Over Load Current (In) = Feeder Load Current X Relay setting = 384 X 125% =480 Amp
Required Over Load Relay Plug Setting= Over Load Current (In) / CT Primary Current
Required Over Load Relay Plug Setting = 480 / 600 = 0.8
Pick up Setting of Over Current Relay (PMS) (I>)= CT Secondary Current X Relay Plug Setting
Pick up Setting of Over Current Relay (PMS) (I>)= 1 X 0.8 = 0.8 Amp
Plug Setting Multiplier (PSM) = Min. Feeder Fault Current / (PMS X (CT Pri. Current / CT Sec. Current))
Plug Setting Multiplier (PSM) = 11000 / (0.8 X (600 / 1)) = 22.92
Operation Time of Relay as per its Curve
Operating Time of Relay for Very Inverse Curve (t) =13.5 / ((PSM)-1).
Operating Time of Relay for Extreme Inverse Curve (t) =80/ ((PSM)2 -1).
Operating Time of Relay for Long Time Inverse Curve (t) =120 / ((PSM) -1).
Operating Time of Relay for Normal Inverse Curve (t) =0.14 / ((PSM) 0.02 -1).
Operating Time of Relay for Normal Inverse Curve (t)=0.14 / ( (22.92)0.02-1) = 2.17 Amp
Here Time Delay of Relay (TMS) is 0.125 Sec so
Actual operating Time of Relay (t>) = Operating Time of Relay X TMS =2.17 X 0.125 =0.271 Sec
Grading Time of Relay = [((2XRelay Error)+CT Error)XTMS]+ Over shoot+ CB Interrupting Time+ Safety
Total Grading Time of Relay=[((2X7.5)+10)X0.125]+0.05+0.17+0.33 = 0.58 Sec
Operating Time of Previous upstream Relay = Actual operating Time of Relay+ Total Grading Time Operating Time of
Previous up Stream Relay = 0.271 + 0.58 = 0.85 Sec
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015
Calculate IDMT over Current Relay Setting (50/51) | Electrical Notes & Articles
Page 2 of 6
Conclusion of Calculation:
Pickup Setting of over current Relay (PMS) (I>) should be satisfied following Two Condition.
(1) Pickup Setting of over current Relay (PMS)(I>) >= Over Load Current (In) / CT Primary Current
(2) TMS <= Minimum Fault Current / CT Primary Current
For Condition (1) 0.8 > =(480/600) = 0.8 >= 0.8, Which found OK
For Condition (2) 0.125 <= 11000/600 = 0.125 <= 18.33, Which found OK
Here Condition (1) and (2) are satisfied so
Pickup Setting of Over Current Relay = OK
Low Over Current Relay Setting: (I>) = 0.8A X In Amp
Actual operating Time of Relay (t>) = 0.271 Sec
High Over Current Relay Setting: (I>>) = 2.5A X In Amp
Actual operating Time of Relay (t>>) = 0.34 Sec
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015
Calculate IDMT over Current Relay Setting (50/51) | Electrical Notes & Articles
Page 3 of 6
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015
Calculate IDMT over Current Relay Setting (50/51) | Electrical Notes & Articles
Page 4 of 6
Reply
Shakeel Ahmad says:
November 15, 2013 at 7:30 am
Dear Jignesh,
what is the best location of REF and SBEF CTs on Transformer side? i have 1000kVA Transformer and we are planning to mount
the CTs either in LV cable box, REF on 1C630 Neutral Cable and SBEF on 1C240 Earth Cable OR Below LV cable box in
Enclosure. Your suggestion please..
Reply
elango.k says:
December 1, 2013 at 4:47 pm
Hello sir- what is the use of low over current(i>) setting and high over current setting(i>>i),
sir i requesting you to post some notes on this topic
thankyou
Reply
kamlesh says:
December 17, 2013 at 8:51 am
why we can not maintain of power factor one. if we mantaitain 1 and above what is problem in transformer and power.
Reply
P.Koteswar Rao says:
December 30, 2013 at 12:06 pm
Dear Sir,
Please advice regarding df / dt relay minimum and maximum setting details.
We are using ABB make, REF type relay for 11kv grid feeder.
We are going to synchronize 30MW,11kv DG with this grid breaker.
Power failure time, I wish to isolate grid feeder.
Please advice.
Reply
Suraj Ram says:
January 2, 2014 at 10:03 am
sir can you please give an example how do understand it on breaker trip curve or Time current curve
Reply
Prabakaran says:
January 5, 2014 at 4:54 am
Sir, thank u for your notes on Normally inverse curve. By the same way plz give the formula for Extermly inverse curve.
Reply
sartajalam says:
January 26, 2014 at 2:19 pm
sir,i need testing procedure of over current relay.
Reply
jagdish ghogare says:
February 17, 2014 at 9:54 am
Dear parmar Sir can i get your phone number so that i can take some help from you
Reply
Murali krishnan says:
February 25, 2014 at 4:19 pm
Dear Jignesh,
please advise where we can find the min fault level data.
Reply
Rohaida says:
May 8, 2014 at 6:56 am
Dear Sir,
Your Electrical Thumb Rules-(Part-8) is referred.
The details: Feeder Fault current Min11KA and Max 22KA.
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015
Calculate IDMT over Current Relay Setting (50/51) | Electrical Notes & Articles
Page 5 of 6
Im working on Overcurrent relay setting of Primary Transformer Protection (2000KVA with 6% impedance) with 200/5 CT ratio.
Can you guide me on how to calculate min & max fault current.
Reply
Bernard Farrugia says:
December 2, 2014 at 10:37 am
Why in the standard IDMT td(I) calculation you havent divided by Beta i.e. by 2.97? as regulated by the IEC
Thanks
Reply
Prageesh says:
February 4, 2015 at 6:33 pm
Dear Sir,
In an excellent manner you have explain 50/51N relay setting. Can you please guide to set the 87 relay for 110/33KV, 50MVA,
50Hz transformer.
Reply
mukund harne says:
February 25, 2015 at 1:40 pm
The details provided are really very useful.
Reply
Aamir Javaid Malik says:
April 25, 2015 at 9:54 am
Dear Sir,
In your example for calculating setting of IDMT over-current rely mentioned above, kindly guide me how would you prevent
relay tripping from transformer inrush current when feeder breaker is switched on. You may assume any capacity of transformer
installed in the outgoing feeder in above example.
Reply
jegatheshwaran says:
May 11, 2015 at 4:38 pm
Sir,
I would like to known how relay can be wiried and implemented and settings and how its configured in relay panel.
And i had a doubt, this realy implementation and configuration and setting are different from one another??????
If its different plz give the notes to get the idea about that please sir
Thank you.
Reply
Muthukumaran says:
May 21, 2015 at 8:55 am
operating time of low current operating time is higher than high current setting
Reply
Pradnya says:
July 11, 2015 at 6:46 pm
Respected sir,
For IDMT relay having CT ratio 300:1, load current 470A, maximum fault current is 2380A and minimum fault current is 720A,
then how to select upper and lower boundaries on TMS & Plug setting of relay.
Kindly guide me sir, looking forward for your positive reply.
Reply
kader says:
July 16, 2015 at 8:35 am
please clarify 0.14 / ( (7.33)0.02-1) = 3.44 Amp , how?
Reply
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015
Calculate IDMT over Current Relay Setting (50/51) | Electrical Notes & Articles
Page 6 of 6
https://electricalnotes.wordpress.com/2013/10/11/calculate-idmt-over-current-relay-setting-5051/
9/30/2015