Dear Sir/Madam,
I'm pleased to introduce you to our complete line of polymer insulated products. The attached
K-LINE INSULATORS catalogue includes the products we are currently offering to the utility
industry.
Other products are under development and will be available shortly. As these products come on
the market, we will issue you the pertinent information. In the meantime, if you require an
insulator configuration not shown in the catalogue, give us a call.
In order to register this catalogue to you, so that we can provide you with updates, please
complete the attached request card and return it to us. If you are passing this catalogue onto one
of your staff, please have them complete the card and return it. If you require an additional
catalogue for someone else in your organization, please have them complete the attached form
(noting "ADDITIONAL CATALOGUE REQUIRED" on the card) and return it to U.S.
We look forward to fulfilling your polymer insulator needs. Should you have any questions or
need further information, feet free to call me at (416) 292-2008.
Sincerely,
K-LINE INSULATORS manufactures all of its products and is registered to the rigid
Quality Assurance Standards of the ISO9001 program. The company is audited on a
continuous basis by its customers and an internationally recognized quality management
auditing firm.
K-LINE INSULATORS is known for its readiness to listen to its customers' needs for
customized polymeric insulator designs that meet their special requirements. We offer
appropriate support in the proper selection of insulators to suit the application, with
training and documentation on special installation requirements. K-LINE INSULATORS
is committed to a continuous improvement policy in quality, service, delivery, and cost
reduction. Much pride comes from the innovation of new products and the continuous
improvements of present products to ensure that the insulators are the most cost effective
and have a long term system performance.
K-LINE INSULATORS approach to innovative insulator solutions is well demonstrated
and respected by its customers.
K-LINE INSULATORS people are totally dedicated to continuous quality and
performance improvement. They are dedicated to developing the best materials and
designs that lead to optimum product solutions. These characteristics amongst others,
have contributed to the success of the various strategic alliances K-LINE INSULATORS
has forged with some of its customers.
K-LINE INSULATORS is sensitive and committed to the needs of its customers and is
always prepared to give them the service they expect and deserve.
Suspension/
Deadend
KL
Company
ID
Voltage Class
Material
Insulator
Type
X
End Fittings *
K-Line
15
28
35
46
69
Shed Design
A - Alternating
sheds
No A Other shed
design
Structure End
Fitting
C- Clevis
S Socket
T - Tongue
S - Silicone
rubber
Line End
Fitting
T - Tongue
H - Thimble
B Ball
E Oval eye
Y Y clevis
N/A
Line Post
N/A
N/A
K - K-clamp
V - Vertical
H - Horizontal
T - Tie-Top C
Neck
TF - Tie-Top F
Neck
E Drop Eye
Special
Variations
R - 90 deg turn on
end fittings
M - Medium SML
70 kN
A - LA insulator
F Steel Fittings
N - Non-standard
A Lock washer
Al Alum base
D - Tinned alum
line fitting
E Eye Nut
G - Gain base
M20 - 20 mm
tapped
M22 - 22 mm
tapped
M24 - 24 mm
tapped
N - Non-standard
Station Post
CP - Cap &
Pin
P - Post
Railway
N/A
RW Railway
C- Clevis
S Socket
T Tongue
B Ball
Riser
A - Alternating
sheds
No A Other shed
design
Guy
Insulated
length in
inches
N/A
RSI Riser
support
insulator
N/A
Note:
* Different fittings will be designated by the addition of a number to the letter.
Sebastian Marra
K-Line Insulators Limited
February 19, 2002
N/A
N/A
C- Clevis
H - Thimble
T Tongue
R Roller
B - Threaded
M12 - 12 mm
tapped
M16 - 16 mm
tapped
M20 - 20 mm
tapped
C- Clevis
S Socket
T Tongue
B Ball
U - Clamp
D - Tin plated
aluminum line
fitting
X 5/8 tapped
base
T - Tongue
H - Thimble
C- Clevis
R Roller
B - Threaded
R - 90 deg turn on
end fittings
S - Silicone
KL
Compan
y ID
X
Voltage
Class
Suspensi
on/Deade
nd
X
Shed
Design
H High
leakage
Insulator
Material
Type
N/A
N/A
Line Post
K-Line
69
115
138
161
230
Station
Post
SSilicone
rubber
End Fittings
Line End
Fitting
Structure
End Fitting
S Socket
B - Ball
C- Clevis
T - Tongue
T - Tongue
H - Thimble
Y Y Clevis
E - Eye
E - Eye
E - Eye
V - Vertical
HHorizontal
AAlterna
ting
sheds
G Gain
base
BF Flat
No. of
Sheds
Corona
Ring
Other
Additions
M
Medium
ring
N No ring
Al
Aluminum
base
#
N/A
P - Post
A - IEC
B IEC20
R 90 Deg
S SS pin
M12 - 12 mm
tapped
M16 - 16 mm
tapped
M20 - 20 mm
tapped
N - Nonstandard
Catalogue D-DS
Performance Benefits
The performance benefits of K-Line Insulators distribution suspension/dead-end insulators are listed below.
Improves Reliability (by minimizes interruptions and outages due to vandalism, pole fires, and flashovers in
all types of environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Distribution suspension/dead-end insulators are used on overhead lines operating at or below 46 kV. These
insulators are used to support line conductors in suspension or dead-end modes such as line terminations, angles,
and tangents. These insulators can be used with bare or covered conductors.
Core Material
The core rod of the distribution suspension/dead-end insulator is made of a high quality fiberglass that has been
specially formulated for electrical and mechanical applications.
TECHNICAL DATA
SPECIFICATIONS
UNIT
Voltage Class
CEA & ANSI Class
Section Length L
Dry Arcing Distance
Leakage Distance
kV
mm (in)
mm (in)
mm (in)
kV
kV
kV
kV
V
kN (lb)
Nm (ftlb)
kg (lb)
Dry
Wet
Impulse Critical Flashover (Positive)
Test
Radio Influence Voltage
(RIV) at 1 MHz
Max.
Specified Mechanical Load (SML)
Torsional Load
Approx. Weight
Low-Frequency Flashover
KL15ASCTM
15
DS15
322 (12.7)
193 (7.6)
384 (15.1)
100
70
145
15
Below 1
70 (15,700)
83 (62)
0.7 (1.5)
CATALOGUE NUMBER*
KL28ASCTM
KL46SCTN
KL46SCT
28
35/46
46
DS28
DS46
433 (17.0)
548 (21.6)
574 (22.6)
290 (11.4)
386 (15.2)
419 (16.5)
590 (23.2)
850 (33.5)
988 (38.9)
135
155
180
105
135
150
225
285
300
20
30
30
Below 1
Below 5
Below 5
70 (15,700)
90 (20,200) 90 (20,200)
83 (62)
83 (62)
83 (62)
0.8 (1.8)
1.3 (2.8)
1.6 (3.5)
KL46SCTA
46
646 (25.4)
490 (19.3)
1059 (41.7)
200
155
355
30
Below 5
90 (20,200)
83 (62)
2.2 (4.8)
* The catalogue numbers in the above table are for CT clevis-tongue fittings. For other combinations of end
fittings, see End Fittings Section.
End Fittings
There are three standard end fittings that are available on the suspension/dead-end insulators: clevis, tongue,
and thimble eye (See Below). All end fittings are made from high strength, corrosion resistant extruded
aluminum. The end fittings are crimped on to the core rod to provide the mechanical performance. A
watertight seal between the rubber and end fittings eliminate possible moisture ingress. This special silicone
rubber to metal fittings sealing process provides total exclusion of moisture.
The end fittings of the distribution class suspension/dead-end are rated for a specified mechanical strength,
SML of 70 kN (15,700 lb) or 90 kN (20,200 lb).
The clevis and tongue end fittings are the two most common fittings used with additional adaptors and
clamps. The thimble eye end fitting is a unique design that integrates the insulator tongue end fitting and a
conductor performed grip adapter to attach to the line conductor. This thimble eye essentially eliminates one
item in the assembly and from inventory.
For other special end fittings please contact K-Line Insulators.
Clevis - C
Tongue - T
Thimble Eye - H
Catalogue D-LP
15 kV to 69 kV
Performance Benefits
The performance benefits of K-Line Insulators distribution line post insulators are listed below.
Improves Reliability (by minimizing interruptions and outages due to vandalism, pole fires, and
flashovers in all types of environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing
plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Distribution line post insulators are used on overhead distribution lines operating at and below 69 kV. These
insulators are commonly installed on metal or wooden structures to horizontally or vertically support the line
conductor. Also, these insulators are used to support high voltage conductor jumpers or leads.
.
Rod
The core rod of the insulator is made of a high quality fiberglass that has been specially formulated for electrical
and mechanical applications.
K-clamp**
H-Horizontal
V-Vertical
T-TieTop (C-neck)
TF-TieTop (F-neck)
TECHNICAL DATA
SPECIFICATION
UNIT
Voltage Class
CEA Class
Section Length (L)***
Dry Arcing Distance
Leakage Distance
Critical Impulse Flashover
Low-Frequency Flashover
Radio Influence Voltage
(RIV) at 1000 kHz
kV
mm (in)
mm (in)
mm (in)
Positive
Negative
Dry
Wet
Test
Max
kV
kV
kV
V
kN (lb)
kN (lb)
kN (lb)
No.
kg (lb)
KL15S
15
LP15
287 (11.3)
145 (5.7)
275 (10.8)
130
155
75
40
10
2.5
22 (5000)
12.5 (2800)
6 (1350)
2
3.4 (7.4)
CATALOGUE NUMBER*
KL28S
KL35S
KL46S
28
339 (13.3)
190 (7.5)
420 (16.5)
160
205
95
65
15
2.5
22 (5000)
12.5 (2800)
6 (1350)
3
3.7 (8.0)
35
LP28M
415 (16.3)
270 (10.6)
660 (26.0)
195
285
120
85
22
2.5
22 (5000)
12.5 (2800)
6 (1350)
5
4.3 (9.4)
46
LP46
491 (19.3)
345 (13.6)
864 (34.0)
240
350
145
115
30
2.5
22 (5000)
12.5 (2800)
6 (1350)
6
4.7 (10.3)
KL69S
69
LP46M
614 (24.2)
483 (19.0)
1117 (44.0)
310
200
160
30
2.5
22 (5000)
12.5 (2800)
6 (1350)
10
9.1 (20.0)
Ordering Information
To catalogue number, add suffix H for horizontal, V for vertical, T for C-neck Tie-top, TF for the F-neck Tie-top, or K for
K-clamp. Standard base threads are -10 UNC. Different base threads are available upon request.
Fittings
Line End Fitting
The line end fitting of line post insulators are available in four different configurations: horizontal or vertical
clamp-top, tie-top, or K-clamp.
All line end fittings on line post insulators are made of corrosion resistant aluminum alloy castings.
SECTION LENGTH ADJUSTMENT
Line End Fitting
Section Length
Tie-Top
Horizontal
Vertical
K-Clamp
T
H
V
K
Clamp-Top
The conventional horizontal and vertical trunnion accommodates a standard line post insulator, bolted conductor
clamp. On the horizontal design the line end fitting has an additional eye for the attachment of other devices
during installation or maintenance activities.
Tie-Top
The tie-top is designed for tying a conductor to the neck of the insulator. It is available in two standard neck
sizes: C or F-neck.
K-Clamp
K-Line Insulators Limited has introduced a new concept in the polymer line post live end fitting design. This end
fitting is referred to as the K clamp. The uniqueness of this end fitting is a result of the many advantages its
has over the traditional horizontal, vertical and tie-top configurations.
Some advantages of the K clamp include:
1) Excellent corrosion resistant aluminum casting
2) A long, smooth contoured conductor clamping zone
3) The clamp accommodates a full range of conductor sizes
4) A single captive live-line operable bolt
5) All parts are captive
6) Lower overall length permits standard cover up hoods to effectively cover all insulator sheds
7) The design can be installed in either a horizontal or vertical configuration
8) Inventory reduction is accomplished because one insulator is used for both configurations and a
separate clamp is not required
9) The price of the new insulator is cost comparative with the purchase of a standard trunnion post
insulator and a separate clamp
10) Substantial labour cost savings in stringing, sagging and conductor clamping
11) Other savings related to shipping, stocking and maintenance
Catalogue D-SP
Performance Benefits
The performance benefits of K-Line Insulators distribution station post insulators are listed below.
Improved Reliability (interruptions and outages due to vandalism, and flashovers in all types of
environments are a thing of the past)
Eliminate or Reduce Maintenance (such as washing and trouble calls) and is compatible with existing
porcelain insulators
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation, eliminates catastrophic mechanical failures)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Distribution station post insulators are used in open-type stations operating at and below 46 kV. These insulators
support the bus, leads, or other apparatus within the station.
Rod
The core rod of the distribution station post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.
TECHNICAL DATA
SPECIFICATION
UNIT
KL15SCP
KL25SC
CATALOGUE NUMBER*
KL25SP
KL25SPN
KL35SP
KL46SP
Voltage Class
kV
15
25
28
28
35
46
No.
4 & 205
208
10
210
214
mm (in)
254 (10)
305 (12)
355 (14)
415 (15)
491 (18)
614 (22)
mm (in)
145 (5.7)
190 (7.5)
260 (10.2)
270 (10.6)
345 (13.6)
483 (19.0)
Leakage Distance
mm (in)
275 (10.8)
420 (16.5)
635 (25)
660 (26.0)
864 (34.0)
1117 (44)
Impulse Withstand
kV
125
155
165
180
225
275
kV
130
160
175
195
240
310
kV
40
95
65
120
145
200
Test
kV
10
15
22
22
30
30
Max
2.5
45
(10000)
12.5
(2800)
6 (1350)
2.5
45
(10000)
12.5
(2800)
6 (1350)
2.5
45
(10000)
12.5
(2800)
6 (1350)
2.5
45
(10000)
12.5
(2800)
6 (1350)
2.5
45
(10000)
12.5
(2800)
6 (1350)
kN (lb)
kN (lb)
kN (lb)
2.5
45
(10000)
12.5
(2800)
6 (1350)
No.
10
kg (lb)
3.4 (7.4)
3.7 (8.0)
4.2 (9.2)
4.3 (9.4)
4.7 (10.3)
9.1 (20.0)
Number of Sheds
Approx. Weight
* Ordering Information:
1.
2.
Above catalogue numbers apply to insulators with through holes on both ends.
Add T1 to catalogue numbers for insulators with one end tapped & the other with through holes.
End Bases
The standard base fittings are flat round iron bases that are available with bolt circle mounting holes with
either through or tapped holes. These bases are compatible with the porcelain station post insulator
standard.
The end bases are radialy swaged on to the core rod to provide the mechanical performance and reduce
the stress concentration. Our proprietary design insures a watertight seal between the rubber and end
fitting. This special silicone rubber to metal fittings sealing process prevents moisture ingress to the core
fiberglass rod. For other special base requirements, please contact K-Line Insulators Limited.
Corrosion protection of the end bases is provided by hot-dip galvanizing to CSA G164 and ASTM A153
specifications.
Catalogue T-DS
Performance Benefits
The performance benefits of K-Line Insulators transmission suspension/deadend insulators are listed below.
Improved Reliability (interruptions and outages due to vandalism, pole fires, and flashovers in all types of
environments are a thing of the past)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Transmission suspension/deadend insulators are used on transmission lines operating at and above 66kV. These
insulators are installed on metal or wooden structures on cross arms to hold the conductor longitudinally (dead-end) or
vertically (suspension). The connections to the structures or arms and line vary depending on the Utilities preference.
Rod
The core rod of the transmission suspension/deadend insulator is made of a high quality fiberglass that has been
specially formulated for electrical and mechanical applications.
TECHNICAL DATA
TECHNICAL DATA
Catalogue
Number
Voltage
Class
kV
KL69HBS13
KL69HBS16
69
KL69HBS19
KL115HBS22
Section
Length (Note 1)
L
mm
(in)
Dry Arcing
Distance
mm
(in)
Leakage
Distance
mm
(in)
Positive
Critical
Impulse
Flashover
Low
Frequency
Flashover
Weight
(Note 2)
kV
Dry
kV
Wet
kV
kg
(lb)
660 (26.0)
523 (20.6)
1466 (57.7)
355
215
170
2.9 (6.3)
764 (30.1)
627 (24.7)
1798 (70.8)
425
260
205
3.3 (7.2)
867 (34.1)
732 (28.8)
2131 (83.9)
485
300
235
3.6 (8.0)
970 (38.2)
818 (32.2)
2461 (96.9)
540
335
265
4.2 (9.2)
1074 (42.3)
917 (36.1)
2794 (110.0)
600
375
300
4.5 (10.0)
1179 (46.4)
1021 (40.2)
3127 (123.1)
660
415
335
5.0 (10.9)
1281 (50.4)
1128 (44.4)
3460 (136.2)
725
455
370
5.4 (11.8)
1384 (54.5)
1229 (48.4)
3792 (149.3)
785
495
400
5.8 (12.7)
KL138HBS37
1488 (58.6)
1331 (52.4)
4125 (162.4)
845
530
430
6.1 (13.1)
KL161HBS40
1590 (62.6)
1410 (55.5)
4458 (175.5)
895
560
460
7.5 (16.4)
1694 (66.7)
1514 (59.6)
4790 (188.6)
960
605
495
7.9 (17.3)
KL161HBS46
1798 (70.8)
1618 (63.7)
5123 (201.7)
1025
650
530
8.3 (18.2)
KL230HBS49
1903 (74.9)
1722 (67.8)
5456 (214.8)
1090
695
570
8.6 (19.0)
2004 (78.9)
1824 (71.8)
5789 (227.9)
1155
740
605
9.0 (19.9)
2108 (83.0)
1928 (75.9)
6121 (241.0)
1220
785
640
9.5
KL115HBS25
115
KL115HBS28
KL138HBS31
KL138HBS34
KL161HBS43
KL230HBS52
KL230HBS55
138
161
230
(20.8)
Notes:
1.
Section lengths are based on ball and socket hardware. For lengths of insulators with alternate end fittings combination see Section Lengths.
2.
Weight includes standard rings where applicable. See section on Corona Rings.
End Fittings
The end fittings on the transmission insulator are made of high strength, cast (forged) steel. The insulators have a
specified mechanical load (SML) rating of 120 kN (27,000 lbs.). Also, all insulators are proof tested to 60 kN
(13,500 lbs.) in tension.
The end fittings are radialy swaged on to the core rod to provide the mechanical performance and reduce the
stress concentration. Our proprietary design insures a watertight seal between the rubber and end fitting. This
special silicone rubber to metal fittings sealing process prevents moisture ingress to the core fiberglass rod.
Hot-dip galvanizing to CSA G164 and ASTM A153 Standard provides corrosion protection of the end fittings.
The cotter key is made from stainless steel.
The standard end fittings that are available are listed and detailed in the below. For other special end fittings
contact K-Line Insulator Limited.
Section Lengths
The section lengths (L) published on the Technical Data sheet are for the ball and socket end fittings. For alternate
combinations of end fittings, use the following table to establish section lengths.
Section Length Adjustment
End Fitting
ANSI Ball / Socket
ANSI Ball / Y-clevis
ANSI Ball / oval Eye
oval Eye / oval Eye
Clevis / Tongue
End Fitting
Designation
BS
BY
BE
EE
CT
Section Length
L (see Technical Data sheet)
L + 36 mm (1.4)
L + 41 mm (1.6)
L + 84 mm (3.3)
L + 21 mm (0.8)
CATALOGUE T-LP
Performance Benefits
The performance benefits of K-Line Insulators transmission line post insulators are listed below.
Improved Reliability (interruptions and outages due to vandalism, pole fires, and flashovers in all types of
environments are a thing of the past)
Eliminate or Reduce Maintenance (such as washing and less trouble calls) and is compatible with existing
plant
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Transmission line post insulators are used on overhead transmission lines operating at and above 66 kV. These
insulators are commonly installed either vertically or horizontally on metal or wooden structures to support the
conductor. Also, these insulators are used to support high voltage conductor jumpers or leads.
Rod
The core rod of the transmission line post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.
TECHNICAL DATA
Catalog
Number
Voltage
Class
KV
KL69ASH13
KL69ASH16
KL115ASH25
KL138ASH28
KL138ASH31
KL161ASH34
KL161ASH37
L
mm
(in)
Dry
Arcing
Distance
Leakage
Distance
mm
mm
KL69ASH19
KL115ASH22
Section
Length
(See Note)
115
138
161
(in)
(in)
(24.3)
1544 (60.8)
Positive
Critical
Impulse
Flashover
Low
Frequency
Flashover
kV
Dry
kV
Wet
kV
380
250
225
Ultimate
Cantilever
Load
kN
(lbs)
29.4 (6600)
(29.2)
1890 (74.4)
450
295
260
26.1 (5870)
520
340
295
22.9 (5140)
595
385
330
19.6 (4410)
665
430
365
16.5 (3700)
735
475
410
14.9 (3340)
805
520
450
13.3 (2980)
880
560
475
11.7 (2630)
955
600
495
10.1 (2275)
Note: Section length based on a horizontal trunnion and without any support base. For alternate bases and
line fittings (as well as overall lengths and weights of these) refer to the section on fittings and weights.
Gain Base
CATALOGUE T-SP
Performance Benefits
The performance benefits of K-Line Insulators transmission station post insulators are listed below.
Improved Reliability (interruptions and outages due to vandalism, and flashovers in all types of
environments are a thing of the past)
Eliminate or Reduce Maintenance (such as washing and trouble calls) and is compatible with existing
porcelain insulators
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation, eliminates catastrophic mechanical failures)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
Transmission station post insulators are used in open-type stations operating at and above 66 kV. These insulators
support the bus, leads, or other apparatus within the station.
Rod
The core rod of the transmission station post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.
TECHNICAL DATA
Catalogue
Voltage
Number
(See Notes 1, Class
2, & 3)
kV
KL69ASP13
KL69ASP16
KL115ASP22
KL115ASP25
KL138ASP28
KL138ASP31
KL161ASP34
KL161ASP37
69
115
138
161
Section
Length
L
mm
(in)
Dry
Arcing
Distance
Leakage
Distance
mm
mm
(in)
(in)
Positive
Impulse
Withstand
kV
Low
Frequency
Flashover
Dry
kV
Wet
kV
Ultimate
Cantilever
Strength
kN
(lbs)
Equivalent
Height to
ANSI
Technical
Reference
Number
762 (30.0)
605 (23.8)
1534 (60.4)
355
245
195
29.9 (6725)
TR216/278
895 (35.2)
742 (29.2)
1890 (74.4)
430
295
240
26.2 (5885)
2583 (101.7)
565
385
320
19.7 (4440)
TR286/287
635
430
360
16.5 (3705)
690
470
400
15.1 (3405)
TR288/289
765
520
450
13.3 (2995)
830
555
480
11.7 (2640)
900
595
510
10.2 (2290)
Ordering Information:
1.
2.
3.
Above catalogue numbers apply to insulators with through holes on both ends.
Add T1 to catalogue numbers for insulators with one end tapped & the other with through holes.
Add T2 to catalogue number for insulators with both ends tapped.
End Bases
The standard base fittings are flat round iron bases that are available with bolt circle mounting holes with
either through or tapped holes. These bases are compatible with the porcelain station post insulator
standard.
The end bases are radialy swaged on to the core rod to provide the mechanical performance and reduce
the stress concentration. Our proprietary design insures a watertight seal between the rubber and end
fitting. This special silicone rubber to metal fittings sealing process prevents moisture ingress to the core
fiberglass rod. For other special base requirements, please contact K-Line Insulators Limited.
Corrosion protection of the end bases is provided by hot-dip galvanizing to CSA G164 and ASTM A153
specifications.
Catalogue GI
Guy Strain
Polymer Insulators
Guy Strain
Polymer Insulators
Safety codes mandate the elect rical strength of guy insulators to have a dry fl as hover voltage at least twice the
voltage to ground of the highest voltage supply circuit with which the guy could come in contact, and a wet
flashover equal to the highest voltage between any two conductors. When using porcelain, two or more
insulators are usually needed to comply with these requirements.
Fibreglass guy strain insulators so located that there is a possibility of contact with the supply conductors are
prone to electrical tracking and failure. Paint coatings are easily removed in handling, and by weathering, and do
not adequately protect the rod. In chemical environments, crystalline fracture of the unprotected rod can occur.
K-Line guy strain insulators are protected from the environment including the effects of voltage, ultra-violet rays
and acid rain by a fully bonded, electrically track-free, and impenetrable EPDM or Silicone rubber sheath. The
electrical and mechanical requirements of the safety codes are easily met by K-Line Insulators. The insulators are
manufactured under a registered Canadian Standards Association Z299.3-1985 quality assurance program. Each
assembled insulator is proof tested, and permanently marked to show the date of test.
TECHNICAL DATA
SPECIFICATION
INSULATED LENGTH A
CATALOG NUMBER
UNIT
KL-11
KL-24
KL-36
KL-54
KL-78
in (mm)
11 (280)
115
60
24 (610)
235
146
36 (915)
335
235
54 (1370)
485
370
78 (1980)
680
550
22,000(100)
11,700(52)
22,OOO(100)
11.700(52)
22.000(100)
11,700(52)
22,OOO(100)
11,700(52)
42(56)
1.5(.7)
15
42(56)
2 (.9)
15
42(56)
3.3(1.5)
15
42(56)
4.4 (2)
15
DRY
60 Hz FLASHOVER
kV
WET
DESIGN TENSION STRENGTH
Ib (kN
22OOO (100)
Ib (kN)
11,700(52)
TENSION PROOF TEST LOAD
DESIGN TORQUE RATING
ft-lb. (N m)
42(56)
NET WEIGHT
Ib (kg)
1.3(.6)
STANDARD PACKAGE
24
ORDERING INFORMATION:
To catalog number, add suffix CT for clevis-tongue, CC for clevis-clevis, RR
for roller-roller,
or HH for thimble eye-thimble eye
Catalogue EI
Extension Insulators
Extension Insulators
K-Line dead-end extension insulators are manufactured by coupling either silicone or EPDM sleeved rod to polymer dead-end insulators.
Extension insulators are made using the same manufacturing methods and quality assurance program as the dead-end and guy strain
insulators. Each dead-end extension insulator is mechanically proof tested to 10,000 lbs.
For installations in normal operating environments, K-Line EPDM insulators are recommended. For extremely contaminated, salt laden or
chemical environments, K-Line SILICONE insulators are the ultimate solution.
The Technical Data table (See Next Section) shows the standard lengths available. Custom lengths are available on request.
Extension Insulators
TECHNICAL DATA
CATALOG
NUMBER
KL15S - 11
KL15S -24
KL15S x36
KL23 x 11
KL23 - 24
KL28E x 11
KL28E -24
KL28E x 36
KL28S 11
KL28S 24
KL28S x 36
KL35 - 11
KL35 -24
KL35 Sir 36
KL46 x 11
KL46 x 24
KL46 of 36
KL46S x 11
KL46S x 24
KL46S x 36
KL46SN x 11
KL46SN x 24
KL46SN x 36
INSULATOR
MATERIAL
Silicone
EPDM
EPDM
Silicone
EPDM
EPDM
Silicone
Silicone
DIMENSIONS
(inches)
'A' 'B'
VOLTAGE CRITICAL
RATING IMPULSE
FLASHOVER
VOLTAGE-
29.5
42.5
545
30.5
43.5
55.5
110
240
360
11.0
24.0
360
340
470
590
0
34
47.1
59.0
35.0
48.0
60.0
39.5
52.5
64.5
39.5
52.5
64.5
38.5
51.5
63.1
11.0
24.0
36.0
STANDARD
PACKAGE
SIZE
15
145
9 UNITS
23
160
5 UNITS
28
215
9 UNITS
28
215
9 UNITS
35
235
5 UNITS
46
300
5 UNITS
46
300
9 UNITS
35
285
9 UNITS
0
11
0
360
110
24.0
360
11.0
24.0
36.0
11.0
24.0
36.0
11.0
24.0
36.0
ORDERING INFORMATION:
Add Suffix S to catalogue number for silicone rod
Note: The critical Impulse flashover voltage values Shown are based on the insulator
Section to"
WEIGHT
(lbs.)
2.6
3.1
3.5
3.5
4.0
44
3.0
3.5
3.9
3.1
3.6
4.1
49
5.4
5.8
5.8
6.3
6.6
3.8
4.3
46
3.4
4.3
Interphase Spacers
Overview
With the environmental exposure to ice and/or wind Overhead Transmission and Distribution
Lines that are bare open-wire design are quite susceptible to conductor motion that may result in
outages or interruptions on the electrical system due to conductor contact, flashovers, or any
plant damage. Interphase spacers were developed to minimize the probability of these
occurrences by insuring that conductors remain apart during their movement.
Interphase Spacer
K Line interphase spacers consist of silicone rubber insulation over a fiberglass rod. They are
very light and flexible. They are connected on the conductor with clamps with or without armour
rods. The interphase spacers meet the requirements of CEA LWIWG-01, IEEE 1024, ANSI
C29.11 and CSA C411.4.
Experience
In the past 20 years many Canadian Utilities such as Ontario Hydro, Manitoba Hydro, and
Hydro-Quebec have installed interphase spacers. Also, they are widely used by other utilities in
countries such as Australia, Germany, Japan, USA, and Switzerland. They have been applies on
distribution and transmission lines operating from 4.16 to 500 kV. There have not been any
problems reported with the K -Line interphase spacers.
Application
One or two interphase spacers are installed in each span. One spacer is installed if there are two
vertically positioned conductors and it is installed at one-third of the span. Two spacers are
installed if there are three vertically positioned conductors. The first spacer is installed between
the mid and lower conductors one-third of the span from one end. The second spacer is installed
between the mid and upper conductor one-quarter of the span from the other end.
Sebastian Marra, P. Eng.
Manager of Engineering
K Line Insulators Limited
August 11, 2000
Catalogue D-IPS
Performance Benefits
The performance benefits of K-Line Insulators distribution suspension/dead-end insulators are listed below.
Improves Reliability (by minimizes interruptions and outages due to vandalism, pole fires, and flashovers in
all types of environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)
Application
One or two interphase spacers are installed in each span. One spacer is installed if there are two
vertically positioned conductors and it is installed at one-third of the span. Two spacers are installed if
there are three vertically positioned conductors. The first spacer is installed between the mid and lower
conductors one-third of the span from one end. The second spacer is installed between the mid and
upper conductor one-quarter of the span from the other end.
Core Material
The core rod of the distribution suspension/dead-end insulator is made of a high quality fiberglass that has been
specially formulated for electrical and mechanical applications.
light weight
unlimited applications
UNIT
Voltage Class
CATALOGUE NUMBER*
KL15ARSIU
KL28ARSIU
KL46SNRSIU
KL46SRSIU
KL69HRIU16
15
28
35/46
46
69
kV
Section Length L
mm (in)
mm (in)
389 (15.3)
500
(19.7)
594 (23.4)
619 (24.4)
779 (30.7)
195
(7.6)
290
(11.4)
389 (15.3)
419 (16.5)
627 (24.7)
Leakage Distance
mm (in)
385 (15.1)
590
(23.2)
853 (33.6)
988 (38.9)
1798 (70.8)
kV
100
155
180
260
Low-Frequency Flashover
Dry
Wet
kV
70
105
135
150
205
kV
145
225
285
300
425
Test
kV
15
20
30
30
44
Max.
135
Below 1
Below 1
Below 5
Below 5
Below 10
Nm (ftlb)
83
(62)
83
(62)
83 (62)
83 (62)
83 (62)
kg (lb)
0.7
(1.5)
0.9
(1.9)
2.1 (4.7)
2.2 (4.8)
2.3 (5.1)
* Options:
For 5/8-11UNC tapped hole add X or for tin-plated clamp add D to the catalogue number.
Catalogue MB-PT
Single Circuit
Pole Top Framing Assembly
Single Circuit
Pole Top Framing Assembly
The ultimate in labour saving and convenience is provided by K-Line's single circuit pole-top framing
assembly (35 kV shown). The assembly comes complete in kit form with mounting bracket, polymer line post
insulators, trunnion clamps and insulator mounting studs. Install with two bolts and the structure is ready to
sag.
The hot dip galvanized steel bracket comes with predrilled holes for mounting of riser support insulators and a
grounding lug. The insulators are of silicone, the ultimate in polymer line post insulators for maintenance-free
operation.
.
Clamps
Trunnion Clamp
Part No.
Material
KLOP26AL
Aluminum
KLOP26I
Mallealbe iron
KLOP173
Aluminum
Studs
Conductor Range
0.25 1.07
(6.4mm 27.2mm)
0.25 1.07
(6.4mm 27.2mm)
1.00 1.50
(25.4mm 38.1mm)