Você está na página 1de 108

ZTE E_guard USMS V1.

67 Training
Manual iPowerConfig
Objectives:

To understand the functions of ZTE E_guard USMS V1.67


iPowerConfig;

To understand the basic configuration of ZTE E_guard USMS


V1.67 iPowerConfig;
To comprehend the batch editing tool of ZTE E_guard USMS
V1.67 iPowerConfig;

To master authority settings of ZTE E_guard USMS V1.67


iPowerConfig;

Reference Manuals:
ZTE E_guard USMS Unified Site Management System V1.67
Operation Manual

Target Readers:

System maintenance personnel;

Engineering outsourcing personnel

Contents
Chapter 1 Overview........................................................................................................................1
1.1 Introduction............................................................................................................................1
1.2 Operating Principle................................................................................................................2
1.3 Installation Environment........................................................................................................3
1.3.1 Hardware Environment................................................................................................3
1.3.2 Software Environment..................................................................................................3
1.4 Glossaries..............................................................................................................................3
Chapter 2 Installation and Use......................................................................................................5
2.1 Installation.............................................................................................................................5
2.1.1 Installation Preparation................................................................................................5
2.1.2 Installation Steps..........................................................................................................5
2.2 Use of the iPowerConfig........................................................................................................8
2.2.1 Login.............................................................................................................................9
2.2.2 Site Configuration.......................................................................................................12
2.2.3 Batch Modifying..........................................................................................................23
2.2.4 Synchronizing Level 2 (LSC) and Level-3 (CSC) Supervision Center.......................23
2.2.5 Alarm Scheme............................................................................................................23
2.2.6 Adding User and Setting Authority.............................................................................23
2.2.7 Managing Basic Information.......................................................................................23
2.2.8 Video Integration Configuration Scheme...................................................................23

Chapter 1 Overview
Knowledge Points:
To introduce the functions of the iPowerConfig;
To briefly describe the operating environment of the iPowerConfig.

1.1 Introduction
The iPowerConfig software is a subsystem of E_guard USMS V1.67 system.
It is responsible for adding and configuring devices of NMS and field
supervision units, as well as authority settings of the entire system. It is the
core to ensure the normal running of the entire system.
The location of it in the entire system is as shown in Figure 1.1 -1

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figu

re 1.1-1

System Architecture

Chapter 1 Overview

1.2 Operating Principle


Through the operation of user, the iPowerConfig writes the actual site
configuration information at field into the database ZXM10_CFG. Each
node reads the added information from the iPowerConfig. They build a
perfect power environment supervision system together.

1.3 Installation Environment


1.3.1 Hardware Environment
Recommended configuration:
CPU main frequency: Pentium 4 CPU 3.00GHz
Memory: 1GB
Hard disk: 80GB

1.3.2 Software Environment


Operating system: Windows XP sp2 or later, Windows 2003 or later;
Software environment: .NET FrameWork2.0
vcredist_x86_CHS

1.4 Glossaries
System Template: refers to the database base template managed by the
company, which is saved in base database and must not be changed by the
field.
Field template: refers to the device template derived from the System
Template by user according to actual situation.

Chapter 2 Installation and Use


Knowledge Points:
To introduce the installation of iPowerConfig;
To introduce the operation and site configuration of iPowerConfig;

2.1 Installation
2.1.1 Installation Preparation
These programs must be already installed before installing the iPowerConfig
console: dotnet2fx, WindowsInstaller3.1, sqlncli_CHS, vcredist_x86_CHS.

2.1.2 Installation Steps


1.

Double-click ZXM10-iPowerConfig and click Nest.

Figure 2.1-2 Setup Wizard

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

2.

Select an installation path, click Next.

Figure 2.1-3 Select Installation Path

3.

Click Install to start installation.

Chapter 2 Installation and Use

Figure 2.1-4 Start Installation

4.

Click Finish to complete the installation.

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.1-5 Complete Installation

2.2 Use of the iPowerConfig


Before performing database configuration, we need to plan the networking,
IP, LSC ID, region, site/end office ID, and wiring diagram. Then we need to
carry out as per the following process:
1.

Import system template and make field template according to actual


demand;

2.

Add supervision network;

3.

Add network management equipment under supervision center:


SQL2005

database,

iNodeServer,

iPowerStore,

iPowerManager,

iPowerReport, Safeguard console, iPowerBackup, iPowerClient, and


iPowerScada, and add computer host and add its proper IP in
configuration variable.
4.

Add bus under front PC (image module should be added with safeguard
bus in the safeguard console);

Chapter 2 Installation and Use

5.

Add site;

6.

Add supervision unit;

7.

Add FSU detail: select scan bus and protocol DLL, etc;

8.

Configure supervision channel of supervision unit (EISU needs to


change the channel type, while MISU does not)

9.

Configure virtual expression of door contact, water sensor, mains off,


etc. For EISU, virtual expressions of temperature, voltage and other
channels can be configured by EISU configuration program. While
MISU cannot do this, these expressions need to be added on the
iPowerConfig console.

10. Add device: power equipment, environment device & access control
device, sensors, and audio/video device.
11. Configure four-level alarm scheme and storage scheme.
12. Configure tele-control enabling expression and control success
expression, such as, air-conditioning, turn-off, rectifier module on/off,
etc.
13. Configure site template and copy sites with same configurations.

2.2.1 Login
Click Start > Programs > ZTE E_guard USMS > iPowerConfig >
iPowerConfig or double-click iPowerConfig.exe under the installation
directory to start the iPowerConfig program. The Login window is as shown
in Figure 2.2 -6 .

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-6 Login Window

User Name: name of user added in iPowerConfig console, default is


admin;
Password: password of user when added, default is admin;
Before login the iPowerConfig console, please test database connection and
configure IP of iPowerAuthority Console.
2.2.1.1 Setting Database Connection
This is to set the database to be accessed.

10

Chapter 2 Installation and Use

Figure 2.2-7 Enter IP of Database Server

Server Name: IP address of server where the actual database is located,


127.0.0.1 for local;
Database Name: zxm10_cfg;
Login Name: default is sa;
Password: default is zxm10;
Click Test button to test the connection.
2.2.1.2 Setting Authority Connection
This is to set the IP of iPowerAuthority server.

11

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-8 Enter IP of iPowerAuthority Console

Enter IP address of the iPowerAuthority. If run in local machine, keep it as


127.0.0.1.
Click Test to test the connection.

2.2.2 Site Configuration


The following site information need to be configured in simulation at field:

Table 2.2-1 EISU Template Site


Supervi

Device

sion

Type

Device Name

Actual access
channel

Unit

Channel
configured

Remark
in

Bus
Information

NMS
Camera

Fixed

brick

To

camera

1#

channel of
encoder

EISU

Encoder

Standard 5016

Power

YD2010

COM2

equipme
nt

1#

\
intelligent

port
Gree

intelligent

COM3

air-conditioner

2 # intelligent
port

12

127.0.0.1,10
001

Chapter 2 Installation and Use


ZXDU68

COM4

switching power

3#

intelligent

Board channel

port

supply
Environ

Temperature

Channel 1

ment
equipme

1
Infrared sensor

Channel 9

nt

Board channel

9
Smoke sensor

Smoke

Board channel

Correlate

dedicated

13

a control

channel

channel
DO3

Door contact

Channel 10

Board channel

10
Water sensor

Channel 11

Board channel

11
Access

Access controller

Equipm

Door dedicated

Access port

channel

ent

Table 2.2-2 MISU Template Site


Supervisi

Device

on Unit

Type

Device Name

Actual

Channel

access

configured

channel
MISU

Camera

Fixed

brick

Remark

Bus
Information

in NMS
\

camera

To

2#

channel
of
encoder

Encoder

Standard

7#

5016
Power

YD2010

COM2

equipment

intelligent

port
Gree

13#

intelligent air-

intelligent

conditioner

port

ZXDU68

Environme

COM3

COM4

19#

switching

intelligent

power supply

port

Temperature

AI1

AI1

13

127.0.0.1,1231

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig


nt

Infrared

DI1

DI1

equipment

sensor
Smoke sensor

DI2

DI2

Water sensor

DI3

DI3

Door contact

DI3

DI3

Correlate
a control
channel
DO1

Access

Access

Door

Access port

Equipment

controller

dedicated

channel

When configuring specific site information, please pay close attention to the
differences between configuring EISU and MISU.
2.2.2.1 Configure a Basic Site
2.2.2.1.1 Importing System Template
This is to import the system base data template made by R&D.

Figure 2.2-9 Import System Template

2.2.2.1.2 Making Field (Device) Template

14

Chapter 2 Installation and Use

This is to make field template which is used for database configuration.


Click Utility Management > Template Management Tool > Add Template
to open the Device Template interface, as shown in Figure 2.2 -11 ;

Figure 2.2-10 Click Add Template

Select the desired semaphore to make field template.

15

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-11 Device Template Window

Site level can be the default level selected by the system automatically.
2.2.2.1.1 Adding Supervision Network
This is to add a supervision network, i.e. LSC or CSC supervision center.
Configure Supervision Center > Center and Region List > Add
Supervision Center to open the Add Supervision Center dialog, as shown
in Figure 2.2 -12 .

16

Chapter 2 Installation and Use

Figure 2.2-12 Create Supervision Network

IsCSC: 1 for level-3 supervision center (CSC), 0 for level-2 supervision


center;
LSC ID: 1 for level-3 supervision network, any number between 2~64 for
level-2 supervision network;
LSC Name: the name of the supervision network to be created, use (region
+ supervision network) mode;
Click OK to confirm.
2.2.2.1.2 Adding Region
This is to add region information.
Click Supervision Center > Center and Region List > ** Supervision
network, click Add Region to open the Add Region dialog, as shown
in Figure 2.2 -13 .

17

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-13 Add Region

Add region information according to actual regions at field, mainly for


classification management and display of sites.
For example, if there are Nanshan, Luohu, and Futian in Shenzhen (LSC),
then add these three regions for convenient site management to Shenzhen
LSC.
Region ID: set ID of region, range from 1 ~254, ID under a same LSC
should be unique;
Region Name: name of the region;
Up Region ID: If region nested, select the superior region of it.
Note: When adding supervision center, the system adds the network
management equipments needed for building NMS system automatically.
2.2.2.1.3 Adding Other Network Management Equipments
This is to add network management equipments other than the default ones
added by the system automatically.
Click Supervision Center > Center and Region List > ** Supervision
network > Supervision Center > Network Management Equipment, click

18

Chapter 2 Installation and Use

Add Network Management Equipment to open the Add NMS Device


dialog, as shown in Figure 2.2 -14 .

Figure 2.2-14 Add NMS Device

Add these NMS devices: iPowerClient, iPowerScada, Safeguard,


iPowerSync (only in V1.6 NMS level-3 networking), iPowerDiesel Adapter
and (Only when diesel generator scheduling system is used).
Device ID: generated by the system;
User Device ID: Not required;
Device Type: Type of NMS device;
Launch Time: generated by the system;
Device Module: select the template used by the device;
Device Name: Device name defined by user;
Host IP: Enter the IP address of the computer where the network
management software is installed.
Click OK to confirm.

19

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

After added, they are displayed as below

Figure 2.2-15 Network Management Equipments Added

Site Device is generated by the system automatically when adding site, do


not have to change it. The purpose is to manage the supervision center as a
device.
The Device ID at the left of each device is the basis of registration of node in
building NMS system.

Note
How many iPowerScadas and iPowerClients should be added depends on
the actual quantity.

2.2.2.1.4 Adding Computer Device


This is to add computers of the field.
Click Supervision Center > Center and Region List > ** Supervision
network > Supervision Center > Computer, click Add Computer to open
the Add Computer Device dialog, as shown in Figure 2.2 -16 .

20

Chapter 2 Installation and Use

Figure 2.2-16 Add Computer Device

Device ID: generated by the system;


User Device ID: Not required;
Device Type: Type of computer device;
Launch Time: generated by the system;
Device Template: select the template used by the device;
Device Name: Device name defined by user;
Host IP: Enter the actual IP address of the computer host
Add all work stations and servers used in the NMS system, for monitoring
the operation conditions of them on the iPowerManager.
Click OK to confirm.

Note:
If computer host has dual NIC, here setting as 127.0.0.1 is OK.

21

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

2.2.2.1.5 Adding Bus Information


This is module scanning bus and door scan bus information.
Click Supervision Center > Center and Region List > **Supervision
network > Supervision Center > **iPowerScada, click Add Scan Bus to
open the Add Scan Bus dialog, as shown in Figure 2.2 -17 .
After adding all NMS devices, we need to add module scan bus and door
scan bus information (if access equipment exists) of iPowerScada. There
are two cases for configuring scan bus according to the manner of working
of iPowerScada.
iPowerScada serves as client;
iPowerScada serves as server.
Communication DLL for these two working modes are different and the bus
parameters are also different.
1. First of all, we introduce the scan bus configuration when iPowerScada
works as client.

Figure 2.2-17 iPowerScada as Client

Scan Bus Type: the type of bus, generally select common scan bus;

22

Chapter 2 Installation and Use

Scan Bus Name: name of scan bus;


Comm Param: parameters of scan bus;
Comm DLL: dynamic link library used by the bus scanning;
Scan Time: time internal of scanning information, just keep default value;
Enter scan bus name and click Generate Parameters to go to the
Configure Scan Bus Parameters window, as shown in Figure 2.2 -18 .
If use EISU, the port of scan bus is fixed as 12315; if use MISU, the port of
bus should be configured according to actual port assignment. Here we
support it is 3000.

Figure 2.2-18 Enter Scan Bus Parameters (use EISU)

IP Address: IP address of site;


Port: Port for bus communication;
Wait Time: waiting time for bus scanning;
Comm DLL: use NetScanClnt.dll when iPowerScada works as client;
The bus parameter configuration when using MISU is the same as EISU.
The steps of adding door scan bus information is the same as adding scan
bus information, except for port selection.

23

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-19 Add Door scan bus

The port of bus is the port number for access control communication. If use
EISU, default is 13215.
2. Second, we introduce the scan bus configuration when iPowerScada
works as server.

24

Chapter 2 Installation and Use

Figure 2.2-20 iPowerScada as Server

Scan Bus Type: the type of bus, generally select common scan bus;
Scan Bus Name: name of scan bus;
Comm Param: parameters of bus;
Comm DLL: dynamic link library used by the bus scanning;
Scan Time: time internal of scanning information, just keep default value;
Enter scan bus name and click Generate Parameters to go to the
Configure Scan Bus Parameters window, click TCP Server tab, as shown
in Figure 2.2 -21 .
If use MISU, type in the MAC address of MISU in the MAC Address field.

25

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-21 Use MISU Supervision Unit

If use EISU, type in the global ID of EISU and go to EISU configuration


program.

Figure 2.2-22 Use EISU Supervision Unit

26

Chapter 2 Installation and Use

Figure 2.2-23 Enter Global ID

Select NetServerEISU.dll in Comm DLL for EISU and NetServer.dll for


MISU;
Meanwhile, we need to set the server IP of bottom supervision unit as the IP
of the iPowerScada where the site belongs to, as shown in Figure 2.2 -24 .

Figure 2.2-24 Enter Server (iPowerScada) IP

2.2.2.1.6 Adding Site Information


This is to add the information of site.
Click Site Device > Site List > **Supervision network > **iPowerScada,
click Add Site to open the Add Site dialog, as shown in Figure 2.2 -25 .
Enter site ID and site name, select site type, region, and networking mode,
and click OK to confirm.

27

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-25 Add Site

Site ID: the ID assigned when planning, must be unique under a same LSC,
under 8000.
Site Name: The name of the site to be added, use (region + site name);
Site Type: Select the type of site, for convenient of statistical management;
User Site ID: Not required;
Networking Mode: Select corresponding networking mode;
Region: Select the region where the site belongs to;
State: After site information is configured, a running state shall be selected.
2.2.2.1.7 Adding Supervision Unit
This is to add supervision unit, such as MISU, EISU, PMU, GSU, and BMU,
and to configure the supervision channels like name, virtual expression, etc.
of supervision unit.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit, click Add Supervision Unit to open the Add
FSU dialog, as shown in Figure 2.2 -25 .

28

Chapter 2 Installation and Use

It is recommended to add supervision unit from system template, as shown


in Figure 2.2 -26 .

Figure 2.2-26 Add FSU (MISU)

The configuration of EISU is the same, except that the device type and
template are different. Select EISU, as shown in Figure 2.2 -27

Figure 2.2-27 Use EISU

Device Type: the type of supervision unit;


Device Template: the template used by the supervision unit;
Device Name: name of the supervision name;
After supervision unit is added, we need to associate the bus information for
supervision unit.

29

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > MISU > FSU Detail Info, click Add FSU Detail
Information to open the FSU Detail Info dialog, as shown in Figure 2.2
-28 .

Figure 2.2-28 FSU Detail Info

Scanbus ID: the bus used by the supervision unit;


Address: the DIP address of supervision unit, generally use 1;
Protocol DLL: protocol used by the supervision unit;
Different supervision units use different protocol DLLs. MISU uses
ParserMisu90.dll, and EISU uses ParserEISU.dll. The protocol DLLs used
by other supervision units are listed in Table 2.2 -3 .

Table 2.2-3 Protocol DLLs for Supervision Units


Protocol DLL
ParserEisu.dll
PaserGsu.dll

Description
EISU protocol parser DLL
GSU protocol parser DLL

30

Chapter 2 Installation and Use


PaserMisu90.dll

MISU protocol parser DLL

PaserPcu.dll

PCU protocol parser DLL

PaserDoor.dll

Door access protocol parser DLL

ProtocolEisu80.dll
ProtocolZXDU300V30.wso
ProtocolEisu.wso

Not used yet


Power protocol central parser DLL
EISU protocol central parser DLL

ProtocolMisu25.dll

Not used yet

ProtocolMisu44.dll

Not used yet

The method of configuring supervision channels of different supervision


units, like MISU and EISU, is different, as described as below:
Supervision unit is MISU
AI, DI, AO, and DO of MISU are not universal, they are configured as below:
(1).Configuring temperature virtual expression
MISU does not do preprocessing to telemeter data at the bottom, so
computed expression is required to be configured in NMS.
Click Site Device > Site List > **Supervision network > **iPowerScada >
** Site > Supervision Unit > MISU > Channel, double-click the channel to
be modified.

Figure 2.2-29 Configure Temperature Computing Expression

The following items need to be configured:

31

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Channel Type: select the proper data type of this channel;


Formula Type: select the formula type of the appropriate expression of this
channel;
Select 1 if calculating the variables of its own channels only. Click
Generate Expression to open the Formula Builder interface, as shown
in Figure 2.2 -30 .

Figure 2.2-30 Formula Builder

For specific slope and offset of expression, please set as per the actual
parameters of sensor.
Click OK to confirm.
After the temperature express is configured, the result is displayed as shown
in Figure 2.2 -31 .

32

Chapter 2 Installation and Use

Figure 2.2-31 Temperature Expression Added

Configuring expression for infrared sensor, vibration sensor, and water


sensor
For infrared, vibration, and water sensors, the original values need to be
negated to reflect the actual values. We take infrared sensor as an example
to introduce.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > MISU > Channel, double-click the channel to
be modified.

Figure 2.2-32 Configure Infrared Computing Expression

33

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Select the actually accessed tele-signal channel, and click Generate


Expression to open the Formula Builder.

Figure 2.2-33 Formula Builder

Figure 2.2-34 Infrared Expression Added

(3) Configuring smoke sensor reset


Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > MISU > Channel, double-click the channel to
be modified.

34

Chapter 2 Installation and Use

Figure 2.2-35 Configure Smoke Sensor Reset

The following items need to be configured:


Channel Name: type in a name recognizable name, like smoke reset;
DO Output Type: select the appropriate output type of DO, smoke is pulse
output;
Channel Type: select the proper data type of this channel;
Pulse Width: set the width of pulse, smoke reset uses pulse type, with width
2000ms;
Formula Type: select the type of the appropriate expression of this channel;

Supervision unit is EISU


Channel 1-12 of EISU are universal, channel 13 is dedicated smoke
channel. They are configured as below:
(1).Configuring temperature
Temperature of EISU has been preprocessed at the bottom, so virtual
expression is not required to be configured in NMS. We only need to change
the name of the appropriate channel for easy management.

35

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Click Site Device > Site List > **Supervision network > **iPowerScada >
** Site > Supervision Unit > EISU > Channel, double-click the channel to
be modified.

Figure 2.2-36 Set Channel Name of Temperature

Configuring expression for infrared, vibration and water sensors


Basically it is similar to MISU, except for channel selection and the needs of
selecting channel type or EISU universal channels. We take infrared sensor
as an example to introduce.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > EISU > Channel, double-click the channel to
be modified.

36

Chapter 2 Installation and Use

Figure 2.2-37 Configure Infrared Expression

Select the corresponding channel and change channel type to DI. The
generation of expression is same as that of MISU. Please pay attention to
the corresponding channel of the expression variable.

Figure 2.2-38 Results Displayed

(3) Configuring smoke sensor reset


Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit > EISU > Channel, double-click the channel to
be modified.

37

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-39 Configure Smoke Reset

2.2.2.1.8 Configuring Power Equipment


This is to add power device, like air-conditioner, rectifier and so on.
Use MISU
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Power Device, click Add Power Device to open the Add Power
Device dialog, as shown in Figure 2.2 -40 .

38

Chapter 2 Installation and Use

Figure 2.2-40 Add Power Device

FSU Device ID: select the FSU, i.e. supervision unit that the device belongs
to.
MISU Device Index: select the intelligent index number of the device;
Device Type: select the type of the device;
Click OK to confirm.
The method of adding ZXDU68 power supply and Gree intelligent airconditioner is the same as adding YD2010, except for the device template.
ZXDU68 is a kind of rectifier power distribution equipment; Gree intelligent
air-conditioner is a kind of common air-conditioner equipment.
Use EISU
The method of configuration when using EISU is the same as the method
when using MISU. Just select EISU for FSU device ID and the EISU Device
Index is accumulated, which is different from MISU. Refer to configuration
table for details.
2.2.2.1.9 Configuring Environment Device
This is to add various environment devices like identification, environment,
and others.
Adding Device

39

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment Device, click Add Environment Device to open the
Add Environment Device dialog, as shown in Figure 2.2 -41 .

Figure 2.2-41 Add ENV Device

Add environment device when using MISU is the same as that of EISU,
except for selecting FSU.
Environment device is not intelligent device, set 0 in MISU Device Index
field.
Correlating and changing corresponding variables
(1) Telemeter
This is to set the properties of telemeter.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment > Telemeter, double-click the channel to be modified.

40

Chapter 2 Installation and Use

Figure 2.2-42 Modify Telemeter

Monitoring Data Name: name of monitoring name, just keep the default;
FSU Device: the FSU device where the monitoring data belongs to,
generally keep it default.
Valid Upper Limit: the maximum value for valid monitoring data;
Valid Lower Limit: the minimum value for valid monitoring data;
FSU Channel ID: the monitoring points of this monitoring data of the
correlated supervision unit i.e. correlated supervision channel.
Precision: decimal places of the value of monitoring data;
Severity: the significance level of the monitoring data;
Limit Bandwidth: default;
Rangeability threshold: default;
Last Value: default.
Select the corresponding supervision channel of supervision unit and set
proper decimal places.

41

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-43 Set corresponding Telesignal of telemeter

The following item needs be configured:


Delay Time: the delay time for reporting alarm, set according to requirements
at field;
Click Alarm Mask Exception to set the mask expression for the
corresponding alarm of the telesignal.

42

Chapter 2 Installation and Use

Figure 2.2-44 Set Alarm Mask Expression for Telemeter

Click Validity Expression to set the validity expression of the telesignal.

43

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-45 Set Validity Expression for Telemeter

The above settings for telemeter must be configured according to actual


requirements at field.
For monitoring data not required can be deleted.

44

Chapter 2 Installation and Use

Figure 2.2-46 Delete Unnecessary Monitoring Data

Telesignal
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment > Telesignal, double-click the channel to be modified.

45

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-47 Modify Telesignal

The following items need to be configured:


FSU Channel ID: the monitoring points of this monitoring data of the
correlated supervision unit i.e. correlated supervision channel.
Generally, Alarm Mask and Other Info do not have to be configured, or
configure them as per actual situation.
Teleadjust
Teleadjust is not required for environment equipments.
Telecontrol
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Environment > Telecontrol, double-click the channel to be
modified.

46

Chapter 2 Installation and Use

Figure 2.2-48 Set Smoke Sensor Reset

The following item needs to be configured:


FSU Channel ID: the monitoring points of this monitoring data of the
correlated supervision unit, select the channel for smoke sensor reset.
2.2.2.1.10 Adding Door Device
This is to add door device and correlate it with appropriate door scan bus
information.
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Door, click Add Door to open the Add Door Device dialog, as shown
in Figure 2.2 -49 .

47

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-49 Add Door Device

Correlate scan bus information for door device:


Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Door > FSU Detail Info, click Add FSU Detail Information to open
the FSU Detail Info dialog.

48

Chapter 2 Installation and Use

Figure 2.2-50 Correlate Door Scanbus

Select the scan bus corresponding to the site, and the protocol DLL
ParserDoor.dll and click OK.
2.2.2.1.11 Copy Site
This is to add site information quickly by setting template site and copying it.
Click Site Device > Site List > **Level-2 Supervision center >
**iPowerScada, right-click an already configured site and click Set as
Template to set the site a template site, as shown in below:

49

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-51 Set as Template

Right-click the template site with icon

, click Copy Site:

Figure 2.2-52 Copy Site

50

Chapter 2 Installation and Use

Right-click the iPowerScada into which the site will be added and select
Paste Site on the right-click menu:

Figure 2.2-53 Paste Site

The Copy Site dialog appears, as shown in Figure 2.2 -54

Figure 2.2-54 Copy Site Dialog

51

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Site ID: the assigned number of site;


Site Name: the name of the site;
Region: select the region the site is located;
Scan Bus ID: correlate the scan bus that this site is using;
Click OK to confirm.
2.2.2.1.12 Changing Running State
This is to change the running state of site, so as to display the site on the
iPowerClient console.
To display the devices under a site on the iPowerClient console, the State of
the site must be changed to Running.
Click Site Device > Site List > **Level-2 Supervision center >
**iPowerScada, right-click and click Edit Site to open the Modify Site
dialog:

Figure 2.2-55 Change Running State

2.2.2.2 Configuring Image Acquisition Module


This is to use image acquisition module to acquire and store pictures from
site.

52

Chapter 2 Installation and Use

If image acquisition is required for site, the following configurations must be


conducted, there are two cases: MISU+PMU and EISU+ camera.
1. Use MISU+PMU:
PMU is used for supporting image acquisition.
Add safeguard image bus in safeguard console as follows:
Click Supervision Center > Center and Region List > **Supervision
Center > SafeGuard > ScanBus, click Add Scan Bus to open the Scan
Bus dialog, as shown in Figure 2.2 -56 .

Figure 2.2-56 Add Safeguard Scan Bus

Scan Bus Name: name of safeguard scan bus;


Bus Param: communication parameters of safeguard scan bus, generally
using IP + Port, for external port of low-end PMU, default is 12315.
It is not recommended to connect more than 500 picture manager units.
Add PMU device in supervision unit:
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Supervision Unit, click Add Supervision Unit, as shown in Figure
2.2 -57 .

53

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-57 Add PMU Device

Correlate safeguard bus:


Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > PMU > FSU Detail Info, click Add FSU Detail Information, as
shown in Figure 2.2 -58 .

54

Chapter 2 Installation and Use

Figure 2.2-58 Correlate Safeguard Bus

Bus ID: select the scan bus used by the PMU in transmitting picture;
MAC Address: MAC address of low-end PMU.
Add camera:
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Video Device, click Add Video Device, as shown in Figure 2.2
-59 .

55

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-59 Add Camera

Select PMU in FSU Device ID field.


iPowerScada scan bus employs the mode of TCP server:

56

Chapter 2 Installation and Use

Figure 2.2-60 Connect Image +MISU

Scan Bus Type: the type of bus, generally select common scan bus;
Scan Bus Name: name of scan bus;
Comm Param: parameters of scan bus;
Comm DLL: dynamic link library used by the bus scanning;
Scan Time: time internal of scanning information, just keep default value;
Enter scan bus name and click Generate Parameters to go to the
Configure Scan Bus Parameters window. Click TCP Server tab, enter the
MAC address of MISU.

57

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-61 Supervision Unit is MISU

2. EISU+ Camera
When EISU is used at the bottom, it is required to add safeguard bus,
safeguard EISU device, and camera.
The method of adding safeguard bus and camera is the same as that when
using MISU, except for selecting EISU Door instead of PMU. The port of
safeguard bus needs to be the one for low-end EISU security console
parameters. Default is 12615, as shown in Figure 2.2 -62 .

Figure 2.2-62 Set Security Console Port

Add safeguard EISU device as follows:


Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site >Supervision Unit, click Add Supervision Unit, as shown in Figure
2.2 -63 .

58

Chapter 2 Installation and Use

Figure 2.2-63 Add Safeguard EISU

Correlate safeguard bus:


Click Site Device > Site List > **Supervision network > **iPowerScada >
EISU Door > FSU Detail Info, click Add FSU Detail Information, as shown
in Figure 2.2 -64 .

Figure 2.2-64 Correlate Safeguard Bus

59

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Bus ID: select the scan bus used for communication of EISU Door;
Device Unique Address: the global unique number of the EISU door in this
site, as shown in Figure 2.2 -65

Figure 2.2-65 Set Global ID

Add camera:
Click Site Device > Site List > **Supervision network > **iPowerScada >
**Site > Video Device, click Add Video Device, as shown in Figure 2.2
-66 .

Figure 2.2-66 Add Camera

Select EISU Door in FSU Device ID field.

2.2.3 Batch Modifying


2.2.3.1 Batch Modifying Monitoring Data
This is to set virtual expression of monitoring data by batch.

60

Chapter 2 Installation and Use

Click Utility management > Monitory Data Batch Modifying Tool:


If the expression for controlling rectifier on or off needs to be modified by
batch, we can do it as per the following steps:

Figure 2.2-67 Batch Modifying Telecontrol Expression

Select the site, and check the Successful Control Expression check box,
click Generate Expression to open the Generate Expression window, as
shown in Figure 2.2 -68 .

61

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-68 Generate Expression

Set the successful control expression:

62

Chapter 2 Installation and Use

Figure 2.2-69 Set Successful Control Expression

After complete settings, click OK.

63

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-70 Update

Batch modifying of other expressions is similar.


2.2.3.2 Batch Modifying Monitory Point
This is to set virtual expression of monitory point by batch.
Click Utility management > Batch Modify Monitory Point, the following
window appears:
The expression of mains supply failure needs to be modified by batch at
field, and whether the AI2 mains supply voltage is below 100V needs to be
judged through the DI channel 50 of MISU.

64

Chapter 2 Installation and Use

Figure 2.2-71 Set Mains Supply Failure Expression

Since mains supply failure is judged through the value of other channel, so it
is a level-2 formula.
Select Two-level formula and click Generate Expression to open the
Formula Builder window, as shown in Figure 2.2 -72 .

65

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-72 Set Mains Supply Failure Expression by Batch

After settings completed, click Update.

66

Chapter 2 Installation and Use

Figure 2.2-73 Update Mains Supply Failure Expression

2.2.4 Synchronizing Level 2 (LSC) and Level-3 (CSC) Supervision Center


2.2.4.1 Setting Database Connection Information
This is to synchronizing the data between level-2 and level-3 databases.
Click Utility Management > Database Synchronization Tool to go to the
synchronization main window; level-2 and 3 databases can be refreshed
mutually. Here is the data refresh from level-2 supervision center to level-3.
When building level-3 network, changes for level-2 center need to be
refreshed into level-3 center, as below:

Figure 2.2-74 Set Level-3 Database Information

67

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Set correct level-3 database information and click Test to check if


connection is normal.
2.2.4.2 Synchronizing by System Difference

Figure 2.2-75 Refresh Level-2/3 Database by System Difference

When the first time refreshing level-2/3 database, only one change record is
displayed here, just click Import All.
2.2.4.3 Synchronizing by Customized
This is to synchronize the contents selected by users.
Click By Customized tab, select the contents to be synchronized, click
Import.

68

Chapter 2 Installation and Use

Figure 2.2-76 Refresh Level-2/3 Database by Customized

2.2.4.4 Synchronizing Basic Information


This is to synchronize some basic information, like four-level alarm scheme,
storage strategy, and so on.

Figure 2.2-77 Synchronize Basic Information

Click Basic Information tab, select the items to be synchronized and click
Synchronize button.

69

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

2.2.5 Alarm Scheme


2.2.5.1 Four-level Alarm Scheme
This is to change the scheme of how alarm is generated on the
iPowerScada.
Click Alarm and Storage Management > Four Level Alarm Scheme to go
to the alarm scheme main window:

Figure 2.2-78 Four-Level Alarm Scheme

Click Add to open the add four-level alarm scheme window.


When monitoring data is telemeter:

70

Chapter 2 Installation and Use

Figure 2.2-79 Add - Telemeter

Note:
1.

The currently added alarm scheme is under the selected supervision


center.

2.

Telemeter must be set up with upper and lower limits and the upper limit
must be greater than the lower limit. But it is unnecessary to set alarm
level. Telesignal, however, must be set up with alarm level, but upper &
lower limits are not necessary.

3.

When adding telemeter (the State Data Type is less than 1000.)
scheme, state data type, explanation value, alarm delay, alarm clear
delay, and Delta value must be set.

4.

Each monitoring data type can correspond with only one state type.
However, each state type can correspond with multiple state types.

5.

Alarm Delay, Alarm Clear Delay, and Delta can only be positive
number.

When monitoring data is telemeter:

71

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-80 Add - Telesignal

Note:
Double-click a data row or select it and click Modify to open a dialog box.
When Monitoring Type is tele-signal (above 1000), the dialog is as shown
in figure below:

72

Chapter 2 Installation and Use

Figure 2.2-81 Four Level Alarm Scheme Tele-signal

Click OK, the configured data is saved into database. When


Monitoring Type is telemeter (under 1000), alarm upper & lower
limits must be set, and the upper limit must be greater than alarm
lower limit.

73

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-82 Four Level Alarm Scheme Tele-meter

Click OK, the configured data is saved into database.


To delete, select one or more data rows, and click Delete, the
Warning dialog appears, as shown in Figure 2.2 -83 :

Figure 2.2-83 Warning

Click OK to delete the selected data, click Cancel to cancel.


2.2.5.2 Special Four Level Alarm Scheme
This is to set special alarm scheme to monitoring data in special situations.
Click Special Four Level Alarm Scheme tab, as shown in Figure 2.2 -84 :

74

Chapter 2 Installation and Use

Figure 2.2-84 Special Four Level Alarm Scheme

Select one data; click Edit to open the Detail of Special Four Level
Alarm Scheme window. When Monitoring Data Type is telesignal
(above 1000), the alarm severity level must be selected, as shown in
Figure 2.2 -85 :

Figure 2.2-85 Detail of Special Four Level Alarm Scheme

75

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

To delete, select one or more data rows, click Delete on the title bar,
the following Warning dialog will appears:

Figure 2.2-86 Warning

Click OK to delete the selected data, click Cancel to cancel.

2.2.6 Adding User and Setting Authority


This is to set the authority of user for login which node(s), region(s), and/or
what type(s) of device(s).
Note: User belongs to a user group and has the system function authority of
role.
2.2.6.1 Adding Department
This function is used to create a department for managing users.
Click User Management > User Authority Configuration Scheme >
Department > ** Supervision Network, click Add Department.

76

Chapter 2 Installation and Use

Figure 2.2-87 Add Department

2.2.6.2 Adding Role


This function is to create role and allocate system functions for the role.
Click User Management > User Authority Configuration Scheme > Role
> ** Supervision Network, click Add Role.

77

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-88 Add Role

Select the role that you added just now to assign appropriate authority
information to it, as below:

Figure 2.2-89 Configure Authority for Role

78

Chapter 2 Installation and Use

2.2.6.3 Adding User Group


This function is to add user group information.

Figure 2.2-90 Add User Group

2.2.6.4 Adding User


This is to add user information.
Click the user group to which you want to add user, click Add User
Information, input the user information according to actual situation and
assign a role for the user, click OK.

79

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-91

2.2.6.5 Adding Site and Device Monitoring Authority


This is to configure appropriate monitoring authority information over site(s)
and device(s) for user group.
Select the desired user group and configure special site authority, normal
site authority and device type authority for the group.

Figure 2.2-92 Configure Site and Device Authority

80

Chapter 2 Installation and Use

Special Site Authority: can be exactly the authority scheme of individual


site.
Normal Site Authority: Site authority scheme by site type and region.
Device Type Authority: Device monitority authority by device type.

2.2.7 Managing Basic Information


2.2.7.1 Adding/Modifying Site Type
This is to add/modify the type according to requirements of customer.
Click Basic Info Management > Site Type, click Add Site Type.

Figure 2.2-93 Add Site Type

Enter a site type and click OK.


2.2.7.2 Adding Site Level
This is to add/modify the level of site according to requirements of
customers.
Click Basic Info Management > Site Level, click Add Site Level.

81

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-94 Adding Site Level

Enter a site level name and click OK.


2.2.7.3 Modifying Alarm Color
This is to change the color of the four-level alarms displayed in the network
management system.
Click Basic Info Management > Alarm Severity, select the severity level to
be changed, double-click and change the color of it.

82

Chapter 2 Installation and Use

Figure 2.2-95 Change Color of Alarm Severity

2.2.8 Video Integration Configuration Scheme


In the video integration system, safeguard sub-system consists of safeguard
data center and safeguard client. Video Integration Configuration scheme of
iPowerConfig console is a tool for device configuration and data
synchronization in video integration. Therefore, the Video Integration
Configuration tool should have the following functions:
Adding, modifying, and deleting video related devices;
Updating video devices configuration of multimedia center unit I1000;
Correlating DI and devices
2.2.8.1 Preparation
Before running the Video Integration Configuration scheme, the following
preparation must be done:
1.

System templates of video devices, such as small platform system


template, encoder template, decoder template, camera template, etc.
have been applied successfully.

2.

The applied templates have been imported into database by using the
iPowerConfig. See Importing System Device Template for details.

83

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

3.

Field templates have been configured accordingly based on the


template management tool.

In the next sections, we mainly introduce the third step: how to make field
template for vide device and what should be paid attention.
2.2.8.1.1 Making Field Template for Small Platform Device
Small platform device is NMS device. Suppose system template of video
device has been applied successfully and has been imported into database.
Start the iPowerConfig console, click Utility Management > Template
Management Tool, select NMS > Small Platform Server in the Device
Template Tree, as shown in figure below:

Figure 2.2-96 Select Small Platform Server

Click Add Template open the Device Template dialog, as shown in figure
below:

84

Chapter 2 Installation and Use

Figure 2.2-97 Device Template

The left pane lists the system template(s) that you imported into database
using the iPowerConfig. Select one, and input a name for the field template,
and enter remarks, as shown in figure below:

Figure 2.2-98 Enter Field Template Name

Click OK, the field template of small platform device has been made.

85

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Note: the five-teles (telemeter, telesignal, teleadjust, telecontrol, and


teleconfig), especially teleconfig must be selected and must not be missed
when making small platform field template. Default is all selected, do not
deselect them).
2.2.8.1.2 Making Field Template for Encoder
Encoder device is video device. So click Video Device > Encoder in the
Device Template Tree, as shown in figure below:

Figure 2.2-99 Select Encoder

Click Add Template to open the dialog. Select the system template to be
used from the left pane, type in the name of the field template and input
remark. Select DI and DO in Telesignal and Teleadjust. Click OK, the
encoder field template has been made.
2.2.8.1.3 Making Field Template for Decoder
The steps for making decoder field template is the similar to encoder.
Note: all configuration variables must be selected when making decoder field
template.
2.2.8.1.4 Making Field Template for Camera
The steps for making camera field template are the similar to encoder.

86

Chapter 2 Installation and Use

Note: all configuration variables must be selected when making camera field
template.
2.2.8.2 Video Device Management Module
2.2.8.2.1 Configuring Small Platform Device
A small platform server must be configured first before using video
integration system. In NMS system, small platform server device is NMS
equipment. So configuring small platform server is the same as configuring
other NMS equipments, such as, iPowerClient, safeguard console, etc., Start
the iPowerConfig and click Supervision Center > Network Management
Equipment > Add Network Management Equipment to open the Add
NMS Device dialog, as shown in figure below:

Figure 2.2-100 Add NMS Device

Enter proper information and click OK, a small platform server has been
added.
To modify small platform record, select the small platform record in
supervision center and click Modify to open the dialog and change it.
To delete small platform record, select the small platform record in
supervision center and click Delete to delete it.

87

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Then we need to configure correct IP address, port number, user name, and
password for the small platform. If not configure these, error may occur
when synchronizing data into video server.
First of all, select the small platform that we just added from the supervision
center node, and click Teleconfig from the right part of the window, as
shown in figure below:

Figure 2.2-101 Teleconfig

We can see that there are 4 rows in the Teleconfig list; they are IP address,
port, user Name and password. Given that these information of the small
platform server are 10.72.13.30, 8000, admin, and 888888 respectively,
Now we need to change these items to the correct ones. First, double-click
the IP Address row to open the Modify Teleconfig dialog and input correct
address, as shown in figure below:

88

Chapter 2 Installation and Use

Figure 2.2-102 Modify Teleconfig

Click OK to confirm. Then we need to repeat the above steps to change the
port, user name and password.
Click Utility Management> Video Integration Configuration Tool to check
the small platform devices under the current supervision center, as shown in
figure below:

Figure 2.2-103 Check the Configured Small Platform Device

We can see that the small platform device we added just now is displayed in
the Device List.

89

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

2.2.8.2.2 Configuring Encoder


After small platform server is configured, we need to configure video
devices.
First of all, we need to configure an encoder device. Click Platform tab at
the bottom left corner of the window, click a small platform node, click
Encoder tab on the right, and click Add Encoder to open the Select Site
dialog, as shown in figure below. This dialog will not appear if add encoder
or decoder in Site Type or Region tab.

Figure 2.2-104 Select Site

Select a site and click OK to open the Add Encoder dialog, as shown in
figure below:

90

Chapter 2 Installation and Use

Figure 2.2-105 Add Encoder

Input relevant information and click OK to confirm.


To modify encoder record, select the encoder record to be changed and click
Modify to open the dialog and change it.
To delete encoder record, select the encoder record that you want to delete
and click Delete to delete it.
2.2.8.2.3 Configuring Camera
After encoder is configured, if camera is required to be configured under the
encoder, select the encoder device under which that you want to configure
camera, click Add Camera to open the Add Camera dialog and enter
appropriate values, as shown in figure below:

91

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-106 Add Camera

Note: Access Channel cannot be repeated under a same encoder. For


example, if a camera is configured with Access Channel 1, then other
cameras cannot be configured as 1 any more.
Click OK to confirm:
To modify camera record, select the camera record to be changed and click
Modify to open the dialog and change it.
To delete camera record, select the camera record that you want to delete
and click Delete to delete it.
2.2.8.2.4 Configuring Decoder
After small platform server is configured, if decoder device is required to be
configured, select the small platform device node under which that you want
configure decoder, click Decoder tab on the right, click Add Decoder to
open the Select Site dialog, as shown in figure below:

92

Chapter 2 Installation and Use

Figure 2.2-107 Select Site

Click OK to open the Add Decoder dialog, as shown in figure below:

Figure 2.2-108 Add Decoder

Click OK, the decoder just added can be seen in the right list, as shown in
figure below:

93

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

To modify decoder record, select the decoder record to be changed and click
Modify to open the dialog and change it.
To delete decoder record, select the decoder record that you want to delete
and click Delete to delete it.
2.2.8.3 Correlating DI and Camera
This function is to correlate DI and cameras within the same site. One DI can
be correlated with more than one camera. Select the DI under a device, for
example, DI under an encoder, as shown in figure below:

Figure 2.2-109 Select DI

Double-click the record to open the Modify Telesignal dialog, as shown in


figure below:

94

Chapter 2 Installation and Use

Figure 2.2-110 Modify Telesignal

Click Alarm Linkage tab, as shown in figure below:

Figure 2.2-111 Alarm Linkage

95

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Double-click the camera to be linked, the Default Position column of this


camera can be edited, input a legal number (positive integer from 0 to 255),
as shown in figure below:

Figure 2.2-112 Set Default Position

Move the mouse cursor away and click OK, the value of the camera which is
to be linked to the DI is set. Open it again; it is displayed as shown in figure
below:

Figure 2.2-113 DI Linked

If the check box is checked, it means the corresponding DI is linked with the
camera.

96

Chapter 2 Installation and Use

To change the value of camera linked to DI, double-click it and change the
value, then click OK to confirm. To delete the value, deselect the check box
before DI, and click OK to confirm.
2.2.8.4 Video Device Synchronization Module
Video device synchronization module is mainly used to synchronize the
video devices configured in NMS into video small platform server. There are
two main synchronization methods. One method is to synchronize by
platform, that is, synchronize devices of platform into video database by
whole. The other method is to synchronize based on difference. This method
is similar to differential synchronization function in Level-2/3 synchronization
tool in NMS.
Note: when using the video device synchronization module, the IP address,
port number, user name and password of small platform must be ensured
correct. Otherwise, error may occur. Refer to Configuring Small Platform
Device for configuring small platform.
2.2.8.4.1 Platform Synchronization
This is to synchronize devices at NMS into video database by whole. To do
this, delete devices at video side first, then synchronize all the devices at
NMS to the video side.
Select a small platform device, right-click
Synchronization, as shown in figure below:

97

and

select

Platform

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-114 Platform Synchronization

The process bar appears, as shown in figure below:

Figure 2.2-115 Process of Synchronization

If synchronization failed, relevant error message will appear.


2.2.8.4.2 Synchronization Based on Difference
This is to synchronize the changes on devices at the NMS side into video
server. The main window is as shown in figure below:

98

Chapter 2 Installation and Use

Figure 2.2-116 Synchronization based on Difference

Select the small platform to be synchronized, click OK, the lower part of the
window lists the different data records; select the record(s) to be
synchronized from the list, as shown in figure below. It is recommended to
test the connection of the small platform by selecting the platform from the
video device management module and clicking Test.

99

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-117 Select Items to be Synchronized

Click Synchronization, the system starts synchronizing the selected data,


as shown in figure below:

100

Chapter 2 Installation and Use

Figure 2.2-118 Synchronization is Process

There is a progress bar at the bottom of the window. Operation Status


column tells you whether the data is synchronized successfully. If yes, it
displays in green. If no, it displays in red.
2.2.8.5 Other Functions
2.2.8.5.1 Copying Video Device ID
This function is to convert device ID of NMS device into that of video device
and save in memory. As shown in figure below, select video device, rightclick and select Copy Video Device ID. This function only works with video
device, encoder, decoder, and camera.

101

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-119 Copy Video Device ID

Click Quick Start at the right part of the window, select Notepad, right-click
and select Paste to paste the video device ID, as shown in figure below:

Figure 2.2-120 Video Device ID Copied

2.2.8.5.2 Copying Site ID


This function is similar to Copying Video Device ID. The only difference is
that this is to copy the site ID of video device.

102

Chapter 2 Installation and Use

2.2.8.5.3 Topological Graph


This is to display the topological structure of video devices in graph. At
present, only encoders are displayed in the graph.
Select an encoder in the Device List, right-click and select Topological
Graph, as shown in figure below:

represents encoder device, and

represents decoder device.

Figure 2.2-121 Select Topological Graph

The following window which shows the topological graph of video devices
appears:

103

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-122 Topological Graph of Video Devices

Click the down arrow at the upper right corner of the window to adjust
the size of the graph.
2.2.8.5.4 Testing Small Platform Connection
This is mainly to test the connection of small platform. It is available only
when small platform node is selected.
Configure correct user name, password, port, and IP address for the small
platform device, click the small platform node, right-click and select Test
Platform Connection, as shown in figure below:

104

Chapter 2 Installation and Use

Figure 2.2-123 Test Platform Connection

If connection is made successfully, the following Prompt box appears:

Figure 2.2-124 Successful Connection

If small platform device configuration (IP address, port, user name and
password) is not correct or the small platform server itself is not connected,
the following Prompt box will appear:

105

ZTE E_guard USMS V1.67 Training Manual - iPowerConfig

Figure 2.2-125 Connection Failure

It means that the current small platform server is disconnected.

106

Appendix A Abbreviations
Abbreviations

Full Name

CMU

Control Monitor Unit

CSC

Centralized Supervision Center

EMU

Environment Monitor Unit

MISU

Multiple Integrative Supervision Unit

ODBC

Open Database Connectivity

PC

Personal Computer

SC

Supervision Center

SM

Supervision Module

SU

Supervision Unit

TCP

Transfer Control Protocol

107