Você está na página 1de 5

PUMP FOUNDATION

1.0 Foundation data.


Length of foundation

Lx

3.820 m

Width of foundation

Ly

1.500 m

Depth of foundation

Lz

0.920 m

Total weight of machine

Wm

8.4 t.

C.G. of machine (load) in X direction

Xim

2100.0 mm

C.G. of machine (load) in Y direction

Yim

750.0 mm

C.G. of machine (load) in Z direction (from


top of foundation)

Zim

1155.0 mm

Operating frequency of machine

fm

1500.0 rpm

Fp

10.0 t/m2

2.4 t/m3

2.0 Machine data.


(Appendix-A)

3.0 Soil data.


Permissible bearing capacity of soil

(BH-3)

4.0 Materials data


Unit weight of concrete

Characteristic strength of concrete

fcu

40.0 N/mm2

Characteristic strength of reinforcement

fy

460.0 N/mm2

Diameter of reinforcement provided

20 mm

200 mm

Spacing of reinforcement
CG-Machine assembly
Xim

Pump Base skid- 3520x1180mm


Ly = 1500.0

Yim

Lx =

3820.0

Note: CG of machine calculated (Xim) based on individual masses of pump and motor

5.0 Centre of gravity - Foundation


C.G. of foundation in X - direction

Xif

1910.0 mm

C.G. of foundation in Y - direction

Yif

750.0 mm

Zif

460.0 mm

C.G. of foundation in Z - direction

71318-00/1132001-Rev.0: Attachment-I

1of 5

6.0 Common centre of gravity


C.G. in X - direction

=
=

C.G. in Y - direction

=
=

C.G. in Z - direction from the base of foundation

(mm*Xim)+(mf*Xif)
(mm + mf)
1985.8 mm
(mm*Yim)+(mf*Yif)
(mm + mf)
750.0 mm
[mm*(Zim+LZ)]+(mf*Zif)
(mm + mf)

1104.4 mm

7.0 Eccentricity
Eccentricity along X - direction

ex

75.8 mm

Percentage of eccentricity along X - direction

% ex

1.98 %

<

5 % - Permissible limit.

Eccentricity along Y - direction

eY

Percentage of eccentricity along Y - direction

% eY

0.00 %

<

5 % - Permissible limit.

OK

0.0 mm
OK

8.0 Design parameters


Mass of Machine

mm

0.9 t.sec2/m

Area of foundation

Af

5.7 m2

Weight of foundation

Wf

Mass of foundation

mf

1.3 t.sec2/m

Total mass of the system

mi

2.1 t.sec2/m

My-y

12.7 t

9.0 Moment of Inertia


M.I. at axis // to width & passing through C.G

=
M.I. at axis // to length & passing through C.G

Mx-x

=
=

M.I. at axis // to depth & passing through C.G

Mz-z

=
=

Static weight of foundation (including exist.base slab)

LyLx3/12
7.0 m4
LxLy3/12
1.1 m4
My-y + Mx-x
8.0 m4

Wf

32.2 t

W f/W m

3.8

(Portion under 45deg distribution of base is included)

Weight ratio between pump and foundation

>

OK

10.0 Check for soil stress


Soil stress below pump plinth are arrived (for indicative purpose only as floor is resting on piles)
conservatively from block foundation principle.
Static weight of foundation + machine

=
=

Area of foundation

Wf + Wm
21.1 t
5.7 m2

For static design, Lateral forces representing 25% of the machine weight and Longitudinal forces
representing 25% of the machine weight shall be considered seperately as different load combination, to
arrive at critical value for the soil pressure.
Load combination 1
71318-00/1132001-Rev.0: Attachment-I

2of 5

Lateral forces acting perpendicular to the shaft

Fx1

=
=

71318-00/1132001-Rev.0: Attachment-I

25 % of machine weight
2.1

3of 5

Distance from the base of fdn to the point of force


F - Max.

W
A

(W ex)
MI Y / ((Lx/2)+ex)

S1

2.1

Fx1 * S1
MI Y / ((Lx/2)+ex)

Maximum soil stress

Fmax

53.71 kN/m2

Minimum soil stress

Fmin

19.77 kN/m2

75 % Fp - permissible bearing pressure

FAll

75.00 kN/m2

>

Fmax & Fmin

25 % of machine weight

2.1 t

2.1 m

OK

Load combination 2
Longitudinal forces acting along the shaft

Distance from the base of fdn to the point of force


F - Max.

W
A

(W ey)
MI x / ((Ly/2)+ey)

Fx2
S2

Fx2 * S2
MI x / ((Ly/2)+ey)

Maximum soil stress

Fmax

67.16 kN/m2

Minimum soil stress

Fmin

6.32 kN/m2

75 % Fp - permissible bearing pressure

FAll

75.00 kN/m2

>

Fmax & Fmin

OK

11.0 Reinforcement
Volume of concrete

5.3 m3

Quantity of steel required (@ 30 kg/m3)

158 kg

Weight of bar

2.47 kg/m

Number of bars // to length of foundation

8 Nos.

Number of bars // to width of foundation

20 Nos.

Number of bars // to length of foundation & act as strips

5 Nos.

Length of bar along length of foundation

10.3 m

Length of bar along length of foundation

5.6 m

Length of bar which act as strips


Total steel provided

=
=
>

12.3 m
631 kg
As - Required

OK

T20 @ 150 c/c (on all 3 sides)


920

New pump plinth


EL+0.80
Existing Base slab

71318-00/1132001-Rev.0: Attachment-I

4of 5

1500

71318-00/1132001-Rev.0: Attachment-I

5of 5

Você também pode gostar