Você está na página 1de 5

PROJECT: SEPCPC Kauswagan 3x135 CFPP

SUBJECT: Pile Capacity Analysis for the Stack Pile


DATE: OCTOBER 21, 2015
AMH conducted a parallel check on the foundation design of the Stack. Assuming that the forces transferred
from the superstructure is correct, the number of piles provided is adequate. The structural design of the
individual pile is also adequate to carry the transferred axial and moment forces as shown in the following
calculation.
1. PILE CAPACITY ANALYSIS

ALL-PILE

Structure

Pile Length
(m)

Diameter
(mm)

Stack Pile

26

700

CivilTech Software

www.civiltech.com

ALLOWABLE CAPACITY
Axial
Lateral
(kN)
(kN)

1520

110

Licensed to

5000

5000

4500

4500

4000

4000

3500

3500

Uplift Capacity, Qup -kN

Compression Capacity, Qdw -kN

ALLOWABLE CAPACITY vs FOUNDATION DEPTH

3000

2500

2000

3000

2500

2000

1500

1500

1000

1000

500

500

0
0

10

15

20

25

30

Foundation Depth, L -m

CivilTech
Software

35

40

45

50

10

15

20

25

30

Foundation Depth, L -m

KAUSWAGAN 3x135 CFPP


Main Power Block - Stack Pile

35

40

45

50

2. SOIL SPRING CONSTANT


a. Stack Pile

Depth
(m)

Depth
Interval
(m)

Horizontal
Subgrade
Modulus,
KH
(kN/m3)

Vertical
Subgrade
Modulus,
KV
(kN/m3)

Horizontal
Spring
Constant, SkH
(KN/m)

Vertical Spring
Constant, SkV
(KN/m)

0.00 - 1.00
1.00 - 2.00
2.00 - 3.00
3.00 - 4.00
4.00 - 5.00
5.00 - 6.00
6.00 - 7.00
7.00 - 8.00
8.00 - 9.00
9.00 - 10.00
10.00 - 11.00
11.00 - 12.00
12.00 - 13.00
13.00 - 14.00
14.00 - 15.00
15.00 - 16.00
16.00 - 17.00
17.00 - 18.00
18.00 - 19.00
19.00 - 20.00
20.00 - 21.00
21.00 - 22.00
22.00 - 23.00
23.00 - 24.00
24.00 - 25.00
25.00 - 26.00
26.00 - 27.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
62,314.50
111,895.50
111,895.50
111,895.50
111,895.50
111,895.50
368,145.00
368,145.00
368,145.00
368,145.00
368,145.00
368,145.00
368,145.00
368,145.00
368,145.00

151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
151,976.80
258,360.60
258,360.60
258,360.60
258,360.60
258,360.60
759,884.20
759,884.20
759,884.20
759,884.20
759,884.20
759,884.20
759,884.20
759,884.20
759,884.20

43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
43,620.15
78,326.88
78,326.88
78,326.88
78,326.88
78,326.88
257,701.51
257,701.51
257,701.51
257,701.51
257,701.51
257,701.51
257,701.51
257,701.51
257,701.51

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
4,188,467.21

3. STAAD MODEL OF PILE FOUNDATION


Dummy plates to connect the
reaction (which acts at the
hollow center) to the pile cap

4. APPLIED LOADING ACCORDING TO SEPC ANALYSIS OF THE SUPERSTRUCTURE

5. MOMENT DIAGRAM OF PILES

6. SPCOL CHECK FOR PILE CAPACITY


P ( kN)
9000
(Pmax)

32

900

M (89) ( k N m)

-4000

(Pmin)

STRUCTUREPOINT - spColumn v4.80 (TM)


Page
1
15 day trial license. Locking Code: 4-23EB4. User: AMH Philippines, Inc., AMH Philippines, Inc.
10/28/15
c:\users\amh 101\desktop\kauswagan stack pile\stack pile 700.col
10:10 PM
ooooo
oo
o
oo
ooooo
oo
o
oo
ooooo

oooooo
oo
oo
oo
oo
oo
oo
oooooo
oo
oo

oooooo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oooooo

ooooo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
ooooo

o
oo
oo
oo
oo
oo
oo
oo o
ooo

oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
ooooo o

o oooooooooo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo

o ooooo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo
oo (TM)

==========================================================================================================
spColumn v4.80 (TM)
Computer program for the Strength Design of Reinforced Concrete Sections
Copyright 1988-2011, STRUCTUREPOINT, LLC.
All rights reserved
==========================================================================================================
Licensee stated above acknowledges that STRUCTUREPOINT (SP) is not and cannot be responsible for either
the accuracy or adequacy of the material supplied as input for processing by the spColumn computer
program. Furthermore, STRUCTUREPOINT neither makes any warranty expressed nor implied with respect to the
correctness of the output prepared by the spColumn program. Although STRUCTUREPOINT has endeavored to
produce spColumn error free the program is not and cannot be certified infallible. The final and only
responsibility for analysis,
design and engineering
documents is the
licensee's. Accordingly,
STRUCTUREPOINT disclaims all responsibility in contract, negligence or other tort for any analysis, design
or engineering documents prepared in connection with the use of the spColumn program.

STRUCTUREPOINT - spColumn v4.80 (TM)

Page

2
15 day trial license. Locking Code: 4-23EB4. User: AMH Philippines, Inc., AMH Philippines, Inc.
10/28/15
c:\users\amh 101\desktop\kauswagan stack pile\stack pile 700.col
PM

General Information:
====================
File Name: c:\users\amh 101\desktop\kauswagan stack pile\stack pile 700.col
Project: stack pile
Column:
pile
Engineer: rcc
Code:
ACI 318-08
Units: Metric

10:10

Run Option: Investigation


Run Axis:
Biaxial

Slenderness: Not considered


Column Type: Structural

Material Properties:
====================
f'c
= 27.58 MPa
Ec
= 24856.5 MPa
Ultimate strain = 0.003 mm/mm
Beta1 = 0.85
Section:
========
Circular:
Gross
Ix =
rx =
Xo =

fy
Es

= 413.7 MPa
= 199955 MPa

Diameter = 700 mm

section area, Ag =
1.17859e+010 mm^4
175 mm
0 mm

Reinforcement:
==============
Bar Set: ASTM A615M
Size Diam (mm) Area (mm^2)
---- --------- ----------# 10
10
71
# 19
19
284
# 29
29
645
# 43
43
1452

384845 mm^2
Iy =
ry =
Yo =

1.17859e+010 mm^4
175 mm
0 mm

Size Diam (mm) Area (mm^2)


---- --------- ----------# 13
13
129
# 22
22
387
# 32
32
819
# 57
57
2581

Size Diam (mm) Area (mm^2)


---- --------- ----------# 16
16
199
# 25
25
510
# 36
36
1006

Confinement: Tied; #10 ties with #32 bars, #13 with larger bars.
phi(a) = 0.8, phi(b) = 0.9, phi(c) = 0.65
Layout: Circular
Pattern: All Sides Equal (Cover to transverse reinforcement)
Total steel area: As = 10320 mm^2 at rho = 2.68%
Minimum clear spacing = 69 mm
16 #29

Cover = 75 mm

Factored Loads and Moments with Corresponding Capacities:


=========================================================
Pu
Mux
Muy
PhiMnx
PhiMny PhiMn/Mu NA depth Dt depth
eps_t
Phi
No.
kN
kNm
kNm
kNm
kNm
mm
mm
--- ----------- ----------- ----------- ----------- ----------- -------- -------- -------- -------- -----1
2479.00
0.00
0.00
763.72
0.00 999.999
359
601 0.00202 0.650
2
2242.00
13.00
238.00
42.71
781.94
3.285
344
600 0.00223 0.664
3
2244.00
4.00
238.00
13.19
784.94
3.298
344
601 0.00224 0.664
4
2324.00
1.00
31.00
24.96
773.85
24.963
350
600 0.00215 0.657
*** End of output ***

RCCADIZ (AMH Philippines, Inc.)


October 21, 2015

Você também pode gostar