Practical Guide to Inspection, Testing & Certication of Electrical Installations
Now join the ends of the primary winding together and join the ends of the secondary winding together. Use an insulation resistance meter set on 500v d.c. to test between the joined ends. Now test between the joined ends and earth. The maximum insulation value permissible in both cases is 1M. If the resistance is less then the transformer is faulty.
Isolation transformer Carry out the test in the same manner as the double wound transformer. The minimum acceptable value for insulation resistance is 1M.
Separated extra low voltage transformers
(SELV and PELV) These transformers are tested using the same procedure as for the step up or down transformer. The insulation resistance test values are different for this test. If the SELV or PELV circuits from the secondary side of the transformer are being tested, then the test voltage must be 250v d.c. and the maximum resistance value is 0.5M although this would be considered a very low value and any value below 5M must be investigated. For a test between the actual transformer windings the test voltage is increased to 500 volts d.c. The minimum insulation resistance value is 1M although any value below 5M should be investigated.
Testing a three phase motor
There are many types of three phase motor but by far the most common is the induction motor, it is quite useful to be able to test them for serviceability. Before carrying out electrical tests it is a good idea to ensure that the rotor turns freely. This may involve disconnecting any mechanical loads. The rotor should rotate easily and you should not be able to hear any rumbling from the motor bearings. Next if the motor has a fan on the outside of it, check that it is clear of any debris which may have been sucked in to it, also check that any air vents into the motor are not blocked.
Correct selection of protective devicess
Generally if the motor windings are burnt out there will be an unmistakable smell of burnt varnish, however it is still a good idea to test the windings as the smell could be from the motor being overloaded. Three phase motors are made up of three separate windings. In the terminal box there will be six terminals as each motor winding will have two ends. The ends of the motor windings will usually be identied as W1, W2, U1, U2. V1, V2. The rst part of the test is carried out using a low resistance ohm meter. Test each winding end to end W1 to W2, U1 to U2 and V1 to V2. The resistance of each winding should be approximately the same and the resistance value will depend on the size of the motor. If the resistance values are different then the motor will not be electrically balanced and it should be sent for rewinding. Provided the resistance values are the same then the next test is carried out using an insulation resistance tester. Join W1 and W2 together, U1 and U2 together and V1 and V2 together. Carry out an insulation resistance test between the joined ends i.e.: W to U then W to V and then between U and V then repeat the test between joined ends and the case, or the earthing terminal of the motor (these tests can be in any order to suit you). Providing the insulation resistance is 2M or greater then the motor is ne. If the insulation resistance is above 0.5M then it could just be dampness and it is often a good idea to run the motor for a while and then carry out the insulation test again as the motor may dry out with use. To reconnect the motor windings in star, join W2, U2 and V2 together and connect the three phase motor supply to W1, U1 and V1. If the motor rotates in the wrong direction swop two of the phases of the motor supply. To reconnect the motor windings in delta, join W1 to U2, U1 to V2 and V1 to W2 and then connect the three phase motor supply one to each of the joined ends. If the motor rotates in the wrong direction, swop two phases of the motor supply.