Você está na página 1de 13

Heat Dissipation from panels/ equipment

Substation Building, BGCS # 3


Heat Dissipation from panels/ equipment
Identification
number

Heat dissipation

Safety

watts

watts

Mechanical room

101

22850

0%

Battery room

102

1190

0%

Communication room
Electrical Equipment room

103
104

1200
82300

20%
20%

Activity

Total

Remarks

watts

22850

1190
1440
98760

1. HVAC control panels 6000 watts (Provided by Electrical ), 2 panels,


each panel 3000W
2. working AHU 12650 watts (Approximately taken)
3. Pressurization units 1500 watts (Approximately taken)
4. Bleed fan 500 watts
5.1700 watts from CCU
6. 500 watts from exhaust fan
1. 190 watts has been considered based on Abu tubul Project
2. 1000 watts has been considered for exhaust fan
1) 1607 watts from telecom panels
Heat dissipation values received from Electrical email

Where applicable confirmation is mandatory from relevant department

Process Interface Building, BGCS-3


Heat Dissipation from panels/ equipment

Activity

Identification
number

Heat dissipation

Safety

Total

watts

watts

Air lock - 1

101

watts
0

Process interface room

102

29920

Electrical Equipment room


Communication room

103
104

3025
1200

20%
20%

3630
1440

Battery room

105

1390

10%

1529

Mechanical room

106

24000

0%

24000

Remarks

1) 23000 watts from I&C panels


2) 6920 watts from PAGA/IPP panels
Heat dissipation values received from Electrical email
1) 1607 watts from telecom panels
1. 190 watts has been considered based on Abu tubul Project
2. 1200 watts has been considered for exhaust fan
1.
2.
3.
4.
5.
6.

HVAC control panels 4000 watts (Provided by Electrical )


AHU 15000 watts (Approximately taken)
Pressurization units 1500 watts (Approximately taken)
2000 watts from CCU
500 watts from exhaust fan
1000 watts from bLEED fan

Where applicable confirmation is mandatory from relevant department

Maintenance Building, BGCS - 3


Heat Dissipation from panels/ equipment

Activity

101
102
103
104
105
106
107
108
109

Warehouse
Haz. Store
Equipment store
Mech. Workshop
Electrical store
Tool store
Air lock
Corridor
Electrical room

Heat
Safety Total
dissipation
watts
watts watts
7000
7000
0%
0
0%
0
0
0%
0
12000
0%
12000
5000
0%
5000
0
0%
0
0
0%
0
2000
0%
2000
1000
0%
1000

110 - Communication room

1200

20%

1440

111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126

500
500
500
0
0
500
500
750
500
0
0
2000
1000
3000
0
0

0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%

500
500
500
0
0
500
500
750
500
0
0
2000
1000
3000
0
0

20500

0%

20500

128 - External store - 2

0%

Workshop area
Machineries
Lathe machine
Pedestal radial drill machines
Grinder machines
Buffing machine
Saw machine
Threading machine

Qty
1
2
2
1
1
1

HP
3
2
2
1
3
3

KW
2.2371
1.4914
1.4914
0.7457
2.2371
2.2371

Document store
Office room - 1
Store
Janitor
Air lock
Office room - 2
Office room - 3
Meeting room
PPE Store
Air lock
Air lock
Corridor
Break room
Open plan office
Shower/ Locker
Toilet

127 - Mechanical

Shaft balancing machine


Milling machine
Pipe saw cutter machine
Hydraulic press machine
lapping machine
Air compressor

1
1
1
1
1
1

10
10.5
3
3
1
15

7.457
7.8298
2.2371
2.2371
0.7457
11.185
42.132

Remarks

1450 BTU/hr is added separately for projector


1) 4822 watts from telecom panels
2) 5000 watts from CCU
3) 500 watts from exhaust fans

1.
2.
3.
4.

HVAC control panels 4000 watts (Provided by Electrical )


AHU 15000 watts (Approximately taken)
Bleed fan 500 watts (Approximately taken)
Pressurization fan 1000 watts (Approximately taken)

Where applicable confirmation is mandatory from relevant


department

Você também pode gostar