AS BUILT DOCUMENT
Sign.
N.
Sign.
N.
Sign.
N.
Sign.
N.
MAURIN
COTILLON
MILER
25/06/2010
AS BUILT
ASB
Sign.
N.
ETIENNE
GUIOT
BINDELE
13/10/2005
GFE
Sign.
N.
ETIENNE
GUIOT
BINDELE
25/05/05
FIRST ISSUE
GFE
ETABLI
ESTABLISHED
VERIFIE
CHECKED
APPROUVE
APPROVED
REV
DATE
Approved
Approved as noted
CONFIRMED
AS TRUE RECORD
Date: 16/05/11
Date : ..
Signature:
ALSTOM
MODIFICATIONS
STAT
Returned
for correction
For information
CHECKED
AND ACCEPTED
Date: ___________
Signature : .
Signature: ___________
LAHMEYER INTERNATIONAL
LAHMEYER INTERNATIONAL
CONTRACTOR:
SCALE
1/1
Power Environment
Hydro
Ce document proprit de ALSTOM ne doit pas tre utilis, copi ou communiqu des tiers sans son autorisation
This document is the exclusive property of ALSTOM and shall not be used, copied or communicated to third parties without their prior authorization
AHS MRW00
INTERNAL USE
SEO-MS200
M1145A41006
1/15
15
VERIFIE
APPROUVE
ESTABLISHED
CHECKED
APPROVED
ETIENNE
GUIOT
BINDELE
25/05/05
FIRST ISSUE
GFE
ETIENNE
GUIOT
BINDELE
13/10/05
GFE
MAURIN
COTILLON
MILER
25/06/10
AS BUILT
ASB
PA 401 A
REV
DATE
MODIFICATIONS
STAT.
M1145A41006-.2/15
PURPOSE...............................................................................................................................................................................4
4.5.2
4.5.3
4.5.4
MANUAL mode.................................................................................................................................................................10
AUTOMATIC mode ..........................................................................................................................................................11
Securities levels.........................................................................................................................................................11
Choice of the main pump ..........................................................................................................................................12
Control principles of the pumps................................................................................................................................13
4.5.4.1
Pump 00SEO001PO ...........................................................................................................................................................13
4.5.4.1.1 Starting conditions .........................................................................................................................................................13
4.5.4.1.2 Information received from the board 400V 20LKA001TB.........................................................................................13
4.5.4.1.3 Information received from the pump 00 SEO 001PO ....................................................................................................13
4.5.4.1.4 Pump fault 00SEO 001PO .............................................................................................................................................13
4.5.4.1.5 TLTE functioning ..........................................................................................................................................................13
4.5.4.2
Pump 00SEO002PO ...........................................................................................................................................................14
4.5.4.2.1 Starting conditions .........................................................................................................................................................14
4.5.4.2.2 Information received from the board 400V 20LKA001TB.........................................................................................14
4.5.4.2.3 Information received from the pump 00 SEO 002PO ....................................................................................................14
4.5.4.2.4 Pump fault 00SEO 002PO .............................................................................................................................................14
4.5.4.2.5 TLTE functioning ..........................................................................................................................................................14
4.6
LABELLING........................................................................................................................................................................15
FACILITIES ........................................................................................................................................................................15
M1145A41006-.3/15
PURPOSE
This document describes the principle of control command of the domestic sewage system.
REFERENCE DOCUMENTS
M1145A41006-.4/15
M1145A41006-.5/15
4.1
OVERVIEW
4.1.1
M1145A41006-.6/15
4.2
CABLING
CTRL Board
00SEO001CR
Level sewage
tank
00SEO001/5SN
CONTROLLER
20KKM
Pump
00SEO001PO
Pump
00SEO002PO
M1145A41006-.7/15
4.2.1
Control mode
Auto
Main pump
Manu
002PO
001PO
00SEO001PO
Start
Fault
00SEO002PO
Stop
Start
RESET
AUTO
Fault
Stop
LAMP TEST
M1145A41006-.8/15
4.3
00SEO001CR
+/- C1
Relay of
Polarity monitoring
+/-S1
Relay of polarity
monitoring
Control board
00SEO001CR
M1145A41006-.9/15
4.4
LEVEL CABLING
Representation with empty tank without water
Sewage tank
Start all pumps
+ alarm
245,50m
00SEO 005SN
To 00SEP001FI
245,60m
00SEO 004SN
244,60m
00SEO 003SN
242,80m
00SEO 002SN
242,50m
00SEO 001SN
Start main
pump
STOP
Pumps 1 & 2
STOP
Pump 1 & 2 +
alarm
Excited if level>
Excited if level>
Excited if level<
Excited if level<
Note : For the 00SEO005SN, see the processing notice AHS MRW 00SEP-NF100
4.5
4.5.1
Operation modes
MANUAL mode
This mode is selected from the board -00SEO001CR through the control mode switch "Auto / Manu" if
the switch is turned on MANUAL position.
The operator who is able to start and stop individually each pump makes all the operations.
All the mechanical securities ("pump" pressure,..) and electrical securities (fault "start LV" of
the pumps,..) are running.
M1145A41006-.10/15
This mode is the secure operation mode of the automatic mode and is also used for the
tests and during the commissioning stage.
4.5.1.2
AUTOMATIC mode
This mode is selected from the board -00SEO001CR through the control mode switch "Auto / Manu" if
the switch is turned on AUTO position.
This mode is the normal operation mode for the domestic sewage system.
The pump control is carried out automatically by the levels detected in the tank and also by
the positions of the main pump selector switches.
Automatics actions
Nota: The starting levels for the "service pump" and "stand-by pump" are saved and
then erased by low level.
4.5.2
Securities levels
M1145A41006-.11/15
4.5.3
The choice of the main pump is made through the switch on the cubicle front face.
The operator has 2 possibilities:
Force the choice of the main pump by positioning the switch on "001PO" or
"002PO".
Let the automatism make cyclically the choice of the main pump.
The change will be made automatically each time the main pump is
stopped.
The switch must be turned on "AUTO" position.
001PO
002PO
AUTO
Stop level
pumps
Relay
fonction
S
XT
M1145A41006-.12/15
4.5.4
4.5.4.1
Pump 00SEO001PO
4.5.4.1.1
Starting conditions
Control level switch located on the 400V ac starter of the pump shall be turned on
AUTO position.
The load rejection output from 20KKM controller shall be ON
If operation mode = auto:
00SEO001PO selected as main pump and level 00SEO003SN reached or
00SEO001PO selected as stand-by pump and fault detected on the main pump
Level 00SEO004SN detected
If operation mode = manu:
Absence of low level 00SEO 002SN
4.5.4.1.2
4.5.4.1.3
4.5.4.1.4
TLTE functioning
An alarm "Too Long Time Functioning" is made in automatic mode. This alarm appears if the pump is
in service after a time T= 30mn.
M1145A41006-.13/15
4.5.4.2
Pump 00SEO002PO
4.5.4.2.1
Starting conditions
Control level switch located on the 400V ac starter of the pump shall be turned on
AUTO position.
The load rejection output from 20KKM controller shall be ON
If operation mode = auto:
00SEO002PO selected as main pump and level 00SEO003SN reached or
00SEO002PO selected as stand-by pump and fault detected on the main pump
Level 00SEO004SN detected
If operation mode = manu:
Absence of low level 00SEO 002SN
4.5.4.2.2
4.5.4.2.3
4.5.4.2.4
TLTE functioning
An alarm "Too Long Time Functioning" is made in automatic mode. This alarm appears if the pump is
in service after a time T=30mn.
M1145A41006-.14/15
4.6
The states and alarms of the 00SEO system are acquired by the controller 20KKM Auxiliaries in
order to be send to the central supervisor (Centralog) located in central control room.
It is given, on borders and via terminal free polarity , the informations below:
Informations acquired by the controller 20KKM
LABELLING
FACILITIES
M1145A41006-.15/15