Escolar Documentos
Profissional Documentos
Cultura Documentos
We begin with a brief review of per unit calculation used in power system analysis.
Review of Per unit Calculation and Modeling of Apparatus
Per unit value of any quantity is the ratio of that quantity to its base value.
Actual Quantity
Per Unit Quantity =
Base Quantity
Quantities like voltage, current, power, impedance etc can be expressed in per unit. In
the per-unit system there are four base quantities: base apparent power in volt-
amperes, base voltage, base current and base impedance.
The following formulae apply to three- phase system, where the base voltage is the
line-to-line voltage in volts or kilovolts and the base apparent power is the three-
phase apparent power in kilovolt – amperes or mega volt- ampere (MVA)
Base(kVA) ×1000
BaseCurrent ( Amp.) =
3 BaseVolts
Base(Volt )
Base Impedance(Ohm.) =
3 BaseCurrent
∆Va Z s Z m Z m I a
∆V = Z Z Z I
b m s m b (1)
∆Vc Z m Z m Z s I c
Applying sequence transformation ∆V1 = Z1 I1 , ∆V2 = Z 2 I 2 and ∆V0 = Z 0 I 0
Where, Z1 = Z 2 = Z s − Z m and Z 0 = Z s + 2Z m
Thus for a transposed transmission line, the positive and negative sequence
impedances are equal. A good approximation for Z 0 is 3 times Z1 .
Modeling of Mutually Coupled Lines (Sub Heading)
If a pair of 3 φ - transmission lines are for enough, then mutual coupling between them is
neglible (or zero). Fig 12.2 shows two three phase rtransmission lines running parallel and
uur uu
close to each other. As per Ampere’s law, [ Ñ ∫ Hi dl = inet ] if the lines a1 , b1 and c1 carry
balanced +ve or –ve sequence currents, flux linking in circuit 2 is zero. (
Q inet (t ) = ia (t ) + ib (t ) + ic (t ) = 0 ) However, for zero sequence currents in circuit 1, flux
linking in circuit 2 is not zero. Thus, we see for parallel coupled lines, mutual coupling is
predominantly seen only in the zero sequence circuit. However, it is not modeled for
positive and negative sequence circuits. The same result can be mathematically derived
as follows.
Consider two three phase transmission lines on the same tower. Assume that all the lines
are transposed. Then all the mutual impedances between the two circuits will be equal.
Let mutual impedance of phase a2 with phases a1 , b1 and c1 be equal to α . Then the
model of such transmission line in phase coordinates is given by,
∆v a 1 Z Z Z I a 1 I a 2
1 s m m 1 1 1
b
∆v = Z m Z s Z m I + jα 1 1 1 I b
b1 2
c1 1
∆v Z m Z m Z s I c 1 1 1 I c 2
∆v 0 1 Z + 2Z I 01 02
1 s m 3α 0 0 I
∆v1 = 11
j 0 0 0 I 1
2
Z − Z I +
21
s m
∆v Z s − Z m I 2 1 0 0 0 I 2 2
It can be seen that mutual coupling between positive and negative sequence network of
parallel transmission lines is zero. But, mutual coupling in zero sequence network is not
zero. Hence three phase faults and line to line faults will not be affected by mutual
coupling. But for all faults involving ground, fault current will be affected by mutual
coupling. This will affect the performance of relays.
With
uur uzero
u rsequence
r uu uu
r excitation, we get uu
r
φa = φb = φc = φ0 . Substitutiting in above equation we get φ0 = 0 . Thus
L0 = N φ0 I 0 = 0 .
Ideally, zero sequence impedance of an ideal core type transformer is zero.
Practically, the flux, φa , φb and φc will not be zero. Rather a leakage flux would exist
in the high reluctance path through air. Hence, leakage impedance of a core type
transformer would be nonzero; its value being much less than positive sequence
impedance.
In contrast, for a shell type transformer (fig 12.4) there exists a low reluctance path
through side limb for zero sequence flux. Hence Z 0 is much higher for shell type
transformer.
Three phase Transformer Using Bank of three Single phase Transformers (Sub’s Sub
Heading)
It can be easily argued that for such a configuration, low reluctance zero sequence
flux path exists and hence appreciable zero sequence flux can stay in the core.
Therefore, zero sequence impedance of three phase transformer bank can be as high
as the positive sequence impedance.
It should be mentioned that actual impedance should also include resistance of the
windings. So far we have discussed characterization of the zero sequence impedance
of the three phase transformer, this impedance may not always appear between the H
(HV) to L (LV) bus. In case of positive or negative sequence currents, there is always
a path for line currents from H to L through the sequence leakage impedance. This is
irrespective of the transformer connection (D/Y or Y/Y etc) because, there is always a
path for positive and negative sequence line currents to flow.
However, zero sequence currents in transformer depend not only on zero sequence
impedance but also on the type of transformer connection. For example, a star
ungrounded winding does not provide any path for flow of zero sequence current. The
neutral current is given by I n = I a + I b + I c = 3I 0 . Since neutral current is ungrounded
I n = 0 and hence I 0 is also zero. Delta winding permit circulating zero sequence
currents which cannot appear in the line. Fig. 12.5 This leads to dependence of zero
sequence transformer model on the type of connection. Fig. 12.6 shows zero sequence
modeling for different transformer connections.
N1 indicates neutral bus for positive sequence, N2 indicates neutral bus for negative
sequence and N0 for zero sequence networks.
c
v
| = | | | |
| | | | |
I abc Y abc Y anc − − − − Y abc V abc
n n1 n 2 nn n
In the above equation, each entry in the Y-matrix is itself a 3 × 3 matrix with a cyclic
T T
structure, Vi abc = Vi a ,Vi b ,Vi c ; I iabc = I ia , I ib , I ic . Vi refers to the voltage of a node
i and I i refers to the current injection at a node i. The sequence transformation on nodal
voltages can be expressed as follows:
V1abc V1012
abc [T ] 012
V2 V2
| = [T ] |
[T ]
| |
abc [T ] 012
Vn Vn
Similar transformation is defined for current vector. Thus, in the sequence coordinates,
the admittance model is given by the following equation,
I1012 T −1 Y11abc T T −1 Y12abc T − − − − T −1 Y1abc
n T V1012
012 −1 abc −1 −1
012
I 2 T Y21 T T Y22 T − − − − T Y2 n T V2
abc abc
| = | | | |
| | | | |
012 −1 abc −1 −1 012
I n T Yn1 T T Yn 2 T − − − − T Ynn T Vn
abc abc
abc
It can be seen that, if 3 × 3 matrix Yij enjoys a cyclic structure, then
Yij0
Yij012 = T −1 Yijabc T = Yij1
2
Yij
Thus, there is no coupling between the zero, positive and negative sequence components
of a balanced network because 3 × 3 matrices Yij and Yii are diagonal matrices.
012 012
By permuting the rows and columns in such a way that all the zero sequence, positive
sequence and negative sequence quantities are grouped together, a three phase admittance
matrix can be described by three decoupled sequence matrices as follows,
I bus
0
YBUS
0
Vbus
0
1 1
I bus =
1
YBUS Vbus
I2 2 2
bus YBUS Vbus
In the above equation each of the sequence admittance matrix represents the
corresponding sequence network.
the time of interest of the study. This impedance is also aggregated in the diagonal of
Ybus
old
. To compute the Thevenin's impedance at faulted bus i, all the current sources are
open circuited (made zero) and then 1 p.u. of current is injected at bus i. In the vector
notations, this process is represented by vector ei where ei s the ith column of identity
matrix. Then, the equation Ybus V = [ ei ] is solved by sparse LU factorization and
old 1 1
forward backward substitution. The ith element of the resulting voltage Vi gives the
Thevenin's impedance. The Thevenin's impedance for negative and zero sequence
networks proceed more or less on similar lines except that loads are not aggregated in
Ybus . Alternatively, loads can also be represented by simple positive sequence current
sources obtained from load flow analysis. Obviously, the result will depend upon the
modeling of load. The fault currents are computed by well known sequence network
interconnections, discussed in the previous lecture.
φa + φb + φc
∆Vb ∆Vc φ ± +− m
2
3φ − short circuit MVA = I 3φ (in pu ) × 3φ − base MVA
S − L − G − short circuit MVA = I S − L −G (in pu ) × 3φ − base MVA
100
j = j 0.2 pu
500