The Influence of Cable Capacitance, Generator

Neutral Grounding and Zig-zag Transformer to Third


Harmonic Produced by Synchronous Generator
M. F. Abdullah, N. H. Hamid, Z. Baharudin, M. H. S. A. Razak and M. I. B. Hisham
Electrical and Electronic Engineering Department, Universiti Teknologi PETRONAS
31750, Tronoh, Perak, Malaysia
mfaris_abdullah@petronas.com.my

synchronous generator related to harmonic distortion level


produced by load. Parallel resonance contributed by network
capacitance in cable, inverter, and household with inductance
in transformer and cable has resulted higher voltage distortion.
While series resonance would cause higher current distortion
when large number of power inverters are connected in the
system [3].

AbstractSalient pole synchronous generator is one of harmonic


sources that causes various power system harmonic problem
especially related to neutral. This paper aims to study the
characteristics of third harmonic voltage and current from
generator when connected to balanced load via cable, generator
load connection with different generator neutral grounding
resistor and generator load connection shunted by zig-zag
transformer. Lab scale experiments have been conducted to vary
all parameters related to cable capacitor and generator neutral
grounding resistor under various combined resistive and
inductive load. Cable capacitance which depends on cable length,
size and number of parallel cable, combined with load impedance
determines the third harmonic current magnitude. The presence
of cable capacitance that interact with generator inductance
resulted to series harmonic resonance at 9th and 15th harmonic
order that causes high 9th and 15th harmonic current flowing
between generator and cable capacitor. Generator neutral
grounding resistor can effectively reduce the third harmonic in
the phase and neutral. However care should be taken not to use
very high generator neutral grounding resistor that can also
restrict earth fault current that may pose problem to the
sensitivity of earth fault protection system. Zig-zag transformer
efficiently divert third harmonic current from generator to enter
the load but high circulating third harmonic current between
generator and zig-zag transformer may pose heating problem to
the equipments.

Electrical parameters of the subsea cable such as cable


capacitance affect the frequency response characteristics for the
same length of different types of subsea cables, although its
influence is not as large as the cable length [4]. The influence
of subsea cable shunt capacitance on harmonic distortion due to
parallel resonance is investigated in detail by [5].
Triplen harmonic current from synchronous generator
return to its neutral via cable capacitance and has caused the
neutral grounding resistor to experience high temperature when
connected to distribution grid [6]. Various transformer winding
configuration of distributed generation interconnection
transformer and neutral grounding reactor sizing have positive
or negative impact on the triplen harmonic current [7]. Triplen
harmonic current is one of the causes contributed to neutral
grounding resistor failure apart from lightning, storms,
earthquakes, extreme temperature changes, vibration etc. [8].
Simulation conducted by [9] has shown that zig-zag
transformer is very effective to reduce triplen harmonic current
from utility entering the load.

Keywords-Third harmonic voltage; third harmonic current;


synchronous generator; cable capacitance; grounding

I.

The objective of this paper is to study the influence of cable


capacitance, generator neutral grounding resistor and zig-zag
transformer on third harmonic voltage and current produced by
low voltage synchronous generator directly connected to
balanced load. In varying the parameters, lab experiment was
conducted and the methodology is described in section II. The
experimental results is presented and discussed in Section III.
Finally the conclusion and recommendation is tabled in
section IV. The term generator will be used to represent salient
pole synchronous generator in the remaining text of this paper.

INTRODUCTION

Harmonic becomes important when their presence in power


system can cause problem to equipment functionality. Some of
these problems related to harmonic voltage and the other to
harmonic current or both. The advancement of electronic
industry resulted in devices that are sensitive to the voltage and
current inputs.
Generally, harmonic study does not go beyond
50th harmonic since above that level their existence is
negligible due to high impedance posed by the power system
network at that frequency. Third harmonic is the first harmonic
number of triplen harmonic which are 3rd, 9th, 15th, etc. series.
Large round rotor synchronous generator in a thermal
power plant has been reported to produce harmonic even under
no load condition [1]. Experiment carried out by [2] revealed
that under various load condition, voltage regulation of

II.

METHODOLOGY

The simulated results on the influence of cable length,


number of parallel cable, cable size and neutral grounding
resistor size on the magnitude of third harmonic current have
been reported by [10]. Lab scale experiment are conducted in
three parts namely, generator directly connected to balanced
load via cable, generator directly connected to balanced load

This work was supported in part by Universiti Teknologi PETRONAS


(UTP)

978-1-4673-4584-2/12/$31.00 2012 IEEE

380

IPEC 2012

The third harmonic current magnitude at generator terminal


is the vector sum of third harmonic current flowing through
cable capacitor and load. Therefore, the magnitude of third
harmonic current at generator terminal depends on combined
impedance of cable capacitor and load. Regardless of load
impedance phase angle magnitude, the magnitude of third
harmonic current at cable capacitor terminal always increase
with increase in cable capacitance. Fig. 2 shows the third
harmonic current magnitude at generator, cable capacitor and
load terminals for combined resistive and inductive load of
686+j686 .

B. Generator Neutral Grounding Resistor


Different value of generator neutral grounding resistor is
applied to generator and load that are connected in star.
Common neutral connection is made for generator with neutral
grounding resistor and load. Combined resistive and inductive
loads are varied for every generator grounding resistor value.
Third harmonic phase/neutral currents and voltages are
measured at generator and load terminals.
C. Generator Shunted by Zig-zag Transformer
In this experiment, generator and load are connected in star
with no neutral impedance. Zig-zag transformer is connected
between the generator and load. Common neutral connection is
made for generator, zig-zag transformer and load. Combined
resistive and inductive loads are varied throughout the
experiment. Third harmonic phase/neutral currents and
voltages measurements are taken at generator, zig-zag
transformer and load terminals.
III.

RESULTS

Recorded experimental third harmonic voltage and current


are phase measurement. Symmetrical and balanced three phase
harmonic voltages produced by generator are:
Va=V1ejwt+ V2ej2wt+ V3ej3wt+.
2

jwt

jwt

j3wt

+.

(2)

j2wt

j3wt

Vc=aV1e + a V2e

+.

(3)

+ V3e

+ V3e

14
12
10
8
4

b' phase

c' phase

Neutral
0.66uF

1.33uF

1.99uF

2.65uF

Load=686+j686
Generator terminal

Third Harmonic Voltage


14
12
10
8

a' phase

6
4

b' phase

c' phase

Neutral
0.66uF

1.33uF

1.99uF

2.65uF

Load=686+j686
Capacitor terminal

Third Harmonic Voltage

where, a=

14
12

Va= V3ej3wt

(4)

Vb= V3ej3wt

(5)

j3wt

(6)

Voltage (V)

Therefore, third harmonic voltage:

Vc= V3e

a' phase

(1)

j2wt

Vb=a V1e + aV2e

Third Harmonic Voltage


Voltage (V)

A. Generator Connected to Load Via Cable


Generator and load are connected in star with no neutral
impedance. Cable capacitor is connected between the generator
and load. Common neutral connection is made for generator,
cable capacitor and load. Different combined resistive and
inductive load are varied with different values of cable
capacitances in the experiment. Third harmonic phase/neutral
currents and voltages measurements are taken at generator,
cable capacitor and load terminals.

in Fig. 1 for combined resistive and inductive load of


686+j686 .

Voltage (V)

with different value of generator neutral grounding resistor and


generator directly connected to balanced load shunted by
zig-zag transformer. Due to generators reactive power
limitation, the cable is only represented by its capacitance
without resistance and inductance. All the experiments will be
using a three-phase 415 V, 50 Hz, 0.2 kW generator as
harmonic source.

A. Generator Connected to Load Via Cable


The first part of the experiment is to vary the cable
capacitance for different fixed loads. The third harmonic
voltage magnitude at generator, cable capacitor and load
terminals decrease when the cable capacitance increase
regardless of load impedance phase angle magnitude as shown

381

10
8

a' phase

6
4

b' phase

c' phase

Neutral
0.66uF

1.33uF

1.99uF

2.65uF

Load=686+j686
Load terminal

Fig. 1. Third harmonic voltage at generator, cable capacitor and load terminals
for combined resistive and inductive load 686+j686 

phase angle magnitude. Fig. 4 shows the third harmonic current


magnitude at generator, cable capacitor and load terminals for
1.99F cable capacitance.

Third Harmonic Current


Current(mA)

50
40
30

The harmonic current spectrum when generator directly


connected to a combined resistive and inductive load show that
almost no current at other harmonic number except third
harmonic. Harmonic series resonance is observed at 9th and 15th
harmonic number and the highest harmonic current of both
harmonic numbers at resonance is shown in Fig. 5. Resonance
at 9th harmonic number occurred at higher capacitor value
while resonance at 15th harmonic number detected at lower
capacitor value.

a' phase

20

b' phase

10

c' phase

Neutral
0.66uF

1.33uF

1.99uF

2.65uF

Load=686+j686
Generator terminal

Third Harmonic Current

Third Harmonic Voltage

70
50
40

Voltage (V)

Current(mA)

60

a' phase

30
20

b' phase

10

c' phase

Neutral
0.66uF

1.33uF

1.99uF

2.65uF

16
14
12
10
8
6
4
2
0

Neutral

Third Harmonic Voltage


Voltage (V)

Current(mA)

Third Harmonic Current

a' phase
b' phase
c' phase
Neutral
1.99uF

c' phase

Cable capacitance=1.99uF
Generator terminal

18
16
14
12
10
8
6
4
2
0
1.33uF

b' phase

686+j120 686+j240 120+j960 686+j686 686+j1200

Load=686+j686
Capacitor terminal

0.66uF

a' phase

2.65uF

16
14
12
10
8
6
4
2
0

a' phase
b' phase
c' phase
Neutral
686+j120 686+j240 120+j960 686+j686 686+j1200

Load=686+j686
Load terminal

Cable capacitance=1.99uF
Capacitor terminal

Fig. 2. Third harmonic current at generator, cable capacitor and load terminals
for combined resistive and inductive load 686+j686 

The third harmonic current magnitude at generator terminal


is the vector sum of third harmonic current flowing through
cable capacitor and load. Therefore, the magnitude of third
harmonic current at generator terminal depends on combined
impedance of cable capacitor and load. Regardless of cable
capacitance values, the magnitude of third harmonic current at
cable capacitor terminal is proportional to the load impedance

382

Voltage (V)

Third Harmonic Voltage

The combined resistive and inductive load is varied for


different fixed capacitance value in the second part of the
experiment. The third harmonic voltage magnitude at
generator, cable capacitor and load terminals are proportional
to the load impedance phase angle magnitude as shown in
Fig. 3 for 1.99F cable capacitance. The bigger the load
impedance phase angle magnitude, the bigger the voltage
magnitude.

16
14
12
10
8
6
4
2
0

a' phase
b' phase
c' phase
Neutral
686+j120 686+j240 120+j960 686+j686 686+j1200
Cable capacitance=1.99uF
Load terminal

Fig. 3. Third harmonic voltage at generator, cable capacitor and load terminals
for 1.99F cable capacitance

Harmonic Current Spectrum

60

60.00

50

50.00

Current(mA)

Current(mA)

Third Harmonic Current


40
30

a' phase

20

b' phase

10

c' phase

Neutral

40.00
30.00
20.00

'a' phase

10.00

'b' phase

0.00
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48

686+j120 686+j240 120+j960 686+j686 686+j1200

'c' phase

Harmonic number
Load=686+j686 Capacitance=0.66uF
Capacitor terminal

Cable capacitance=1.99uF
Generator terminal

Fig. 5. Harmonic current spectrum for 9th and 15th harmonic resonance

Current(mA)

Third Harmonic Current


80
70
60
50
40
30
20
10
0

a' phase
b' phase
c' phase
Neutral
686+j120 686+j240 120+j960 686+j686 686+j1200
Cable capacitance=1.99uF
Capacitor terminal

Current(mA)

Third Harmonic Current


40
35
30
25
20
15
10
5
0

a' phase
b' phase
c' phase
Neutral
686+j120 686+j240 120+j960 686+j686 686+j1200

B. Generator Neutral Grounding Resistor


The generator neutral grounding resistor is varied for
various combined resistive and inductive load. The third
harmonic voltage at generator terminal is almost constant for
all generator neutral grounding resistor values. However, at
load terminal, the third harmonic voltage decrease as the
neutral grounding resistor values increase as shown in Fig. 6
for combined resistive and inductive load of 686+j686 . This
is due to voltage drop at neutral grounding resistor since the
third harmonic current is present in the neutral. The magnitude
reduction of third harmonic voltage is influenced by the
neutral grounding resistance because the neutral third
harmonic current is small.
The phase and neutral third harmonic current at generator
and load terminals decrease as the neutral grounding resistor
values increase as shown in Fig. 7. Almost zero sequence in
nature, the phase neutral current sum at neutral hence resulting
neutral current almost three times phase current magnitude.
The net series impedance of neutral grounding resistor value
and combined resistive and inductive load value determine the
phase/neutral third harmonic current magnitude.

Cable capacitance=1.99uF
Load terminal

Third harmonic voltage


14.00

Fig. 4. Third harmonic current at generator, cable capacitor and load terminals
for 1.99F cable capacitance
Voltage (V)

12.00

Harmonic Current Spectrum


Current(mA)

200.00

10.00
8.00

a' phase

6.00
4.00

b' phase

2.00

c' phase

0.00

150.00

Neutral
0

100.00
'b' phase

0.00
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48

120

240

480

Neutral Grounding Resistor value (ohm)


Generator Terminal

'a' phase

50.00

80

'c' phase

Harmonic number
Load=686+j120 Capacitance=2.65uF
Capacitor terminal

383

960

times phase current magnitude. In Fig. 9, almost all third


harmonic current for phase and neutral from generator flow
through zig-zag transformer and very small amount flow to the
load for all combined resistive and inductive load. This is
because zig-zag transformer provides the least impedance to
ground as compared to combined resistive and inductive load
for third harmonic current to flow.

Third harmonic voltage


14.00

Voltage (V)

12.00
10.00
8.00

a' phase

6.00
4.00

b' phase

2.00

c' phase

0.00

Neutral
0

80

120

240

480

Third harmonic voltage

960
6.00

Neutral Grounding Resistor value (ohm)


Load Terminal

Voltage (V)

5.00

Fig. 6. Third harmonic voltage at generator and load terminals for combined
resistive and inductive load 686+j686 

4.00
a' phase

3.00

b' phase

2.00

c' phase

1.00

Neutral

0.00
686+j686

18.00
16.00
14.00
12.00
10.00
8.00
6.00
4.00
2.00
0.00

686+j1200

686+j4800

4800+j686

Generator terminal

a' phase

Third harmonic voltage

b' phase

6.00

c' phase

5.00

Neutral
0

80

120

240

480

960

Voltage (V)

Current (mA)

Third harmonic current

Neutral Grounding Resistor value (ohm)


Generator Terminal

4.00
a' phase

3.00

b' phase

2.00

c' phase

1.00

Neutral

0.00
686+j686

18.00
16.00
14.00
12.00
10.00
8.00
6.00
4.00
2.00
0.00

686+j1200

686+j4800

4800+j686

Zig-zag transformer terminal

a' phase

Third harmonic voltage

b' phase

6.00

c' phase

5.00

Neutral
0

80

120

240

480

960

Voltage (V)

Current (mA)

Third harmonic current

Neutral Grounding Resistor value (ohm)


Load Terminal

4.00
a' phase

3.00

b' phase

2.00

c' phase

1.00

Fig. 7. Third harmonic current at generator and load terminals for combined
resistive and inductive load 686+j686 

Neutral

0.00
686+j686

686+j1200

686+j4800

4800+j686

Load Terminal

C. Generator Shunted by Zig-zag Transformer


The third harmonic voltage at generator, zig-zag
transformer and load terminals are quite constant for every
combined resistive and inductive load as shown in Fig. 8.
Higher load impedance phase angle magnitude yield higher
voltage magnitude at generator, zig-zag transformer and load
terminals.
Almost zero sequence in nature, the phase neutral current
sum at neutral hence resulting neutral current almost three

384

Fig. 8. Third harmonic voltage at generator, zig-zag transformer and load


terminals for combined resistive and inductive load

Generator neutral grounding resistor provides additional


impedance in the neutral and their resultant impedance with
combined resistive and inductive load determines the
magnitude of third harmonic current. Practically, generator
neutral grounding resistor can be used to reduce third harmonic
current from generator.

Third harmonic current


350.00

Current (mA)

300.00
250.00
200.00

a' phase

150.00

b' phase

100.00

c' phase

50.00

Zig-zag transformer exhibits low impedance earth path for


third harmonic current to return to generator neutral. It diverts
the generator third harmonic current from flowing to the load
but very high third harmonic current circulating between
generator and zig-zag transformer. This may pose heating
problem to generator, zig-zag transformer and generator neutral
grounding resistor.

Neutral

0.00
686+j686

686+j1200

686+j4800

4800+j686

Generator terminal

ACKNOWLEDGMENT

Third harmonic current

The authors would like to thank Universiti Teknologi


PETRONAS (UTP) in particular Research & Innovation Office
(RIO) in providing Short Term Internal Research Fund
(STIRF) for this study.

350.00

Current (mA)

300.00
250.00
200.00

a' phase

150.00

b' phase

100.00

c' phase

50.00

REFERENCES
[1]

Neutral

0.00
686+j686

686+j1200

686+j4800

4800+j686

Zig-zag transformer terminal

Third harmonic current


12.00

Current (mA)

10.00
8.00
6.00
4.00
2.00
0.00
686+j686

686+j1200

686+j4800

4800+j686

Load Terminal

Fig. 9. Third harmonic current at generator, zig-zag transformer and load


terminals for combined resistive and inductive load

IV.

CONCLUSION

The cable capacitor provides the earth path for third


harmonic current to return to generator neutral. Since cable
capacitance is in parallel connection with combined resistive
and inductive load, their net impedance decides the magnitude
of third harmonic current. The presence of cable capacitance
and generator inductance creates series resonance at 9th and 15th
harmonic number. In practice the cable capacitance value
represents cable length, size and number of cable in parallel.

385

Zaneta, B. Anton, M. Mucha, Harmonic Distortion Produced by


Synchronous Generator in Thermal - Power Plant, Proceedings of the
6th WSEAS International Conference on Power Systems, Lisbon,
Portugal, September 22-24, 2006.
[2] A.H. Samra, and K.M. Islam, Harmonic effects on synchronous
generators voltage regulation, Proc. of IEEE Southeastcon95, 26-29
March 1995, USA, pp.376-380.
[3] J. H. R. Enslin and P. J. M. Heskes, Harmonic interaction between a
large number of distributed power inverters and the distributed
network, IEEE Trans. Power Electron., vol. 19, no. 6, pp. 15861593,
Nov. 2004.
[4] X. Liang , S. O. Faried and O. Ilochonwu, "Subsea cable applications in
electrical submersible pump systems", IEEE Trans. Ind. Appl., vol. 46,
no. 2, pp.575 -583 2010.
[5] X. Liang, W. M. Jackson, Influence of Subsea Cables on Offshore
Power Distribution Systems,
IEEE Transactions On Industry
Applications, Vol. 45, No. 6, pp. 2136-2144 November/December 2009.
[6] M. F. Abdullah, N. H. Hamid, Z. Baharudin, M. F. I. Khamis, N. S. R.
Hashim, S. Yusof, Investigation On High Neutral Earthing Resistor
Temperature When Islanded Generator Connected To Utility Grid, The
9th International Power and Energy Conference, Oct. 2010.
[7] R. F. Arritt, R. C. Dugan, Distributed generation interconncetion
transformer and grounding selection, IEEE Power and Energy Society
General Meeting - Conversion and Delivery of Electrical Energy in the
21st Century, USA, 2008.
[8] D. Selkirk, M. Savostianik, K. Crawford, The Dangers of Grounding
Resistor Failure, IEEE Industry Applications Magazine , Sept/Oct.
2010.
[9] H. L. Jou, J. C. Wu, K. D. Wu, W. J. Chiang, Y. H. Chen, Analysis of
zigzag transformer applying in the three-phase four-wire distribution
power system, IEEE Trans. Power Delivery, vol. 20, no. 2, pp.1168
1173, Apr. 2005.
[10] M. F. Abdullah, N. H. Hamid, Z. Baharudin and M. F. I. Khamis,
Triplen Harmonics Currents Propagation Through Medium Voltage
Distribution Network, Fourth International Conference on Modeling,
Simulation
&
Applied
Optimization,
April,
2011.

Você também pode gostar