Escolar Documentos
Profissional Documentos
Cultura Documentos
co m
Turns
ratio
Measured ratio
variations
should be
within 0.5% of
the nameplate
markings.
Some T T R can
perf orm
transf ormer
ratio
measurement
and also
assess if onload tap
changer
contacts are
Fig ure 1 Thre e -p has e Trans fo rme r Turns Rati (TTR) Co nne c tio n d iag ram.
making
satisf actorily
during its transition f rom one tap position to the next position.
St ep 2.
Connect the H designated three-phase test lead with the military style connector at one end to the mating
connection on the test set marked with an H. Ensure that the connectors index notch lines up properly.
St ep 3.
Connect the X designated three-phase test of lead military style connector at one end to the mating
connection on the test set marked with an X. Ensure that the connectors index notch lines up properly.
St ep 4.
Connect the H1, H2, H3 designated test lead to the corresponding H1, H2, H3 transformer terminal / bushing.
Connect the H0 test lead if H0 terminal/bushing is present.
Ref er to Figure 1.
St ep 5.
Connect the X1, X2, X3 designated test leads to the corresponding X1, X2,X3 transf ormer terminals / bushings.
Connect the X0 test lead if X0 terminal/bushing is present.
St ep 6.
Perf orm turns ratio measurements f or all tap positions.
St ep 7.
Confirm that the measured ratios is within 0.5% of the calculated ratios.
Important Note:
Transf ormers that have wye connections but do not have the neutral of the wye brought out shall be tested
f or ratio with three-phase power supply.
Any inequality in the magnetizing characteristics of the three phases will then result in a shif t of the neutral
and thereby cause unequal phase voltages. When such inequality is f ound, the connection should be changed,
either to a delta or to a wye connection, and the line voltages measured.
When these are f ound to be equal to each other and the proper values (1.732 times the phase voltages when
connected in wye), the ratio is correct.
Power Transf ormer Test ing Aut omat ically measuring rat io and winding resist ance of all
t aps/phases
Cant see this video? Click here to watch it on Youtube.
Reference: Substation Commissioning Course Raymond Lee, Technical Trainer