOR FITTERS

30

THERMOSTAT

MAINS POWER
SUPPLY

THREE-WAY
VALVE

PUMP

GAS VALVE

IGNITION
ELECTRODE

DETECTION
ELECTRODE

SAFETY
THERMOSTAT

NTC HEATING
PROBE

FUMES
THERMOSTAT

Cable colours
C = Light blue
M = Brown
N = Black
R = Red
B = White
G/V = Yellow/Green
V = Green

DHW NTC PROBE

DHW PRIORITY
SENSOR

HYDRAULIC PRESSURE
SWITCH

0711_1906 / CG_1928

180 i AT - 240 i

C607504 - GB

INSTRUCTIONS FOR FITTERS

31

THERMOSTAT

MAINS POWER
SUPPLY

THREE-WAY
VALVE

PUMP

GAS VALVE

IGNITION
ELECTRODE

DETECTION
ELECTRODE

SAFETY
THERMOSTAT

NTC HEATING
PROBE

FUMES
THERMOSTAT

Cable colours
C = Light blue
M = Brown
N = Black
R = Red
B = White
G/V = Yellow/Green
V = Green

DHW PRIORITY
SENSOR

0711_1907 / CG_1927

1.180 i AT

C607504 - GB

35. TECHNICAL SPECIFICATIONS


Boiler model LUNA 3 BLUE
Category

180 i AT

1.180 i AT

II2H3P

II2H3P

240 i

240 Fi

1.240 Fi

280 Fi

Rated heat output


Reduced heat output
Rated heat power

Reduced heat power

Useful efficiency according to Directive 92/42/EEC
Central heating system max. pressure
Expansion vessel capacity
Expansion vessel pressure

kW
kW
kW
kcal/h
kW
kcal/h

bar
l
bar

19,4
10,6
17,5
15.050
9,3
8.000

3
8
0,5

19,4
10,6
17,5
15.050
9,3
8.000

3
8
0,5

26,3
11,9
24
20.600
10,4
8.900

26,3
11,9
24
20.600
10,7
9.202

26,3
11,9
24
20.600
10,7
9.202

30,1
11,9
28
24.080
10,7
9.202

3
8
0,5

3
8
0,5

3
8
0,5

3
10
0,5

Max. pressure in DHW system


Minimum dynamic pressure in DHW system

Minimum DHW output
DHW output at T=25 C
DHW output at T=35 C
Specific output (*)
Type

bar
bar
l/min
l/min
l/min
l/min

8
0,15
2,0
10
7,1
8
B11BS







B11BS

Temperature range in heating system


Temperature range in DHW system
Concentric flue duct diameter
Concentric air duct diameter

2-pipe flue duct diameter
2-pipe air duct diameter
Discharge pipe diameter B11BS

C
C
mm
mm
mm
mm
mm

3085
3560




110

3085





110

3085
3560




130

3085
3560
60
100
80
80

3085

60
100
80
80

3085
3560
60
100
80
80

Max. flue mass flow rate (G20)


Min. flue mass flow rate (G20)
Max. temperature of fumes
Min. temperature of fumes
NOx Class

kg/s
kg/s
C
C

0,015
0,012
116
90
5

0,015
0,012
116
90
5

0,021
0,017
120
86
5

0,018
0,013
135
106
5

0,018
0,013
135
106
5

0,016
0,010
140
108
5

Gas used
Natural gas feeding pressure 2H
(G20)
Propane gas supply pressure 3P
(G31)


mbar
mbar

G20-G31
20
50

G20-G31
20
50

G20-G31
20
50

G20-G31
20
50

G20-G31
20
50

G20-G31
20
50

Power supply voltage


Power supply frequency
Power consumption

V
Hz
W

230
50
110

230
50
110

230
50
110

230
50
135

230
50
135

230
50
165

Net weight
Dimensions
Height

width

depth
Protection-limit against humidity and water leakages (**)

kg
mm
mm
mm

31
763
450
345
IP X5D

29
763
450
345
IP X5D

33
763
450
345
IP X5D

41,5
763
450
345
IP X5D

39,5
763
450
345
IP X5D

42
763
450
345
IP X5D

II2H3P

II2H3P

II2H3P

II2H3P

8
8

8
0,15
0,15

0,15
2,0
2,0

2,0
13,7
13,7

16
9,8
9,8

11,4
10,5
10,5

12,5
B11BS C12 - C32 - C42 - C52 - C82 - B22

(*) according to EN 625


(**) according to EN 60529

As BAXI s.p.a. constantly strives to improve its products, it reserves the right to modify the information contained in this document at any time and without prior notice. These Instructions are only meant to provide consumers with use information and
under no circumstance should they be construed as a contract with a third party.

BAXI
Ediz. 1 - 09/09

S.p.A.

36061 BASSANO DEL GRAPPA (VI) ITALIA


Via Trozzetti, 20
Tel. 0424 - 517111
Telefax 0424/38089

C607504

Você também pode gostar