Objectives:
Reference Manuals:
ZTE E_guard USMS Unified Site Management System V1.67
Operation Manual
Target Readers:
Contents
Chapter 1 Overview........................................................................................................................1
1.1 Introduction............................................................................................................................1
1.2 Operating Principle................................................................................................................2
1.3 Installation Environment........................................................................................................3
1.3.1 Hardware Environment................................................................................................3
1.3.2 Software Environment..................................................................................................3
1.4 Glossaries..............................................................................................................................3
Chapter 2 Installation and Use......................................................................................................5
2.1 Installation.............................................................................................................................5
2.1.1 Installation Preparation................................................................................................5
2.1.2 Installation Steps..........................................................................................................5
2.2 Use of the iPowerConfig........................................................................................................8
2.2.1 Login.............................................................................................................................9
2.2.2 Site Configuration.......................................................................................................12
2.2.3 Batch Modifying..........................................................................................................23
2.2.4 Synchronizing Level 2 (LSC) and Level-3 (CSC) Supervision Center.......................23
2.2.5 Alarm Scheme............................................................................................................23
2.2.6 Adding User and Setting Authority.............................................................................23
2.2.7 Managing Basic Information.......................................................................................23
2.2.8 Video Integration Configuration Scheme...................................................................23
Chapter 1 Overview
Knowledge Points:
To introduce the functions of the iPowerConfig;
To briefly describe the operating environment of the iPowerConfig.
1.1 Introduction
The iPowerConfig software is a subsystem of E_guard USMS V1.67 system.
It is responsible for adding and configuring devices of NMS and field
supervision units, as well as authority settings of the entire system. It is the
core to ensure the normal running of the entire system.
The location of it in the entire system is as shown in Figure 1.1 -1
Figu
re 1.1-1
System Architecture
Chapter 1 Overview
1.4 Glossaries
System Template: refers to the database base template managed by the
company, which is saved in base database and must not be changed by the
field.
Field template: refers to the device template derived from the System
Template by user according to actual situation.
2.1 Installation
2.1.1 Installation Preparation
These programs must be already installed before installing the iPowerConfig
console: dotnet2fx, WindowsInstaller3.1, sqlncli_CHS, vcredist_x86_CHS.
2.
3.
4.
2.
3.
database,
iNodeServer,
iPowerStore,
iPowerManager,
Add bus under front PC (image module should be added with safeguard
bus in the safeguard console);
5.
Add site;
6.
7.
Add FSU detail: select scan bus and protocol DLL, etc;
8.
9.
10. Add device: power equipment, environment device & access control
device, sensors, and audio/video device.
11. Configure four-level alarm scheme and storage scheme.
12. Configure tele-control enabling expression and control success
expression, such as, air-conditioning, turn-off, rectifier module on/off,
etc.
13. Configure site template and copy sites with same configurations.
2.2.1 Login
Click Start > Programs > ZTE E_guard USMS > iPowerConfig >
iPowerConfig or double-click iPowerConfig.exe under the installation
directory to start the iPowerConfig program. The Login window is as shown
in Figure 2.2 -6 .
10
11
Device
sion
Type
Device Name
Actual access
channel
Unit
Channel
configured
Remark
in
Bus
Information
NMS
Camera
Fixed
brick
To
camera
1#
channel of
encoder
EISU
Encoder
Standard 5016
Power
YD2010
COM2
equipme
nt
1#
\
intelligent
port
Gree
intelligent
COM3
air-conditioner
2 # intelligent
port
12
127.0.0.1,10
001
COM4
switching power
3#
intelligent
Board channel
port
supply
Environ
Temperature
Channel 1
ment
equipme
1
Infrared sensor
Channel 9
nt
Board channel
9
Smoke sensor
Smoke
Board channel
Correlate
dedicated
13
a control
channel
channel
DO3
Door contact
Channel 10
Board channel
10
Water sensor
Channel 11
Board channel
11
Access
Access controller
Equipm
Door dedicated
Access port
channel
ent
Device
on Unit
Type
Device Name
Actual
Channel
access
configured
channel
MISU
Camera
Fixed
brick
Remark
Bus
Information
in NMS
\
camera
To
2#
channel
of
encoder
Encoder
Standard
7#
5016
Power
YD2010
COM2
equipment
intelligent
port
Gree
13#
intelligent air-
intelligent
conditioner
port
ZXDU68
Environme
COM3
COM4
19#
switching
intelligent
power supply
port
Temperature
AI1
AI1
13
127.0.0.1,1231
Infrared
DI1
DI1
equipment
sensor
Smoke sensor
DI2
DI2
Water sensor
DI3
DI3
Door contact
DI3
DI3
Correlate
a control
channel
DO1
Access
Access
Door
Access port
Equipment
controller
dedicated
channel
When configuring specific site information, please pay close attention to the
differences between configuring EISU and MISU.
2.2.2.1 Configure a Basic Site
2.2.2.1.1 Importing System Template
This is to import the system base data template made by R&D.
14
15
Site level can be the default level selected by the system automatically.
2.2.2.1.1 Adding Supervision Network
This is to add a supervision network, i.e. LSC or CSC supervision center.
Configure Supervision Center > Center and Region List > Add
Supervision Center to open the Add Supervision Center dialog, as shown
in Figure 2.2 -12 .
16
17
18
19
Note
How many iPowerScadas and iPowerClients should be added depends on
the actual quantity.
20
Note:
If computer host has dual NIC, here setting as 127.0.0.1 is OK.
21
Scan Bus Type: the type of bus, generally select common scan bus;
22
23
The port of bus is the port number for access control communication. If use
EISU, default is 13215.
2. Second, we introduce the scan bus configuration when iPowerScada
works as server.
24
Scan Bus Type: the type of bus, generally select common scan bus;
Scan Bus Name: name of scan bus;
Comm Param: parameters of bus;
Comm DLL: dynamic link library used by the bus scanning;
Scan Time: time internal of scanning information, just keep default value;
Enter scan bus name and click Generate Parameters to go to the
Configure Scan Bus Parameters window, click TCP Server tab, as shown
in Figure 2.2 -21 .
If use MISU, type in the MAC address of MISU in the MAC Address field.
25
26
27
Site ID: the ID assigned when planning, must be unique under a same LSC,
under 8000.
Site Name: The name of the site to be added, use (region + site name);
Site Type: Select the type of site, for convenient of statistical management;
User Site ID: Not required;
Networking Mode: Select corresponding networking mode;
Region: Select the region where the site belongs to;
State: After site information is configured, a running state shall be selected.
2.2.2.1.7 Adding Supervision Unit
This is to add supervision unit, such as MISU, EISU, PMU, GSU, and BMU,
and to configure the supervision channels like name, virtual expression, etc.
of supervision unit.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit, click Add Supervision Unit to open the Add
FSU dialog, as shown in Figure 2.2 -25 .
28
The configuration of EISU is the same, except that the device type and
template are different. Select EISU, as shown in Figure 2.2 -27
29
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > MISU > FSU Detail Info, click Add FSU Detail
Information to open the FSU Detail Info dialog, as shown in Figure 2.2
-28 .
Description
EISU protocol parser DLL
GSU protocol parser DLL
30
PaserPcu.dll
PaserDoor.dll
ProtocolEisu80.dll
ProtocolZXDU300V30.wso
ProtocolEisu.wso
ProtocolMisu25.dll
ProtocolMisu44.dll
31
For specific slope and offset of expression, please set as per the actual
parameters of sensor.
Click OK to confirm.
After the temperature express is configured, the result is displayed as shown
in Figure 2.2 -31 .
32
33
34
35
Click Site Device > Site List > **Supervision network > **iPowerScada >
** Site > Supervision Unit > EISU > Channel, double-click the channel to
be modified.
36
Select the corresponding channel and change channel type to DI. The
generation of expression is same as that of MISU. Please pay attention to
the corresponding channel of the expression variable.
37
38
FSU Device ID: select the FSU, i.e. supervision unit that the device belongs
to.
MISU Device Index: select the intelligent index number of the device;
Device Type: select the type of the device;
Click OK to confirm.
The method of adding ZXDU68 power supply and Gree intelligent airconditioner is the same as adding YD2010, except for the device template.
ZXDU68 is a kind of rectifier power distribution equipment; Gree intelligent
air-conditioner is a kind of common air-conditioner equipment.
Use EISU
The method of configuration when using EISU is the same as the method
when using MISU. Just select EISU for FSU device ID and the EISU Device
Index is accumulated, which is different from MISU. Refer to configuration
table for details.
2.2.2.1.9 Configuring Environment Device
This is to add various environment devices like identification, environment,
and others.
Adding Device
39
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment Device, click Add Environment Device to open the
Add Environment Device dialog, as shown in Figure 2.2 -41 .
Add environment device when using MISU is the same as that of EISU,
except for selecting FSU.
Environment device is not intelligent device, set 0 in MISU Device Index
field.
Correlating and changing corresponding variables
(1) Telemeter
This is to set the properties of telemeter.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment > Telemeter, double-click the channel to be modified.
40
Monitoring Data Name: name of monitoring name, just keep the default;
FSU Device: the FSU device where the monitoring data belongs to,
generally keep it default.
Valid Upper Limit: the maximum value for valid monitoring data;
Valid Lower Limit: the minimum value for valid monitoring data;
FSU Channel ID: the monitoring points of this monitoring data of the
correlated supervision unit i.e. correlated supervision channel.
Precision: decimal places of the value of monitoring data;
Severity: the significance level of the monitoring data;
Limit Bandwidth: default;
Rangeability threshold: default;
Last Value: default.
Select the corresponding supervision channel of supervision unit and set
proper decimal places.
41
42
43
44
Telesignal
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment > Telesignal, double-click the channel to be modified.
45
46
47
48
Select the scan bus corresponding to the site, and the protocol DLL
ParserDoor.dll and click OK.
2.2.2.1.11 Copy Site
This is to add site information quickly by setting template site and copying it.
Click Site Device > Site List > **Level-2 Supervision center >
**iPowerScada, right-click an already configured site and click Set as
Template to set the site a template site, as shown in below:
49
50
Right-click the iPowerScada into which the site will be added and select
Paste Site on the right-click menu:
51
52
53
54
Bus ID: select the scan bus used by the PMU in transmitting picture;
MAC Address: MAC address of low-end PMU.
Add camera:
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Video Device, click Add Video Device, as shown in Figure 2.2
-59 .
55
56
Scan Bus Type: the type of bus, generally select common scan bus;
Scan Bus Name: name of scan bus;
Comm Param: parameters of scan bus;
Comm DLL: dynamic link library used by the bus scanning;
Scan Time: time internal of scanning information, just keep default value;
Enter scan bus name and click Generate Parameters to go to the
Configure Scan Bus Parameters window. Click TCP Server tab, enter the
MAC address of MISU.
57
2. EISU+ Camera
When EISU is used at the bottom, it is required to add safeguard bus,
safeguard EISU device, and camera.
The method of adding safeguard bus and camera is the same as that when
using MISU, except for selecting EISU Door instead of PMU. The port of
safeguard bus needs to be the one for low-end EISU security console
parameters. Default is 12615, as shown in Figure 2.2 -62 .
58
59
Bus ID: select the scan bus used for communication of EISU Door;
Device Unique Address: the global unique number of the EISU door in this
site, as shown in Figure 2.2 -65
Add camera:
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Video Device, click Add Video Device, as shown in Figure 2.2
-66 .
60
Select the site, and check the Successful Control Expression check box,
click Generate Expression to open the Generate Expression window, as
shown in Figure 2.2 -68 .
61
62
63
64
Since mains supply failure is judged through the value of other channel, so it
is a level-2 formula.
Select Two-level formula and click Generate Expression to open the
Formula Builder window, as shown in Figure 2.2 -72 .
65
66
67
When the first time refreshing level-2/3 database, only one change record is
displayed here, just click Import All.
2.2.4.3 Synchronizing by Customized
This is to synchronize the contents selected by users.
Click By Customized tab, select the contents to be synchronized, click
Import.
68
Click Basic Information tab, select the items to be synchronized and click
Synchronize button.
69
70
Note:
1.
2.
Telemeter must be set up with upper and lower limits and the upper limit
must be greater than the lower limit. But it is unnecessary to set alarm
level. Telesignal, however, must be set up with alarm level, but upper &
lower limits are not necessary.
3.
When adding telemeter (the State Data Type is less than 1000.)
scheme, state data type, explanation value, alarm delay, alarm clear
delay, and Delta value must be set.
4.
Each monitoring data type can correspond with only one state type.
However, each state type can correspond with multiple state types.
5.
Alarm Delay, Alarm Clear Delay, and Delta can only be positive
number.
71
Note:
Double-click a data row or select it and click Modify to open a dialog box.
When Monitoring Type is tele-signal (above 1000), the dialog is as shown
in figure below:
72
73
74
Select one data; click Edit to open the Detail of Special Four Level
Alarm Scheme window. When Monitoring Data Type is telesignal
(above 1000), the alarm severity level must be selected, as shown in
Figure 2.2 -85 :
75
To delete, select one or more data rows, click Delete on the title bar,
the following Warning dialog will appears:
76
77
Select the role that you added just now to assign appropriate authority
information to it, as below:
78
79
Figure 2.2-91
80
81
82
2.
The applied templates have been imported into database by using the
iPowerConfig. See Importing System Device Template for details.
83
3.
In the next sections, we mainly introduce the third step: how to make field
template for vide device and what should be paid attention.
2.2.8.1.1 Making Field Template for Small Platform Device
Small platform device is NMS device. Suppose system template of video
device has been applied successfully and has been imported into database.
Start the iPowerConfig console, click Utility Management > Template
Management Tool, select NMS > Small Platform Server in the Device
Template Tree, as shown in figure below:
Click Add Template open the Device Template dialog, as shown in figure
below:
84
The left pane lists the system template(s) that you imported into database
using the iPowerConfig. Select one, and input a name for the field template,
and enter remarks, as shown in figure below:
Click OK, the field template of small platform device has been made.
85
Click Add Template to open the dialog. Select the system template to be
used from the left pane, type in the name of the field template and input
remark. Select DI and DO in Telesignal and Teleadjust. Click OK, the
encoder field template has been made.
2.2.8.1.3 Making Field Template for Decoder
The steps for making decoder field template is the similar to encoder.
Note: all configuration variables must be selected when making decoder field
template.
2.2.8.1.4 Making Field Template for Camera
The steps for making camera field template are the similar to encoder.
86
Note: all configuration variables must be selected when making camera field
template.
2.2.8.2 Video Device Management Module
2.2.8.2.1 Configuring Small Platform Device
A small platform server must be configured first before using video
integration system. In NMS system, small platform server device is NMS
equipment. So configuring small platform server is the same as configuring
other NMS equipments, such as, iPowerClient, safeguard console, etc., Start
the iPowerConfig and click Supervision Center > Network Management
Equipment > Add Network Management Equipment to open the Add
NMS Device dialog, as shown in figure below:
Enter proper information and click OK, a small platform server has been
added.
To modify small platform record, select the small platform record in
supervision center and click Modify to open the dialog and change it.
To delete small platform record, select the small platform record in
supervision center and click Delete to delete it.
87
Then we need to configure correct IP address, port number, user name, and
password for the small platform. If not configure these, error may occur
when synchronizing data into video server.
First of all, select the small platform that we just added from the supervision
center node, and click Teleconfig from the right part of the window, as
shown in figure below:
We can see that there are 4 rows in the Teleconfig list; they are IP address,
port, user Name and password. Given that these information of the small
platform server are 10.72.13.30, 8000, admin, and 888888 respectively,
Now we need to change these items to the correct ones. First, double-click
the IP Address row to open the Modify Teleconfig dialog and input correct
address, as shown in figure below:
88
Click OK to confirm. Then we need to repeat the above steps to change the
port, user name and password.
Click Utility Management> Video Integration Configuration Tool to check
the small platform devices under the current supervision center, as shown in
figure below:
We can see that the small platform device we added just now is displayed in
the Device List.
89
Select a site and click OK to open the Add Encoder dialog, as shown in
figure below:
90
91
92
Click OK, the decoder just added can be seen in the right list, as shown in
figure below:
93
To modify decoder record, select the decoder record to be changed and click
Modify to open the dialog and change it.
To delete decoder record, select the decoder record that you want to delete
and click Delete to delete it.
2.2.8.3 Correlating DI and Camera
This function is to correlate DI and cameras within the same site. One DI can
be correlated with more than one camera. Select the DI under a device, for
example, DI under an encoder, as shown in figure below:
94
95
Move the mouse cursor away and click OK, the value of the camera which is
to be linked to the DI is set. Open it again; it is displayed as shown in figure
below:
If the check box is checked, it means the corresponding DI is linked with the
camera.
96
To change the value of camera linked to DI, double-click it and change the
value, then click OK to confirm. To delete the value, deselect the check box
before DI, and click OK to confirm.
2.2.8.4 Video Device Synchronization Module
Video device synchronization module is mainly used to synchronize the
video devices configured in NMS into video small platform server. There are
two main synchronization methods. One method is to synchronize by
platform, that is, synchronize devices of platform into video database by
whole. The other method is to synchronize based on difference. This method
is similar to differential synchronization function in Level-2/3 synchronization
tool in NMS.
Note: when using the video device synchronization module, the IP address,
port number, user name and password of small platform must be ensured
correct. Otherwise, error may occur. Refer to Configuring Small Platform
Device for configuring small platform.
2.2.8.4.1 Platform Synchronization
This is to synchronize devices at NMS into video database by whole. To do
this, delete devices at video side first, then synchronize all the devices at
NMS to the video side.
Select a small platform device, right-click
Synchronization, as shown in figure below:
97
and
select
Platform
98
Select the small platform to be synchronized, click OK, the lower part of the
window lists the different data records; select the record(s) to be
synchronized from the list, as shown in figure below. It is recommended to
test the connection of the small platform by selecting the platform from the
video device management module and clicking Test.
99
100
101
Click Quick Start at the right part of the window, select Notepad, right-click
and select Paste to paste the video device ID, as shown in figure below:
102
The following window which shows the topological graph of video devices
appears:
103
Click the down arrow at the upper right corner of the window to adjust
the size of the graph.
2.2.8.5.4 Testing Small Platform Connection
This is mainly to test the connection of small platform. It is available only
when small platform node is selected.
Configure correct user name, password, port, and IP address for the small
platform device, click the small platform node, right-click and select Test
Platform Connection, as shown in figure below:
104
If small platform device configuration (IP address, port, user name and
password) is not correct or the small platform server itself is not connected,
the following Prompt box will appear:
105
106
Appendix A Abbreviations
Abbreviations
Full Name
CMU
CSC
EMU
MISU
ODBC
PC
Personal Computer
SC
Supervision Center
SM
Supervision Module
SU
Supervision Unit
TCP