Average equivalent
length (m)
Page II-1
90 screwed elbow
Standard screwed tee
(150mm)
Gate valve
Alarm
1.89
8.61
0.81
5.07
Also, by BS5306:Part 2:1990, Section 4, 17.4.6.3, for ordinary group III Hazard (OH III), if the
distance between the highest and lowest sprinklers is less than 15m, the following pump requirement
should be follow:
Nominal Rating
Pressure at
Flow
pump outlet
1.4 bar
2250
L/min
High Flow
Pressure
Flow
at C
gauge
2.9 bar
1350
L/min
Low Flow
Pressure at
Flow
C gauge
3.2 bar
1100
L/min
If the distance between the highest and lowest sprinklers is between 30m and 45m, the following
pump requirement should be follow:
Pressure at
pump outlet
Flow
2.5 bar
3100
L/min
Pressure
at C
gauge
5.9 bar
Flow
Pressure at
C gauge
Flow
1350
L/min
6.2 bar
1100
L/min
Page II-2
height)
OH III
Control valves
3.5m (Floor-to-floor
LG1
3m
Nominal flow
L = 50m pipe run + 4 bends + 2 gate valve + 1 tee + 1 alarm
= 50 + 4(1.89) + 2(0.81) + 8.61 + 5.07
= 72.9 m
PL = 1.35 x 10-8 x 72.9 x (2250)1.85
= 1.57 bar
Pd = 0.1 x 6.5
= 0.65 bar
The nominal flow requirement = 1.4 + 1.57 + 0.65
= 3.62 bar/2250L=36.2 mH/2250L
The actual flow requirement = 40mH/2250L
High flow
L = 50m pipe run + 4 bends + 2 gate valve + 1 tee + 1 alarm
= 50 + 4(1.89) + 2(0.81) + 8.61 + 5.07
= 72.9 m
PL = 1.35 x 10-8 x 72.9 x (2250)1.85
= 1.57 bar
Pd = 0.1 x 6.5
= 0.65 bar
The nominal flow requirement = 2.9 + 1.57 + 0.65
= 5.12bar/1350L = 51.2mH/1350L
The actual flow requirement = 56mH/1350L
Low flow
L = 50m pipe run + 4 bends + 2 gate valve + 1 tee + 1 alarm
= 50 + 4(1.89) + 2(0.81) + 8.61 + 5.07
= 72.9 m
PL = 1.35 x 10-8 x 72.9 x (2250)1.85
= 1.57 bar
Pd = 0.1 x 6.5
= 0.65 bar
The nominal flow requirement = 3.2 + 1.57 + 0.65
= 5.42bar/2250L = 54.2mH/1100L
The actual flow requirement = 60mH/1100L
Since the maximum height of a zone is 45m, the maximum reached floor is 14. Therefore, The
served floors for zone 1 are ranged from 1/F to 14/F. Also, the same as before, the actual pump
rating is accessed by adding the nominal rating to a 10% safety factor. Hence, the result is shown
as follow.
14/F
40m
OH III
G/F
Control valves
3m
Nominal flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 70 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 94.8 m
PL = 1.35 x 10-8 x 94.8 x (3100)1.85
= 3.68 bar
Pd = 0.1 x 40
= 4 bar
The nominal flow requirement = 2.5 + 3.68 + 4
= 10.2 bar/3100L=102 mH/3100L
The actual flow requirement = 115mH/3100L
High flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 70 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 94.8 m
PL = 1.35 x 10-8 x 94.8 x (3100)1.85
= 3.68 bar
Pd = 0.1 x 40
= 4 bar
The nominal flow requirement = 5.9 + 3.68 + 4
= 13.6 bar/3100L=136 mH/1350L
The actual flow requirement = 150mH/1350L
Low flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 70 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 94.8 m
PL = 1.35 x 10-8 x 94.8 x (3100)1.85
= 3.68 bar
Pd = 0.1 x 40
= 4 bar
The nominal flow requirement = 6.2 + 3.68 + 4
= 13.9 bar/3100L=139 mH/1100L
The actual flow requirement = 153mH/1100L
40m
OH III
15G/F
Control valves
43m
Nominal flow
L = 110m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 110 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 135m
PL = 1.35 x 10-8 x 135 x (3100)1.85
= 5.24 bar
Pd = 0.1 x 80
= 8 bar
The nominal flow requirement = 2.5 + 5.24 + 8
= 15.8 bar/3100L=158 mH/3100L
The actual flow requirement = 173mH/3100L
High flow
L = 110m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 110 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 135m
PL = 1.35 x 10-8 x 135 x (3100)1.85
= 5.24 bar
Pd = 0.1 x 80
= 8 bar
The nominal flow requirement = 5.9 + 5.24 + 8
= 19.2 bar/1350L=192 mH/1350L
The actual flow requirement = 211mH/1350L
Low flow
L = 110m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 110 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 135m
PL = 1.35 x 10-8 x 135 x (3100)1.85
= 5.24 bar
Pd = 0.1 x 80
= 8 bar
The nominal flow requirement = 6.2 + 5.24 + 8
= 19.5 bar/1100L=195 mH/1100L
The actual flow requirement = 215mH/1100L
G/F
Page II-5
Control valves
3m
Nominal flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 58 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 52.8 m
PL = 1.35 x 10-8 x 52.8 x (3100)1.85
= 2.05 bar
Pd = 0.1 x 28
= 2.8 bar
The nominal flow requirement = 2.5 + 2.05 + 2.8
= 7.35 bar/3100L=73.5mH/3100L
The actual flow requirement = 81mH/3100L
High flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 58 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 52.8 m
PL = 1.35 x 10-8 x 52.8 x (3100)1.85
= 2.05 bar
Pd = 0.1 x 28
= 2.8 bar
The nominal flow requirement = 5.9 + 2.05 + 2.8
= 10.8 bar/3100L=108 mH/1350L
The actual flow requirement = 118mH/1350L
Low flow
L = 70m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 58 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 52.8 m
PL = 1.35 x 10-8 x 52.8 x (3100)1.85
= 2.05 bar
Pd = 0.1 x 28
= 2.8 bar
The nominal flow requirement = 6.2 + 2.05 + 2.8
= 11.1 bar/3100L=111 mH/1100L
The actual flow requirement = 122mH/1100L
Control valves
11F
34m
Page II-6
Nominal flow
L = 84m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 84 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 109m
PL = 1.35 x 10-8 x 109 x (3100)1.85
= 4.23 bar
Pd = 0.1 x 54
= 5.4bar
The nominal flow requirement = 2.5 + 4.23 + 5.4
= 12.1 bar/3100L=121 mH/3100L
The actual flow requirement = 133mH/3100L
High flow
L = 84m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 84 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 109m
PL = 1.35 x 10-8 x 109 x (3100)1.85
= 4.23 bar
Pd = 0.1 x 54
= 5.4bar
The nominal flow requirement = 5.9 + 4.23 + 5.4
= 15.5 bar/1350L=155 mH/1350L
The actual flow requirement = 171mH/1350L
Low flow
L = 84m pipe run + 5 bends + 2 gate valve + 1 tee + 1 alarm
= 84 + 5(1.89) + 2(0.81) + 8.61 + 5.07
= 109m
PL = 1.35 x 10-8 x 109 x (3100)1.85
= 4.23 bar
Pd = 0.1 x 54
= 5.4bar
The nominal flow requirement = 6.2 + 4.23 + 5.4
= 15.8 bar/1100L=158 mH/1100L
The actual flow requirement = 174mH/1100L
From the above calculation, the duty pump ratings can be found. In addition, the duty curves are
summarized as below:
Page II-7
725
62
155
217
123
180
1100
60
153
215
122
174
1350
1750
2350
56 Duty Pump
44 Chart 38
150
141
131
211
200
190
118
105
97
171
165
153
2700
3100
123
181
88
145
115
173
81
133
200
150
Head (m)
Zone 1(Block 1)
Zone 2(Block 1)
Zone 1(Block 2)
Zone 2(Block 2)
100
50
0
725
1100
1350
1750
2350
2700
3100
Flow rate
Page II-8
Rating
8.1 mH/1 l/s
60 mH/1 l/s
115 mH/1 l/s
43 mH/1 l/s
74.5mH/1 l/s
2.3 Pressure for starting the jockey, duty and standby pumps
As mentioned before, the duty pump, jockey pump and standby pump will operate automatically
when the pressure drop below 95%, 90% and 80% of the designated pressure, Their starting
pressures are as follow:
Pumps for Public Services at LG/F & /GF
Type of Pump
Duty pump
Jockey pump
Standby pump
Starting pressure
8.1mH x 0.95 = 7.7 mH
8.1mH x 0.9 = 7.3 mH
8.1mH x 0.8 = 6.5 mH
Pumps for zone 2 (Block 1)
Type of Pump
Duty pump
Jockey pump
Standby pump
Starting pressure
115mH x 0.95 = 110 mH
115mH x 0.9 = 104 mH
115mH x 0.8 = 92 mH
Starting pressure
60mH x 0.95 = 57 mH
60mH x 0.9 = 54 mH
60mH x 0.8 = 48 mH
Page II-9
Type of Pump
Duty pump
Jockey pump
Standby pump
Starting pressure
74mH x 0.95 = 71 mH
74mH x 0.9 = 67 mH
74mH x 0.8 = 60 mH
Starting pressure
43mH x 0.95 = 41 mH
43mH x 0.9 = 39 mH
43mH x 0.8 = 35 mH
Page II-10
y l/s
Water
Tank
Pumps
Water
Main
G
Effective Volume
= 75m3
The internal tank size =
10200(L) x 6050(W) x 1620(H)mm
As mentioned before, the horizontal pipe run from the F/S pump room to the farthest shop 4 is 50m.
the pressure losses are:
(b) 100mm diameter pipe
PL = 1.35 x 10-8 x 72.9 x (1000)1.85
= 0.35 bar < 0.5bar
100mm heavy grade G.I. pipe is used for the upeed and horizontal distribution pipe.
According to Code of Practice of Minimum Fire Services Installations and Equipment, the
minimum quantity of water required to be available which is regarded to the floor area factors of
the largest floor. As the gross floor area in the proposed building is Over 460m2 but not
exceeding 920m2. Therefore, a 27000L (27m3) roof tank should be installed in both buildings.
The effective volume of the tank is 27000L
The Internal tank size is 3.5m(L) x 3.5m(W) x 2.5M(H)
Assume an internal diameter 100mm galvanised steel pipe is used as the main distribution pipe.
Then water flow velocity = 1.3m/s
Pressure loss per unit length= 400 Pa /m run
Equivalent length of pipe = 1.7 m
By the relation that Pressure(P) is proportional to the square flow rate (Q),i.e. P Q2,
Pressure at 28/F is 3.5 + 1.5 bar = 5 bar,
Flow rate at 27/F is 450 l/min = 7.5 L/s
k = 8900
Also, Pressure at 27/F is 3.5 + 1.5 + 3 - 3x 0.04 = 7.88 bar
Flow rate = 9.4 L/s
With reference to COP, it states that the fire pumps shall be capable to provide adequate flow for
any 2 hydrant outlets ( i.e. each with a flow of 450 L/min at a running pressure of not less than
350kPa ) operating simultaneously with an aggregate flow of not less than 900 L/min.
The flow rate of the pump = 7.5 + 9.4
= 20L/s = 1020L/min
For the approximate length of horizontal running at roof = 5m,
the static head from the pump to the fire hydrant outlet = 5m and assume there is no fitting loss
Then, the pump head = 50-5+(5+5) x 0.04
~ 60mH (10% safety margin)
The rating for both Roof Pump are 1020 l//min with 60 mH.