Brochure

High Power Laboratory, Ludvika, Sweden


Testing and third party certification of
power transmission and distribution
equipment

Integrity and Independence


well established and documented

Various kinds of high voltage electrical equipment such as circuit breakers, disconnectors, earthing switches, power transformers, instrument transformers, surge arresters, switchgear
cubicles etc; are tested at the High Power Laboratory in
accordance with the international or regional standards.

SATS is a member of STL (Short-circuit Testing Liaison), an


international organization of similar testing and certification
bodies. STL has framed the guidelines for uniform application
of the standards with regard to the test methods, measurement, evaluation and issue of type test reports/certificates.

Accreditation
The High Power Laboratory, Ludvika is accredited by
SWEDAC (Swedish Government Body) in accordance with
ISO/IEC 17025. The quality system, competence of personnel, adequacy of test equipment and calibration of measuring equipment are checked and assessed periodically
by SWEDAC for their compliance to ISO/IEC 17025. This
assures that the tests are performed correctly and impartially.

Strengthened by its long experience and reputation, the High


Power Laboratory, Ludvika lives up to the trustworthiness and
professionalism demanded of it by the clients.

Affiliation and International cooperation


The laboratory is affiliated to SATS, an independ ent certification body based in Scandinavia and accredited according to
EN 45011. SATS Certification issues Reports of Performance/
Type Test Certificates for tests performed at the High Power
Laboratory, Ludvika, under the supervision of its inspectors.

2 High Power Laboratory, Ludvika, Sweden

1297
ISO/IEC 17025
Affiliated to SATS Certification, an independent certification
body accredited acc. to EN 45011 and a member of the STLA
(Short-circuit Testing Liaison Agreement). Accredited by SWEDAC

Latest technology combined with long experience

Short-circuit testing was started in Ludvika 75 years ago in 1933


with the installation of the first short-circuit generator, at that time
the largest in the world. The testing technology since then has
been developed continuously contributing to the long collective
experience in the field. The present test station was established
50 years ago. The test and measuring equipment has been upgraded and modernized since then to meet the demands imposed by the ever increasing capacity of products to be tested
and their stringent standards.

High expectations and preparedness


The Laboratory is well geared to meet the requirements of the
clients for the development tests which require advanced test
and measuring equipment, experienced test engineers with
adequate knowledge of the products to be tested in order to
support the development process.
The type tests for certification needs the complete range test
circuits and measuring equipment fulfilling the requirements
of the standards. The Laboratory is equipped and accredited
for a wide range of such certification tests.
At the forefront
A fully automated modern synthetic test facility was established in 1996 replacing the first generation of synthetic test
circuit from the sixties. This combined with the two s.c. generators permit testing of high voltage circuit-breakers of voltage ratings up to 800 kV.
Measurement, data collection and analysis system is of the
most advanced technology available. With highly reliable and
accurate optically isolated measurements, automated calculation and presentation of test data, the Laboratory has been in
the forefront of development activities in this area.
The Laboratory has also established test facilities for
the operational tests of HVDC and SVC valves, a unique
resource, using both direct and synthetic test methods.

High Power Laboratory, Ludvika, Sweden 3

Adequate resources
a basic requirement

The large base of installed equipment is a necessity for performing the requested tests on various products. The laboratorys
resources have been augmented over the years in order to meet
with the changing requirements.
The laboratory is equipped with two short-circuit generators which together can deliver 4,000 MVA of short-circuit
power for direct testing. Together with the synthetic test
circuit a short-circuit power of over 75,000 MVA can be
realized in the laboratory.
There are nine test cells of different dimensions for testing of
various kinds of products. Apart from the high speed measuring system there exist facilities to record the test with high
speed digital video camera which can be synchronized with
the test oscillogram during playback to give a better understanding of the happenings during test.

In the High Current Laboratory, which is an integral part of the


High Power Laboratory, tests are performed with continuous
high currents to check the temperature rise limits of the
power equipment under normal operation conditions.
In the Mechanical Test Laboratory, also a part of the High
Power Laboratory, tests are performed on switching equipment such as circuit breakers in order to verify their mechanical endurance. Tests are also performed here to verify the
mechanical withstand properties of the components and the
fully assembled products.

Site overview
The High Power Laboratory is situated on the banks of lake
Vsman as a part of the ABB industrial complex in Ludvika.
ABB in Ludvika has been a leading center for development
and manufacturing of various high voltage transmission equipment for more than 100 years. The laboratory is spread over
an area of 15 000 sq. m which includes the high power, high
current and mechanical testing with over 20 test bays and a
large workshop.

High current testing

Workshop

The high voltage laboratory STRI, located next door, completes the type test facilities available in the location.
Mechanical testing

4 High Power Laboratory, Ludvika, Sweden

Synthetic test circuit

CurrentCurrent
circuit circuit
MB

Test circuit
Test circuit

MS

Voltage circuit

Voltage circuit

AB

AL

LH
RE

GR

LB
CH

TB

GS

LF
Cd

CE

RB

ML
CB

Synthetic test facility

Generators

Test cells

Test cells

ce
Control room and offi

High Power Laboratory, Ludvika, Sweden 5

Test facilities

Direct testing

Synthetic testing

Max. short-circuit power

4000 MVA

Single-phase test

550 kV, 80 kA

Max. test voltage 3

145 kV

Three-phase test

245 kV, 63 kA

Max. test voltage 1

250 kV

Main capacitor banks

6.7 MJ

Frequency

16 2/3 60 Hz

Two circuits

880 kV d.c.

Max. test current

100 kA rms

4-parameter TRV and a.c. recovery voltage


Short-circuit making tests with time delay less than 5 s
Capacitive current switching testsl

Other test facilities


Temperature-rise test

Up to 25 kA rms

HVDC thyristor valves (direct and synthetic tests)

Measurement and control

Power frequency voltage test

600 kV rms

Fast digital transient recorders with optic-fibre isolated digitizers located in

Mechanical tests

endurance

test cells

snap-back

High speed digital video recording system

cantilever

Automated data processing system, in accordance with IEC and STL

tightness

guidelines

environmental

Fully-automated control systems for short-circuit generators and synthetic


test circuits
High current measurements traceable to the STL reference shunt

New generation measurement system

Optic fiber isolation and


high speed recording
(100 MSa/s) in all channels

Automatic measurements for quicker evaluation

6 High Power Laboratory, Ludvika, Sweden

Short time withstand current


Short-circuit making capacity
Short-circuit breaking capacity
Short-line fault
Out-of-phase
Line-charging switching
Cable-charging switching
Capacitor bank switching
Shunt reactor switching
Temperature-rise tests
Internal-arc tests

Induced current switching

Ferro-resonance
Breaking capacity
Service duty tests
Power arc tests

Reactor & line-traps

Insulators sets

On-load tap changers

Transient performance

Mechanical endurance

Voltage transformers

Switch-fuse units

High voltage switches

Bus-transfer current switching


Pressure-relief

Current transformer

Surge arresters

Power transformers

Metal enclosed switchgear

HV circuit breakers

Test

MV circuit breakers

Equipment

Disconnector & earthing switch

Feasible tests

High Power Laboratory, Ludvika, Sweden 7

ABB AB
High Power Laboratory
SE-771 80 LUDVIKA, SWEDEN
Tel: +46 (0)240 78 26 06
Fax: +46 (0)240 78 26 19
E-mail: highpowerlab@se.abb.com
www.abb.com/highvoltage

NOTE! ABB AB is working continuously to improve the products.


We therefore reserve the right to change designs, dimensions and
data without prior notice.

Copyright 2010 ABB, All right reserved. Publication 1HSM 9543 52-01en, High Power Laboratory, Edition 2, 2010-11. Design: byBrick. Print: www.henningsons.se

Contact us

TEST REPORT

BQ 07-206 Rev .1

2009-10-01

SUBJECT

Type-tests

TYPE OF APPARATUS

SFs-gas circuit-breaker type LTB 170D1 /B


with operating mechanism type FSA1 (single-pole operation)

RATINGS

170 kV, 3150 A, 50 Hz, 40 kA, -30C, LIWL 750 kV

STANDARDS

IEC 62271-100, 2006, Ed .1.2

MANUFACTURER

ABB AB , Ludvika, Sweden

REFERENCE DOCUMENT

Type-tests are summarized in Document BT 909 Rev.1

The test reports constituting the summary of type-tests are:


Description

Document

- Dielectric tests

SATS 04-S07

- Temperature rise tests

SATS 03-A30

- Mechanical and environmental tests

SATS 07-A34
ETksP703478

- Short-time current test

SATS 03-A42

- Making and breaking tests

SATS 03-A42
SATS 04-A13
SATS 03-A57

I hereby certify that the values obtained and the performance of the
apparatus during the tests justify the relevant ratings assigned by
the manufacturer.

ABBAS

;:
~Z?E"it Breakers
Lennart Eriksson
Quality Department

ABBAS
~~

FOrfattare- Author

Natasa Tomljanovic, PPH/H8/8T


Godkannare - Approved by

.-1 /)

Anders Alfredsson , PPH/H8/8T /'-1'-j

Rapport
Report

Fran- From

Datum-Date

PPH/H8/8T

2009-09-09

Utredning teoretisk

Christer Gustavsson , PPH/H8/8D

mental investigation

lvl Slulrapport

Pki!Akl

Delrapport
Partial report
Anlal l extsidor- No. of text pages

~ Final report

11

Provning/undersokning avslulad

Antal bilagesidor - No. or supplem. pages

Tesllinvesligalion finished

LIWL 750 kV, IEC.


Sammanfattning - Summary

Sheet

Revision 1:

D1slribulion

Enbart sida1 -Page 1 only

Debileras ordernr - Debit Order No

lvl sokning- Test experi-

tests for single-pole operated


SF5-gas circuit-breaker type LT8 17001/8
170 kV, 3150 A, 50 Hz, 40 kA, -30C,

1 (11 )

undersOkning -Analysis,
theoretical investigation

with operating mechanism type FSA 1

Sida- Page

. dat a an d SUmmary 0 f typeRa t .lngS, d es1gn

Tilel -Tille

Reg

Ordernr- Ref. No

Provning, experim. under-

Uppdragsgivare - Requested by

BT 909 Rev.1

Ratings

Design data

3-5

Summary of type-tests

6 - 11

Low and high temperature test updated (page 6)

ABBAS

BT909 Rev.1
Page 2

RATINGS
Apparatus

SFs-gas circuit-breaker type LTB 17001/8

RATINGS ASSIGNED BY THE MANUFACTURER:


Voltage ....... .

170

kV

Insulation level:
Lightning impulse withstand voltage:
Phase to ground .. .... .
Across the open switching device .

750
750

kV (peak)
kV (peak)

325
325

kV (rms)
kV (rms)

Normal current...........................................................................

3150

Frequency ................. .

50

Hz
kA
%

Minimum opening time

40
43
28

Transient recovery voltage:


Rate of rise ......................................... ..
Peak voltage ....................................... ..

291

First pole to clear factor

1.5

Short-line fault characteristics:


Surge impedance ......................................... .
Peak factor ................................................. .

450

Short-circuit making current ....................................... .

100

kA (peak)

Out-of-phase:
Breaking current ..................... .
Out-of-phase voltage factor ...................................... ..

10.0
2.5

kA

100

kA (peak)

Power frequency withstand voltage:


Phase to ground ........ ...... .. ...... ..... .. ...... .... .
Across the open switching device .. .

Short-circuit breaking current:


a.c. component rms value .............. ..
d.c. component..

Short-time current:
Peak withstand current .
Short-time withstand current ..................................... .
Duration ........................................ .
Capacitive current switching capability:
Line-charging breaking current .
Cable-charging breaking current
Voltage multiplying factor ................................... .
Class ........... ..
Supply voltage:
Closing device
Opening device

ms

kVi)lS
kV

ohms

1.6

40

kA

63
160
1.4

A
A

C2
110 or 220
110 or 220

Vd.c.
Vd.c.

Operating sequence

0- 0.3s- CO- 3m in- CO

Mechanical endurance class

M2

Interrupter pressure at 20C

0.7

MPa(abs)

,.,Jlllll
......

ABBAB

BT 909 Rev.1
Page 3

DESIGN DATA
Apparatus

SFs-gas circuit-breaker type LTB 17001/B

DESCRIPTION
The SF5-gas circuit-breaker type LTB 170D1/B is of the auto-puffer type intended for use in
conventional open air switchyards.
The circuit breaker consists of three breaker poles each connected by mechanical linkage to an
operating device. The operating devices are provided with shunt releases for closing and
opening operation and has motor-charged closing spring for closing of the circuit-breaker.
During the closing operation the opening spring is charged.
The breaker pole consists of a breaking unit with two main circuit terminals, a hollow support
insulator enclosing the insulating pull rod and a link gear in a housing of cast aluminum. The
circuit-breaker poles are mounted on a common pole beam.
The breaking unit consists of an upper and a lower main circuit terminal and a breaking chamber
insulator containing upper and lower current collectors and a sliding auto-puffer unit with its
moving main and arcing contacts, compression cylinder, self-blast chamber and extinguishing
nozzle. The upper current path with the fixed contacts is connected to the upper terminal and the
lower terminal connects the lower current path with the auto-puffer unit.
The auto-puffer unit is connected to the linkage system in the mechanism housing through the
insulating pull rod inside the support insulator.

TECHNICAL INFORMATION
Type of circuit-breaker

LTB 170D1/B

Minimum clearance between live parts and earth

See dimension print

Total length of break per pole

68 mm

Number of breaks per pole


Mass of complete circuit breaker

See dimension print

Resistance in main circuit

:>40 f.lO

Closing time

s 75 ms

Opening time

28-35 ms

Break time

s 50 ms

Gas pressure range at 20C

0.60-0.70 MPa(abs)

Rated power consumption at rated operating voltage:


Closing coil

500W

Opening coil

500W

Maximum terminal load:


Static
Dynamic

1500 N
3000N

Jl 1111
,.,II' II'

ABBAB

BT 909 Rev.1
Page 4
DESIGN DATA

Apparatus

SFs-gas circuit-breaker type LTB 17001/B


Ambient temperature

-30C to +40C

Earthquake withstand capability

0.5 g

Circuit-breaker operating mechanism

One device type FSA1/pole

Method of closing

Through stored energy in closing


springs ensuring trip-free closing.

DRAWINGS
Insulator type

Composite

Porcelain

Product specification, list

1HSB495452-DA

1HSB495452-DA

Produkt specification, assembly drawing

1HSB495452-DB

1HSB495452-DB

Dimension print

1HSB425450M401

1HSB425450M401

Breaker unit, list

1HSB425412-T

1HSB425412-T

Breaker unit, assembly drawing

1HSB425412-U

1HSB425412-U

Breaking chamber insulator

1HSB422732-W

1HSB422732-B

Upper current path, assembly

2GBD000005-002

2GBD000005-002

Insulator rod, detailed drawing

1HSB422184-CZ

1HSB422184-CZ

Puffer unit, assembly drawing

2GBD000567

2GBD000567

Puffer cylinder

2GBD000013

2GBD000013

Nozzle

2GBD000017

2GBD000017

Tulip contact

2GBD000016

2GBD000016

Lower current path, assembly

2GBD000045

2GBD000045

Post insulator, assembly

1HSB422732-X

1HSB422732-C

Operating mechanism type FSA 1, list

1HYB400572-A

1HYB400572-A

Note:

Some of the tests referred to, are performed on circuit-breaker type LTB 14501/8 with operating mechanism BLK 222. Circuit
breakers LTB 14501/8 and LTB 17001/B are equipped with the identical breaking chambers and the travel characteristics of
the operating mechanism types BLK 222 and FSA1 are identical. Hence, the tests performed on LTB 14501/8 with operating

mechanism BLK 222 are also valid for LTB 17001/B with operating mechanism FSA 1.

jl 1111
Jill I I

~408

5. OYNA~IC FORCE AT OPERATION.


QYNAMiSK KRAFT VIO MANOVRERING

.""

<D
~

'<
"C
<D

,...
-1
tD

6. CLEAR SPACING FOR REViSION.


FRITT AVST AND FOR REVIS:CN.

....0

7. BREAKER CHA~,SER INSULA:OR.


8RYTKAMMARISOLA!\T,

B. POST :NSULA TOR

STODISOLANT.

!~; !

to

9. OPEN/CLOSED INDICA TOR.


TUIFRAN INDIKERiNG.

qq!
~~3il !!

'"'"
~
!~~-!< ~

DENSiTETSVAKT.

(/)

11. MASTER CUB:CLE.

P~P ~

MASTER SKAP.

" 8 ~ "'

hh~

12. SLAVE CUBICLES.


SLAV SKAP.

4545

;g~~@

'"

I"
,N

(HORIZO~T AU

.......

...
--...-~~

~ ~t?cW'.'l.\'.1'1~'
'1 \

""I''
1i \

~~

''.
~ 'l ''. ,_
..... : ,'
'

.t;C()t1

";;o

lz
-1

Sft- BREAKER LTB 1700118 WITH OPERATiNG MECHANISM TYPE FSA~


SF(,- BRYTARE LTB 1700118 MEO MANOVERDON TYP FSA1

l.tfl.IJ
'I ~~I

i~-

C GtJStaVSSOO

;;.w:;,-.--

'
1-+"..001
'

"""'

~4(7x)

15000 N IVERTICAU

2000

lc

!I 1":

!\

/..
11 ' fir1~'1
;t
\._!I I~ \

ro' I li

!;'::'!

s:

10. DENSITY SWITCH.

.;E~!:

00

1:

I VILKEN RiKTNING SOM KELST.

1f
;h t

ru

(jJ

N STATJ 3000 N DYN.

G. HOLES FOR EARTHING CLAMP.


HAL FOR JORDNINGSKLAMMA.

"
"
.,.;:;:'

.A

3. TERMINAL LOAD: MAX 1500 N STAT


/3000 N OYN IN ANY DIRECTION.
BELASTNING I ANSLUTNING: MAX.

~.

."'

)>
OJ
OJ
)>
OJ

:;

2. TERMINAL OF ALUMINfJM, T -20.


Al\'SLUTN,"lGSPLATTA AV ALUMINIIJt',,

~500

;p

co'

1. CABLE INLET SIZE SEE FIG.


KA8EUNTAG STORLEK SE FIG.

0zzJ
i zzzl
'-'..!
..... !-=-!

(J)

lai' ""w

r-zc.

255

~~~ 1j

2/lln[ooooo] o~

2067

"

2007..()6.12 )PPiH/1-IViBD
2001..00.1~

1'"'""'""--~

,.

SF6 CIRCUIT BREAKER

lcP,...;:;,,.._

SF6 BAYTAAE

' en

'"""'""'"':'

1~""""""1 J

''

tD
-1

<D

-u
ru
(0

<D

(1)

:<

01

~
~

ABBAB

BT 909 Rev.1

Page 6
DIELECTRIC TESTS
Type of test

Standard

Lightning impulse voltage test U

IEC 62271-100

1 .2/50 )..I.S, pes + neg

CL 6.2.6.2

Power frequency voltage test, 60 s

IEC 62271-100

Phase to earth

Dry

Test value

750

750

Between phases

750

Across open gap

750

750

325

365

Phase to earth

Dry

kV, rms

Between phases

325

Across open gap

325

365

325

325

Cl. 6.2.6.1

Wet

Phase to earth

kV, rms

Between phases

325

Across open gap

325

Power frequency voltage test on

IEC 62271-100

Control and auxiliary circuit

auxiliary and control circuits, 60s

CL6.2.10

as a whole to earth

Radio interference voltage test

lEG 62271-100

Test Voltage

Cl. 6.3

kV, peak

Requirement

Breaker Open

V,rms

SATS 04-807 1l

325

2000

kV, rms

108

108

J.IV, rms

<2500

422

<2500

19

Breaker Closed

Reports

SATS 04-$07 ll

TEMPERATURE RISE TESTS


Temperature rise test

Standard

Requirement

Test value

Circuit-breaker with plug-in contacts

IEC 62271-100

Test current

A,rms

3150

3150

at normal current until steady-state

Cl. 6.5

Contacts

dT, (K)

S:65

46.1

conditions

Connections

s:75

47.6

(Temperature rise< 1 K!hour)

External contacts

s:65

36.3

Auxiliary and control circuits

IEC 62271-100
Cl. 6.5.5

Test Voltage, Open/Close coils

v, d.c.

110

Open/Close coils, Class E

dT, (K)

<80

Reports
SATS 03-A30 2l

<80

Motor, Class E

MECHANICAL AND ENVIRONMENTAL TESTS


Mechanical and environmental tests

Standard

Mechanical operation test on circuitbreaker at ambient temperature

IEC 62271-100
Cl. 6.101.2

Number of operating cycles

Low and high temperature test

IEC 62271-100
Cl. 6.101.3

Test temperature

Class

Requirement

Test value

10 000

10 000

SATS 07 -A34 2 l

-30

-50

ETksP703478 4 l

+40

+70

Reports

M2

l Test performed on circuit breaker type LTB 17001/B with operating mechanism BLK 222
lTest pertormed on circuit breaker type LTB 14501/B with operating mechanism BLK 222
lTest performed on circuit breaker type LTB 14501/8 with operating mechanism FSA1
4
l Test performed on circuit breaker fiilled with gas mixture 52%SFtl48%N 2

2
3

Jl 1111
,.,1111

ABBAS

BT 909 Rev.1

Page 7

SHORT-TIME WITHSTAND CURRENT AND PEAK WITHSTAND CURRENT TEST


Performed in accordance with IEC 62271-100, Cl. 6.6
Requirements
Peak current

Short-time current

Duration

kA, peak

kA, rms

100
1

Corresponding test

40

Peak current

Short-time current

Duration

Report

k.A, peak

kA, rms

No.

108

41.2

3.04

SATS 03-A42

>

>Test performed on circuit breaker type LTB 170 01/B with operating mechanism BLK 222

,.,
Jlllll

ABBAS

BT 909 Rev.1
Page 8

SHORT-CIRCUIT MAKING AND BREAKING TESTS


Performed in ace. with IEC 62271-100, CL 6.106

T10

Test duty

No. of poles
Requirements

Operating sequence

T60

T1 oos (a)

T100S (b)

nooa
1
0-3min-O3min-O

0-0.3s-CO-

0-0.3s-CO-

3min-CO

0-0.3s-CO3min-CO

C-3min-C

3min-CO

0-0.3s-CO3min-CO

98

98

Making

appl. volt.

kV

peak current

kA

100

100

Make/break current

a.c. comp.

kA

4 (20%)

12 (20%)

24 (10%)

40

40

40

d.c. camp.

<20

<20

<20

<20

<20

51

kV

147

147

147

147

147

kV

208

208

,,"'

kV

156

156

156

gS

52

78

78

uc

kV

312

291

291

312

312

312

Recovery voltage

a.c.
equiv. d.c.

TRV

11

208

319

321

gS

46

64

gS

10

2-16

Making

"

appl. volt

kV

22.0-22.9

21.7-22.7

22.7-23.2

144

peak current

kA

5.5-6.4

16.0-18.8

36.0-40.1

59.4

63.4-108

Make/break current

a.c. camp.

kA

4.1-4.3

11.6-12.5

23.8-24.7

40.8

40.5-41.3

41.4-41.8

d.c. camp.

<20

<20

<20

<20

<20

28-37 ~)

)<S

'2

"

t3

Corresponding

T30

tests

d.c.

kV

Measured TRV peak value

kV

Prospective TRV

Recovery voltage

,,"'
uc

t2
t3

Reports

"

"

209-210

61

219-221

S)

136-139

31

25.7-26.8

102-103

31

105-115 31

314-321

251-252

267-290

kV

173

147

166

'"kV

57

67

81

316

256

294

275

242

291

2.7

1.1

1.7

SATS 04-A13

SATS 03-A42

245-322

324

321-323

329

,,,'"

45

66

,.s

4.7

4.4
SATS 03-A42

71

"

,,

11
21

ln case of synthetic testing with d.c. recovery voltage (current injection method)
In case of two parameter TRV
1 a.c. recovery voltage after 0.1s
41
d.c component measured at current zero
51
Test performed on circuit breaker type LTB 14501/8 with operating mechanism BLK 222
61 Recovery voltage at Trf8
71
Test performed on circuit breaker type LTB 17001/B with operating mechanism BLK 222
3

,.,II
Jl 1111

ABBAS

BT 909 Rev.1
Page 9

SHORT-LINE FAULT TESTS


Performed in ace. with IEC Publ. 62271-100, Cl. 6.109

Test duty

L9o

L7s

0 -0.3s- CO -3min- CO

0 -0.3s- co -3m in- co

kA

36

30

kV

98

98

104

No. of poles
Requirements

Operating sequence

a.c. comp.

Breaking current

a. c.

Recovery voltage

equiv. d.c.

TRV

"1

kV

104

side

t1

)IS

52

52

"c

kV

194

194

t2

)IS

208

208

'3

" "s

to

"s

2.0

2.0

Um

kV

189

180

ur

kV

24.5

67.0

toL

)IS

01

0.1

Stat

kVhts

7.4

69

a.c. camp.

kA

36.5-38.3

kV

80.7-81.2 31

80.6-82.5 31

Um

kV

189-191

182-195

source

"1

kV

107

107

side

t1

"s

52

52

"c

kV

196

196

t2

)IS

177

177

t3

" "s

to

)IS

1.5

1.5

source and

um

kV

193

186

fine side

ur

kV

28.5

72.5

toL

"s

0.1

0.1

Stat

kV/~s

source and

Corresponding

Breaking current

Recovery voltage

31

Measured TRV peak value


Prospective TRV

kV

source

line side

tests

,,

Report
11

7.83

7.86
SATS 03-A42

41

In case of synthetic testing with d.c. recovery voltage (current injection method)

21 In case of two parameter TRV

31
4

a. c. recovery voltage after 0.1s


l Test performed on circuit breaker type LTB 17001/B with operating mechanism BLK 222

,.,Jlllll

ABBAS

BT 909 Rev.1

Page 10
OUT-OF-PHASE MAKING AND BREAKING TESTS
Performed in ace. with IEC

62271~ 100,

CL 6.110

Test duty

Out-of-phase Test duty No. 2

No. of poles
Requirements

C-0-0-0

Operating sequence
Making

Breaking current

Recovery voltage

appf. volt

kV

peak current

kA

a.c. camp

kA

10

d.c. comp.

<20

kV

245

kV

347

"1

kV

260

t1

,,s

156

uc

kV

434

'2

,s

312-624

a.c.
equiv. d.c

TRV

t3

Corresponding

Making

tests
Make/break current

196

,,

"

'"

,s

2-16

appl. volt.

kV

352

peak current

kA

17.3

a.c. camp.

kA

10.4-10.5

d.c. camp.

<20

"

Recovery voltage

kVa.c

183-184

31

Measured TRV peak value

kV

435-436

Prospective TRV

u1

kV

320

t1

189

uc

'"kV

443

'2

,s

513

t3

Report

"

"

pS

us

6.3
SATS 03-A42 41

11 In case of synthetic testing with d.c. recovery voltage (current injection method)
21 In case of two parameter TRV
31
a.c. recovery voltage after 0.1s
41
Test performed on circuit breaker type LTB 17001/B with operating mechanism BLK 222

,.,Jlllll

Page No.1 (54)

SATS

Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Report of Performance No. 04-807


ABB Power Technology Products AB, High Voltage Products, Ludvika,
Client
Sweden
Test object

A three -pole operated SF6-gas circuit-breaker type


LTB 17001/B

Designation

Circuit breaker LTB 17001/B


Operating mechanism BLK 222

Manufacturer

ABB Power Technology Products AB, High Voltage Products

Ratings assigned by
the manufacturer

Nominal voltage
Nominal current
Rated frequency
Rated gas-pressure
Lock-out gas-pressure

Tests performed

Test object in closed and open position:


Power frequency withstand voltage test, wet, level 325 kV rms 50Hz
Power frequency withstand voltage test, dry, level 365 kV rms 50Hz
Lightning impulse withstand voltage test, wet, level 750 kV
Chopped lightning impulse withstand voltage test, wet, level 968 kV
Radio Interference voltage test (RIV) at 108 kV rms 50Hz

Standards

IEC 60060-1,1989; IEC 62271-100, 2001; IEC 60694, 1996, ANSI C37.06,
C37.09, NEMA107 1987

Testing station

STRI AB, Ludvika, Sweden


The laboratory is accredited (no: 1534) by SWEOAC

Date of tests

20 August- 5 September, 2003

Test results

The test object fulfilled the requirements in accordance with the


standards
No flashover or puncture occurred.
RIV at 108 kV measured according to: IEC
max. 422 f.LV
Nema max. 44 flV

The documents
forming this report

Title page and 54 numbered pages

Ludvika 2004-05-15
Place and date

Serial No. 8665 487


Serial No. 8665 488

170 kV
3150 A
50/60 Hz
0.70 MPa (abs) at 20 C SF6-gas
0.60 MPa (abs) at 20 C SF6-gas

Page No.2 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

Contents

RoP No. 04-S07

Page

List of drawings of the test object............................................................................................... 3


1 Test object ........................................................................................................................... 4
2 Tests .................................................................................................................................... 4
2.1 Lightning impulse withstand voltage test ......................................................................... 5
2.2 Chopped lightning impulse withstand test ....................................................................... 6
2.3 Radio Interference Voltage test (RIV) IEC....................................................................... 6
2.4 Radio Interference Voltage test (RIV) NEMA ............................................................... 10
2.5 Power frequency withstand voltage test, dry ................................................................. 11
2.6 Power frequency withstand voltage test, wet................................................................. 11
3
Atmospheric conditions and correction factors................................................................ 12
4 Test circuits........................................................................................................................ 13
4.1 Test circuit for the lightning impulse withstand voltage test .......................................... 13
4.2 Test circuit for power frequency withstand voltage test................................................. 13
5 Dimension drawing ............................................................................................................ 14
6 Photograph of the test object ............................................................................................ 15
7 Oscillograms................................................................................................................. 16-54
The tests were witnessed by:
Mr. Gran Olsson, representing SATS Certfication, Norway

Page No.4 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Test object
Three-phase operated SF6-gas circuit breaker

Circuit breaker
Type
Serial No.
Rated gas pressure
Lock-out gas pressure

LTB 170 D1/B


8665 487
0,7 Mpa (abs) at 20 oC SF6-gas
0,6 Mpa (abs) at 20 oC SF6-gas

Operating mechanism
Type
Serial No.

BLK 222
8665 488

Tests
Power frequency withstand voltage test, wet, level 325 kV rms 50Hz
Power frequency withstand voltage test, dry, level 365 kV rms 50Hz
Lightning impulse withstand voltage test, wet, level 750 kV
Chopped lightning impulse withstand voltage test, wet, level 968 kV
Radio Interference voltage test (RIV) at 108 kV rms 50Hz according to Nema 107 and
IEC62271-100
The test object is considered to be fully symmetrical.
As references the following designations have been used in this report.
Terminal A, B = upper terminal
Terminal a, b = lower terminal
F= frame
The frame was connected to ground during all the tests.
All tests were performed at lock-out gas pressure.
Three oscillograms and the oscillograms from the reduced impulse of each test
position are included in this report. See pages 16-54
All oscillograms are available on request.

Page No.5 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


2.1
Level

RoP No. 04-S07

Lightning impulse withstand voltage test


750 kV Test object in open position

Measured
voltage
(kV)
449
750
461
754
750-754
747-750
447
747-750
443
750-754
443
754
443
747-754

Polarity

Voltage
applied to

Earth
connected to

Number of
impulses

Oscillogram
number

Positive
Positive
Negative
Negative
Negative
Positive
Positive
Positive
Negative
Negative
Negative
Negative
Positive
Positive

A
A
A
A
a
a
b
b
b
b
B
B
B
B

a-F
a-F
a-F
a-F
A-F
A-F
B-F
B-F
B-F
B-F
b-F
b-F
b-F
b-F

1
15
1
15
15
15
1
15
1
15
1
15
1
15

1
4-18
19
20-35
37-51
58-72
137
140-154
156
157-171
172
173-188
189
190-204

No flashover or puncture occurred.


Level

750 kV Test object in closed position

Measured
voltage
(kV)
449
746-750
740-754
436
750-757
743-750

Polarity

Voltage
applied to

Earth
connected to

Number of
impulses

Oscillogram
number

Positive
Positive
Negative
Negative
Negative
Positive

A, a
A, a
A, a
B, b
B, b
B, b

F
F
F
F
F
F

1
15
15
1
15
15

73
74-89
91-105
106
107-121
122-136

No flashover or puncture occurred.

Page No.6 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


2.2
Level

RoP No. 04-S07

Chopped lightning impulse voltage test


968 kV Test object in open position

Measured
voltage
(kV)
960-970
786-1002
986-992
976
997-1002
997-1013
997-1002
970-976

Time to
chop
( s)
2,09-2,26
2,23-2,42
2,25-2,38
2,16-2,26
2,33-2,50
2,04-3,07
2,79-2,97
2,33-2,48

Polarity

Positive
Negative
Negative
Positive
Positive
Negative
Negative
Positive

Voltage
Earth
applied to connected to

Number of
impulses

Oscillogram
number

3
3
3
3
3
3
3
3

219-221
222-224
225-227
231, 232, 234
251-253
254-256
257-259
261-263

Earth
connected to

Number of
impulses

Oscillogram
number

F
F
F
F

3
3
3
3

235-237
238-240
241-243
246-248

B
B
b
b
a
a
A
A

b-F
b-F
B- F
B-F
A-F
A-F
a-F
a-F

No flashover or puncture occurred.


Level

968 kV Test object in closed position

Measured
voltage
(kV)
981-992
1008-1018
986-1002
981-992

Time to
Polarity
Voltage
chop
applied to
( s
2,18-2,23 Positive
B, b
2,44-2,64 Negative
B, b
2,65-2,94 Negative
A, a
2,21-2,36 Positive
A, a

No flashover or puncture occurred.

2.3

Radio Interference Voltage test (RIV) IEC

Level 108 kVrms Test object in closed position


Voltage applied to: A, a
Earth connected to: B ,b, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59
69
79
88
98

RIV-level
V)
17
17
11
11
11
11
7
7
7
7
7
11
11
11
11
11

Time
(minutes)
5

Page No.7 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


108
98
88
79
69
59
49
39
29

19
11
11
11
11
11
11
4
4

Background noise level before the test: 4 V


Background noise level after the test: 4 V
Level 108 kVrms Test object in open position
Voltage applied to: A
Earth connected to: a, B, b, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59
69
79
88
98
108
98
88
79
69
59
49
39
29

RIV-level
V)
422
33
24
21
13
11
11
11
11
11
11
11
11
17
27
42
422
42
27
24
17
11
11
4
4

Background noise level before the test: 4 V


Background noise level after the test: 4 V

Time
(minutes)
5

RoP No. 04-S07

Page No.8 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


Level 108 kVrms Test object in open position
Voltage applied to: a
Earth connected to: A, B, b, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59
69
79
88
98
108
98
88
79
69
59
49
39
29

RIV-level
V)
53
42
27
19
7
7
7
7
4
7
7
11
15
24
33
42
53
42
27
17
11
11
7
4
4

Time
(minutes)
5

Background noise level before the test: 4 V


Background noise level after the test: 4 V
Level 108 kVrms Test object in closed position
Voltage applied to: B, b
Earth connected to: A, a, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59

RIV-level
V)
33
24
21
19
11
11
11
7
4
7
7
11

Time
(minutes)
5

RoP No. 04-S07

Page No.9 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


69
79
88
98
108
98
88
79
69
59
49
39
29

15
24
33
42
33
24
21
17
11
11
7
4
4

Background noise level before the test: 4 V


Background noise level after the test: 4 V

Level 108 kVrms Test object in open position


Voltage applied to: b
Earth connected to: A, a, B, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59
69
79
88
98
108
98
88
79
69
59
49
39
29

RIV-level
V)
60
53
42
27
17
11
7
7
4
7
7
11
15
24
27
42
60
53
27
17
11
11
7
4
4

Background noise level before the test: 4 V


Background noise level after the test: 4 V

Time
(minutes)
5

RoP No. 04-S07

Page No.10 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


Level 108 kVrms Test object in open position
Voltage applied to: B
Earth connected to: A, a, b, C, c, F
Applied voltage
(kV)
108
98
88
79
69
59
49
39
29
39
49
59
69
79
88
98
108
98
88
79
69
59
49
39
29

RIV-level
V
33
24
17
11
7
7
7
7
4
7
7
7
11
11
17
24
33
24
17
11
11
7
7
4
4

Time
(minutes)
5

Background noise level before the test: 4 V


Background noise level after the test: 4 V

2.4

Radio Interference Voltage test (RIV) NEMA

RIV measurement at 108 kV, 50 Hz applied voltage


The background level was measured to 2 V
Measured
voltage
(kV)
108
108
108
108
108
108

Voltage
applied to

Earth
connected to

RIV level
( V)

Breaker
position

A, a
a
A
B
b
B, b

B, b, C, c, F
A, B, b, C, c, F
a, B, b, C, c, F
A, a, b, C, c, F
B, A, a, C, c, F
A, a, C, c, F

19
44
26
21
58
41

closed
open
open
open
open
closed

RoP No. 04-S07

Page No.11 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


2.5

RoP No. 04-S07

Power frequency withstand voltage test, dry

Level 365 kV

rms

50Hz

Measured
voltage
(kV)
365
365
365
365
365
365

Voltage
applied to

Earth
connected to

Breaker
position

Time
(sec)

A, a
a
A
B
b
B, b

B, b, C, c, F
A, B, b, C, c, F
a, B, b, C, c, F
A, a, b, C, c, F
B, A, a, C, c, F
A, a, C, c, F

closed
open
open
open
open
closed

60
60
60
60
60
60

No flashover or puncture occurred

2.6

Power frequency withstand voltage test, wet

Level 325 kV rms 50Hz


Measured
voltage
(kV)
325
325
325
325
325
325

Voltage
applied to

Earth
connected to

Breaker
position

Time
(sec)

A, a
a
A
B
b
B, b

B, b, C, c, F
A, B, b, C, c, F
a, B, b, C, c, F
A, a, b, C, c, F
B, A, a, C, c, F
A, a, C, c, F

closed
open
open
open
open
closed

60
60
60
60
60
60

No flashover or puncture occurred

Precipitation rate during the wet tests


Pole A:
Pole B:
Resistivity:

98

1,3 mm/min vertical component


1,2 mm/min horizontal component
1,3 mm/min vertical component
1,0 mm/min horizontal component

Page No.12 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


3

Atmospheric conditions and correction factors


Correction factors for external insulation calculated according to:
IEC 60060-1:1989 cl. 11.
Correction factor for dry tests: Kt=k1*k2
Correction factor for wet tests: k1
k1=air density correction factor
k2=humidity correction factor
Lightning impulse withstand voltage test, level 750 kV
t=20C
k1=0.99

b=992 mbar
k2=0.97

h=8.1 g/m 3
Kt =0.96

Chopped lightning impulse withstand voltage test, level 968 kV


t=20C
k1=0.99

b=992 mbar
k2=0.98

h=8.1 g/m 3
Kt =0.97

Power frequency withstand voltage test, dry, level 365 kV, 50 Hz


t=20C
k1=0.99

b=992 mbar
k2=0.99

h=8.1 g/m 3
Kt =0.98

Power frequency withstand voltage test, wet, level 325 kV, 50Hz
t=20C
k1=0.99

b=992 mbar
k2=0.99

Kt=1.00 applied in all tests.

Kt =1,0

RoP No. 04-S07

Page No.13 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


4

4.1

RoP No. 04-S07

Test circuits

Test circuit for the lightning impulse withstand voltage test


Voltage
divider

Rs=200

Ru

C=0.9 nF

Cg= 37,5 nF
R pg=1,8k
Testobject

R=150
Rsg=192

Impulse generator

Equipment used in the test:


Haefely SVG 1600 kV impulse generator.
Haefely CR 1600 impulse voltage divider.
Haefely DIAS 730 impulse registration system.

4.2

Test circuit for power frequency withstand voltage test


Voltage
divider

Testobject

Transformer

Equipment used in the tests:


ABB test transformers 400 kV no. 27931 and control desk C.
Haefely KK600 voltage divider.

Page No.14 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


5

Dimension drawing

RoP No. 04-S07

Page No.15 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


6

Photograph of the test object at the RIV test

Set-up in testing hall

RoP No. 04-S07

Page No.16 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment


7

Oscillograms

RoP No. 04-S07

Page No.17 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.18 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.19 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.20 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.21 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.22 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.23 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.24 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.25 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.26 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.27 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.28 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.29 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.30 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.31 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.32 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.33 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.34 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.35 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.36 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.37 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.38 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.39 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.40 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.41 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.42 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.43 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.44 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.45 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.46 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.47 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.48 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.49 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.50 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.51 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.52 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.53 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

Page No.54 (54)

SATS Scandinavian Association for Testing of Electric Power Equipment

RoP No. 04-S07

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 1 of 9

LTB170D1/B
FSA1

Order No:
Serial No:

KD3000222/10
1HSB01323011

Customer
ABB SAKTI INDUSTRI
Customer reference
3162026688

Country
INDONESIA

Standard
IEC 62271-100

Test completed
2013-08-19

Circuit Breaker
LTB170D1/B
Mechanism
FSA1

Serial number

ABB reference

Project

1HSB01323011

KD3000222/10

K10006573

1HSB01323011-A1
1HSB01323011-B1
1HSB01323011-C1

KD3000222/10

K10006573

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.
ABB AB
High Voltage Products/Circuit Breakers
Quality

Date: 2013-08-20
Per Lindholm
Test witnessed by

...........................................................

.............................................................

...........................................................

.............................................................

...........................................................

ABB AB
Postal address:
ABB AB
High Voltage Products
SE-771 80 Ludvika, Sweden

Visiting address:
Lyviksvgen 4

Telephone:
0240-78 20 00
+46 240 78 20 00

Telefax:
0240-78 32 20
+46 240 78 32 20

Bank details:
223-1686

VAT No.:
SE556029702901
Registered office: Ludvika

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT
LTB170D1/B
FSA1

Page 2 of 9
Order No:
Serial No:

KD3000222/10
1HSB01323011

Rated data
Rated filling pressure for operation:

0,70

MPa(abs)

Check of rating plates

Approved: Q7

MECHANISM RESULTS
Resistance in ohms of auxiliary circuits
Description
Closing coil 1
Opening coil 1
Opening coil 2
Antipumping relay 1
Extra relay 1
Extra relay 2
Density blocking relay 1
Density blocking relay 2
Density blocking relay 3
Heater anticondense
Heater total
All resistances checked

Mechanism No.
1HSB01323011-A1
24
24
24
0
0
0
0
0
0
0
0

Mechanism No.
1HSB01323011-B1
24
25
25
8090
8060
8020
8060
8080
8070
226
82

Mechanism No.
1HSB01323011-C1
24
25
25
0
0
0
0
0
0
0
0
Approved Q7

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT
LTB170D1/B
FSA1

Page 3 of 9
Order No:
Serial No:

KD3000222/10
1HSB01323011
Approved
Q7
Q7
Q7
Q7
Q7
Q7
Q71
Q7
Q7
Q71
Q71

Check of
Wiring acc. To circuit diagram
Local/remote operation
Blocking relays
Antipumping relays
Time relays
Extra relays
On-line-motor starter does not trip for 10 consecutive operations
Auxiliary contacts
Thermostat settings
Counter
All adjustments and paint marking

Settings
Description
Thermostat
Close spring setting
Trip spring setting

Unit
C
mm
mm

Mech. 1
10,0
123
103,0

Mech. 2
10,0
110
95,0

Mech. 3
10,0
120
97,0
Approved: Q7

Spring charge at nominal voltage


Description
Charging time
Motor current

Unit
s
A

Mech. 1
9,1
3,4

Mech. 2
8,6
3,0

Mech. 3
9,1
3,3
Approved: Q7

Lowest operating voltage


Description
Close coil 1
Trip coil 1
Trip coil 2

Unit
VDC
VDC
VDC

Mech. 1
52
57
51

Mech. 2
57
45
52

Mech. 3
46
57
57
Approved: Q7

Power frequency test of auxiliary circuits


1 second 50 Hz 2,0 kV
- second 50 Hz - kV, motor

Approved: Q71
Approved: -

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 4 of 9

LTB170D1/B
FSA1

Order No:
Serial No:

KD3000222/10
1HSB01323011

POLE RESULTS
Resistance in main circuit
Phase
A
B
C

Unit
Ohm
Ohm
Ohm

Part 1
36
36
37

Part 2

Part 3

Part 4

Approved: Q71

Power frequency test performed at 0,60 MPa(abs)


60 seconds 50 Hz breaking unit
60 seconds 50 Hz to earth:

325 kV
325 / kV

Approved: Q71
Approved: Q71

1,15 MPa(abs)

Approved: Q71

Overpressure test on each pole


10 minutes duration

Tightness test on each pole

Approved: Q71

OPERATING TEST
Test assumptions
Technical provision:
Conversion table:
Fill pressure:
Operations
5 Close and Open
5 Close and Open
5 Close and Open
5 Close-Open
5 Open-0.3s-Close

1HSB425452-36 REV.C
CSB1_FSA
0,70 MPa(abs)
Voltage
level
Min
Max
Nom
Nom
Nom

Motor
VAC
196
253
230
230
230

Close 1 Close 2
VDC
VDC
94
121
110
110
110

Trip 1
VDC
77
121
110
110
110

Trip 2
VDC
77
121
110
110
110

Trip 3
VDC

Operating test
At least 25 operations as above
Stored energi test O 0.3s- CO- 3min- CO

Approved: Q7
Approved: -

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

LTB170D1/B
FSA1

Page 5 of 9
Order No:
Serial No:

KD3000222/10
1HSB01323011

Test Samples
Oper
.

Oper Volt
No. level

Cc

Tc

Ph

A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C

Close

Min.

Open

Min.

Close

15

Max.

Open

16

Max.

Close

25

Nom.

Open

26

Nom.

Open

41

Nom.

Cc

Tc

Ph

A
B
C
A
B
C

Oper
.

Oper Volt
No. level

C-O

31

Nom.

O-C-O

37

Nom.

Operation times
pole contact
1
2
3
4
ms ms ms ms
65,9
67,4
67,1
37,7
36,7
37,2
62,6
63,7
63,7
31,7
30,9
31,4
65,3
65,0
65,1
32,5
32,0
32,5
32,2
32,0
33,0

Interval times 1
pole contact
1
2
3
4
ms ms ms ms
41,2
43,7
42,3
282,7
283,1
282,5

Cont. Cont. Over- Re- Damp Time


stroke speed travel bounce time difference
a
b
mm
m/s
mm
mm
ms
ms
ms
111,2
3,3 10,5
2,4
7,8 -28,7
111,5
3,1
8,3
1,0
8,4 -31,8
110,7
3,1
8,9
1,2
8,9 -30,9
110,5
5,1
3,1
0,5 14,8 -9,1 15,3
111,2
5,0
2,0
0,9 15,3 -8,8 16,4
110,5
5,2
1,5
0,5 14,8 -9,3 14,9
111,0
3,3 10,6
2,2
7,5 -28,7
111,6
3,1
8,1
1,1
8,0 -31,7
110,7
3,1
8,8
1,3
8,9 -30,9
110,8
5,0
2,6
0,8 15,0 -9,0 15,6
111,4
5,0
1,6
1,1 15,4 -8,7 17,4
110,7
5,2
1,2
0,8 14,9 -9,2 15,3
111,2
3,2
9,5
1,8
8,0 -29,8
111,6
3,1
8,1
0,9
7,9 -31,9
110,7
3,1
8,7
1,2
8,1 -31,1
110,9
5,1
2,9
0,8 14,8 -9,0 15,3
111,4
5,0
1,6
1,1 15,3 -8,8 16,6
110,7
5,2
0,8
0,8 15,1 -9,3 15,2
110,8
5,1
2,7
0,7 14,9 -9,1 15,2
111,7
5,0
1,5
1,1 15,5 -8,8 17,1
110,6
5,2
0,8
0,8 15,1 -9,3 15,7

Interval times 2
Time
pole contact
difference
1
2
3
4
a
b
ms ms ms ms
ms
ms
8,0 -29,9
8,5 -32,3
8,6 -31,1
41,1
-9,1 15,3
43,5
-8,9 16,9
44,7
-9,5 15,2

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 6 of 9

LTB170D1/B
FSA1

Main Test sequence Close

Nom.

Order No:
Serial No:

KD3000222/10
1HSB01323011

Operation No 25

140

A1

120

B1
C1
1a

100

2a
3a

80

1b

mm

2b
3b

60

40

20

T1

T2
T3

15
10
5
0

Ic1

50

100

Operation data
Motor
Close coil 1

Trip coil -

230 VAC

110 VDC

150
ms

Contact times in ms
Main
Contact time
Close/Open interval
A1
65,3
(0,0 - 70,0)
B1
65,0
(0,0 - 70,0)
C1
65,1
(0,0 - 70,0)
Aux.
Contact time
Close/Open Close/Open
1a
73,3
1b
35,5
2a
72,9
2b
33,1
3a
73,2
3b
34,0

8,0
-29,8
7,9
-31,9
8,1
-31,1

Travel parameters
Description
Travel speed 1
Contact Stroke
OverTravel
Rebounce

T3
3,1
110,7
8,7
1,2

Unit
m/s
mm
mm
mm

T1
3,2
111,2
9,5
1,8

T2
3,1
111,6
8,1
0,9

200

Close/Open interval

Aux-Main

Limits
(3,0 - 3,5)
(109,0 - 112,0)
(0,0 - 12,0)

250

300

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 7 of 9

LTB170D1/B
FSA1

Main Test sequence Open

Nom.

Order No:
Serial No:

KD3000222/10
1HSB01323011

Operation No 26

140

120

A1
T1
T2

B1
C1

100 T3

1a
2a
3a

80
mm

1b
2b
3b

60

40

20

0
15
10
5
0

Ic1

20

40

60

Operation data
Motor
Close coil -

Trip coil 1

230 VAC

110 VDC

80

100
ms

Contact times in ms
Main
Contact time
Close/Open interval
A1
32,5
(28,0 - 35,0)
B1
32,0
(28,0 - 35,0)
C1
32,5
(28,0 - 35,0)
Aux.
Contact time
Close/Open Close/Open
1a
23,5
1b
47,8
2a
23,2
2b
48,6
3a
23,2
3b
47,7
Travel parameters
Description
Travel speed 1
Contact Stroke
OverTravel
Rebounce
Damping time

Unit
m/s
mm
mm
mm
ms

T1
5,1
110,9
2,9
0,8
14,8

T2
5,0
111,4
1,6
1,1
15,3

120

140

Close/Open interval

Aux-Main
-9,0
15,3
-8,8
16,6
-9,3
15,2

T3
5,2
110,7
0,8
0,8
15,1

Limits
(5,0 - 5,2)
(109,0 - 112,0)

(13,5 - 17,5)

160

180

200

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 8 of 9

LTB170D1/B
FSA1

Main Test sequence Close-Open

Order No:
Serial No:

Nom.

KD3000222/10
1HSB01323011

Operation No 31

140

120

A1
B1
C1

100

1a
2a
3a

80
mm

1b
2b
3b

60

40

20

T1

T2

T3

15
10
5
0

Ic1

20

40

60

Operation data
Motor
Close coil 1

Trip coil 1

230 VAC

110 VDC

110 VDC

80

100

120
ms

Contact times in ms
Main
Contact time
Close/Open interval
A1
65,2
(0,0 - 70,0)
41,2
B1
65,4
(0,0 - 70,0)
43,7
C1
65,7
(0,0 - 70,0)
42,3
Aux.
Contact time
Close/Open Close/Open
1a
73,2
25,4
1b
35,3
87,8
2a
73,9
28,1
2b
33,1
95,0
3a
74,3
25,9
3b
34,6
91,5

140

160

Close/Open interval

Aux-Main
8,0
-29,9
8,5
-32,3
8,6
-31,1

180

200

220

240

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 9 of 9

LTB170D1/B
FSA1

Main Test sequence

Order No:
Serial No:

Open-0.3s-Close-Open Nom.

KD3000222/10
1HSB01323011

Operation No 37

140

120

A1
T1
T2

B1
C1

100 T3

1a
2a
3a

80
mm

1b
2b
3b

60

40

20

15
10
5
0

Ic1

50

100

150

Operation data
Motor
Close coil 1

Trip coil 1

230 VAC

110 VDC

110 VDC

200

Contact times in ms
Main
Contact time
Close/Open interval
A1
32,6
(28,0 - 35,0)
282,7
B1
32,0
(28,0 - 35,0)
283,1
C1
32,6
(28,0 - 35,0)
282,5
Aux.
Contact time
Close/Open Close/Open
1a
23,5
299,7
24,9
1b
47,9
237,5
87,5
2a
23,1
301,4
26,1
2b
48,9
234,4
94,0
3a
23,1
301,0
27,0
3b
47,8
236,0
91,6

250
ms

300

Close/Open interval
41,1
43,5
44,7
Aux-Main
-9,1
15,3
-8,9
16,9
-9,5
15,2

350

400

450

500

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 1 of 9

LTB170D1/B
BLK222

Order No:
Serial No:

KD2000199/20
1HSB01226114

Customer
ABB SAKTI INDUSTRI
Customer reference
3162020024

Country
INDONESIA

Standard
IEC 62271-100

Test completed
2012-09-14
Serial number

ABB reference

Project

Circuit Breaker
LTB170D1/B

1HSB01226114

KD2000199/20

K10004868

Mechanism
BLK222

1HSB01226114-A1

KD2000199/20

K10004868

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.
ABB AB
High Voltage Products/Circuit Breakers
Quality

Date: 2012-09-17
Herbert Andersson
Test witnessed by

...........................................................

.............................................................

...........................................................

.............................................................

...........................................................

ABB AB
Postal address:
ABB AB
High Voltage Products
SE-771 80 Ludvika, Sweden

Visiting address:
Lyviksvgen 4

Telephone:
0240-78 20 00
+46 240 78 20 00

Telefax:
0240-78 32 20
+46 240 78 32 20

Bank details:
223-1686

VAT No.:
SE556029702901
Registered office: Ludvika

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT

Page 2 of 9

LTB170D1/B
BLK222

Order No:
Serial No:

KD2000199/20
1HSB01226114

Rated data
Rated filling pressure for operation:

0,70

MPa(abs)

Check of rating plates

Approved: Q71

MECHANISM RESULTS
Resistance in ohms of auxiliary circuits
Description
Closing coil 1
Opening coil 1
Opening coil 2
Antipumping relay 1
Extra relay 1
Extra relay 2
Extra relay 3
Density blocking relay 1
Density blocking relay 2
Motor contactor 1
Heater anticondense
Heater total
All resistances checked

Mechanism No.
1HSB01226114-A1
50
51
50
7840
7800
7960
7860
8070
8040
113
670
241

Mechanism No.

Mechanism No.
-

Approved Q71

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT

Page 3 of 9

LTB170D1/B
BLK222

Order No:
Serial No:

KD2000199/20
1HSB01226114
Approved
Q71
Q71
Q71
Q71
Q71
Q71
Q71
Q71
Q71
Q71
Q71

Check of
Wiring acc. To circuit diagram
Local/remote operation
Blocking relays
Antipumping relays
Time relays
Extra relays
On-line-motor starter does not trip for 10 consecutive operations
Auxiliary contacts
Thermostat settings
Counter
All adjustments and paint marking

Settings
Description
Thermostat
Closing spring charge
Trip spring setting

Unit
C

mm

Mech. 1
10,0
118,0
61,0

Mech. 2

Mech. 3
-

Approved: Q71

Spring charge at nominal voltage


Description
Charging time
Motor current

Unit
s
A

Mech. 1
10,3
12,9

Mech. 2

Mech. 3
-

Approved: Q71

Lowest operating voltage


Description
Close coil 1
Trip coil 1
Trip coil 2

Unit
VDC
VDC
VDC

Mech. 1
46
40
40

Mech. 2

Mech. 3
-

Approved: Q71

Power frequency test of auxiliary circuits


1 second 50 Hz 2,0 kV
- second 50 Hz - kV, motor

Approved: Q71
Approved: -

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 4 of 9

LTB170D1/B
BLK222

Order No:
Serial No:

KD2000199/20
1HSB01226114

POLE RESULTS
Resistance in main circuit
Phase
A
B
C

Unit
Ohm
Ohm
Ohm

Part 1
37
36
37

Part 2

Part 3

Part 4

Approved: Q71

Power frequency test performed at 0,60 MPa(abs)


60 seconds 50 Hz breaking unit
60 seconds 50 Hz to earth:

325 kV
325 / kV

Approved: Q71
Approved: Q71

1,15 MPa(abs)

Approved: Q71

Overpressure test on each pole


10 minutes duration

Tightness test on each pole

Approved: Q71

OPERATING TEST
Test assumptions
Technical provision:
Fill pressure:
Operations
5 Close and Open
5 Close and Open
5 Close and Open
5 Close-Open
5 Open-0.3s-Close

1HSB425452-23 REV.B S.1


0,70 MPa(abs)
Voltage
level
Min
Max
Nom
Nom
Nom

Motor
VDC
94
121
110
110
110

Close 1 Close 2
VDC
VDC
94
121
110
110
110

Trip 1
VDC
77
121
110
110
110

Trip 2
VDC
77
121
110
110
110

Trip 3
VDC

Operating test
At least 25 operations as above
Stored energi test O 0.3s- CO- 3min- CO

Approved: Q71
Approved: -

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

LTB170D1/B
BLK222

Page 5 of 9
Order No:
Serial No:

KD2000199/20
1HSB01226114

Test Samples
Oper. Oper. Volt Cc
No. Level

Close
Open
Close
Open
Close
Open
Open

5
6
15
16
25
26
41

Min.
Min.
Max.
Max.
Nom.
Nom.
Nom.

1
1
1
-

Oper. Oper. Volt Cc


No. Level

C-O
O-C-O

31
37

Nom.
Nom.

1
1

Tc

1
1
1
2

Tc

1
1

Operation times
pole
A
B
C
ms
ms ms
27,9 28,0 28,6
23,1 23,1 22,8
27,0 27,1 27,7
21,2 21,2 20,9
27,2 27,4 27,9
21,6 21,5 21,3
21,5 21,5 21,2

Cont. Cont. Cont. Over


Re- Damp
stroke speed speed travel bounce time
1
2
mm
m/s
m/s
mm
mm
ms
110,9
4,9
3,2
8,8
1,0
111,0
5,2
-1,8
3,6 14,7
110,9
4,9
3,3
8,8
1,0
110,9
5,1
-1,8
3,7 14,7
111,0
4,9
3,2
8,7
1,1
110,9
5,1
-1,8
3,7 14,7
110,9
5,2
-1,8
3,8 14,7

Interval times 1
Interval times 2
pole
pole
A
B
C
A
B
C
ms
ms ms
ms ms
ms
34,5 35,2 34,2
255,7 255,8 256,6 34,2 34,5 34,1

Time
difference
a
b
ms
ms
3,6 -11,5
-4,1
9,5

Time
difference
a
b
ms
ms
3,9 -11,5
-4,2
9,6
3,7 -11,4
-4,1
9,8
3,8 -11,4
-4,2
9,6
-4,1
9,5

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 6 of 9

LTB170D1/B
BLK222

Main Test sequence Close

Order No:
Serial No:

Nom.

KD2000199/20
1HSB01226114

Operation No 25

140

A1

120

B1
C1
1a

100

1b

mm

80

60

40

20

T1

2
Ic1

0
0

20

40

60

80

100

ms

Operation data
Motor
Close coil 1

Trip coil -

110 VDC

110 VDC

Contact times in ms
Main
Contact time
Close/Open interval
A1
27,2
(0,0 - 40,0)
B1
27,4
(0,0 - 40,0)
C1
27,9
(0,0 - 40,0)
Aux.
Contact time
Close/Open Close/Open
1a
31,0
1b
15,8
Travel parameters
Description
Travel speed 1
Travel speed 2
Contact Stroke
OverTravel
Rebounce

Unit
m/s
m/s
mm
mm
mm

T1
4,9
3,2
111,0
8,7
1,1

Close/Open interval

Aux-Main
3,8
-11,4

Limits
(3,1 - 3,6)
(109,5 - 111,7)
(6,6 - 9,8)

120

140

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 7 of 9

LTB170D1/B
BLK222

Main Test sequence Open

Nom.

Order No:
Serial No:

KD2000199/20
1HSB01226114

Operation No 26

140

120

A1
T1

B1
C1

100

1a
1b

mm

80

60

40

20

2
Ic1

0
0

20

40

60

80

100

ms

Operation data
Motor
Close coil -

Trip coil 1

110 VDC

110 VDC

Contact times in ms
Main
Contact time
Close/Open interval
A1
21,6
(19,0 - 25,0)
B1
21,5
(19,0 - 25,0)
C1
21,3
(19,0 - 25,0)
Aux.
Contact time
Close/Open Close/Open
1a
17,4
1b
31,2
Travel parameters
Description
Travel speed 1
Contact Stroke
OverTravel
Rebounce
Damping time

Unit
m/s
mm
mm
mm
ms

T1
5,1
110,9
-1,8
3,7
14,7

Close/Open interval

Aux-Main
-4,2
9,6

Limits
(109,5 - 111,7)

120

140

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 8 of 9

LTB170D1/B
BLK222

Main Test sequence Close-Open

Order No:
Serial No:

Nom.

KD2000199/20
1HSB01226114

Operation No 31

140

120

A1
B1
C1

100

1a
1b

mm

80

60

40

20

T1

2
Ic1

0
0

20

40

60

80

100

120

140

160

ms

Operation data
Motor
Close coil 1

Trip coil 1

110 VDC

110 VDC

110 VDC

Contact times in ms
Main
Contact time
Close/Open interval
A1
27,3
(0,0 - 40,0)
34,5
(0,0 - 42,0)
B1
27,3
(0,0 - 40,0)
35,2
(0,0 - 42,0)
C1
27,9
(0,0 - 40,0)
34,2
(0,0 - 42,0)
Aux.
Contact time
Close/Open Close/Open
1a
30,9
27,4
1b
15,8
56,1

Close/Open interval

Aux-Main
3,6
-11,5

180

200

220

240

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 9 of 9

LTB170D1/B
BLK222

Main Test sequence

Order No:
Serial No:

Open-0.3s-Close-Open Nom.

KD2000199/20
1HSB01226114

Operation No 37

140

120

A1
T1

B1
C1

100

1a
1b

mm

80

60

40

20

2
Ic1

0
0

50

100

150

Operation data
Motor
Close coil 1

Trip coil 1

110 VDC

110 VDC

110 VDC

200

Contact times in ms
Main
Contact time
Close/Open interval
A1
21,5
(19,0 - 25,0)
255,7
B1
21,5
(19,0 - 25,0)
255,8
C1
21,2
(19,0 - 25,0)
256,6
Aux.
Contact time
Close/Open Close/Open
1a
17,4
263,4
27,0
1b
31,0
234,7
54,7

250
ms

300

Close/Open interval
34,2
(0,0 - 42,0)
34,5
(0,0 - 42,0)
34,1
(0,0 - 42,0)
Aux-Main
-4,1
9,5

350

400

450

500