Transformer Sequence Impedance Test Sheets

Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T201

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Positive Sequence Impedance


a.

The test is done by keeping the LV Side Short Circuited and HV Side is supplied with 3 phase 400V AC Supply.

b.

The test have been carried out for Nominal Tap, Highest and Lowest TAP
HV

Ea

LV

Test 1:- HV Sup

Eb

Ec

Transformer Sequence Impedance Test Sheets


1 of 30

Tap Position

Voltage Applied
(V)

238.4

11

229.6

25

228.9

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T201

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

b.

The various Cases of Tests have been provided below

Case 1:- HV Supplied/ LV Open Circuited/ Tertiary Closed


HV

LV

Test 1:- HV Sup

Transformer Sequence Impedance Test Sheets


2 of 30

Tap Position

Voltage Applied
(V)

231.9

11

233.9

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T201

Voltage Level

Primary

Date:

24-Feb-16

220

A
V

Secondary
kV

34.5

kV

13B

233.7

25

228.9

Case 2:- HV Supplied/ LV Short Circuited/ Tertiary Closed


HV

LV

Test 2:- HV Sup

A
V

Tap Position

Voltage Applied
(V)

232.8

11

232.2

13B

232

25

229.8

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

Transformer Sequence Impedance Test Sheets


3 of 30

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T201

Voltage Level

Primary

Date:

24-Feb-16
b.

220

Secondary
kV

34.5

kV

The various Cases of Tests have been provided below

Case 3:- LV Supplied/ HV Short Circuited/ Tertiary Closed


LV

HV

A
V

Test 3:- LV Sup


Tap Position

Voltage Applied
(V)

5.13

11

5.43

13B

5.67

25

5.52

Case 3:- LV Supplied/ HV Open Circuited/ Tertiary Closed


LV

HV

Test 1:- LV Sup

Transformer Sequence Impedance Test Sheets


4 of 30

Tap Position

Voltage Applied
(V)

5.59

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T201

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

A
V

Calculation To Determine The Equivalent Zero Sequence Impedance at HV, LV and Tertiary
ZHT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Open

ZLT

Impedance measured in Secondary Circuit with Teritary Shorted and Primary Open

ZHLT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Shorted

ZLHT

Impedance Measured in Secondary circuit with Teritary Shorted and Primary Shorted

ZH

Primary Impedance

ZHT-ZT

ZL

Secondary Impedance

ZLT-ZT

ZT

Tertiary Impedance

SQRT(ZHT*(ZLT-ZLHT))

Transformer Sequence Impedance Test Sheets


5 of 30

Tertiary
9.9

kV

nce

1:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

% of 120MVA Base

1.817

131.21

120

25.71

2.34

98.12

120

24.34

3.599

63.60

120

23.19

Transformer Sequence Impedance Test Sheets


6 of 30

Tertiary
9.9

kV

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

1:- HV Supplied/ LV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.82

88.96

120

10.06

10.65

65.89

120

9.43

Transformer Sequence Impedance Test Sheets


7 of 30

Tertiary
9.9

kV

11.3

62.04

120

9.34

16.2

42.39

120

8.92

2:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.8

89.54

120

10.13

10.52

66.22

120

9.48

11.17

62.31

120

9.38

16.24

42.45

120

8.93

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

Transformer Sequence Impedance Test Sheets


8 of 30

Tertiary
9.9

kV

3:- LV Supplied/ HV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

19.85

0.78

120

4.51

21.52

0.76

120

4.41

22

0.77

120

4.50

21.4

0.77

120

4.50

1:- LV Supplied/ HV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

21.71

0.77

120

4.50

Transformer Sequence Impedance Test Sheets


9 of 30

Tertiary
9.9

kV

nd Tertiary Winding
65.89
0.77

64.88

-0.24

66.22

0.76

1.01

64.88

-0.24
1.01

Transformer Sequence Impedance Test Sheets


10 of 30

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T202

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Positive Sequence Impedance


a.

The test is done by keeping the LV Side Short Circuited and HV Side is supplied with 3 phase 400V AC Supply.

b.

The test have been carried out for Nominal Tap, Highest and Lowest TAP
HV

Ea

LV

Test 1:- HV Sup

Eb

Ec

Transformer Sequence Impedance Test Sheets


11 of 30

Tap Position

Voltage Applied
(V)

228.6

11

229.6

25

228.9

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T202

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

b.

The various Cases of Tests have been provided below

Case 1:- HV Supplied/ LV Open Circuited/ Tertiary Closed


HV
A

Transformer Sequence Impedance Test Sheets


12 of 30

LV

Test 1:- HV Sup


Tap Position

Voltage Applied
(V)

218.7

11

215.8

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T202

Voltage Level

Primary

Date:

24-Feb-16

220

A
V

Secondary
kV

34.5

kV

13B

216.5

25

216

Case 2:- HV Supplied/ LV Short Circuited/ Tertiary Closed


HV
A

A
V

LV

Test 2:- HV Sup


Tap Position

Voltage Applied
(V)

217.3

11

217

13B

216.7

25

215.7

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

Transformer Sequence Impedance Test Sheets


13 of 30

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T202

Voltage Level

Primary

Date:

24-Feb-16
b.

220

Secondary
kV

34.5

kV

The various Cases of Tests have been provided below

Case 3:- LV Supplied/ HV Short Circuited/ Tertiary Closed


LV

HV

A
V

Test 3:- LV Sup


Tap Position

Voltage Applied
(V)

5.691

11

5.674

13B

5.665

25

5.602

Case 3:- LV Supplied/ HV Open Circuited/ Tertiary Closed


LV
A

Transformer Sequence Impedance Test Sheets


14 of 30

HV

Test 1:- LV Sup


Tap Position

Voltage Applied
(V)

5.7

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T202

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

A
V

Calculation To Determine The Equivalent Zero Sequence Impedance at HV, LV and Tertiary
ZHT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Open

ZLT

Impedance measured in Secondary Circuit with Teritary Shorted and Primary Open

ZHLT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Shorted

ZLHT

Impedance Measured in Secondary circuit with Teritary Shorted and Primary Shorted

ZH

Primary Impedance

ZHT-ZT

ZL

Secondary Impedance

ZLT-ZT

ZT

Tertiary Impedance

SQRT(ZHT*(ZLT-ZLHT))

Transformer Sequence Impedance Test Sheets


15 of 30

Tertiary
9.9

kV

nce

1:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

% of 120MVA Base

1.747

130.85

120

25.64

2.34

98.12

120

24.33

3.599

63.60

120

23.16

Transformer Sequence Impedance Test Sheets


16 of 30

Tertiary
9.9

kV

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

1:- HV Supplied/ LV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.35

89.27

120

10.10

9.82

65.93

120

9.44

Transformer Sequence Impedance Test Sheets


17 of 30

Tertiary
9.9

kV

10.5

61.86

120

9.31

15.31

42.33

120

8.90

2:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.32

89.06

120

10.07

9.93

65.56

120

9.38

10.52

61.80

120

9.31

15.34

42.18

120

8.87

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

Transformer Sequence Impedance Test Sheets


18 of 30

Tertiary
9.9

kV

3:- LV Supplied/ HV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

21.17

0.81

120

4.69

20.84

0.82

120

4.75

20.81

0.82

120

4.75

20.99

0.80

120

4.66

1:- LV Supplied/ HV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

21.33

0.80

120

4.67

Transformer Sequence Impedance Test Sheets


19 of 30

Tertiary
9.9

kV

nd Tertiary Winding
65.93
0.80

65.38

0.26

65.56

0.82

0.54

65.38

0.26
0.54

Transformer Sequence Impedance Test Sheets


20 of 30

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T203

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Positive Sequence Impedance


a.

The test is done by keeping the LV Side Short Circuited and HV Side is supplied with 3 phase 400V AC Supply.

b.

The test have been carried out for Nominal Tap, Highest and Lowest TAP
HV

Ea

LV

Test 1:- HV Sup

Eb

Ec

Transformer Sequence Impedance Test Sheets


21 of 30

Tap Position

Voltage Applied
(V)

240.9

11

239.7

25

239.2

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T203

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

b.

The various Cases of Tests have been provided below

Case 1:- HV Supplied/ LV Open Circuited/ Tertiary Closed


HV

LV

Test 1:- HV Sup

Transformer Sequence Impedance Test Sheets


22 of 30

Tap Position

Voltage Applied
(V)

233.9

11

232.2

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T203

Voltage Level

Primary

Date:

24-Feb-16

220

A
V

Secondary
kV

34.5

kV

13B

232.8

25

230.9

Case 2:- HV Supplied/ LV Short Circuited/ Tertiary Closed


HV

LV

Test 2:- HV Sup

A
V

Tap Position

Voltage Applied
(V)

234.5

11

232.9

13B

232.9

25

233.8

Tests To Determine The Equivalent Zero Sequence Impedance


a.

The test is carried out by suplying a current of rated frequency between parallel connected phase terminals and the neutral termina
current.

Transformer Sequence Impedance Test Sheets


23 of 30

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T203

Voltage Level

Primary

Date:

24-Feb-16
b.

220

Secondary
kV

34.5

kV

The various Cases of Tests have been provided below

Case 3:- LV Supplied/ HV Short Circuited/ Tertiary Closed


LV

HV

A
V

Test 3:- LV Sup


Tap Position

Voltage Applied
(V)

5.5

11

5.4

13B

5.6

25

5.7

Case 3:- LV Supplied/ HV Open Circuited/ Tertiary Closed


LV

HV

Test 1:- LV Sup

Transformer Sequence Impedance Test Sheets


24 of 30

Tap Position

Voltage Applied
(V)

5.6

Transformer Sequence Impedance Test Sheets


Substation:

New Zakher Grid

Transformer
rating

90/120 MVA

Transformer ID:

T203

Voltage Level

Primary

Date:

24-Feb-16

220

Secondary
kV

34.5

kV

A
V

Calculation To Determine The Equivalent Zero Sequence Impedance at HV, LV and Tertiary
ZHT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Open

ZLT

Impedance measured in Secondary Circuit with Teritary Shorted and Primary Open

ZHLT

Impedance Measured in Primary circuit with Teritary Shorted and Secondary Shorted

ZLHT

Impedance Measured in Secondary circuit with Teritary Shorted and Primary Shorted

ZH

Primary Impedance

ZHT-ZT

ZL

Secondary Impedance

ZLT-ZT

ZT

Tertiary Impedance

SQRT(ZHT*(ZLT-ZLHT))

Transformer Sequence Impedance Test Sheets


25 of 30

Tertiary
9.9

kV

nce

1:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

% of 120MVA Base

1.849

130.29

120

25.71

2.451

97.80

120

24.34

3.778

63.31

120

23.19

Transformer Sequence Impedance Test Sheets


26 of 30

Tertiary
9.9

kV

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

1:- HV Supplied/ LV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.93

88.49

120

10.01

10.64

65.47

120

9.37

Transformer Sequence Impedance Test Sheets


27 of 30

Tertiary
9.9

kV

11.32

61.70

120

9.29

16.4

42.24

120

8.88

2:- HV Supplied/ LV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

7.92

88.83

120

10.05

10.65

65.61

120

9.39

11.3

61.83

120

9.31

16.62

42.20

120

8.88

utral terminal. It is expressed in Ohms and is given by 3 times test voltage/test

Transformer Sequence Impedance Test Sheets


28 of 30

Tertiary
9.9

kV

3:- LV Supplied/ HV Short cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

21.18

0.78

120

4.53

20.58

0.79

120

4.58

21.65

0.78

120

4.52

21.74

0.79

120

4.58

1:- LV Supplied/ HV Open cicuited/ Tertiary Closed


Current
Measured (A)

Impedance
Calculated ()

MVA Base

Zero Sequence
Impedance %

21.25

0.79

120

4.60

Transformer Sequence Impedance Test Sheets


29 of 30

Tertiary
9.9

kV

nd Tertiary Winding
65.47
0.79

65.00

0.32

65.61

0.79

0.47

65.00

0.32
0.47

Transformer Sequence Impedance Test Sheets


30 of 30