Escolar Documentos
Profissional Documentos
Cultura Documentos
P631/P632/P633/P634
Transformer Differential Protection
P631
P632
P633
P634
-302
-302
-302
-302
-401/402
-401/402
-401/402/403
-401/402
-602
-602
-602
-602
List of Contents
U-4
2
2.1
2.1.1
2.1.2
U-5
U-5
U-5
U-7
U-16
U-19
U-20
U-20
2.4
2.5
Functional Details
Serial Interfaces
PC Interface
"Logical" Communication
Interface 1
"Logical" Communication
Interface 2
Measured Data Input
Main Functions
Conditioning the Measured
Variables
Assignment of "Logical"
Communication Interfaces to
Physical Communication Channels
Multiple Signaling of the
Measuring-Circuit Monitoring
Function
Differential Protection
Thermal Overload Protection
2.6
Measuring-Circuit Monitoring
2.7
2.8
Overfluxing Protection
Programmable Logic
2.1.3
2.2
2.3
2.3.1
2.3.2
2.3.3
U-24
U-25
(Function Group DIFF)
(Function Groups
THRM_1 and THRM_2)
(Function Groups
MCM_1 to MCM_4)
(Function Group V/f)
(Function Group LOGIC)
U-25
U-27
U-29
U-31
U-39
U-3
In software version -602, several new features have been added to the P63x functions.
These will now be described with reference to the P631 / P632 / P633 / P634 manual with
print number AFSV.12.06661 EN.
In addition to the software changes, the following new order options have become
available:
Two options (with or without angle brackets) are offered for flush panel mounting. The
dimensional drawings and required panel cutouts are shown in the Supporting
Documents packed with the devices as are the location and terminal connection
diagrams.
1 Overview Changes in Software Version -602
Hardware
Connection
Plans
Software
-302
-401/402/403 -602
New Features
PC:
COMM1:
COMM2:
MEASI:
MAIN:
DIFF:
U-4
V/f:
LOGIC:
2 Functional Details
2.1 Serial Interfaces
The P63x has a PC interface as a standard component. Communication module A is
optional and can have one or two communication channels depending on the design
version. Communication between the P63x and the control stations computer is through
communication module A. Setting and readout are possible through all P63x interfaces.
If the communication module A with two communication channels is installed, settings for
two "logical" communication interfaces will be available. The settings for "logical"
communication interface 1 (COMM1) can be assigned to physical communication
channels 1 or 2 (see section entitled 'Main Functions'). If the COMM1 settings have been
assigned to communication channel 2, then this means that the settings for "logical"
communication interface 2 (COMM2) will automatically be active for communication
channel 1. Communication with the P63x via communication channel 2 is only possible
when the PC interface is inactive. As soon as communication occurs through the PC
interface, communication channel 2 is "dead". Channel 2 will then be re-enabled once
the PC interface Timeout has elapsed.
If tests are run on the P63x, the user is advised to activate the test mode so that the PC
or the control system will evaluate all incoming signals accordingly (see section entitled
"Main Functions").
2.1.1 PC Interface (Function Group PC)
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P63x and the PC to function, several settings must be made in
the P63x.
An operating program is available as an accessory for P63x control (see Chapter 13).
U-5
U-1
U-6
PC interface settings
MODBUS
DNP 3.0
COURIER
In order for data transfer to function properly, several settings must be made in the P63x.
The communication interface can be blocked through a binary signal input. In addition, a
signal or measured-data block can also be imposed through a binary signal input.
U-7
U-2
U-8
U-3
"Logical" communication interface 1: settings for the IEC 60870-5-103 interface protocol
U-9
U-4
U-10
"Logical" communication interface 1: settings for the IEC 870-5-101 interface protocol
U-5
U-11
U-6
U-12
U-7
U-13
U-8
U-14
Checking spontaneous
signaling
For interface protocols per IEC 60870-5-103, IEC 870-5-101 or ILS-C, there is the option
of selecting a signal for testing purposes. This transmission of this signal to the control
station as sig. start or sig. end can then be triggered via the local control panel.
U-9
U-15
U-16
U-10
U-17
Checking spontaneous
signaling
There is the option of selecting a signal for testing purposes. This transmission of this
signal to the control station as sig. start or sig. end can then be triggered via the local
control panel.
U-11
U-18
U-12
Figure in
the 601 Manual:
Replace by Figure:
3-19
U-12
U-19
U-20
Figure in
the 601 Manual:
Replace by Figure:
3-29
U-13
3-30a
U-14
3-30b
U-15
U-13
Connection of the measured variables to the P63x, connection of the fourth current transformer set to the transformers of the
neutral-point-to-ground connections
U-21
U-14
U-22
Connection of the measured variables to the P63x, looping of the fourth current transformer set into the ground connections of the
phase current transformers, Part 1 of 2
U-15
Connection of the measured variables to the P63x, looping of the fourth current transformer set into the ground connections of the
phase current transformers, Part 1 of 2
U-23
2.3.2
There are one or two communication channels available, depending on the design
version of communication module A (see section entitled "Technical Data"). The "logical"
communication interfaces COMM1 and COMM2 can be assigned to these physical
communication channels.
If "logical" communication interface COMM1 is assigned to communication channel 2,
then this means that the settings for "logical" communication interface 2 (COMM2) will
automatically be active for communication channel 1. Communication with the P139 via
communication channel 2 is only possible when the PC interface is inactive. As soon as
communication occurs through the PC interface, communication channel 2 is "dead".
Channel 2 will then be re-enabled once the PC interface Timeout has elapsed.
U-16
U-24
2.3.3
The signals of the measuring-circuit monitoring function are grouped to form a multiple
signal.
U-17
Replace by Figure
3-78
U-18
U-25
U-18
U-26
U-19
Replace by Figure:
3-111
U-20
U-27
U-20
U-28
U-21
U-29
Measuring-circuit
monitoring
The ratio of negative- to positive-sequence current is used as the criterion for measuringcircuit monitoring. The measuring-circuit monitoring function is triggered if the set ratio
Ineg / Ipos is exceeded and either the negative- or the positive-sequence current exceeds
0.02 Inom. After the set operate delay period has elapsed, a warning signal is issued.
U-22
U-30
U-23
U-31
U-24
U-32
U-25
Warning stage
U-33
U-26
U-34
100
t/s 10
1.00
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
V/f
U-27
U-35
After a starting, the elapsed starting time is accumulated in a buffer. If the starting drops
out, the buffer memory will be discharged. The discharge gradient is determined by the
set cooling time. If there is another starting, the buffer memory will be recharged. If the
accumulated starting time reaches the tripping time determined by the P63x then the trip
signal is issued. Figure U-28 shows the buffer content during an interrupted starting. In
case A, the tripping time determined by the P63x is not reached by the accumulated
starting time. In case B, on the other hand, a trip signal results.
U-28
U-36
U-29
U-37
U-30
U-38
U-39
energy.automation-information@areva-td.com