Você está na página 1de 53

Committed Project

Parameters
Ballynahulla 220/110kV Station
(CP0651)
Revision History
Revision
Date

Description

Originator

Approver

R0

29/03/2012

First Issue

Kieran French

Stephen Murray

R1

15/06/2012

Revised Timelines

Kieran French

Stephen Murray

R2

27/06/2012

Section 1.3.2 amended

Kieran French

Stephen Murray

R3

16/08/2012

Kieran French

Stephen Murray

R4

10/01/2013

Kieran French

Stephen Murray

R5

18/06/2013

Revised Protection Spec

Kieran French

Stephen Murray

R6

22/04/2014

Revised Protection Spec

Brian Mullins

Alan McHugh

Revised Protection spec &


Cordal cable rating amended
Amendment to Full CPP - Grant
of planning document included
as appendix

COPYRIGHT EirGrid
All rights reserved. No part of this work may be modified or reproduced or
copied in any form or by means - graphic, electronic or mechanical, including
photocopying, recording, taping or information and retrieval system, or used
for any purpose other than its designated purpose, without the written
permission of EirGrid

TABLE OF CONTENTS
INTRODUCTION

PROJECT DESCRIPTION

OUTLINE DESIGN

1.
1.1

OUTLINE DESIGN PHILOSOPHY

1.2
BALLYNAHULLA 220 / 110KV GIS STATION
1.2.1 220/110kV GIS Station - HV Equipment
1.2.2 HV GIS Bay Equipment Ratings
1.2.3 Ballynahulla 220/110kV GIS Station Civil Works
1.2.4 220kV Remote Station Works
1.2.5 110kV Remote Station Works

4
4
4
4
5
5

1.3
220KV & 110KV CIRCUIT DESIGN
1.3.1 220kV OHL Design
1.3.2 220kV & 110kV Cable Design

5
5
6

1.4

TRANSFORMERS

1.5

PROTECTION

1.6

CONTROL AND TELECOMMUNICATIONS

1.7

EARTHING & LIGHTNING PROTECTION

1.8

AS BUILT PARAMETERS

2.

FUNCTIONAL SPECIFICATION

3.

INDICATIVE PROGRAMME

10

4.

TSO COSTS/ FINANCIAL ISSUES

11

5.

PLANNING PERMISSION DOCUMENTATION

11

6.

LANDOWNER AGREEMENTS

12

7.

TSO OUTAGE AVAILABILITY DURING CONSTRUCTION & COMMISSIONING

12

8.

COMMISSIONING PROCEDURES

12

9.

ENERGISATION PROCEDURES

12

10.

CLIENT ENGINEER DETAILS

12

11.

APPENDICES

13

INTRODUCTION
The Infrastructure Agreement shall be implemented to ensure that the development of the
project agreement for the above committed project is reached. It is envisaged under the
Infrastructure Agreement that the TSO will issue a committed project parameter (CPP) to the
TAO. The TAO will develop a project implementation plan (PIP) from this CPP and submit to
the TSO for approval. Once the CPP is finalised and the PIP is determined or agreed to be
satisfactory, then the Project Agreement shall be prepared.

PROJECT DESCRIPTION
This document outlines the requirements for the construction of the new Ballynahulla
220/110kV GIS station.

The station is to be looped in to the existing Clashavoon Tarbert 220kV line. The loop-in
sections are required to be via 220kV cables which are to have a rating consistent with
600mm2 HTLS conductor at 800C.

A new 110kV cable is to be constructed from the planned Cordal 110kV station to the
proposed new Ballynahulla 220/110kV station as part of this project. The requirements for
Cordal 110kV station will be catered for under a separate CPP.

The Ballynahulla 220kV GIS station is to be constructed as per the SLD XDN-SLD-CP0651F-BYH-001 Rev 06 and is to consist of the following;

2 x 220kV Line Bays

1 x 220/110kV Transformer Bay (Connected on the A2/B2 section of busbar)

4 x 220kV Spare line bays

1 x Spare Transformer bay (On the A1/B1 section of busbar)

2 x 220kV Sectionaliser Bays

2 x 220kV Wing coupler Bays

1 x 220/110kV 250MVA transformer (double wound), 16% impedance, 16 taps, vector


group YN, yon, d5. A neutral earth switch is to be provided on the transformer.

The Ballynahulla 110kV GIS station will consist of a double busbar arrangement containing
the following;

1 x 110kV Line Bays

1 x 110/220kV Transformer Bay

5 x 110kV Spare Line Bays

1 x 110/220kV Spare Transformer Bay

2 x 110kV Sectionaliser Bays

2 x 110kV Wing coupler Bays

1.

OUTLINE DESIGN

The following document defines the functional requirements and site specific requirements for
the construction of the new Ballynahulla 220/110kV station and the associated works required
at the remote station circuit ends.

1.1

OUTLINE DESIGN PHILOSOPHY

Work shall be designed with safety, reliability, maintainability and ease of operation as the
primary consideration. Due consideration shall be given to the environment.

1.2
1.2.1

BALLYNAHULLA 220 / 110KV GIS STATION


220/110KV GIS STATION - HV EQUIPMENT

The TAO are to construct a new 220/110kV GIS station in accordance with the SLD XDNSLD-CP0651-F-BYH-001 Rev 06, and the planning drawings which have been sent
separately to the TAO via CD. The SLD XDN-SLD-CP0651-F-BYH-001 Rev 06 is included
as an appendix to this document.
1.2.2

HV GIS BAY EQUIPMENT RATINGS

The required ratings for the 220kV and 110kV equipment are as per the Single Line Diagram
XDN-SLD-CP0651-F-BYH-001 Rev 06, included as an appendix to this CPP.
1.2.3

BALLYNAHULLA 220/110KV GIS STATION CIVIL WORKS

The civil design for the construction of the new Ballynahulla 220/110kV station shall be as per
the planning application drawings which have been sent separately to the TAO.
The 220kV and 110kV GIS buildings are to be constructed to house the ultimate development
of the 220/110kV station.
An access road and bridge is to be constructed to the new station in accordance with the
planning drawings sent separately to the TAO.

1.2.4

220KV REMOTE STATION WORKS

1.2.4.1

BALLYVOUSKILL 220KV STATION

The protection requirements associated with the Ballynahulla 220kV bay (previously known
as the Kiskeam 220kV) at Ballyvouskill 220kV station have been specified as part of CP0650
and should not be scoped as part of this project.
1.2.4.2

KNOCKANURE 220KV STATION

The protection requirements associated with the Ballynahulla 220kV bay (previously known
as the Kiskeam 220kV) at Knockanure 220kV station have been specified as part of CP0500
and should not be scoped as part of this project.
110KV REMOTE STATION WORKS

1.2.5

The protection requirements associated with the Ballynahulla 110kV bay at Cordal 110kV
station will be catered for under a separate CPP and should not be scoped as part of this
project.

1.3

220KV & 110KV CIRCUIT DESIGN

1.3.1

220KV OHL DESIGN

The station is to loop in to the existing Clashavoon Tarbert 220kV circuit. This will result in
two new 220kV circuits;

Ballynahulla - Ballyvouskill 220kV station

Ballynahulla Knockanure 220kV station

This will require the installation of two 220/110kV line interface towers.

1.3.2

220KV & 110KV CABLE DESIGN

The 220kV connections to the new Ballynahulla 220/110kV GIS station will occur by means of
underground cable.
The 220kV cables required as part of this project are to have a rating equivalent to 600mm2
HTLS conductor at 800C. This is due to the uprate of the Clashavoon Tarbert 220kV line as
part of CP0763. The line will be uprated from 600mm2 ACSR @ 800C to a rating consistent
with 600mm2 HTLS conductor at 800C.
A 110kV cable circuit to the new Cordal station is required to be installed as part of this
project. A minimum rating equivalent to 1000mm2 Al cable is required for this circuit.
Refer to the single line diagram XDN-SLD-CP0651-F-BYH-001 Rev 06, included as an
appendix to this document.

1.4

TRANSFORMERS

1 x 220/110kV Power Transformer is required to be installed as part of the construction of the


new Ballynahulla 220/110kV GIS station. The parameters of this transformer are to be as
follows;

1 x 220/110kV 250MVA transformer (double wound)

16% impedance

16 taps

vector group YN, yon, d5

A neutral earth switch is to be provided on the transformer

1.5

PROTECTION

The protection requirements for the new 220/110kV GIS station are included as an appendix
to this CPP. Please refer to the document entitled Protection Requirements for Ballynahulla
220/110kV Transmission Station Revision 1.7, dated 07/03/2014.
Note:

Bay H1 in Ballynahulla 220kV station will be used for a future 110kV connection to either
Glenlara or Knockacummer. The connection node and method (OHL or Cable) will be known
shortly and the requirements of such will be covered under a separate CPP.

1.6

CONTROL AND TELECOMMUNICATIONS

The control and telecommunications requirements for the new 220/110kV GIS station are
included as an appendix to this CPP. Please refer to the document entitled Ballynahulla
220kV SCS Station CP0651 NCC Signals_v4.0, dated 13 February 2014, included as an
appendix to this document.

1.7

EARTHING & LIGHTNING PROTECTION

New station to be built as per the EirGrid functional requirements.

1.8

AS BUILT PARAMETERS

Provide as built parameters in a format to be agreed by EirGrid.

2.

FUNCTIONAL SPECIFICATION

The functionality of the following list of term contract equipment and systems meet the
requirements of the TSO.
It is assumed that term contract will be used where possible. In the case where term contract
equipment is not used, the TAO shall submit to the TSO the alternative designs or
technologies for review.
The appropriate sections of the following documentation shall be adhered to:
Station Functional Specifications 110/220/400kV
110/220/400kV Station General
00
Requirements

Doc Number
XDS-GFS-00-001-R1

06

110/220/400kV Control and Protection

XDS-GFS-06-001-R0

07

Station Control and Protection Cabinets and


Marshalling Kiosks

XDS-GFS-07-001-R0

08

Station Auxiliary Power Supplies

XDS-GFS-08-001-R0

09
10

Station 220V, 48V and 24V Lead Acid


Batteries and Chargers
220V/48V/24V DC and 230/400V/110V AC
Distribution Boards

XDS-GFS-09-001-R1
XDS-GFS-10-001-R0

11

Auxiliary Cables and Wiring System

XDS-GFS-11-001-R0

12

Earthing and Lightning Protection

XDS-GFS-12-001-R0

13A

Station Civil and Building Works

XDS-WTS-13-001-R0

13B

GIS Station Civil and Building Works

14

Station Electrical & Mechanical Services for


Transmission System Control Buildings

XDS-GFS-14-001-R0

15

Fire Detection & Fire Alarm System

XDS-GFS-15-001-R0

16

Intruder Detection & Security monitoring


System for Transmission Stations

XDS-GFS-16-001-R0

17

Galvanised Fabricated Steelwork

XDS-GFS-17-001-R0

18

Station Hot Dip Galvanising of Iron and


Steel Other Than Wire

XDS-GFS-18-001-R0

19

Steel Masts & Girders

XDS-GFS-19-001-R0

20

Pre-commissioning Requirements

XDS-GFS-20-001-R0

XDS-GWTS-13-001-R0

21

22
23

25

EirGrid Blackstart Shutdown System


Control Specification for Wind Farm Power
Stations Connected to the Transmission
system
Alert System Control Specification for
Transmission Stations
Alert System Control Specification for
Generators Connected to the Transmission
system
110/220/400kV Gas Insulated Switchgear
(GIS) Connected to the Transmission
System

Station Functional Specifications - 220kV

XDS-GFS-21-001-R0

XDS-GFS-22-001-R0
XDS-GFS-23-001-R0

XDS-GFS-25-001-R0

Doc Number

220kV Circuit Breakers

XDS-FFS-01-001-R0

220kV Disconnectors & Earthing Switches

XDS-FFS-02-001-R0

220kV Instrument Transformers

XDS-FFS-03-001-R0

220kV Surge Arrester

XDS-FFS-04-001-R0

220kV Post Insulators

XDS-FFS-05-001-R0

Cable Functional Specifications - 220kV

Doc Number

General Requirements

CDS-FFS-00-001-R0

Route Selection

CDS-FFS-01-001-R0

Cable Materials

CDS-FFS-02-001-R0

Cable Civil Works

CDS-FFS-03-001-R0

Cable Installation

CDS-FFS-04-001-R0

Doc Number

OHL Functional Specifications - 110kV


1

General Requirements

LDS-HFS-00-001-R0

3.

INDICATIVE PROGRAMME

Milestone

Date

Submission of Planning Application:


Ballynahulla 220/110kVGIS Station:
Expected grant of Planning Permission:
Ballynahulla 220/110kVGIS Station:
Outline CPP Submission

June 2012
November 2012
June 2012

Receipt of PIP by TSO

November 2012

Project Agreement date

January 2013

Target Completion date

Q4 2015

10

4.

TSO COSTS/ FINANCIAL ISSUES

The estimated cost to be incurred by TSO in connection with the construction the new
Ballynahulla 220/110kV station and the associated OHL works are shown below.
The TSO direct costs are estimated to be 5.0m; this is for cable / OHL route selection, site
selection and project management costs of the TSO (review of commissioning and
energisation procedures, Capital Approval preparation, managing the preparation of project
parameters, review of CPPs and PIP, preparation of Project Agreement and overall project
coordination) and the costs incurred by the TSO in preparing civil functional specifications,
design review and site conformance auditing.

5.

PLANNING PERMISSION DOCUMENTATION

Planning application drawings included

Planning
Application
Drawings will
be sent to
TAO
on
separate CD

Environmental Impact Statement


Env. Report
Environmental Report Included (Landscape, Cultural Heritage and Flora will issue to
& Fauna reports)
TAO
on
separate CD
Decision of planning authority included (letter of approval)

11

Included
appendix

as

6.

LANDOWNER AGREEMENTS

Landowner lists, agreements, access arrangements etc to follow.

7.

TSO OUTAGE AVAILABILITY DURING CONSTRUCTION & COMMISSIONING

The outage constraints will be reviewed following receipt of the outage requirements from the
TAO.

These outages will be included in the relevant EirGrid Transmission Outage Program closer
to the energisation date. However the timing and the length of the outage will be subject to
prevailing conditions, available ESB Networks resources and progress on the line. The actual
outages will be determined closer to the program date.

8.

COMMISSIONING PROCEDURES

The commissioning procedures shall be issued in draft form to the TAO 40 business days
prior to commissioning. The final version of the procedures will be issued 20 business days
prior to start of commissioning.

9.

ENERGISATION PROCEDURES

Energisation procedures shall be issued in draft form to the TAO 20 business days prior to
scheduled energisation. The final version of the procedures shall issue 10 business days
prior to scheduled energisation.

10.

CLIENT ENGINEER DETAILS

Name

Kieran French

Stephen Murray

Telephone number

01 2370466

01 2370425

Mobile Number

087 9860296

087 1958713

Email address

kieran.french@eirgrid.com

Stephen.murray@eirgrid.com

12

APPENDICES

11.

XDN-SLD-CP0651-F-BYH-001 Rev 06
Ballynahulla Protection Specification Version 1.7 (Document Title: Protection
Requirements for Ballynahulla 220/110kV Transmission Station Revision 1.7)
Ballynahulla 220kV SCS Station CP0651 NCC Signals_v4.0

13

Title:
CPP:
Revision:
Date:

Protection Requirements for Ballynahulla 220 kV / 110 kV Transmission Station


CP0651
1.7
07/03/2014

1. Summary

Ballynahulla is a new 220 / 110 kV transmission station that will be constructed along the path of
the existing Clashavoon Tarbert 220 kV line.
This specification is based on the SLD XDN-SLD-CP0651-F-BYH-001. Rev05
The following is assumed for Ballynahulla 220 kV GIS busbar:
220 kV GIS double busbar
One 220 kV transformer bay T2102 (250 MVA)
Two 220 kV line bays (Ballyvouskill and Knockanure)
One spare 220 kV transformer bay
Four spare 220 kV line bays
Two 220 kV wing coupler bays (K1 and K2)
Two 220 kV sectionalising circuit breaker bays (SA1-2 and SB1-2)
The following is assumed for Ballynahulla 110 kV GIS busbar:
110 kV GIS double busbar
One110 kV transformer bays T2102 (250 MVA)
One spare 110 kV transformer bay
One110 kV line bay (Cordal)
Five spare 110 kV line bays
Two 110 kV wing coupler bays (K1 and K2)
Two 110 kV sectionalising circuit breaker bays (SA1-2 and SB1-2)
It is assumed that the new station will be equipped with a SCS as per the current term contract.
The protection for the spare bays will not be specified as part of this project.
2. Ballynahulla Protection Communications Requirements:

The protection at Ballynahulla will require access to the fibre network for Differential
communications and for Impedance protection teleprotection signalling. As access to the
fibre network in this region is limited, the communication requirements, as outlined in the
following sections, must be given consideration at the earliest point in the design process.
3. Ballynahulla Protection Relay Requirements:

The GRL100 relays for this station have been specified with the additional backup distance
protection function to cater for the phased provisioning of FO based protection
communications. The communications infrastructure in this region will be built as part of the
Ballyvouskill, Kilpaddoge, Knockanure and Ballynahulla projects. As the timeline for the
completion of each project is not clearly defined at this stage, the backup distance function in
the GRL will allow the lines to be operated with duplicate impedance protection until such time
as the communications infrastructure is completed. A modified protection elementary will be
required for these relays and must be requested at the earliest possible stage in the design
process.

-1-

4. Ballynahulla Bus Zone / Circuit Breaker Failure Protection:

4.1.
4.2.
4.3.

4.4.
4.5.
4.6.

Install a combined BZP/CBF scheme for the new 220 kV busbar. The scheme must be
specified to cater for the initial development of the busbar and have adequate
capacity for any future bays.
A 220 kV Bus Zone Protection trip should block local auto-reclosing and initiate
transmission of PTT and auto-recloser block signals to the relevant remote stations (2
second signal duration).
Stage 1 operation of the 220 kV circuit breaker fail protection scheme should result in:
o Attempted triple pole tripping (trip commands to both sets of trip coils) of the
failed CB
o The blocking of the local auto-recloser (Line Bays only)
o The transmission of PTT and auto-recloser block signals to the remote end (2
second signal duration)
Install a combined BZP/CBF scheme for the new 110 kV busbar. The scheme must be
specified and designed to cater for the initial development of the busbar and for any
future bays.
A 110 kV Bus Zone Protection trip should block local auto-reclosing and initiate
transmission of PTT and auto-recloser block signals to the relevant remote stations (2
second signal duration).
Stage 1 operation of the 110 kV circuit breaker fail protection scheme should result in:
o Attempted triple pole tripping (trip commands to both sets of trip coils) of the
failed CB
o The blocking of the local auto-recloser (Line Bays only)
o The transmission of PTT and auto-recloser block signals to the remote end (2
second signal duration)

-2-

5. Ballynahulla Check and Controlled Synchronising Facilities:

5.1.
5.2.

5.3.
5.4.
5.5.

All 220 kV circuit breakers must be provided with synchronising facilities. The DIRECT
CLOSE and SYNC CLOSE modes shall be available both remotely (NCC) and locally.
The 220 kV line bays (Knockanure and Ballyvouskill) and the 220 kV coupler bays (SA1-2
CB, SB1-2 CB, K1 CB and K2 CB) must have a CONTROLLED SYNCHRONISING facility that
will be available to a local operator only. This must be extendable to the spare feeder
bays.
All 110 kV circuit breakers must be provided with synchronising facilities. The DIRECT
CLOSE and SYNC CLOSE modes shall be available both remotely (NCC) and locally.
It is acceptable to implement the CHECK SYNCHRONISING facility using the available
functionality within the Siemens SCS.
The CONTROLLED SYNCHRONISING system should be implemented as follows:
5.5.1. Install a synchronising relay (e.g. an ABB Synchrotact).
5.5.2. Install a cabinet with:
Synchroscope, double voltmeter, double frequency meter, delta voltage meter,
and a delta frequency meter.
Dedicated Controlled Synchronising SMD switch.
Indication lamps operated by the synchronising relay to indicate that the
voltage difference, angular difference and frequency difference are all within
the permitted range for close commands to be issued and when the sync relay
is ready to give a permissive close command.
The above cabinet should be installed close to SCS HMI so that operator
carrying out the synchronising operation is able to see the overall station busbar
configuration on the SCS and the synchronising instrumentation outlined above.
5.5.3.
5.5.4.
5.5.5.

The SCS should provide a facility to locally select Control Sync mode.
The CB to be Control Sync closed should be selectable locally via the SCS HMI.
When a CB has been selected for Control Sync the SCS shall:
5.5.5.1. Provide the necessary incoming and reference voltages(R and S phases)
to the synchronising relay (depending on CB selected for Control Sync
Close and busbar configuration)
5.5.5.2. Set up the routing of synchronising relay close command to the selected
CB. The CONTROLLED SYNC close command to the selected CB shall also
be routed via a dedicated SMD switch (wired in series with the
synchronising relay close command contacts.

-3-

6. Knockanure - Ballynahulla 220kV line

Teleprotection facilities for this feeder shall be provided by TEBIT and PLC. Differential
protection communications shall be provided by the FIBRE NETWORK network.
6.1.

At Ballynahulla on the Knockanure bay:


6.1.1. Install current instrument transformers with ratios of 2500/1/1/1 A (two protection
cores and one metering core).
6.1.2. Install ring type current instrument transformers, outside of the GIS, with ratios of
3500/1 A for use with the combined BZ/CBF protection.
6.1.3. Install voltage instrument transformers with winding ratios of 220 kV /3 / 100V/3 /
100V/3 / 100V/3.
6.1.4. Install a TEBIT teleprotection interface in the OPMUX node at Ballynahulla.
6.1.5. Install a PLC teleprotection interface.
6.1.6. Install HF PLC coupling rated to at least 2500 A.
6.1.7. Install Surge Arrestors.
6.1.8. Install a Toshiba GRL100 line differential relay with backup impedance protection.
The relay will be configured to provide differential protection via the FO interface
and distance protection in POTT mode via the TEBIT/PLC teleprotection interfaces.
The relay shall be configured to provide single / three pole tripping and autoreclosing. The 220 kV VT secondary circuits and VTMCB trip signals must be wired
into this relay.
6.1.9. Install a Siemens 7SA612 line impedance protection relay and configure it to
provide distance protection in POTT mode with DCEF protection via the TEBIT/PLC
teleprotection interfaces. The relay shall also be configured to provide single /
three pole tripping and auto-reclosing.
6.1.10. Install Trip Test switches for both relays (three pole trip only).
6.1.11. Test socket arrangements should be to current standards.
6.1.12. Provide NCC remote control of reclosing.
6.1.13. Teleprotection channels should be assigned as follows:
PLC Unit 1
CH1 7SA612 / GRL100 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
TEBIT
CH1 7SA612 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
CH3 GRL100 POTT Tx/Rx
CH4 AR Block Tx/Rx.

-4-

6.2.

At Knockanure on the Ballynahulla bay:


This protection has already been specified as part to the Knockanure Project (CP0500).
6.2.1. Install current instrument transformers with ratios of 2500/1/1/1 A (two protection
cores and one metering core).
6.2.2. Install ring type current instrument transformers, outside of the GIS, with ratios of
3500/1 A for use with the combined BZ/CBF protection.
6.2.3. Install voltage instrument transformers with winding ratios of 220 kV /3 / 100V/3 /
100V/3 / 100V/3.
6.2.4. Install a TEBIT teleprotection interface in the OPMUX node at Knockanure.
6.2.5. Install a PLC teleprotection interface.
6.2.6. Install HF PLC coupling rated to at least 2500 A.
6.2.7. Install Surge Arrestors.
6.2.8. Install a Toshiba GRL100 line differential relay with backup impedance protection.
The relay will be configured to provide differential protection via the FO interface
and distance protection in POTT mode via the TEBIT/PLC teleprotection interfaces.
The relay shall be configured to provide single / three pole tripping and autoreclosing. The 220 kV VT secondary circuits and VTMCB trip signals must be wired
into this relay.
6.2.9. Install a Siemens 7SA612 line impedance protection relay and configure it to
provide distance protection in POTT mode with DCEF protection via the TEBIT/PLC
teleprotection interfaces. The relay shall also be configured to provide single /
three pole tripping and auto-reclosing.
6.2.10. Install Trip Test switches for both relays (three pole trip only).
6.2.11. Test socket arrangements should be to current standards.
6.2.12. Provide NCC remote control of reclosing.
6.2.13. Teleprotection channels should be assigned as follows:
PLC Unit 1
CH1 7SA612 / GRL100 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
TEBIT
CH1 7SA612 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
CH3 GRL100 POTT Tx/Rx
CH4 AR Block Tx/Rx.

-5-

7. Ballynahulla Ballyvouskill 220kV line

Teleprotection for this feeder will be provided by TEBIT (fibre) and PLC. Differential protection
communications will be provided by the FIBRE NETWORK network.
7.1.

At Ballynahulla on the Ballyvouskill bay:


7.1.1. Install current instrument transformers with ratios of 2500/1/1/1 A (two protection
cores and one metering core).
7.1.2. Install ring type current instrument transformers, outside of the GIS, with ratios of
3500/1 A for use with the combined BZ/CBF protection.
7.1.3. Install voltage instrument transformers with winding ratios of 220 kV /3 / V/3 /
100V/3 / 100V/3.
7.1.4. Install a TEBIT teleprotection interface in the OPMUX node at Ballynahulla.
7.1.5. Install a PLC teleprotection interface.
7.1.6. Install HF PLC coupling rated to at least 2500 A.
7.1.7. Install Surge Arrestors.
7.1.8. Install a Toshiba GRL100 line differential relay with backup impedance protection.
The relay will be configured to provide differential protection via the FO interface
and distance protection in POTT mode via the TEBIT/PLC teleprotection interfaces.
The relay shall be configured to provide single / three pole tripping and autoreclosing. The 220 kV VT secondary circuits and VTMCB trip signals must be wired
into this relay.
7.1.9. Install a Siemens 7SA612 line impedance protection relay and configure it to
provide distance protection in POTT mode with DCEF protection via the TEBIT/PLC
teleprotection interfaces. The relay shall also be configured to provide single /
three pole tripping and auto-reclosing.
7.1.10. Install Trip Test switches for both relays (three pole trip only).
7.1.11. Test socket arrangements should be to current standards.
7.1.12. Provide NCC remote control of reclosing.
7.1.13. Teleprotection channels should be assigned as follows:
PLC Unit 1
CH1 7SA612 / GRL100 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
TEBIT
CH1 7SA612 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
CH3 GRL100 POTT Tx/Rx
CH4 AR Block Tx/Rx.

-6-

7.2.

At Ballyvouskill on the Ballynahulla bay:


This protection has already been specified as part to the Ballyvouskill project CP650
7.2.1. Install current instrument transformers with ratios of 2500/1/1/1 A (two protection
cores and one metering core).
7.2.2. Install ring type current instrument transformers, outside of the GIS, with ratios of
3500/1 A for use with the combined BZ/CBF protection.
7.2.3. Install voltage instrument transformers with winding ratios of 220 kV /3 / 100V/3 /
100V/3 / 100V/3.
7.2.4. Install a TEBIT teleprotection interface in the OPMUX node at Ballyvouskill.
7.2.5. Install a PLC teleprotection interface.
7.2.6. Install HF PLC coupling rated to at least 2500 A.
7.2.7. Install Surge Arrestors.
7.2.8. Install a Toshiba GRL100 line differential relay with backup impedance protection.
The relay will be configured to provide differential protection via the FO interface
and distance protection in POTT mode via the TEBIT/PLC teleprotection interfaces.
The relay shall be configured to provide single / three pole tripping and autoreclosing. The 220 kV VT secondary circuits and VTMCB trip signals must be wired
into this relay.
7.2.9. Install a Siemens 7SA612 line impedance protection relay and configure it to
provide distance protection in POTT mode with DCEF protection via the TEBIT/PLC
teleprotection interfaces. The relay shall also be configured to provide single /
three pole tripping and auto-reclosing.
7.2.10. Install Trip Test switches for both relays (three pole trip only).
7.2.11. Test socket arrangements should be to current standards.
7.2.12. Provide NCC remote control of reclosing.
7.2.13. Teleprotection channels should be assigned as follows:
PLC Unit 1
CH1 7SA612 / GRL100 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
TEBIT
CH1 7SA612 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
CH3 GRL100 POTT Tx/Rx
CH4 AR Block Tx/Rx.

-7-

8. Ballynahulla 220 kV Wing Coupler Protection (K1 and K2)

8.1.
8.2.
8.3.
8.4.

Install current instrument transformers with ratios of 3500/1/1/1/1 A (three protection cores
and one metering core). The CT must be installed with at least one protection class core
on either side of the circuit breaker. This is a requirement for the BZP scheme.
Install a Siemens 7SJ611 over current protection relay.
Install a Trip Test switch for the over current relay (three pole trip only).
Test socket arrangements should be to current standards.

9. Ballynahulla 220 kV Sectionalising Circuit Breaker Protection (SA1-2 and SB1-2)

9.1.
9.2.
9.3.
9.4.

10.

Install current instrument transformers with ratios of 3500/1/1/1/1 A (three protection cores
and one metering core). The CT must be installed with at least one protection class core
on either side of the circuit breaker. This is a requirement for the BZP scheme.
Install a Siemens 7SJ611 over current protection relay.
Install a Trip Test switch for the over current relay (three pole trip only).
Test socket arrangements should be to current standards.

Ballynahulla spare 220/110 kV Coupling Transformer Bays


10.1. Install current instrument transformers with ratios of 1000/1/1/1 A (two protection cores
and one metering core) on the 220 kV side of the transformer.
10.2. Ensure that there is adequate space for the future installation of ring type current
instrument transformers, outside of the GIS on the 220 kV side of the transformer, with
ratios of 3500/1 A for use with the combined BZ/CBF protection.
10.3. Install 220 kV side voltage instrument transformers with winding ratios of 220 kV /3 /
100V/3 / 100V/3 / 100V/3.
10.4. Install current instrument transformers with ratios of 2000/1/1/1 A (two protection cores
and one metering core) on the 110 kV side of the transformer.
10.5. Ensure that there is adequate space for the future installation of ring type current
instrument transformers, outside of the GIS on the 110 kV side of the transformer, with
ratios of 2500/1 A for use with the combined BZ/CBF protection.
10.6. Install 110 kV side voltage instrument transformers with winding ratios of 110 kV /3 /
100V/3 / 100V/3 / 100V/3.

-8-

11. Ballynahulla 220/110 kV Coupling Transformer Protection ( T2102)

NOTE: The 220 kV star point of the transformer will be solidly earthed. Earthing of the 110 kV star
points of the transformer will be via a 110 kV neutral earthing switch.
11.1. Install current instrument transformers with ratios of 1000/1/1/1 A (two protection cores
and one metering core) on the 220 kV side of the transformer.
11.2. Install ring type current instrument transformers, outside of the GIS on the 220 kV side of
the transformer, with ratios of 3500/1 A for use with the combined BZ/CBF protection.
11.3. Install a 1000/1 A ring type CT on the 220 kV neutral of the transformer.
11.4. Install a 2000/1 A ring type CT on the 110 kV neutral of the transformer.
11.5. Install 220 kV side voltage instrument transformers with winding ratios of 220 kV /3 /
100V/3 / 100V/3 / 100V/3.
11.6. Install current instrument transformers with ratios of 2000/1/1/1 A (two protection cores
and one metering core) on the 110 kV side of the transformer.
11.7. Install ring type current instrument transformers, outside of the GIS on the 110 kV side of
the transformer, with ratios of 2500/1 A for use with the combined BZ/CBF protection.
11.8. Install 110 kV side voltage instrument transformers with winding ratios of 110 kV /3 /
100V/3 / 100V/3 / 100V/3.
11.9. Install an ABB RET670 transformer differential protection relay. This relay must be
configured to provide transformer differential protection along with 220 kV and 110 kV
restricted earth fault (REF) protection.
11.10. Install a Siemens 7SA612 impedance protection relay on the 220kV side of the
transformer.
11.11. Install a Siemens 7SA612 impedance protection relay on the 110kV side of the
transformer.
11.12. Install Trip Test switches for the 7SA612 and RET670 relays.

12. Ballynahulla Spare 220kV feeder bays

12.1. At Ballynahulla on the spare 220 kV feeder bays:


12.1.1. Install current instrument transformers with ratios of 2500/1/1/1 A (two protection
cores and one metering core).
12.1.2. Install 220 kV side voltage instrument transformers with winding ratios of 220 kV /3
/ 100V/3 / 100V/3 / 100V/3.
12.1.3. Ensure that there is adequate space for the future installation of ring type current
instrument transformers, outside of the GIS.

-9-

13. Ballynahulla Cordal 110kV Line

Teleprotection for this feeder will be provided via the fibre network.
13.1. At Ballynahulla on the Cordal bay:
13.1.1. Install current instrument transformers with ratios of 1250/1/1/1 A (two protection
cores and one metering core).
13.1.2. Install ring type current instrument transformers, outside of the GIS, with ratios of
2500/1 A for use with the combined BZ/CBF protection.
13.1.3. Install voltage instrument transformers with winding ratios of 110 kV /3 / 100V/3 /
100V/3 / 100V/3.
13.1.4. Install Surge Arrestors.
13.1.5. Install a TEBIT teleprotection interface in the OPMUX node at Ballynahulla.
13.1.6. Install a Toshiba GRL100 line differential relay with backup distance protection. The
relay will be configured to provide differential protection via the FO interface and
distance protection in POTT mode via the TEBIT teleprotection interface. The relay
shall be configured to provide three pole tripping and auto-reclosing. The 110 kV VT
secondary circuits and VTMCB trip signals must be wired into this relay.
13.1.7. Install a Siemens 7SA612 line impedance protection relay and configure it to provide
distance protection in POTT mode and DCEF protection. The relay shall be
configured to provide three pole tripping and auto-reclosing. SPS functionality is also
required as outlined below.
13.1.8. Install Trip Test switches for both relays (three pole trip only).
13.1.9. Test socket arrangements should be to current standards.
13.1.10. Provide NCC remote control of reclosing.
13.1.11. Teleprotection channels should be assigned as follows:
TEBIT
CH1 7SA612 / GRL100 POTT Tx/Rx
CH2 7SA612 DCEF Tx/Rx.
CH3 SPS Tx
CH4 AR Block Tx/Rx.
13.2. The following Special Protection Functionality is required at Ballynahulla on the Cordal
bay.
13.2.1. In the event of the Cordal CB opening the SPS transmit output of the distance relay
on the Cordal bay will provide a 2 second pulse to CH3 of the TEBIT teleprotection
interface. This will be initiated by the CB status i/p to the relay. The SPS Rx input will
not be used. Upon operation of the SPS function, an SPS Operate signal should be
annunciated locally and provided to NCC.
13.2.2. There shall be a local SPS Enable / Disable facility.
13.2.3. There shall be NCC remote control of the SPS Enable / Disable facility.
13.2.4. The status of the SPS Scheme shall be indicated locally and shall be brought back to
the NCC.
13.2.5. There shall be a Sub Remote Control switch for the SPS remote control and the status
of the switch shall be brought back to NCC.

- 10 -

14. Ballynahulla 110 kV Wing Coupler Protection (K1 and K2)

14.1. Install current instrument transformers with ratios of 2500/1/1/1/1 A (three protection cores
and one metering core). The CT must be installed with at least one protection class core
on either side of the circuit breaker. This is a requirement for the BZP scheme.
14.2. Install a Siemens 7SJ611 over current protection relay.
14.3. Install a Trip Test switch for the over current relay (three pole trip only).
14.4. Test socket arrangements should be to current standards.
15. Ballynahulla 110 kV Sectionalising Circuit Breaker Protection (SA1-2 and SB1-2)

15.1. Install current instrument transformers with ratios of 2500/1/1/1/1 A (three protection cores
and one metering core). The CT must be installed with at least one protection class core
on either side of the circuit breaker. This is a requirement for the BZP scheme.
15.2. Install a Siemens 7SJ611 over current protection relay.
15.3. Install a Trip Test switch for the over current relay (three pole trip only).
15.4. Test socket arrangements should be to current standards.
16. Ballynahulla Spare 110kV feeder bays

16.1. At Ballynahulla on the spare 110 kV feeder bays:


16.1.1. Install current instrument transformers with ratios of 1250/1/1/1 A (two protection
cores and one metering core).
16.1.2. Install voltage instrument transformers with winding ratios of 110 kV /3 / 100V/3 /
100V/3 / 100V/3.

17.

Disturbance Recorder / Relay Remote Interrogation Cabinet


17.1. Install 2 No. dedicated free standing cabinets to house disturbance recorder, relay
remote interrogation and associated communication hardware. One cabinet will be
installed in the 220 kV control room and the other installed in the 110 kV control room.
17.2. Install a dedicated 220V DC MCB in both cabinets. An uninterruptible power supply
(MINI-DC-UPS/12DC/4 - 2866598 with integrated power supply unit, 4 A, in combination
with MINI-BAT/12/DC 2.6 Ah), shall be provided and installed in the 220 kV cabinet.
17.3. A DIN Rail Mounted PSU 220 AC/DC to 12V DC (RS #: 486-732) shall be supplied and
installed in the 110 kV cabinet.
17.4. 1 No. shielded Ethernet connections (Cat5e) are required from the ESB Telecoms IP
network (via a FO/Ethernet converter in the case of a distributed station layout or CAT5e
in the case of a traditional relay room layout). These shall be supplied to the disturbance
recorder cabinet in the 220 kV control room.
17.5. 1 No. Unmanaged Ethernet switch shall be supplied. (MOXA EDS205A-M-ST). It will be
installed in the disturbance recorder cabinet in the 220 kV control building. It will be
connected to the MOXA IMC-21 in the 110 kV control building via fibres running between
the two buildings. Twin 62.5/125m ST-ST terminated fibre patch leads shall be used
(length as required)
17.6. 1 No. Ethernet to fibre converters shall be supplied. (MOXA IMC-21-M-ST). One will be
installed in the disturbance recorder cabinet in the 110 kV control building and will be
connected to the MOXA EDS205A-M-ST via fibres running between the two control
buildings.

18. Disturbance Recorder

18.1. 2 No. eMS sub.net disturbance recorders will be supplied by EirGrid. Each recorder will be
ordered with, wedding ring interposing current transformers, GPS time synchronisation
and 2 analogue modules (6 voltage and 6 current inputs). One recorder will be installed
in the Disturbance Recorder cabinet in the 220 kV control building and the other installed
in the Disturbance Recorder cabinet in the 110 kV control building.
18.2. CT connections from Knockanure 220 kV and Ballyvouskil 220 kV shall be presented in the
220 kV disturbance recorder cabinet. CT connections should be presented on URTK-SP
- 11 -

18.3.

18.4.

18.5.

18.6.

phoenix type terminals with a 300mm loop of wire threaded through the interposing
wedding ring type CT. The interposing wedding ring type CT shall be DIN rail mounted.
VT connections from Knockanure 220 kV and Ballyvouskil 220 kV shall be presented in the
220 kV disturbance recorder cabinet. Provide a connection to the VT secondary circuits
via sets of dedicated 1A fuses. VT connections should be presented using URTK-S type
phoenix connectors to allow connection via shrouded 4mm test plugs.
CT connections from Cordal 110 kV and Glenlara 110 kV shall be presented in the 110 kV
disturbance recorder cabinet. CT connections should be presented on URTK-SP phoenix
type terminals with a 300mm loop of wire threaded through the interposing wedding ring
type CT. The interposing wedding ring type CT shall be din rail mounted.
VT connections from Cordal 110 kV and Glenlara 110 kV shall be presented in the 110 kV
disturbance recorder cabinet. Provide a connection to the VT secondary circuits via sets
of dedicated 1A fuses. VT connections should be presented using URTK-S type phoenix
connectors to allow connection via shrouded 4mm test plugs.
ESBT to provide analogue GPS signals to bothe disturbance recorder cabinets. Any GPS
antenna used should be installed on an outside wall, should have a clear view of the sky
and not be overshadowed. Such an antenna should have a surge arrester installed
where the antenna coaxial cable enters the building and must be adequately earthed.
The coaxial cable should be terminated with TNC type plugs and supplied to each of the
disturbance recorders in the two disturbance recorder cabinets.

19. Remote Interrogation

19.1. Remote interrogation shall be provided to all Siemens distance and multifunction relays.
19.2. 1 No. Moxa NPort 5110 Ethernet to serial converter shall be supplied with DIN rail mount.
19.3. 1 No. Siemens RS232 Digsi cable (7XV5100-4 /BB) shall be supplied to connect the Moxa
5110 and the first mini star coupler.
19.4. 5 No. Siemens Mini Star Couplers shall be supplied (7XV5450-0BA00/BB)
19.5. 3 No. Twin 62.5/125m ST-ST terminated 1m fibre patch leads shall be provided to
cascade the mini star couplers.
19.6. 13 No. Siemens FO - RS485 converter shall be supplied to connect the fibre to the rear
port RS485 on a version 4 Siemens relay (7XV5650-0BA00/BB).
19.7. 13 No. Siemens RS485 male to male leads (7XV5103-1AAxx) shall be supplied to connect
the Siemens FO to Serial converter and the rear service port C on Siemens V4 Relay.
19.8. 7 No. Twin 62.5/125m ST-ST terminated fibre patch leads shall be provided (length as
required) to connect the mini star coupler to the following 220 kV bay relays:
Coupler K1 220 kV 7SJ611,
Ballyvouskil 220 kV 7SA612,
Knockanure 220 kV 7SA612,
Coupler K2 220 kV 7SJ611,
SA 1-2 220 kV 7SJ611,
T2102 220 kV 7SA612.
SB 1-2 220 kV 7SJ611,
19.9. 6 No. Twin 62.5/125m ST-ST terminated fibre patch leads shall be provided (length as
required) to connect the mini star coupler to the following 110 kV bay relays:
Coupler K1 110 kV 7SJ611,
Cordal 110 kV 7SA612,
SA 1-2 110 kV 7SJ611,
Coupler K2 110 kV 7SJ611,
SB 1-2 110 kV 7SJ611,
T2102 110 kV 7SA612.
19.10.
2 No. Twin 62.5/125m ST-ST terminated fibre patch leads (length as required) shall
be run between the Disturbance Recorder cabinet in the 220 kV control room and the
Disturbance Recorder cabinet in the 110 kV control room.
19.11.
Fibre should be run to all spare/future bays where cabinets are in place. If cabinets
are not in place, fibres should be ordered and run at a later stage.

- 12 -

20. Time Synchronisation

20.1. All Siemens V4 and Toshiba protection relays to be provided with IRIG-B time
synchronisation from a dedicated GPS-synchronised time source. In the case of
distributed SCS stations the SCS clock is acceptable (no additional work), but in
centralised stations a suitable dedicated clock (e.g. Hopf 6875, Siemens Order Code #
7XV5664-0AA00) GPS antenna, and surge arrestor (e.g. Hopf 4495, Siemens Order Code #
7XV5664-0LA00)should be installed. The clock should provide IRIG-B time synchronisation
to the relays as follows:
SiemensV4 relays - These relays have a dedicated 9pin DSub serial port on the
backpane. The optical output of the GPS clock should be connected via a twin
62.5/125 m ST-ST terminated fibre patch lead to the Siemens Time Sync
transceiver (Order Code # 7XV5654-0BA00). The RS485 output of the time sync
transceiver is connected in daisy-chain fashion to all the Siemens relays using
Siemens cable 7XV5104-0AAxx.
Toshiba relays - These relays have dedicated BNC (coaxial) ports on the backpane.
The BNC output of the clock should be connected in a daisy-chain fashion to all
Toshiba GRL100 and GRZ100 relays using standard coaxial cable. A BNC Tconnector should be used to connect the coaxial cable daisy-chain to each
relay.

- 13 -

Siemens

Hardware Required

General

6 7 8 9

1 2 3 4 5

6 7 8 9

1 2 3 4 5

Note:
Fibres to spare bays and trafos should be run if there are cabinets in place for these bays. If not than these fibres can be
left unrun.

6 7 8 9

1 2 3 4 5

Fibres are available from Wood Communications (http://www.woodcomm.ie)

5 4 3 2 1

9 8 7 6

+Vin
+OC3
+OC2
+OC1

CLK

X1

IRIGB/
DCF77Out

GPSIn
hopf6875

Vin
OC3
OC2
OC1

C1C3

DEF

FL1

FL2

X2

GPSTimingSignalReceiver,
Model#:7XV56640AA00

SignalFromGPSTimeSource
(FL2)

TimeSyncTransceiver,
Model#:7XV56640BA00

Siemens

Hardware

X1
DSub

Shouldtherebeinexcessof12devices,aMiniStarcouplerisrequired.7XV54500BA00(withSTconnectors)
Upto48devicescanbeconnectedwith4SyncTransceivers,4TAdaptersand1MiniStarcoupler
RefertoTimeSyncTransceiverandMiniStarcouplerManualsforcorrectDIPswitchsettings.

Notes:
a.
1No.SyncTransceiverRequiredforEVERY12devicesconencted.
(Note:TCableAdapterRequiredwhenmorethan6devicesconnected.7XV51043AA00)
BNCTConnectorstobeusedwhendaisychainingToshibadevices.
RefertodevicedocumentationregardingoutputprotocolforFL1andFL2.

b.
c.
d.
e.
f.

ToSyncTransceiver#1
ToSyncTransceiver#2

ToSyncTransceiver#3
ToSyncTransceiver#4

Toshiba

Siprotec4
PortA

BNCTConnector

IRIGBBNC
Connection

Siemens

YBusCable,Model#:7XV51040AAxx

Toshiba

BNCTConnector

IRIGBBNC
Connection

Siemens

Siprotec4
PortA

YBusCable,Model#:7XV51040AAxx

Toshiba

IRIGBBNC
Connection

Siemens

Siprotec4
PortA

BusExtensionCable,Model#:7XV51041AAxx

21. NCC Signal List - Ballynahulla

Bay
Knockanure 220 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA POTT RX
7SA POTT TX
7SA TRIP 1P
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX
GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
GRL TRIP 1P
Carrier Fail
Device FAIL
AR BLK Rx

GRL100

PLC Interface
ABB TEBIT

- 14 -

Bay
Ballyvouskill 220 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA POTT RX
7SA POTT TX
7SA TRIP 1P
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX
GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
GRL TRIP 1P
Carrier Fail
Device FAIL
AR BLK Rx

GRL100

PLC Interface
ABB TEBIT

Bay
220 kV SCB SA1-2

Relay
7SJ611

220 kV SCB SB1-2

7SJ611

220 kV Coupler K1

7SJ611

220 kV Coupler K2

7SJ611

NCC Text
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP

- 15 -

Bay
T2102

Relay
7SA612 220 kV

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA REVERSE PU
7SA T2 EXPIRED
7SA FWD TRIP
7SA REV TRIP
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA REVERSE PU
7SA T2 EXPIRED
7SA FWD TRIP
7SA REV TRIP
RET DIFF TRIP
RET REF TRIP
RET RELAY FAIL

7SA612 110 kV

RET670

- 16 -

Bay
BZP/CBF Protection
220kV

Relay

NCC Signal Text


GRB100 INSP/MTCE SWITCH
KNOCKANURE
GRB100 INSP/MTCE SWITCH
BALLYVOUSKILL
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH COUPLER
K1
GRB100 INSP/MTCE SWITCH COUPLER
K2
GRB100 INSP/MTCE SWITCH SA1-2
GRB100 INSP/MTCE SWITCH SB1-2
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH T2102
GRB100 BBP OFF (COMMON)
GRB100 CBF OFF (COMMON)
GRB100 TRIPS BLKED (COMMON)
GRB100 OPEN CT (COMMON)
GRB100 OUT OF SERV (PER BAY)
GRB100 CBF RETRIP (PER BAY)
GRB100 CBF BB TRIP (PER BAY)
GRB100 ZONE TRIP (PER BAY)
GRB100 CB FAULTY (PER BAY)

GRB100

GRB100

- 17 -

Bay
Cordal 110 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA SPS Operation
7SA POTT RX
7SA POTT TX
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX
GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
Device FAIL
AR BLK Rx

GRL100

ABB TEBIT

Bay
110 kV SCB SA1-2

Relay
7SJ611

110 kV SCB SB1-2

7SJ611

110 kV Coupler K1

7SJ611

110 kV Coupler K2

7SJ611

NCC Text
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP

- 18 -

Bay
BZP/CBF Protection
110kV

Relay

NCC Signal Text

GRB100

GRB100 INSP/MTCE SWITCH SPARE


GRB100 INSP/MTCE SWITCH CORDAL
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH COUPLER
K1
GRB100 INSP/MTCE SWITCH COUPLER
K2
GRB100 INSP/MTCE SWITCH SA1-2
GRB100 INSP/MTCE SWITCH SB1-2
GRB100 INSP/MTCE SWITCH SPARE
GRB100 INSP/MTCE SWITCH T2102
GRB100 BBP OFF (COMMON)
GRB100 CBF OFF (COMMON)
GRB100 TRIPS BLKED (COMMON)
GRB100 OPEN CT (COMMON)
GRB100 OUT OF SERV (PER BAY)
GRB100 CBF RETRIP (PER BAY)
GRB100 CBF BB TRIP (PER BAY)
GRB100 ZONE TRIP (PER BAY)
GRB100 CB FAULTY (PER BAY)

GRB100

Bay
CONTROLLED SYNC
SCHEME

Relay
Siemens SCS or ABB
SYNCHROTACT 5

NCC Signal Text


CONTROLLED SYNC MODE SELECTED
VOLTAGES MATCHED
FREQUENCIES MATCHED
SLIP WITHIN TOLERANCE
PHASE ANGLES MATCHED
SYNC RELAY CLOSE COMMAND
SYNC RELAY FAIL

- 19 -

Ballynahulla SPS PI & Command list


Bay

Relay

NCC Text

Cordal

SPS Commands

SPS ON COMMAND
SPS OFF COMMAND

SPS Position Indication

SPS ON
SPS OFF

SPS sub remote control


indication

SPS SUB RC ON
SPS SUB RC OFF

22. NCC Signal List - Knockanure

As Specified in CP0500

23. NCC Signal List Ballyvouskill

As Specified in CP0650

- 20 -

CP0651 Ballynahulla 220 kV Station

Version
1.0

Dated
06-Feb-12

Modifications
First Issue

2.0

26-Mar-12

3.0

13-Sep-13

Station name change to Ballynahulla


Removal of Glenlara signals, now a spare bay
T2101 added as per revised SLD

4.0

13-Feb-14

T2101 removed as per revised SLD

Prepared By
Ray Dorney
Ray Doyle
Ray Dorney
Ray Doyle
Ray Dorney
Miriam Ryan (PSP&M)
Ray Dorney
Miriam Ryan (PSP&M)

Ballynahulla 220 kV SCS GIS Station

SIGNAL LIST

4.0

13-Feb-14

Based on: XDN-SLD-CP651-F-BYH-001 Rev06 10/01/2014

XDN-SLD-CP651-FBYH-001 Rev 06

Digital Input Signals (to EirGrid)


Double Point Status Indications (P.I)

To be provided By:

Comment

(each individual input identified separately for clarity)

220 kV Busbar
In Ballynahulla 220 kV Station, on the 220 kV Sectionaliser SA1-2 Bay (F0A):
220kV SA1-2 CB
220kV SA1-2 CB
220kV Sectionaliser SA1-2 SA1
220kV Sectionaliser SA1-2 SA1
220kV Sectionaliser SA1-2 SA2
220kV Sectionaliser SA1-2 SA2

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

220kV Sectionaliser SA1-2 CB Direct/Synch


220kV Sectionaliser SA1-2 CB Controlled Synch OFF/Controlled Synch ON

Direct/Synch double bit


off/on (double bit)

ESB Networks
ESB Networks

220kV Sectionaliser SA1-2 Bay Sub Remote Control Switch


220kV Sectionaliser SA1-2 Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

220kV Sectionaliser SA1-2 NCC/Local Switch


220kV Sectionaliser SA1-2 NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Sectionaliser SB1-2 Bay (F0B):


220kV SB1-2 CB
220kV SB1-2 CB
220kV Sectionaliser SB1-2 SB1
220kV Sectionaliser SB1-2 SB1
220kV Sectionaliser SB1-2 SB2
220kV Sectionaliser SB1-2 SB2

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

220kV Sectionaliser SB1-2 Bay CB Direct/Synch


220kV Sectionaliser SB1-2 CB Controlled Synch OFF/Controlled Synch ON

Direct/Synch double bit


off/on (double bit)

ESB Networks
ESB Networks

220kV Sectionaliser SB1-2 Bay Sub Remote Control Switch


220kV Sectionaliser SB1-2 Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

220kV Sectionaliser SB1-2 NCC/Local Switch


220kV Sectionaliser SB1-2 NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the Knockanure 220 kV Bay (F1):


Knockanure 220kV DA
Knockanure 220kV DA
Knockanure 220kV DB
Knockanure 220kV DB
Knockanure 220kV CB
Knockanure 220kV CB
Knockanure 220kV DL
Knockanure 220kV DL
Knockanure 220kV DE
Knockanure 220kV DE

open
closed
open
closed
open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Knockanure CB Bay Direct/Synch

Direct/Synch double bit

ESB Networks

Each 220 kV bay will have a direct/synch in an


SCS station

Knockanure 220kV CB Controlled Synch OFF/Controlled Synch ON

off/on (double bit)

ESB Networks

When in the ON position Synch/Direct mode is


disabled on the bay

Knockanure 220kV Bay Sub Remote Control Switch


Knockanure 220kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

Knockanure 220kV NCC/Local Switch


Knockanure 220kV NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

Knockanure 220kV Bay Auto Reclosing


Knockanure 220kV Bay Auto Reclosing

off
on

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the T2102 220 kV Bay (F2):


T2102 220kV DA
T2102 220kV DA
T2102 220kV DB
T2102 220kV DB
T2102 220kV CB
T2102 220kV CB

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

T2102 220kV Bay Sub Remote Control Switch


T2102 220kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

T2102 220kV NCC/Local Switch


T2102 220kV NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

T2102 OLTC Local/Remote Control Switch (Tap)


T2102 OLTC Local/Remote Control Switch (Tap)

off (Local)
on (Remote)

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the Ballyvouskill 220 kV Bay (F4):


Ballyvouskill 220kV DA
Ballyvouskill 220kV DA
Ballyvouskill 220kV DB
Ballyvouskill 220kV DB
Ballyvouskill 220kV CB
Ballyvouskill 220kV CB
Ballyvouskill 220kV DL
Ballyvouskill 220kV DL
Ballyvouskill 220kV DE
Ballyvouskill 220kV DE

open
closed
open
closed
open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Ballyvouskill CB Bay Direct/Synch

Direct/Synch double bit

ESB Networks

Ballyvouskill 220kV CB Controlled Synch OFF/Controlled Synch ON

off/on (double bit)

ESB Networks

Ballyvouskill 220kV Bay Sub Remote Control Switch


Ballyvouskill 220kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

Ballyvouskill 220kV NCC/Local Switch


Ballyvouskill 220kV NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

Ballyvouskill 220kV Bay Auto Reclosing


Ballyvouskill 220kV Bay Auto Reclosing

off
on

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Coupler K1 Bay (F9):


220kV K1 DA
220kV K1 DA
220kV K1 DB
220kV K1 DB
220kV K1 CB
220kV K1 CB

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

220kV K1 CB Direct/Synch
220kV K1 CB Controlled Synch OFF/Controlled Synch ON

Direct/Synch double bit


off/on (double bit)

ESB Networks
ESB Networks

K1 220kV Bay Sub Remote Control Switch


K1 220kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

K1 220kV Bay NCC/Local Switch


K1 220kV Bay NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Coupler K2 Bay (F10):

PSOP (Ballynahulla)

When in the ON position Synch/Direct mode is


disabled on the bay

This is a common PI from all the control


switches on the bay

When in the ON position Synch/Direct mode is


disabled on the bay

This is a common PI from all the control


switches on the bay

Each 220 kV bay will have a direct/synch in an


SCS station
When in the ON position Synch/Direct mode is
disabled on the bay

When in the ON position Synch/Direct mode is


disabled on the bay

This is a common PI from all the control


switches on the bay

220kV K2 DA
220kV K2 DA
220kV K2 DB
220kV K2 DB
220kV K2 CB
220kV K2 CB

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

220kV K2 CB Direct/Synch
220kV K2 CB Controlled Synch OFF/Controlled Synch ON

Direct/Synch double bit


off/on (double bit)

ESB Networks
ESB Networks

K2 220kV Bay Sub Remote Control Switch


K2 220kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

K2 220kV Bay NCC/Local Switch


K2 220kV Bay NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SA1-2 Bay (H0A):


110kV SA1-2 CB
110kV SA1-2 CB
110kV Sectionaliser SA1-2 SA1
110kV Sectionaliser SA1-2 SA1
110kV Sectionaliser SA1-2 SA2
110kV Sectionaliser SA1-2 SA2

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

110kV Sectionaliser SA1-2 CB Direct/Synch

Direct/Synch double bit

ESB Networks

110kV Sectionaliser SA1-2 Bay Sub Remote Control Switch


110kV Sectionaliser SA1-2 Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

110kV Sectionaliser SA1-2 NCC/Local Switch


110kV Sectionaliser SA1-2 NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SB1-2 Bay (H0B):


110kV SB1-2 CB
110kV SB1-2 CB
110kV Sectionaliser SB1-2 SB1
110kV Sectionaliser SB1-2 SB1
110kV Sectionaliser SB1-2 SB2
110kV Sectionaliser SB1-2 SB2

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

110kV Sectionaliser SB1-2 CB Direct/Synch

Direct/Synch double bit

ESB Networks

110kV Sectionaliser SB1-2 Bay Sub Remote Control Switch


110kV Sectionaliser SB1-2 Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

110kV Sectionaliser SB1-2 NCC/Local Switch


110kV Sectionaliser SB1-2 NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the T2102 110 kV Bay (H2):


T2102 110kV DA
T2102 110kV DA
T2102 110kV DB
T2102 110kV DB
T2102 110kV CB
T2102 110kV CB
T2102 110kV Neutral Earth
T2102 110kV Neutral Earth

open
closed
open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

T2102 110kV Bay Sub Remote Control Switch


T2102 110kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

T2102 110kV NCC/Local Switch


T2102 110kV NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the Cordal 110 kV Bay (H4):


Cordal 110kV DA
Cordal 110kV DA
Cordal 110kV DB
Cordal 110kV DB
Cordal 110kV CB
Cordal 110kV CB
Cordal 110kV DL
Cordal 110kV DL
Cordal 110kV DE
Cordal 110kV DE

open
closed
open
closed
open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Cordal 110kV CB Direct/Synch

Direct/Synch double bit

ESB Networks

Cordal 110kV Bay Sub Remote Control Switch


Cordal 110kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

Cordal 110kV NCC/Local Switch


Cordal 110kV NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

Cordal 110kV Bay Auto Reclosing


Cordal 110kV Bay Auto Reclosing

off
on

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Coupler K1 Bay (H9):


110kV K1 DA
110kV K1 DA
110kV K1 DB
110kV K1 DB
110kV K1 CB
110kV K1 CB

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

110kV K1 CB Direct/Synch

Direct/Synch double bit

ESB Networks

K1 110kV Bay Sub Remote Control Switch


K1 110kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

K1 110kV Bay NCC/Local Switch


K1 110kV Bay NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Coupler K2 Bay (H10):


110kV K2 DA
110kV K2 DA
110kV K2 DB
110kV K2 DB
110kV K2 CB
110kV K2 CB

open
closed
open
closed
open
closed

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

110kV K2 CB Direct/Synch

Direct/Synch double bit

ESB Networks

K2 110kV Bay Sub Remote Control Switch


K2 110kV Bay Sub Remote Control Switch

off (Local)
on (Remote)

ESB Networks
ESB Networks

K2 110kV Bay NCC/Local Switch


K2 110kV Bay NCC/Local Switch

Local
NCC

ESB Networks
ESB Networks

Miscellaneous Double Point Status Indications (P.I)


220kV Station Blue Alert
220kV Station Blue Alert
220kV Station Blue Alert Acknowledge
220kV Station Blue Alert Acknowledge

off
on
off
on

ESB Networks
ESB Networks
ESB Networks
ESB Networks

Station Local/Remote Control switch (Master)


Station Local/Remote Control switch (Master)

off (Local)
on (Remote)

ESB Telecoms
ESB Telecoms

Remote Control Test Command


Remote Control Test Command

off
on

ESB Telecoms
ESB Telecoms

Single Point Status Indications


Pre-Switch Siren

off/on (single bit)

ESB Networks

When in the ON position Synch/Direct mode is


disabled on the bay

This is a common PI from all the control


switches on the bay

110 kV Busbar

Analogue Input Signals (to EirGrid)

To be provided by:

PSOP (Ballynahulla)

This is a common PI from all the control


switches on the bay

This is a common PI from all the control


switches on the bay

This is a common PI from all the control


switches on the bay

This is a common PI from all the control


switches on the bay

220 kV Busbar
In Knockanure 220 kV Station, on the 220 kV Sectionaliser SA1-2 Bay (F0A):
220kV Sectionaliser SA1-2 Amps
220kV Sectionaliser SA1-2 MW

0 - 3500
-1600 - 0 - +1600

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

220kV Sectionaliser SA1-2 MVAr

-800 -0 - +800

0.5/100

MVAr

ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay

220kV Sectionaliser SA1-2 MVA

-1600 - 0 - +1600

0.5/100

MVA

ESB Networks

Only MVA should be displayed on EMS

In Ballynahulla 220 kV Station, on the 220 kV Sectionaliser SB1-2 Bay (F0B):


220kV Sectionaliser SB1-2 Amps
220kV Sectionaliser SB1-2 MW

0 - 3500
-1600 - 0 - +1600

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

220kV Sectionaliser SB1-2 MVAr

-800 -0 - +800

0.5/100

MVAr

ESB Networks

220kV Sectionaliser SB1-2 MVA

-1600 - 0 - +1600

0.5/100

MVA

ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay
Only MVA should be displayed on EMS

In Ballynahulla 220 kV Station, on the Knockanure 220 kV Bay (F1):


Knockanure 220kV kV
Knockanure 220kV MW
Knockanure 220kV MVAr
Knockanure 220kV Amps

0 - 264
-1600 - 0 - +1600
-800 -0 - +800
0 - 2500

0.5/100
0.5/100
0.5/100
0.5/100

kV
MW
MVAr
Amps

ESB Networks
ESB Networks
ESB Networks
ESB Networks

A single phase will suffice

0 - 264
-600 - 0 - +600
-300 -0 - +300
0 - 1000

0.5/100
0.5/100
0.5/100
0.5/100

kV
MW
MVAr
Amps

ESB Networks
ESB Networks
ESB Networks
ESB Networks

A single phase will suffice

0 - 17

1/100

Taps

ESB Networks

In Ballynahulla 220 kV Station, on the Ballyvouskill 220 kV Bay (F4):


Ballyvouskill 220kV kV
Ballyvouskill 220kV MW
Ballyvouskill 220kV MVAr
Ballyvouskill 220kV Amps

0 - 264
-1600 - 0 - +1600
-800 -0 - +800
0 - 2500

0.5/100
0.5/100
0.5/100
0.5/100

kV
MW
MVAr
Amps

ESB Networks
ESB Networks
ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Coupler K1 Bay (F9):


220kV Coupler K1 Amps
220kV Coupler K1 MW

0 - 3500
-1600 - 0 - +1600

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

220kV Coupler K1 MVAr

-800 -0 - +800

0.5/100

MVAr

ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay

220kV Coupler K1 MVA

-1600 - 0 - +1600

0.5/100

MVA

ESB Networks

Only MVA should be displayed on EMS

In Ballynahulla 220 kV Station, on the 220 kV Coupler K2 Bay (F10):


220kV Coupler K2 Amps
220kV Coupler K2 MW

0 - 3500
-1600 - 0 - +1600

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

220kV Coupler K2 MVAr

-800 -0 - +800

0.5/100

MVAr

ESB Networks

220kV Coupler K2 MVA

-1600 - 0 - +1600

0.5/100

MVA

ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SA1-2 Bay (H0A):


110kV SA1-2 Amps
110kV SA1-2 MW

0 - 2500
-570 - 0 - +570

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

110kV SA1-2 MVAr

-285 -0 - +285

0.5/100

MVAr

ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay

110kV SA1-2 MVA

-570 - 0 - +570

0.5/100

MVA

ESB Networks

Only MVA should be displayed on EMS

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SB1-2 Bay (H0B):


110kV SB1-2 Amps
110kV SB1-2 MW

0 - 2500
-570 - 0 - +570

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

110kV SB1-2 MVAr

-285 -0 - +285

0.5/100

MVAr

ESB Networks

110kV SB1-2 MVA

-570 - 0 - +570

0.5/100

MVA

ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay
Only MVA should be displayed on EMS

In Ballynahulla 220 kV Station, on the T2102 110 kV Bay (H2):


T2102 110kV kV
T2102 110kV MW
T2102 110kV MVAr
T2102 110kV Amps

0 - 132
-450 - 0 - +450
-225 -0 - +225
0 - 2000

1/100
0.5/100
0.5/100
0.5/100

kV
MW
MVAr
Amps

ESB Networks
ESB Networks
ESB Networks
ESB Networks

A single phase will suffice

In Ballynahulla 220 kV Station, on the Cordal 110 kV Bay (H4):


Cordal 110kV kV
Cordal 110kV MW
Cordal 110kV MVAr
Cordal 110kV Amps

0 - 132
-285- 0 - +285
-140 -0 - +140
0 - 1250

1/100
0.5/100
1/100
0.5/100

kV
MW
MVAr
Amps

ESB Networks
ESB Networks
ESB Networks
ESB Networks

A single phase will suffice

In Ballynahulla 220 kV Station, on the 110 kV Coupler K1 Bay (H9):


110kV K1 Amps
110kV K1 MW

0 - 2500
-570 - 0 - +570

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

110kV K1 MVAr

-285 -0 - +285

0.5/100

MVAr

ESB Networks

110kV K1 MVA

-570 - 0 - +570

0.5/100

MVA

ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Coupler K2 Bay (H10):


110kV K2 Amps
110kV K2 MW

0 - 2500
-570 - 0 - +570

0.5/100
0.5/100

Amps
MW

ESB Networks
ESB Networks

110kV K2 MVAr

-285 -0 - +285

0.5/100

MVAr

ESB Networks

110kV K2 MVA

-570 - 0 - +570

0.5/100

MVA

ESB Networks

In Ballynahulla 220 kV Station, on the T2102 220 kV Bay (F2):


T2102 220kV kV
T2102 220kV MW
T2102 220kV MVAr
T2102 220kV Amps
T2102 Tap Position

4-20

mA

A single phase will suffice

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay
Only MVA should be displayed on EMS

110 kV Busbar

Digital Output Signals (from EirGrid)


Double Command Outputs (Remote Control)

To be provided to:
(each individual relay output identified separately)

220 kV Busbar
In Ballynahulla 220 kV Station, on the 220 kV Sectionaliser SA1-2 Bay (F0A):
220kV SA1-2 CB
220kV SA1-2 CB
220kV Sectionaliser SA1-2 SA1
220kV Sectionaliser SA1-2 SA1
220kV Sectionaliser SA1-2 SA2
220kV Sectionaliser SA1-2 SA2

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

220kV Sectionaliser SA1-2 CB Direct/Synch

Direct/Synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Sectionaliser SB1-2 Bay (FBA):


220kV SB1-2 CB
220kV SB1-2 CB
220kV Sectionaliser SB1-2 SB1
220kV Sectionaliser SB1-2 SB1
220kV Sectionaliser SB1-2 SB2
220kV Sectionaliser SB1-2 SB2

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

220kV Sectionaliser SB1-2 CB Direct/Synch

Direct/Synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the Knockanure 220 kV Bay (F1):


Knockanure 220kV DA
Knockanure 220kV DA
Knockanure 220kV DB
Knockanure 220kV DB
Knockanure 220kV CB
Knockanure 220kV CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

Knockanure Bay CB Direct/Synch

Direct/Synch double bit

pulse

0.5 second ESB Networks

Knockanure 220kV Auto Reclosing


Knockanure 220kV Auto Reclosing

off
on

pulse
pulse

0.5 second ESB Networks


0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the T2102 220 kV Bay (F2):


T2102 220kV DA

open

pulse

0.5 second ESB Networks

PSOP (Ballynahulla)

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay
Only MVA should be displayed on EMS

The SCS should be programmed to perform


this calculation using a voltage from a suitable
line bay
Only MVA should be displayed on EMS

T2102 220kV DA
T2102 220kV DB
T2102 220kV DB
T2102 220kV CB
T2102 220kV CB

closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

T2102 Tap Lower


T2102 Tap Raise

lower
raise

pulse
pulse

0.5 second ESB Networks


0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the Ballyvouskill 220 kV Bay (F4):


Ballyvouskill 220kV DA
Ballyvouskill 220kV DA
Ballyvouskill 220kV DB
Ballyvouskill 220kV DB
Ballyvouskill 220kV CB
Ballyvouskill 220kV CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

Ballyvouskill Bay CB Direct/Synch

Direct/Synch double bit

pulse

0.5 second ESB Networks

Ballyvouskill 220kV Auto Reclosing


Ballyvouskill 220kV Auto Reclosing

off
on

pulse
pulse

0.5 second ESB Networks


0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Coupler K1 Bay (F9):


220kV K1 DA
220kV K1 DA
220kV K1 DB
220kV K1 DB
220kV K1 CB
220kV K1 CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

220kV K1 CB Direct/Synch

direct/synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 220 kV Coupler K2 Bay (F10):


220kV K2 DA
220kV K2 DA
220kV K2 DB
220kV K2 DB
220kV K2 CB
220kV K2 CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

220kV K2 CB Direct/Synch

direct/synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SA1-2 Bay (H0A):


110kV SA1-2 CB
110kV SA1-2 CB
110kV Sectionaliser SA1-2 SA1
110kV Sectionaliser SA1-2 SA1
110kV Sectionaliser SA1-2 SA2
110kV Sectionaliser SA1-2 SA2

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

110kV Sectionaliser SA1-2 Bay CB Direct/Synch

Direct/Synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Sectionaliser SB1-2 Bay (H0B):


110kV SB1-2 CB
110kV SB1-2 CB
110kV Sectionaliser SB1-2 SB1
110kV Sectionaliser SB1-2 SB1
110kV Sectionaliser SB1-2 SB2
110kV Sectionaliser SB1-2 SB2

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

110kV Sectionaliser SB1-2 Bay CB Direct/Synch

Direct/Synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the T2102 110 kV Bay (H2):


T2102 110kV DA
T2102 110kV DA
T2102 110kV DB
T2102 110kV DB
T2102 110kV CB
T2102 110kV CB
T2102 110kV Neutral Earth Switch
T2102 110kV Neutral Earth Switch

open
closed
open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

In Ballynahulla 220 kV Station, on the Cordal 110 kV Bay (H4):


Cordal 110kV DA
Cordal 110kV DA
Cordal 110kV DB
Cordal 110kV DB
Cordal 110kV CB
Cordal 110kV CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Cordal 110 kV CB Direct/Synch

direct/synch

pulse

0.5 second ESB Networks

Cordal 110kV Bay Auto Reclosing


Cordal 110kV Bay Auto Reclosing

off
on

pulse
pulse

0.5 second ESB Networks


0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Coupler K1 Bay (H9):


110kV K1 DA
110kV K1 DA
110kV K1 DB
110kV K1 DB
110kV K1 CB
110kV K1 CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

110kV K1 CB Direct/Synch

direct/synch

pulse

0.5 second ESB Networks

In Ballynahulla 220 kV Station, on the 110 kV Coupler K2 Bay (H10):


110kV K2 DA
110kV K2 DA
110kV K2 DB
110kV K2 DB
110kV K2 CB
110kV K2 CB

open
closed
open
closed
open
closed

pulse
pulse
pulse
pulse
pulse
pulse

0.5 second
0.5 second
0.5 second
0.5 second
0.5 second
0.5 second

110kV K2 CB Direct/Synch

direct/synch

pulse

0.5 second ESB Networks

Miscellaneous Double Command Outputs (Remote Control)


220kV Station Blue Alert
220kV Station Blue Alert

off
on

pulse
pulse

0.5 second ESB Networks


0.5 second ESB Networks

Remote Control Test Command


Remote Control Test Command

off
on

pulse
pulse

0.5 second ESB Telecoms


0.5 second ESB Telecoms

Single Command Outputs


Pre-Switch Siren On

on

pulse

0.5 seconds ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

110 kV Busbar
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Analogue Output Signals (from EirGrid)


None
General Station Monitoring

Ganged Signal Title

To be Provided By:

All single bit signals (only new signals listed)


Non Protection alarms
SA1-2 220kV CB LOW SF6 Gas Pressure
SA1-2 220kV CB Pole discrepancy Trip.
SA1-2 220kV CB Insufficient SF6 - CB OP blocked
SA1-2 220kV CB SF6 Lockout - CB Op Blocked
SA1-2 220kV CB Mech box fault
SA1-2 220 kV Interlock bypassed switch
SA1-2 220 kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
SA1-2 220 kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

SB1-2 220kV CB LOW SF6 Gas Pressure


SB1-2 220kV CB Pole discrepancy Trip.
SB1-2 220kV CB Insufficient SF6 - CB OP blocked
SB1-2 220kV CB SF6 Lockout - CB Op Blocked

off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks

PSOP (Ballynahulla)

This will time out after 30 seconds

SB1-2 220kV CB Mech box fault


SB1-2 I220 kV interlock bypassed switch
SB1-2 220 kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
SB1-2 220 kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks

Knockanure 220kV CB LOW SF6 Gas Pressure


Knockanure 220kV CB Pole discrepancy Trip.
Knockanure 220kV CB Insufficient SF6 - CB OP blocked
Knockanure 220kV CB SF6 Lockout - CB Op Blocked
Knockanure 220kV CB Mech box fault
Knockanure I220 kV interlock bypassed switch
Knockanure 220 kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
Knockanure 220 kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

T2102 220kV CB LOW SF6 Gas Pressure


T2102 220kV CB SF6 Lockout - CB Op blocked
T2102 220kV CB Insufficient SF6 - CB Op Blocked
T2102 220kV CB Pole discrepancy Trip.
T2102 220kV CB Mech box fault
T2102 220kV Interlock bypassed switch
T2102 110kV CB LOW SF6 Gas Pressure
T2102 110kV CB SF6 Lockout - CB Op Blocked
T2102 110kV CB Insufficient SF6 - CB Op Blocked
T2102 110kV CB Mech box fault
T2102 110kV Interlock bypassed switch
T2102 SCS - BCU Internal Fault/Comms Fail to Prot. Device
T2102 SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

T2102 Tap Change in Progress


T2102 Oil Temp Alarm
T2102 Oil Temp Trip
T2102 Low Oil Alarm
T2102 Winding Temp Alarm
T2102 Winding Temp Trip
T2102 Buchholz Alarm
T2102 Buchholz Trip
T2102 Pressure Surge Trip
T2102 Fan Fault
T2102 Pressure Relief Alarm
T2102 Hydran Fail
T2102 Hydran Gas Alarm
T2102 Mini Trans High Gas Alarm
T2102 Mini Trans Unit Fail Alarm
T2102 OLTC Gas Pressure Alarm
T2102 OLTC Mech Box Fault

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Ballyvouskill 220kV CB LOW SF6 Gas Pressure


Ballyvouskill 220kV CB Pole discrepancy Trip.
Ballyvouskill 220kV CB Insufficient SF6 - CB OP blocked
Ballyvouskill 220kV CB SF6 Lockout - CB Op Blocked
Ballyvouskill 220kV CB Mech box fault
Ballyvouskill I220 kV interlock bypassed switch
Ballyvouskill 220 kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
Ballyvouskill 220 kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

K1 220kV CB LOW SF6 Gas Pressure


K1 220kV CB Pole discrepancy Trip.
K1 220kV CB Insufficient SF6 - CB OP blocked
K1 220kV CB SF6 Lockout - CB Op Blocked
K1 220kV CB Mech box fault
K1 220kV interlock bypassed switch
K1 220kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
K1 220kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

K2 220kV CB LOW SF6 Gas Pressure


K2 220kV CB Pole discrepancy Trip.
K2 220kV CB Insufficient SF6 - CB OP blocked
K2 220kV CB SF6 Lockout - CB Op Blocked
K2 220kV CB Mech box fault
K2 220kV interlock bypassed switch
K2 220kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
K2 220kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

SA1-2 110kV CB LOW SF6 Gas Pressure


SA1-2 110kV CB SF6 Lockout - CB Op Blocked
SA1-2 110kV CB Insufficient SF6 - CB Op Blocked
SA1-2 110kV CB Mech box fault
SA1-2 110kV Interlock bypassed switch
SA1-2 110kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
SA1-2 110kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

SB1-2 110kV CB LOW SF6 Gas Pressure


SB1-2 110kV CB SF6 Lockout - CB Op Blocked
SB1-2 110kV CB Insufficient SF6 - CB Op Blocked
SB1-2 110kV CB Mech box fault
SB1-2 110kV Interlock bypassed switch
SB1-2 110kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
SB1-2 110kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Cordal 110kV CB LOW SF6 Gas Pressure


Cordal 110kV CB SF6 Lockout - CB Op Blocked
Cordal 110kV CB Insufficient SF6 - CB Op Blocked
Cordal 110kV CB Mech box fault
Cordal 110kV Interlock bypassed switch
Cordal 110kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
Cordal 110kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

K1 110kV CB LOW SF6 Gas Pressure


K1 110kV CB SF6 Lockout - CB Op Blocked
K1 110kV CB Insufficient SF6 - CB Op Blocked
K1 110kV CB Mech box fault
K1 110kV Interlock bypassed switch
K1 110kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
K1 110kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

K2 110kV CB LOW SF6 Gas Pressure


K2 110kV CB SF6 Lockout - CB Op Blocked
K2 110kV CB Insufficient SF6 - CB Op Blocked
K2 110kV CB Mech box fault
K2 110kV Interlock bypassed switch
K2 110kV SCS - BCU Internal Fault/Comms Fail to Prot. Device
K2 110kV SCS BCU Comms Fail

off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

Station Miscellaneous Alarms


General Transmission Station Alarm
Fire Alarm
Intruder Alarm

off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks

off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

AC Board - AC MCB TRIP


220V DC Battery 1 charger No.1 fail alarm
220V DC Battery 1 charger No.2 fail alarm
220V DC Battery 1 Charger No.1 AC MCB OPEN/ TRIP
220V DC Battery 1 Charger No.2 AC MCB OPEN/ TRIP
220V DC MCB Trip (220V DC Board No.1)
220V DC Battery 1 Over Voltage
220V DC Battery 1 Earth Fault
220V DC Battery 1 Under Voltage
220V DC Battery 1 Supervisory MCB TRIP
220V DC Battery 1 Supervisory MCB OPEN
220V DC Battery 2 charger No.1 fail alarm
220V DC Battery 2 charger No.2 fail alarm
220V DC Battery 2 Charger No.1 AC MCB OPEN/ TRIP
220V DC Battery 2 Charger No.2 AC MCB OPEN/ TRIP
220V DC MCB Trip (220V DC Board No.2)
220V DC Battery 2 Over Voltage
220V DC Battery 2 Earth Fault
220V DC Battery 2 Under Voltage

Signal Ganged into a common alarm 220V DC

220V DC Battery Supervis Alarm off/on

off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

220V DC Battery Supervis Alarm off/on

PSOP (Ballynahulla)

This assumes there is 2 220V DC boards in the


station
Signal Ganged into a common alarm 220V DC

220V DC Battery Supervis Alarm off/on


220V DC Battery 2 Supervisory MCB TRIP
220V DC Battery 2 Supervisory MCB OPEN
220kV Station LT Failure
220kV Diesel Generator Fail to start Alarm
220kV Rural Supply AC MCB Open/Trip

off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks

SCS HMI PC
SCS SLC Failure
REC Relay fault
Remote Access
SCS energy supply Fail
SCS diagnostics alarms
Station logic controller (slc)
Fibre Fail GPS Fail
Bay comms Fail
Master Scada switch
Inverter fail
SCS Comms bay unit fail
SCS Comms 48V charger fault

offline/online
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on
off/on

ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks
ESB Networks

PSOP (Ballynahulla)

Outage Requirements
Are there any particular outage
difficulties (e.g. busbar outages
or line outages)?

Outage requirements are not available at this stage. An


accurate account of the difficulties associated in granting
outages for this project can not be given until a number
of stations have been energised. The outage
requirements should be requested at a later date.

If so, when can these outages


take place?

N/A

Outage Constraints

Transformer Earthing
Are the neutrals of the 220kV
transformers to be earthed?

T2102
220 kV Yes
110 kV Yes

If so is a solid earth satisfactory

T2102
220 kV - Yes
110 kV No

If not is a manual or motorised


disconnect required?

T2102
220 kV N/A
110 kV Motorised

If motorised should they be rated to


operate under load conditions?

Yes

Is a locking facility for EirGrid


required to be available on the N/E
disconnect?

Yes

Diesel Generator
Is there are a requirement for a
diesel generator in this station?

Yes

Transformer Earthing

1. NCC Signal List - Ballynahulla

Bay
Knockanure 220 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA POTT RX
7SA POTT TX
7SA TRIP 1P
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX
GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
GRL TRIP 1P
Carrier Fail
Device FAIL
AR BLK Rx

GRL100

PLC Interface
ABB TEBIT

Bay
Ballyvouskill 220 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA POTT RX
7SA POTT TX
7SA TRIP 1P
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX

GRL100

Protection

GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
GRL TRIP 1P
Carrier Fail
Device FAIL
AR BLK Rx

PLC Interface
ABB TEBIT

Bay
220 kV SCB SA1-2

Relay
7SJ611

220 kV SCB SB1-2

7SJ611

220 kV Coupler K1

7SJ611

220 kV Coupler K2

7SJ611

Bay
T2102

Relay
7SA612 220 kV

NCC Text
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA REVERSE PU
7SA T2 EXPIRED
7SA FWD TRIP
7SA REV TRIP
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA REVERSE PU
7SA T2 EXPIRED
7SA FWD TRIP
7SA REV TRIP
RET DIFF TRIP
RET REF TRIP
RET RELAY FAIL

7SA612 110 kV

RET670

Bay
BZP/CBF Protection 220kV

Relay
GRB100

NCC Signal Text


GRB100 Insp/mtce Switch Knockanure
GRB100 Insp/mtce Switch Ballyvouskill
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch Coupler K1
GRB100 Insp/mtce Switch Coupler K2

Protection

GRB100 Insp/mtce Switch SA1-2


GRB100 Insp/mtce Switch SB1-2
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch t2102
GRB100 BBP OFF (Common)
GRB100 CBF OFF (Common)
GRB100 TRIPS BLKED (Common)
GRB100 OPEN CT (Common)
GRB100 OUT OF SERV (Per Bay)
GRB100 CBF RETRIP (Per Bay)
GRB100 CBF BB TRIP (Per Bay)
GRB100 ZONE TRIP (Per Bay)
GRB100 CB FAULTY (Per Bay)

GRB100

Bay
Cordal 110 kV

Relay
7SA612

NCC Text
7SA RELAY FAIL
7SA VTMCB TRIP
7SA DIST. km
7SA DCEF RX
7SA DCEF PU
7SA DCEF REV PU
7SA DCEF TRIP
7SA DCEF TX
7SA R PHASE PU
7SA S PHASE PU
7SA T PHASE PU
7SA NEUTRAL PU
7SA RECL CMD
7SA REVERSE PU
7SA T2 EXPIRED
7SA DIST TRIP
7SA SPS Operation
7SA POTT RX
7SA POTT TX
GRL100 DIST TRIP
GRL100 DIFF TRIP
GRL RECL CMD
GRL POTT RX
GRL POTT TX
GRL COMMS FAIL
GRL RELAY FAIL
Device FAIL
AR BLK Rx

GRL100

ABB TEBIT

Bay
110 kV SCB SA1-2

Relay
7SJ611

110 kV SCB SB1-2

7SJ611

110 kV Coupler K1

7SJ611

110 kV Coupler K2

7SJ611

NCC Text
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP
7SJ RELAY FAIL
7SJ TRIP

Protection

Bay
BZP/CBF Protection 110kV

Relay
GRB100

NCC Signal Text


GRB100 Insp/mtce Switch Spare
GRB100 Insp/mtce Switch Cordal
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch spare
GRB100 Insp/mtce Switch Coupler K1
GRB100 Insp/mtce Switch Coupler K2
GRB100 Insp/mtce Switch SA1-2
GRB100 Insp/mtce Switch SB1-2
GRB100 Insp/mtce Switch SPare
GRB100 Insp/mtce Switch t2102
GRB100 BBP OFF (Common)
GRB100 CBF OFF (Common)
GRB100 TRIPS BLKED (Common)
GRB100 OPEN CT (Common)
GRB100 OUT OF SERV (Per Bay)
GRB100 CBF RETRIP (Per Bay)
GRB100 CBF BB TRIP (Per Bay)
GRB100 ZONE TRIP (Per Bay)
GRB100 CB FAULTY (Per Bay)

GRB100

Bay
Controlled Sync Scheme

Relay
Siemens SCS or ABB Synchrotact 5

NCC Signal Text


Controlled Sync mode selected
Voltages matched
Frequencies matched
Slip within tolerance
Phase angles matched
Sync relay close command
Sync relay fail

Ballynahulla SPS PI & Command list


Bay
Cordal

Relay
SPS Commands

NCC Text
SPS ON COMMAND
SPS OFF COMMAND
SPS ON
SPS OFF
SPS SUB RC ON
SPS SUB RC OFF

SPS Position Indication


SPS sub remote control indication

2. NCC Signal List - Knockanure

As Specified in CP0500
3. NCC Signal List Ballyvouskill
As Specified in CP0650

Protection

Telecoms

Telecoms

Você também pode gostar