H 7201 (1035)

H 7201

H 7201: Feed Line and Distribution Fuse Board


for SELV and PELV (24 V or 48 V power supply systems)
L1/L2 rail current rating max. 92 A
max. 63 A current rating for each individual feed terminal
for safeguarding up to 6 individual circuits with circuit breakers
the circuit breakers are not included within the scope of delivery.

L2

XG1

L1+

L3

L2+
5

H 7201

(3)

XG2

XG3

F1

SF1

F2

SF2

F3

F4

SF4

F5

SF5

F6

SF6

L1+

L1+
L2+
L-

L2+
L-

(2)

(1)

XG14

SF3

2 3

4 5 6 7

F1 F3 F5
*) F2 F4 F6
Diagnostic Signals
from Circuit breakers
Suitable for digital Inputs
*) Contact 2 not used

XG4

XG6

XG8

1 2 3

1 2 3

1 2 3

XG10

XG13

1 2 3

XG11

1 2 3

XG9

2 3

XG5

1 2 3

XG12

XG7

1 2 3

L-

L-

L-

L-

L-

L-

L-

1 2

Loop for
Circuit breaker
monitoring

Figure 1: Circuit Diagram

Explanations

(1) Circuit breaker with monitoring contact.


(2) Circuit breaker monitoring is operational (XG12) if the sliding switches
(SF1 to SF6) are set to the used position on the circuit breaker slots in use:
used position
equipped with circuit breaker
unused position not equipped with circuit breaker
(3) By inserting the provided jumper into the XG2 terminal, the two separated power rails are connected with one another.

Design:
For mounting on an NS 35 mounting rail in accordance with EN 60715.
Printed circuit board with sockets for 2 circuit breakers of up to 60A and
4 circuit breakers of up to 16A
Width
Height
Installation depth
Protection class
Weight
Temperature range

208 mm (total width)


108 mm (total height)
132 mm (equipped with circuit breakers)
IP 20
0.80 kg (without circuit breakers)
0 to 60 C

All rights and technical modifications reserved:


HIMA Paul Hildebrandt GmbH, P.O. Box 1261, D-68777 Brhl

1/3

H 7201 (1035)
Preferred Type of Circuit Breaker (not included within the scope of delivery of the H 7201):
Fuse

Nominal
current

Make

F1, F2, F5, F6

4A

E-T-A

Type

HIMA no.

2210-S211-P1T2-H111 4 A

57 0350040

F1, F2, F5, F6

16 A

E-T-A

2210-S211-P1T2-H111 16 A

57 0350160

F3, F4

30 A

E-T-A

8345-C01A-R0T1-DB1B2B 30A

57 0304031

F3, F4

60 A

E-T-A

8345-C01A-R0T1-DB1B2B 60A

57 0304061

Table 1: Preferred Type of Circuit Breakers

Terminals and Wiring:


Terminal

Min./max. wire cross section (mm2)

XG2: L+ feed line

0.2 / 16 flexible, 10 with wire end ferrule

XG1:, XG3: L- feed line

0.2 / 16 flexible, 10 with wire end ferrule

XG13: L+/L- outgoing line

0.5 / 25 flexible

XG4 to XG7: L- outgoing line

0.2 / 2.5 flexible

XG8 to XG11: L+ outgoing line

0.2 / 2.5 flexible

XG12: circuit breaker monitoring

0.2 / 2.5 flexible

Table 2: Terminals and Wiring

Diagnostic Signal Connector XG14:


The diagnostic signals can be used to detect the status of the outgoing lines XG8 through
XG11 and XG13.
HIGH signal -> voltage present
LOW signal -> voltage not present
The diagnostic signals are suitable for digital inputs of type 3 (in accordance with IEC 611312) and can be evaluated by e.g. a PES.
Front View:

Figure 2: Front View with Circuit Breakers "F1...F6"

Mounting
We recommend mounting the H 7201 horizontally or vertically (with respect to the label located on the front) to ensure sufficient ventilation.
HI 800 357 Rev. 0.08

2/3

H 7201 (1035)

Warning! Unnecessary shut down!


At an ambient temperature 60C and a nominal current rating of all circuit breakers of the H 7201, the current rating must be reduced to 80 % of the nominal current rating.

HI 800 357 Rev. 0.08

3/3