SAUDI ARAMCO INSPECTION CHECKLIST
Air Cooled Condenser Installation SAIC-K-4039 18-May-05 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Condenser units shall be mounted on a concrete housekeeping pad, at a
SAES-K-001
A1 minimum of 100 mm (4") above the floor or a minimum of 150 mm (6")
Para 5.1.1
above unpaved ground.
Access doors shall be provided to every valve, coil, filter, damper or
SAES-K-001
A2 mechanical device for inspection and/or adjustment and be within
Para 5.1.3
reachable distance
SAES-K-001
A3 Air cooled condenser unit shall be mounted level.
Para 5.3.3
Operational equipment of condensing unit shall be mounted on a base SAES-K-001
A4
frame. Para 4.8.3.4
Condenser fan motors, 25 tons and larger units, shall have a separate
SAES-K-001
A5 overload relay protection. This protection shall be in addition to other
Para 4.8.10.3
built-in condenser motor protection devices
Rooms or spaces other than Refrigeration Machinery Rooms where any
refrigerant-containing portion of the condensing unit is located shall be
provided with one of the following means of ventilation
(UMC Para 1105.7)
1- Permanent gravity ventilation openings of not less than 2 square feet
net free area opening directly to the outside of the building or extending
to the outside of the building by continues ducts SAES-K-100
A6
2-Mechanical exhaust system, discharging it to the outside Section 1
Exception:
A- condensing unit in a room or space if the cubical content exceeds 1,000 cubic feet per
horsepower of the unit
B- Condensing unit in a room or space that has permanent
gravity ventilation an area of 2 square feet or more to
other rooms or openings exceeding 1,000 cubic feet per
horsepower

Refrigeration Systems or portions thereof (Condenser) shall not be SAES-K-100


A7
located within a required exit enclosure (UMC Para 1105.8) Section 1
REMARKS:

REFERENCE DOCUMENTS:
1-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 31 May, 2004
2-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 31 May, 2004
3-Uniform Mechanical Code (UMC), 1997

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:
*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED