Operation for E5@N/E5@N-H/E5@N-HT

Operation for E5@N/E5@N-H/E5@N-HT

CSM_E5_N_E5_N-H_operation_TG_E_4_2

Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.

Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Power ON

Start in manual mode.

Start in automatic mode.

Press the O Key or the


PF Key for at least 1 s. *4

Operation
Level

Adjustment
Level
Press the
O Key less than 1 s.

a-m

PF Key

Manual
mode

*3

Press the O Key


for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)

PF Key

Press the
O+ M
Keys for at
least 1 s.
c

25
100

*5
*4

Press the PF Key


for at least 1 s.

Manual
Control Level

*5

Monitor/Setting
Item Level

Press the
O+ M
Keys for at
least 3 s.
(Display
will flash
after 1st
second.)

Press the
O Key for
at least 1 s.

Control stops.

Press the O Key for at


least 3 s. (Display will flash
after 1st second.)

25
100

Protect Level

*1
Note: The time taken to
move to the protect
level can be adjusted
by changing the
Move to protect level
time setting.

Communications Setting
Level

Initial Setting
Level

Press the
O Key for less than 1 s.

Input password while


amoV is displayed. (Set
value 169)

Press the O Key


for at least 1 s.

Advanced Function
Setting Level
Control in progress
Input password.
Control stopped
Calibration Level

*2

Not displayed for some models

Level change
*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN).
*5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display

Meaning

Action

s.err (S. Err)

Input error
*2
A/D
converter
error *2

Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.

e333 (E333)
e111 (E111)

Memory
error

Status at error
Control output *1
Alarm output
Operates as above
OFF
the upper limit.
OFF

OFF

OFF

OFF

Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range,
will be displayed under -1999 and
above 9999. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Advanced Type
E5CN-H/E5AN-H/E5EN-H
Power ON

Start in manual mode.

Start in automatic mode.

Press the O Key or the


PF Key for at least 1 s. *4

Operation
Level

a-m

Manual
mode

*3

Press the O Key


for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)

Adjustment
Level

Press the
O Key less than 1 s.
Press the
O Key less than 1 s.

PID Setting
Level

Press the
O Key less
than 1 s.

Bank Setting
Level

Press the PF Key


for at least 1 s. *4

Manual
Control Level

PF Key

Press the
O Key less
than 1 s.

Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)

25.0
100.0

Protect Level

Press the O Key for at


least 3 s. (Display will flash
after 1st second.)

25.0

PF Key *5

Monitor/Setting
Item Level

*5

Press the O Key


for at least 1 s.

Press the O+
M Keys for at
least 1 s.

Note: The time taken to


move to the protect
level can be adjusted
by changing the
Move to protect level
time setting.

100.0
*1

Control stops.

Communications Setting
Level

Initial Setting
Level

Press the
O Key for less than 1 s.

Press the O Key


for at least 1 s.

Input password while


amov is displayed.
(Set value 169)
Advanced Function
Setting Level
Input password.

Control in progress
Control stopped

*2

Calibration Level

Not displayed for some models


Level change

*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display

Meaning

s.err (S. Err)

Input error
*2

e333 (E333)
e111 (E111)

Action

Status at error
Control output *1

Alarm output

Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.

OFF

Operates as above
the upper limit.

A/D
converter
error *2

Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.

OFF

OFF

Memory
error

Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.

OFF

OFF

Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range,
will be displayed under -19999
and
above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Power ON

Start in manual mode.

Start in automatic mode.

Operation
Level

a-m
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)

Manual
mode

Program
Setting Level

Press the
O Key less than 1 s.
Press the
O Key less than 1 s.

PID Setting
Level

Press the
O Key less
than 1 s.

Adjustment
Level

Press the
O Key less
than 1 s.

Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)

Press the O+
M Keys for at
least 1 s.
c

Press the PF Key


for at least 1 s.

Manual
Control Level

25.0

100.0

Protect Level

Monitor/Setting
Item Level

Press the O Key


for at least 1 s.

25.0

Press the O Key for at


least 3 s. (Display will flash
after 1st second.)

Note: The time taken to


move to the protect
level can be adjusted
by changing the
Move to protect level
time setting.

100.0

Control stops.

Communications Setting
Level

Initial Setting
Level

Press the
O Key for less than 1 s.

Press the O Key


for at least 1 s.
Advanced Function
Setting Level
Input password.

Control in progress
Control stopped

Calibration Level

Not displayed for some models


Level change

*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning
OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.
*5. When the PF Setting parameter is set to PFDP. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display

Meaning

s.err (S. Err)

Input error
*2

e333 (E333)
e111 (E111)

Action

Status at error
Control output *1

Alarm output

Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.

OFF

Operates as above
the upper limit.

A/D
converter
error *2

Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.

OFF

OFF

Memory
error

Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.

OFF

OFF

Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range,
will be displayed under -19999
and
above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Parameters
Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Some parameters are not displayed depending on the
model of the Controller and parameter settings.
For details, refer to the E5CN/E5AN/E5EN/E5GN
Digital Temperature Controllers User's Manual Basic
Type (Cat. No. H156).
Starting in manual mode.

PF Key *2

Power ON

Manual Control Level


Press the PF Key for
at least 1 s. *1

Adjustment
Level

Press the O
PID
Key or the PF
25 Control Key for at least
only
1 s.
*1
PV/MV

PF Key *2
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display

Starting in
automatic
mode.

Initial Setting Level


Press the
O Key for
at least 1 s.

Press the O Key less than 1 s.

in-t Input Type


5

Press the O Key less than 1 s.

M
in-h

Operation Level
Press the O Key less than 1 s.

0.0 Input Shift Value parameters.

2-point shift
M
Limit
insl Lower
Temperature

0.0 Input Shift Value

off

0.0

M
Burnout
hb1 Heater
Detection 1

M
i
M
d

M
Overcurrent
oc1 Heater
Detection 1
50.0

M
hb2
0.0

M
oc2
50.0

M
lcr1
0.0
0.0

M
hs1

Heating/cooling
M
c-db Dead Band

0.0

M
of-r

1.0

0.0

M
hs2
C

M
soak Soak Time

Leakage Current 2
Monitor

HS Alarm 2

M
wt-b

off

M
sp-0

M
mv-s

SP 0

M
sp-2

MV at Stop

M
Current 2
lcr2 Leakage
Monitor

MV at PV Error

SP used by
multi-SP
SP 2

M
sp-3 SP 3

M
sprt SP Ramp Set Value
off

M
ol-h

105.0

M
ol-l

MV Upper Limit

MV Lower Limit

orl MV Change Rate Limit


0.0

M
sqrp
0.0

Extraction of Square Root


Low-cut Point

Alarm Value
Upper Limit 2

M
Value
al2l Alarm
Lower Limit 2

M
al-3 Alarm Value 3
0

M
Value
al3h Alarm
Upper Limit 3
0

M
prst Program Start

rset

M
Value
al3l Alarm
Lower Limit 3

M
d-u

M
s-hc

M Initial Setting/
Protect:
icpt Communications
This protect level restricts movement
1 to the initial setting, communications

M levels.
Change Protect:
wtpt Setting
Protects changes to setups by

off operating the front panel keys.

M
Key Protect
pfpt PF
Restricts PF key operation
off (E5AN/E5EN only)

M
Mask Enable:
pmsk Parameter
Displayed only when a
on parameter mask is set.

M
to Move to Protect Level:
prlp Password
Password setting
0

Standard or
Heating/Cooling

stnd

M
st ST (Self-tuning)
on

M
ptrn

For input type of


temperature, standard
control, or PID

Program Pattern

off When assigning PID or

control output to ON/OFF


output

cp Control Period (Heating)

M
o MV Monitor (Heating)

20

M
c-cp

Set the ON/OFF


output cycle.
Control Period (Cooling)

20

M
orev Direct/Reverse Operation
or-r

Press the O and M Keys for at least 1 s.

Operation/Adjustment Protect:
oapt Restricts displaying and
modifying menus in operation,
0 adjustment, and manual control
levels.

Limit the set point


SP Lower Limit

onof

Move to Protect Level:


Displayed only when a password
0 is set. Restricts moving to protect
level.

M
sl-l

M
cntl PID ON/OFF

0.0

Protect Level

SP Upper Limit

-200

M
c-o MV Monitor (Cooling)

Note: The time taken to move to the protect


level can be adjusted by changing the
"Move to protect level time" setting.

Temperature Unit
C, F
For input type of
temperature

1300

0.0

Press the O and M Keys for


at least 3 s.

M
sl-h

M
sktr Soak Time Remain

Decimal Point

0 For input type of analog

setting, and advanced function setting

-5.0

M
al2h
0

0.0

pmov

0.0

0
C

M
mv-e

SP 1

0
C

M
Current 1
lcr1 Leakage
Monitor

Wait Band

0.0

M
sp-1

Heater Current 2 Value


Monitor

1.0

50.0

0.0

M Hysteresis settings
chys Hysteresis (Cooling)

50.0

M
lcr2

Manual Reset Value


Clear the offset during

M
hys Hysteresis (Heating)

0.0

M
ct2

M
al-2 Alarm Value 2
0

0.0

50.0 stabilization of P or PD
C

M
Current 1 Value
ct1 Heater
Monitor

PID settings

M
Value
al1l Alarm
Lower Limit 1

M
dp

M
Point During
sp-m Set
SP Ramp

Derivative Time

control.

HS Alarm 1

Integral Time

1.00

Heater Overcurrent
Detection 2

Leakage Current 1
Monitor

Multi-SP
Set Point Setting

M
Value
al1h Alarm
Upper Limit 1
0

M
c-sc Cooling Coefficient

Heater Current 2
Value Monitor

Heater Burnout
Detection 2

m-sp

40

0.0

Added when
auto/manual select
M addition is ON.

Press the
O Key
for at
least 3 s.

M
al-1 Alarm Value 1
0

M
Switch
a-m Auto/Manual
PID control only.

233

0.0

M
ct2

M
p Proportional Band
8.0

1-point shift
M
Set either
Limit
insh Upper
of these
Temperature

AT Execute/Cancel

M
Current 1
ct1 Heater
Value Monitor

M
Value/
25 Process
Set Point

0.0

off

M
cmwt Communications
Writing

ins Temperature Input Shift

run
Set either of these parameters.

M
at

M
in-l Scaling Lower Limit

r-s RUN/STOP

Process Value
Added when Additional
PV display is ON.

Set either of these parameters.

l.adj

25

Set either of these parameters.

Adjustment Level
Display
Displayed only
once when
entering
adjustment level.

Scaling Upper Limit

100

M
alt1

Press the O Key


less than 1 s.

Communications
Setting Level

Note: Displayed only for models with communications.


Changes are effective after cycling power or
after a software reset.

Alarm 1 Type

M
alh1
0.2

Alarm 1
Hysteresis

Setting:
psel Protocol
Switches between

cwf CompoWay/F (SYSWAY)


and Modbus.

M
u-no Communications Unit No.
1

M
Communications
bps Baud Rate
9.6

CompoWay/F
(SYSWAY) only

M
len Communications
Data Length
7

M
sbit Communications
Stop Bits
2

M
prty Communications Parity
even

M
sdwt

*1. When the PF Setting


parameter is set to A-M for a
Controller with a PF Key
(E5AN/E5EN).
*2. When the PF Setting
parameter is set to PFDP for a
Controller with a PF Key
(E5AN/E5EN).

Send Data Wait Time

20

Operation for E5@N/E5@N-H/E5@N-HT

Monitor/Setting Item Level


25

Monitor/Setting
Item Display 1

PF

(E5AN/E5EN only)
Monitor/Setting
Item Display 2

Monitor/Setting
Item Display 3

PF

Monitor/Setting
Item Display 4

PF

Monitor/Setting
Item Display 5

PF

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

Press the O Key for at least 1 s.

alt2

Advanced Function Setting Level

Alarm 2 Type

0.2

M
alh3

0.2

M
mspu Multi-SP Uses

M
a2lt Alarm 2 Latch

M
spru

M
a3lt Alarm 3 Latch

SP Ramp Time Unit

Alarm 3
Hysteresis

M
Sequence
rest Standby
Reset

M
to Protect Level
prlt Move
Time

M
sb1n

M
sero Input Error Output

off

M
tr-h

Linear output

n-o

Transfer Output
Upper Limit

M
sb2n

100.0

M
Output
tr-l Transfer
Lower Limit

n-o

M
sb3n

0.0

M
o1-t Linear Current Output
4-20

n-o

M
hbu

Linear output

M
of Multi-SP Uses
ev-m Number
Two SPs: 1

none

M
ev-2
stop

on Method

M
Command
rlrv MB
Logic Switching

Auxiliary Output 3
Open in Alarm

off

M
colr PV Change Color

HB ON/OFF

red

off

M
Burnout
hbh Heater
Hysteresis
0.1

Event Input
Assignment 2

M
of Square
sqr Extraction
Root Enable

M
Junction
cjc Cold
Compensation

on

Event Input
Assignment 1

0.65

setting/communications

M protect is set to 0.

0.8

Move by setting password (169).

M
at-h AT Hysteresis
0.8

M
a2on Alarm 2 ON Delay
M
a3on Alarm 3 ON Delay
M
a1of Alarm 1 OFF Delay
0

M
a2of Alarm 2 OFF Delay
0

M
Cycle MV
lcma Limit
Amplitude
20.0

M
inf Input Digital Filter
0.0

M
pvad Additional PV Display
off

M
o-dp

M
a1on Alarm 1 ON Delay

M
at-g AT Calculated Gain

0 Displayed when initial

5.0

M
alfa

M
to Advanced
amov Move
Function Setting Level:

M
pv-b PV Stable Band

M
st-b ST Stable Range
15.0

off

M
hsh HS Alarm Hysteresis
0.1

M
a3of Alarm 3 OFF Delay
0

M
istp Input Shift Type
ins1

M
at Stop and Error
mvse MV
Addition
off

MV Display

off

M
Display
ret Automatic
Return Time

0
C

M
Select
amad Auto/Manual
Addition
off

M
rt RT

off

off

M
lbal LBA Level

M (E5AN/E5EN only)
pfd2 Monitor/Setting Item 2
M
pfd3 Monitor/Setting Item 3
0

M
pfd4 Monitor/Setting Item 4
0

8.0
C

M
pfd1 Monitor/Setting Item 1

M
lba LBA Detection Time

off

Auxiliary Output 2
Open in Alarm

M
hbl Heater Burnout Latch

1 Four SPs: 2

M
ev-1

Auxiliary Output 1
Open in Alarm

PF Setting
(E5AN/E5EN only)

off

tr-t Transfer Output Type

pf
a-m

M
hsl HS Alarm Latch

off

HS Alarm Use

on

off

off

M
alt3 Alarm 3 Type

hsu

off

off

M
2
alh2 Alarm
Hysteresis

a1lt Alarm 1 Latch

init Parameter Initialization

M
lbab LBA Band
3.0

M
pfd5

Monitor/Setting Item 5

M
Output 1
out1 Control
Assignment

M
spdp

M
out2

Control Output 2
Assignment

M
odsl MV Display Selection

Auxiliary Output 1
Assignment

M
Decimal Point
pvdp PV
Display

none

M
sub1
alm1

M
sub2

Auxiliary Output 2
Assignment

alm3

"PV/SP" Display
Screen Selection

on

M
PV Status Display
pvst Function
off

alm2

M
sub3

Auxiliary Output 3
Assignment
(E5AN/E5EN only)

M
csel Character Select
on

M
t-u Soak Time Unit
m

M
alsp Alarm SP Selection
sp-m

M
MV
manl Manual
Limit Enable
off

M
Rate of Change
pvrp PV
Calculation Period
4

M
csca

off

Automatic Cooling
Coefficient Adjustment

M
Overcurrent
ocu Heater
Use
on

M
Overcurrent
ocl Heater
Latch

M
Status Display
svst SV
Function
off

M
Refresh
d.ref Display
Period
0.25

M
Output 1
ra1m Control
ON/OFF Count
0 Monitor

M
ra2m

Control Output 2
ON/OFF Count

0 Monitor

M
ra1

Control Output 1
ON/OFF Count

0 Alarm Set Value

M
Output 2
ra2 Control
ON/OFF Count
0 Alarm Set Value

M
Counter
rac ON/OFF
Reset
0

M
to Calibration
cmov Move
Level
0

off

M
och
0.1

Heater Overcurrent
Hysteresis

Operation for E5@N/E5@N-H/E5@N-HT


Advanced Type
E5CN-H/E5AN-H/E5EN-H
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157).

Power ON
Manual Control
Level

Protect Level

Operation
Level

Adjustment
Level

Initial Setting
Level

Communications Setting
Level

PID Setting
Level

Bank Setting
Level

Monitor/Setting
Item Level

Advanced
Function Setting
Level

Press the O Key less than 1 s.

Bank Setting Level

PID Setting Level


Press the O Key less than 1 s.

Display PID Selection

Press the O Key less than 1 s.

Display Bank Selection


d.bnk Bank0

d.pid PID1
1
d.pid

2 PID2

d.bnk Bank1
1

d.pid

d.bnk
d.
bnk

3 PID3

22 Bank2

d.pid
8

d.bnk Bank7

PID8

M
1.i

M
8.d

PID 1 Derivative Time

8.olh
M
8.oll

M
PID 1 Automatic Selection
1320.0 Range Upper Limit

PID 1 Cooling Coefficient

1.00

PID 8 Automatic Selection


1320.0 Range Upper Limit

M
PID 8 Cooling Coefficient

1.00
PID 1 LBA Detection Time

M
8.lba
0

7.pid

M
0.a3h

0.0

M
0.a1h

M
c

0.a3l

0.0

0.a1l
0.0

M
0.sok

0.a-2
M

0.a-1

0.0
PID 8 LBA Detection Time

0.a2l

0.a-3

0.wtb

Bank 7 SP

0.0

0.0

7.lsp
M

0.0

0.0

M
8.aut

8.csc

M
0

PID 8 MV Lower Limit

M
0.0

-5.0

1.aut

1.lba

105.0
PID 1 MV Lower Limit

-5.0

M
1.csc

PID 8 MV Upper Limit

M
0.spr
off

105.0

0.a 2h
0.0

0.pid

40.0
PID 8 MV Upper Limit

M
1

PID 8 Derivative Time

0.lsp
0.0

233.0

40.0

M
1.oll

M
8.i PID 8 Integral Time

PID 1 Integral Time

M
1.olh

M
PID 8 Proportional Band

8.0

233.0

1.d

M
8.p

7.a-2

7.a 2h

7.a2l

M
7.spr

Bank 7
0.0 Alarm Value 1

M
7.a1h

Bank 7
Alarm Value
0.0 Upper Limit 1

Bank 7
Alarm Value
0.0 Lower Limit 1

7.a1l

Bank 7
Alarm Value
0.0 Upper Limit 2

Bank 7 SP
off Ramp Set Value

M
7.a-1

Bank 7
0.0 Alarm Value 2

Bank 7 PID
Set No.

M
c

Bank 7
Alarm Value
0.0 Lower Limit 2

M
7.a-3 Bank 7

0.0 Alarm Value 3

M
7.a3h

Bank 7
Alarm Value
0.0 Upper Limit 3

M
7.a3l

Bank 7
Alarm Value
0.0 Lower Limit 3

M
7.sok

off

Set either of these parameters

PID 1 Proportional Band

8.0

Set either of these parameters

1.p

Set either of these parameters

Bank 7 Soak Time

M
7.wtb

Bank 7 Wait Band

off

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Starting in manual mode.

Manual Control Level


PID
Press the O
25.0 Control Key or the PF
100.0 only
Key for at least
1 s. *1
PV/MV

Press the PF Key


for at least 1 s.

Starting in
automatic
mode.

*1

Press the O
and M Keys for
at least 3 s.

Press the O Key less than 1 s.

at
off

c
c

8.0

M
i

AT Execute/Cancel

cmwt

M
irda

40.0

Infrared Communications Use

SP Mode

lsp

0.0

M
ct1

M
of-r

Heater Current 1

M
hys

Heater Burnout

1.0

0.0 Detection 1

M
oc1

M
chys

M
soak

Heater Overcurrent
50.0 Detection 1

ct2

Heater Current 2

M
hb2
0.0

M
oc2
50.0

Heater Burnout
Detection 2

mv-s

mv-e

M
hs1

M
sprt

Leakage Current 1
0.0 Monitor

0.0

M
hs2
50.0

0.0

HS Alarm 1

0.00

M
c

M
ol-h

Leakage Current 2
Monitor

105.0

ol-l
HS Alarm 2

-5.0

M
orl
Temperature Input Shift

Bank No.

0.0 Lower Limit 1

Remote SP Monitor

Set Point During

M
ct1

Heater Current 1 Value

M
c

ct2

Heater Current 2 Value


0.0 Monitor

lcr2

Alarm Value

M
al2l

Press the O
and M Keys for
at least 1 s.

Alarm Value

0.0 Lower Limit 2

0.0 Monitor

lcr1

al2h

0.0 Upper Limit 2

0.0 SP Ramp

M
al-3
0.0

Alarm Value 3

M
al3h Alarm Value

Leakage Current 1

0.0 Upper Limit 3

M
al3l Alarm Value

Leakage Current 2

0.0 Lower Limit 3

0.0 Monitor

MV at PV Error

Alarm Value 2

0.0

0.0 Monitor

MV at Stop

al-2

M
Wait Band

M
al1l Alarm Value
M

M
Soak Time

Alarm Value

0.0 Upper Limit 1

0.0

sp-m

Hysteresis settings

al1h

prst Program Start


rset

0.0

M
c-o

sktr Soak Time Remain

MV Monitor (Heating)

MV Monitor (Cooling)

0.0

v-m

SP Ramp Set Value

Valve Opening
Monitor

0.0

M
MV Upper Limit

Lower Limit
Temperature
Input Shift Value

0.0

MV Lower Limit

PF Key *2
MV Change Rate Limit

Monitor/Setting Item Level

(E5AN-H/E5EN-H only)

1-point shift

Upper Limit
Temperature
0.00 Input Shift Value
2-point shift
M

0.00

rsp

control.

Hysteresis (Heating)

M
c

Manual Reset Value


Clear the offset during

Auto/Manual Switch
PID control only.
Added when
auto/manual select
addition is ON.

Heating/cooling

Alarm Value 1

0.0

insh

insl

bank

al-1
M

off

M
ins

Dead Band

0.0

lcr1

M
lcr2

a-m
Press
the O
Key for
at least
3 s.

50.0

PID settings
Derivative Time

off

Heater Overcurrent
Detection 2

M
c

M
wt-b

run

Process Value/
0.0 Set Point

Integral Time

1.0 Hysteresis (Cooling)

0.0 Value Monitor

r-s RUN/STOP

25.0

50.0 stabilization of P or PD

0.0 Value Monitor

M
hb1

M
c-sc Cooling Coefficient
M
c-db

Process Value
Added when Additional
PV display is ON.

1.00

off

spmd

25.0

Proportional Band

233.0

Communications
off Writing

Set either of these parameters.

Adjustment Level
Display
Displayed only
once when
entering
adjustment level.

Set either of these parameters.

l.adj

Operation Level

Set either of these parameters.

Adjustment Level

Set either
of these
parameters.

db
2.0

Position Proportional
Dead Band

oc-h

25.0 Monitor/Setting
Item Display 1

Monitor/Setting
Item Display 2

PF

PF

Monitor/Setting
Item Display 3

0.0

PF

Open/Close Hysteresis

0.8

M
sqrp

Extraction of Square
Root
0.0 Low-cut Point

Monitor/Setting
Item Display 4

PF

Monitor/Setting
Item Display 5

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to


5 parameters (advanced function setting level).

PF Key *2

*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).

Operation for E5@N/E5@N-H/E5@N-HT

Press the O Key for at least 1 s.


Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display

Initial Setting Level


Press the O Key less than 1 s.

Press the O Key less than 1 s.

Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
to Protect Level:
pmov Move
Displayed only when a password

0 is set. Restricts moving to protect


level.

Operation/Adjustment
Protect:

oapt Restricts displaying and

modifying menus in
0 operation, adjustment, and
manual control levels.

icpt
0

Initial Setting/
Communications Protect:
This protect level restricts
movement to the initial setting,
communications setting, and
advanced function setting levels.

Setting Change Protect:


Protects changes to setups
off by operating the front panel
keys.

wtpt
M

pfpt

PF Key Protect
Restricts PF key operation

off (E5AN-H/E5EN-H only)

M
Mask Enable:
pmsk Parameter
Displayed only when a
on parameter mask is set.

M
Password to Move to
Protect Level:
0 Password setting

prlp

in-t

Communications
Setting Level

Input Type

Displayed only for models with communications. Changes


are effective after cycling power or after a software reset.

in-h

M
in-l

Scaling Upper Limit

dp

d-u
c

Communications
Data Length
c

M
sbit
2

M
sl-h

Decimal Point

Temperature Unit
C, F
For input type of
temperature

M
s-hc

20

100.0

0.0

M
o1-t

Standard or
Heating/Cooling

ST (Self-tuning)
For input type of
temperature,
standard control, or
PID
Program Pattern

off

cp

c-cp

When assigning PID or


control output to ON/OFF
output
Control Period (Heating)
Set the ON/OFF
output cycle.
Control Period (Cooling)

20

M
orev Direct/Reverse Operation
or-r

M
alt1

Alarm 1 Type

M
0.2

Bank Numbers Used

M
ev-1
none

Event Input
Assignment 1

M
ev-3
none

Event Input
Assignment 3

M
ev-4
none

Event Input
Assignment 4

M
clfl

Closed/Floating

flot

M
calb

Motor Calibration

off

alh1

Linear output

stop

Valid Program Bank

20

Linear Current Output

Input
ev-2 Event
Assignment 2

M
7

Transfer Output
Lower Limit

4-20

Transfer Output
Upper Limit

M
tr-l

ev-b

pbnk

Linear output

M
st
M
ptrn

stnd

on

Alarm 3
Hysteresis

tr-t Transfer Output Type

tr-h

Limit the set point


M
sl-l SP Lower Limit

pid
Send Data Wait Time

M
alh3

off
SP Upper Limit

M
cntl PID ON/OFF

0.2

-200.0

even

Alarm 3 Type

1300.0
Communications
Stop Bits

M
prty Communications Parity

sdwt

alt3

Alarm 2
Hysteresis

Scaling Lower Limit

0 For input type of analog

Communications
Baud Rate
9.6
CompoWay/F
(SYSWAY) only

M
alh2
0.2

M
bps

len

0
Communications Unit No.

Alarm 2 Type

100
Protocol Setting:
psel Switches between
cwf CompoWay/F (SYSWAY)
and Modbus.

u-no

alt2

M
mot

Travel Time

30
Alarm 1
Hysteresis

M
sqr
off

Extraction of Square
Root Enable

M
Move to Advanced Function
Level:
amov Setting
Displayed when initial
0 setting/ communications

protect is set to 0.

Move by setting password (169).

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Manual Control
Level

Protect Level

Operation
Level

Adjustment
Level

Initial Setting
Level

Communications Setting
Level

PID Setting
Level

Bank Setting
Level

Monitor/Setting
Item Level

Advanced
Function Setting
Level

Press the O Key for at least 1 s.


Advanced Function Setting Level

o-dp
init

Parameter Initialization

off
SP Ramp Time Unit

Standby Sequence
Reset

Auxiliary Output 2

cjc
Heater Burnout
Hysteresis

off

ST Stable Range

pv-b

AT Calculated Gain

M
AT Hysteresis

PV Change Color
c

PV Stable Band

M
20.0

M
Input Digital Filter

M
0

M
pmvd

Control Output 1
Assignment

Control Output 2
Assignment

Auxiliary Output 1
Assignment

odsl MV Display Selection

Auxiliary Output 2
Assignment

M
PID Set Automatic
Selection Hysteresis

Character Select

Soak Time Unit

pf

svst
off

SV Status Display
Function

M
Direct Setting of

d.ref
0.25

Display Refresh
Period

M
ra1m

Control Output 1
ON/OFF Count

0 Monitor

M
Automatic Cooling

ra2m

Control Output 2
ON/OFF Count

0 Monitor

M
Heater Overcurrent
Use

ra1

Control Output 1
ON/OFF Count

0 Alarm Set Value

M
Heater Overcurrent

Heater Overcurrent
Hysteresis

ra2

Control Output 2
ON/OFF Count

0 Alarm Set Value

M
Counter
rac ON/OFF
Reset

M
a-m

PV Status Display
Function

M
Manual MV
Limit Enable

M
0.1

pvst
off

off Latch

och

PV Decimal Point
Display

M
PV Dead Band

ocl

pvdp
on

off Coefficient Adjustment

on

"PV/SP" Display

4 Screen Selection

PID Set Automatic


Selection Data

PV Rate of Change
17 Calculation Period

alm2

ocu

Monitor/Setting Item 5

spdp

off Position Proportional MV

csca

pfd5

Remote SP Input
Error Output

pvrp

t-u
Alarm 3 OFF Delay

off

3.0

on

M
0

LBA Band

Monitor/Setting Item 4

0.0

csel

a2of Alarm 2 OFF Delay

a3of

lbab

sub2

LBA Level

p-db

pfd4

M
SP Tracking

M
c

alm1
Alarm 3 ON Delay

00
Additional PV Display

0.50

manl

sub1

a1of Alarm 1 OFF Delay

pidh
LBA Detection Time

Monitor/Setting Item 3

8.0

none
Alarm 2 ON Delay

0.0

pv

HS Alarm Hysteresis

out2

M
a3on

lbal

o
Alarm 1 ON Delay

0
Limit Cycle MV
Amplitude

pidi

out1

M
a2on

M
c

0.8

off

pfd3

M
Remote SP
Lower Limit

off

M
a1on

M
rseo

lba

MB Command
Logic Switching

5.0

1.0

on

Monitor/Setting Item 2

M
Remote SP
Upper Limit

off

HS Alarm Use

Cold Junction

M
c

M
sptr

0.1

red

0.65

-200.0

RT

hsh

M
colr

alfa

Input Error Output

rspl

pfd2
0

M
c

hsl HS Alarm Latch

M
rlrv

off

Time

1300.0

Auto/Manual Select
Addition

off

hsu

on Compensation
Method

15.0

pvad

Alarm 3 Latch

inf

rt

off

off

lcma

Alarm 2 Latch

M
sero

at-h

on

3
HB ON/OFF

Burnout
hbl Heater
Latch

M
a2lt

on

at-g

amad

rsph

Monitor/Setting Item 1

M
Remote SP Enable

M
c

pfd1
1

off

MV at Stop and Error


Addition

prlt Move to Protect Level

st-b

off

off

n-o Open in Alarm

0.1

mvse

a3lt

hbh

rspu

off

sb1n Auxiliary Output 1


n-o Open in Alarm

hbu

off

sb2n

ins1

a1lt Alarm 1 Latch

M
rest

M
off

Alarm SP Selection

sp-m

Input Shift Type

istp

Display
ret Automatic
Return Time

M
spru

alsp

MV Display

off

M
PF Setting

cmov
0

Move to Calibration
Level

Operation for E5@N/E5@N-H/E5@N-HT


Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-HT/E5AN-HT/
E5EN-HT Digital Controllers User's Manual
Programmable Type (Cat. No. H169).

Power ON
Manual
Control Level

Operation
Level

Program Setting
Level

Initial Setting
Level

Communications Setting
Level

Protect Level

Adjustment
Level

Monitor/Setting
Item Level

PID Setting
Level

Advanced
Function Setting
Level

Adjustment Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.

PID Setting Level


Press the O Key less
than 1 s.

l.adj

at
d.pid PID1
1
d.pid

M
cmwt

2 PID2

off

d.pid

d.pid
8

M
1.p
M
1.i

PID 1 Proportional Band


c

M
8.d PID 8 Derivative Time
40. 0

8.ol h
PID 1 MV Lower Limit

-5. 0

M
1.aut

M
1.csc

Range Upper Limit


PID 1 Cooling

1. 00 Coefficient

M
1.lba

PID 1 LBA Detection


0 Time

PID 8 Automatic
Selection
1320. 0 Range Upper Limit

8.aut

M
8.c sc PID 8 Cooling
Coefficient
1. 00
M
8.lba PID 8 LBA Detection
0 Time

M
ct1
0. 0

M
hb1
0. 0

Integral Time
PID settings

M Heating/cooling
c-db Dead Band
0.0

Manual Reset Value


Clear the offset during
50.0 stabilization of P or PD
control.

of-r

M
oc2

M
hys

1. 0

Heater
Overcurrent
50. 0 Detection 2

M
lcr1 Leakage Current 1

M
chys
1.0

Monitor

M
wt-b

Hysteresis
(Heating)
Hysteresis settings
Hysteresis
(Cooling)

50 .0

Wait Band

M
Current 2
lcr2 Leakage
Monitor

0. 0

0. 0

M
db

Position
Proportional
2. 0 Dead Band

M
oc-h

Open/Close
Hysteresis

M
Extraction of
sqrp Square Root
M
stb

MV at Reset

Standby Time

0.00

M
SP
psps Program
Shift Value
0. 0

M
-200.0

M
ps1
-2 00.0

RSP 0 before
Correction

RSP 1 before
Correction

M
ps10
-2 00.0

RSP 10 before
Correction

M
0

bc1

M
mv-r

M
Change
orl MV
Rate Limit

bc0

of f

HS Alarm 1

-5. 0

ps0

M
ol-l MV Lower Limit

0. 0 Low-cut Point

Derivative Time

1.00

MV Upper Limit

105 .0

0. 8

M
c-sc Cooling Coefficient

Heater Burnout
Detection 1

Heater Burnout
0. 0 Detection 2

M
p Proportional Band

40.0

M
hb2

0. 0

Limit
inslLower
Temperature

M
d

0. 0

M
hs1

1-point shift
Set
either
Upper Limit
of these
Temperature
0. 00 Input Shift Value parameters
M 2-point shift

23 3 .0

Heater Current 1
Value Monitor

50.0 Detection 1

0.0

M
insh

M
i

M
ol-h

Temperature Input
Shift

8. 0

Fixed SP

PID 8 MV Lower Limit

PID 1 Automatic

M
Current 2
ct2 Heater
Value Monitor

-5. 0

1320. 0 Selection

SP Mode

PID 8 MV Upper Limit

10 5. 0

M
8.ol l

M
fs p

M
ins

0. 00 Input Shift Value

M
oc1 Heater
Overcurrent

PID 1 MV Upper Limit

105. 0

0. 0

233. 0

PID 1 Derivative Time

40. 0

M
1.oll

PID 8 Proportional Band

M
8.i PID 8 Integral Time

PID 1 Integral Time

M
1.olh

8.p
8. 0

233. 0

1.d

M
spmd
psp

8. 0

0. 00

Communications
Writing

off Use

PID8

HS Alarm 2

50 .0

AT Execute/
Cancel

MV at PV Error

0.0

M
irda Infrared
Communications

3 PID3

mv-e
hs2

M
off

Display PID Selection

Adjustment Level
Display
Displayed only
once when
entering
adjustment level.

RSP Broken-line
Correction Value 0

RSP Broken-line
Correction Value 1

M
bc10
0

RSP Broken-line
Correction Value 10

10

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Starting in manual mode.

Manual Control Level


Press the PF Key
for at least 1 s.*1

Press the O Key


or the PF Key for
at least 1 s. *1

PID

25 .0 Control
100.0 only

PV/MV

Starting in
automatic
mode.

Press the O
and M Keys for
at least 3 s.

Press the O Key less than 1 s.

Operation Level

Program Setting Level

Operation Level
d.prg
d.prg
0
d.prg
1

Press the
O Key for
at least 3 s.

Display Program Selection

d.prg

s-n o

Number of Segments
8 Used, 1 to 32

25.0

ct 2

PV

0.0

Display Segment Selection, END or 0 to

Number of Segments 1
d.seg
d.seg
end
d.seg
0
d.se g
1

M
lcr 1
M
lcr 2

Switch

prg

M
Program Number

r-r

pid

styp

al-1

Alarm Value 1
c

0.0
M
c

Ral1h

0.0
M

Ra l1 l
c

0.0
M

Alarm Upper
Limit 1

Alarm Lower
Limit 1

al-2

Alarm Value 2

Alarm Upper
Limit 2

0.0
M

Ral2l
0.0
M

al-3

Alarm Lower
Limit 2

Alarm Value 3

0.0
M

Ral3h

0.0

Alarm Upper
Limit 3

al3l

0.0

Alarm Lower
Limit 3

Rrp t

sp

Segment n SP

Hold

Rpr

0.0
M

time

Segment n Ramp
Rate

Segment n Time

M
c- o MV Monitor (Cooling)

Hold

off

M
adv

0.0

M
V-m

Advance

Valve Opening

0.0 Monitor

off

M
stb m

Press the O
and M Keys for
at least 1 s.

0.0

0.0
M

M
o MV Monitor (Heating)

M
Remaining Standby

0.00 Time Monitor

M
Program
prg t Elapsed
Time Monitor

0.00
M

0.00

0.0
M

Ral2h

Segment n Format

Run/Reset

rst

M
No.
seg Segment
Monitor

ramp
M

Leakage Current 2

0.0 Value Monitor

PID Set No.

Leakage Current 1

0.0 Value Monitor

(See note.)

M
a-m Auto/Manual

Heater Current 2

0.0 Value Monitor

M
25.0 PV/SP

Program
Repetitions

lin k
end
M

Program Link
Destination

ts1 s

Time Signal 1

on1

Time Signal 1
ON Time

0 Set Segment
M

0.00
M

of1

M
rptm

Program Execution

0 Repetition Monitor

M
rsp Remote SP Monitor
0.0

Heater Current 1

ct1

0.0 Value Monitor

M
Time Signal 1

0.00 OFF Time


M

ts2s
0

Time Signal 2
Set Segment

on2
0.00

Time Signal 2
ON Time

of2

0.00

Time Signal 2
OFF Time

PF Key *2

Monitor/Setting Item Level


25 .0
0.0

Monitor/Setting
Item Display 1

(E5AN/EN-HT only)

Monitor/Setting PF
Item Display 2

PF

Monitor/Setting
Item Display 3

PF

Monitor/Setting
Item Display 4

PF

Monitor/Setting
Item Display 5

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to


5 parameters (advanced function setting level).

PF Key *2

*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT).

11

Operation for E5@N/E5@N-H/E5@N-HT

Press the O Key for at least 1 s.


Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display

Initial Setting Level


Press the O Key less than 1 s.

Press the O Key less than 1 s.

Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
to Protect Level:
pmov Move
Displayed only when a password
is set. Restricts moving to protect

0
M

level.

Communications
Setting Level

Operation/Adjustment

0
M

9.6

dp

len

d-u

Setting Change Protect

sbit
2

M
prty Communications Parity

pfptPF Key Protect


off

Send Data Wait Time

sl-l

SP Lower Limit

M
Password to Move to

s-hc

0
M

Standard or
Heating/Cooling

stnd
Control Period (Heating)

M
Control Period (Cooling)

20

Alarm 1 Type

Alarm 2 Type

Hysteresis

Alarm 3 Type

Alarm 3
Hysteresis

0.2
M

Tt-u

Program Time Unit

Time/Rate of
t-pr Step
Rise Programming

pru

Time Unit of
Ramp Rate

rtsm Reset Operation


p-on

Operation after Power ON

cont

eset

Operation at End of Operation

off

Extraction of Square
Root Enable

rst

tr-t

sqr

Travel Time

alh3

30
M

M
Alarm 2

0.2

stop

alt3

Motor Calibration

alh2

calb

M
Alarm 1
Hysteresis

0.2

flot
M

time

alt2

clfl Closed/Floating

h-m
M

alh1

Input
ev-4 Event
Assignment 4

or-r

Event Input
Assignment 3

off

orev Direct/Reverse Operation


alt1

ev-3

mot

20

c-cp

Event Input
Assignment 2

off

cp

ev-2

none
M

pid

Level:
prlp Protect
Password setting

Event Input
Assignment 1

none
M

none
M

cntl PID ON/OFF

on
M

ev-1

M
SP Upper Limit

-200.0
M

Linear Current Output

none

1300.0
M

20

Parameter Mask Enable

Temperature Unit

sl-h

even

sdwt

Decimal Point

Communications
Stop Bits

o1-t
4-20

Communications
Data Length

Transfer Output
Lower Limit

M
Scaling Lower Limit

off
M

pmsk

Communications
Baud Rate
CompoWay/F
only

tr-l
0.0

0
M

M
7

wtpt

M
bps

Initial Setting/
Communications Protect

in-l

Transfer Output
Upper Limit

M
Scaling Upper Limit

100
M

Communications
Unit No.

tr-h
100.0

in-h

oapt Protect

Input Type

Protocol Setting:
psel Switches between
cwf CompoWay/F and
Modbus.

u-no

icpt

in-t

Displayed only for models with communications. Changes


are effective after cycling power or after a software reset.

pvst PV Start
sp

M
Transfer Output Type

amov

Move to Advanced Function


Setting Level

12

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Manual
Control Level

Operation
Level

Program Setting
Level

Initial Setting
Level

Communications Setting
Level

Protect Level

Adjustment
Level

Monitor/Setting
Item Level

PID Setting
Level

Advanced
Function Setting
Level

Press the O Key for at least 1 s.


Advanced Function Setting Level

init

Parameter Initialization

cjc
on

off

a
M

sb1n
n-o

Standby Sequence
Reset

colr

PV Change Color

sub2

pv-b

PV Stable Band

Auxiliary Output 3
Open in Alarm

a2on Alarm 2 ON Delay

hbu

HB ON/OFF

a3on

hbl

Heater Burnout
Latch

a1of

Heater Burnout
Hysteresis

a2of

sb3n
n-o

0.1
M

alfa
at-g

at-h

20.0
M

inf

on
M

rt

Input Digital Filter

MV Display

ret
off

Automatic Display
Return Time

Move to Protect Level


Time

off
M

out1
o

out2
none
M

ocu

ocl
off

och

pf

0.25

ra2m

SV Status Display
Function

Display Refresh
Period

Control Output 1
ON/OFF Count
Monitor

M
0

Control Output 2
ON/OFF Count
Monitor

M
Manual MV
Limit Enable

ra1

Direct Setting of
Position Proportional MV

ra2

Control Output 1
ON/OFF Count
Alarm Set Value

M
0

Control Output 2
ON/OFF Count
Alarm Set Value

M
PV Rate of Change

rac
0

ON/OFF Counter
Reset

M
Automatic Cooling
Coefficient Adjustment

pend

Program End ON Time

0.0

M
Heater Overcurrent

Heater Overcurrent
Latch

s-u

Standby Time Unit

h-m

psad
off

Program SP Shift
Value Addition

M
Heater Overcurrent

0.1 Hysteresis

r-r
M

d.ref

PV Dead Band

rcad
off

RSP Broken-line
Correction
Display Addition

M
Control Output 2
Assignment

PV Status Display
Function

M
Control Output 1
Assignment

off

ra1m

M
LBA Band

M
Input Error Output

csca

svst

PID Set Automatic


Selection Hysteresis

on Use

sero

lbab

pvst

M
PID Set Automatic
Selection Data

lbal LBA Level

3.0

M
3

pvrp

off

M
Alarm 3 Latch

Remote SP Input
Error Output

M
LBA Detection Time

8.0

SP Tracking

17 Calculation Period

M
Alarm 2 Latch

off

prlt

HS Alarm Hysteresis

off

a3lt

lba

a2lt

pmvd
M

M
off

manl

off

0.1

a1lt Alarm 1 Latch

p-db

PV Decimal Point
Display

off

hsh

on

pidh

MV Display Selection

hsl HS Alarm Latch

off

pvdp

off
M

on
M

Remote SP
Lower Limit

off

pidi

"PV/SP" Display
Screen Selection

off

rseo

Monitor/Setting Item 5

odsl

0.0
HS Alarm Use

spdp

Remote SP
Upper Limit

M
RT

pfd5

0.50

hsu

sptr

Monitor/Setting Item 4

M
Remote SP Enable

M
Auto/Manual Select
Addition

off
Additional PV Display

rspl

pv

amad

rsph

pfd4

off

Limit Cycle MV
Amplitude

Alarm SP Selection

off

at Reset and Error


mvre MV
Addition

AT Hysteresis

off

o-dp

Input Shift Type

ins1

0.0
M

pvad

Alarm 3 OFF Delay

istp

rspu

Monitor/Setting Item 3

0
M

sp-m

-200.0
M

0.8
M

lcma

Alarm 2 OFF Delay

AT Calculated Gain

Character Select

1300 .0
M

1.0
M

alsp

pfd3
M

M
Alarm 1 OFF Delay

a3of

Auxiliary Output 3
Assignment

off

csel

Monitor/Setting Item 2

M
Alarm 3 ON Delay

0.65
M

sub3

Monitor/Setting Item 1

off
M

pfd2

on

on
M

hbh

Alarm 1 ON Delay

0
M

Auxiliary Output 2
Assignment

a1on

n-o
M

pfd1

alm3 (E5AN/E5EN-HT only)

5.0
M

Auxiliary Output 2
Open in Alarm

sb2n

Auxiliary Output 1
Assignment

M
Auxiliary Output 1
Open in Alarm

alm1

alm2
M

red

sub1

rest

Cold Junction
Compensation
Method

PF Setting

cmov
0

Move to Calibration
Level

13

Você também pode gostar