Escolar Documentos
Profissional Documentos
Cultura Documentos
Jon F. Daume
Bonneville Power Administration
March 14-15, 2011
1
Class Outline
Power system troubles
Symmetrical components
Per unit system
Electrical equipment impedances
Sequence networks
Fault calculations
2
Fault Causes
Lightning
Wind and ice
Vandalism
Contamination
External forces
Cars, tractors, balloons, airplanes, trees, critters,
flying saucers, etc.
Equipment failures
System disturbances
Overloads, system swings
4
Fault Types
One line to ground (most common)
Three phase (rare but most severe)
Phase to phase
Phase to phase to ground
Symmetrical
Components
Unbalanced System:
Phase to phase fault
One line to ground
fault
Phase to phase to
ground fault
Open pole or
conductor
Unbalanced load
8
A
A
Balanced
System
B
Unbalanced System
Ib0
Ia0
Ic1
Ic0
Zero Sequence
Ia1
Ia2
Ib2
Positive Sequence
Ic2
Negative Sequence
Ib1
10
Sequence Quantities
Condition
3 Phase load
3 Phase fault
Phase to phase fault
One line to ground fault
Two phase to ground fault
Open pole or conductor
Unbalanced load
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
11
a Operator
a
a = -0.5 + j 3= 1 120
2
a2 = -0.5 j 3= 1 240
2
1
1 + a + a2 = 0
a2
13
Ib
Ic
3I0 = Ia + Ib + Ic
17
Eb
Ec
3 VO Polarizing Potential
3V0
18
Example
IA = 3 + j4
IB = -7 - j2
IC = -2 + j7
+j
IC = -2+j7
IA = 3+j4
IB = -7-j2
-j
20
Zero Sequence
Ia0 = (IA + IB + IC)/3
= [(3+j4)+(-7-j2)+(-2+j7)]/3
= -2 + j3 = 3.61 124
Ib0
Ia0
Ic0
21
Positive Sequence
Ia1 = (IA + aIB + a2IC)/3
= [(3+j4)+(-0.5+j3/2)(-7-j2)
+(-0.5-j3/2)(-2+j7)]/3
= [(3+j4)+(5.23-j5.06)+(7.06-j1.77)]/3
= 5.10 - j 0.94 = 5.19 -10.5
Ib1 is rotated -120
Positive Sequence
Ic1
Ia1
Ib1
23
Negative Sequence
Ia2 = (IA + a2IB + aIC)/3
= [(3+j4)+(-0.5-j3/2)(-7-j2)
+(-0.5+j3/2)(-2+j7)]/3
= [(3+j4)+(1.77+j7.06)+(-5.06-j5.23)]/3
= -0.1 + j 1.94 = 1.95 92.9
Ib2 is rotated +120
Negative Sequence
Ia2
Ib2
Ic2
25
Ic0
Ic2
Ic1
Ia
Ia0
Ia2
Ia1
Ib
Ib0
Ib1
Ib2
26
27
+, -, 0 Sequence Networks
Fault
Simple 2 Source Power System Example
1PU
V1
V2
V0
I1
I2
Z1
I0
Z2
Z0
28
3 Phase fault
Phase to phase fault
One line to ground fault
Two phase to ground fault
D
D
D
D
D
D
D
D
D
29
Per Unit
30
Per Unit
Per unit values are commonly used for fault
calculations and fault study programs
Per unit values convert real quantities to
values based upon number 1
Per unit values include voltages, currents and
impedances
Per Unit
Convert equipment impedances into per unit
values
Transformer and generator impedances are
given in per cent (%)
Line impedances are calculated in ohms
These impedances are converted to per unit
ohms impedance
32
33
Base kV
Use nominal equipment or line voltages
765 kV
525 kV
345 kV
230 kV
169 kV
138 kV
115 kV
69 kV
34.5 kV
13.8 kV
12.5 kV
etc.
34
Base Ohms
2756.3
1190.3
529.0
132.3
47.6
11.9
1.9
1.6
Base Amps
110.0
167.3
251.0
502.0
836.7
1673.5
4183.7
4618.8
36
Conversions
Percent to Per Unit:
base MVA
x % Z of equipment
3 MVA rating
100
= Z pu @ base MVA
If 100 MVA base is used:
% Z of equipment = Z pu
3 MVA rating
37
38
39
40
Evaluation of System
Components
Determine positive, negative, and zero
sequence impedances of various devices
(Z1, Z2, Z0)
Only machines will act as a voltage source in
the positive sequence network
Connect the various impedances into networks
according to topography of the system
Connect impedance networks for various fault
types or other system conditions
41
Synchronous Machines
~
Machine values:
Machine reactances given in % of the
machine KVA or MVA rating
Ground impedances given in ohms
42
Synchronous Machines
Machine values:
Subtransient reactance (X"d)
Transient reactance (X'd)
Synchronous reactance (Xd)
Negative sequence reactance (X2)
Zero sequence reactance (X0)
43
Synchronous Machines
Machine neutral ground impedance: Usually
expressed in ohms
Use 3R or 3X for fault calculations
Calculations generally ignores resistance
values for generators
Calculations generally uses Xd for all
impedance values
44
Generator Example
Machine nameplate values:
250 MVA, 13.8 kV
X"d = 25% @ 250 MVA
X'd = 30% @ 250 MVA
Xd = 185% @ 250 MVA
X2 = 25% @ 250 MVA
X0 = 10% @ 250 MVA
45
Generator Example
Convert machine reactances to per unit @
common MVA base, (100):
X"d = 25% / 250 = 0.1 pu
X'd = 30% / 250 = 0.12 pu
Xd = 185% / 250 = 0.74 pu
X2 = 25% / 250 = 0.1 pu
X0 = 10% / 250 = 0.04 pu
base MVA
x % Z of equipment = Z pu @ base MVA
3 MVA rating
100
46
Generator Example
R1
jX1 = 0.1
R2
jX2 = 0.1
R0
jX0 = 0.04
47
Transformers
Ih
H
Vh
Zh
1:N
Zx
Ze
Zhx
Transformers
Impedances in % of the transformer MVA
rating
Convert from circuit voltage to tap voltage:
%Xtap = %Xcircuit kV2circuit
kV2tap
49
Transformers
Convert to common base MVA:
%X @ base MVA =
base MVA x %X of Transformer
MVA of Measurement
%X of Transformer = pu X @ 100 MVA
MVA of Measurement
X1 = X2 = X0 unless a special value is given for
X0
50
Transformer Example
250 MVA Transformer
13.8 kV - 230 kV Yg
10% Impedance @ 250 MVA
X = 10% = 0.04 pu @ 100 MVA
250
X1 = X2 = X0 = X
Assume R1, R2, R0 = 0
51
Transformer Example
R1
jX1 = 0.04
R2
jX2 = 0.04
R0
jX0 = 0.04
52
Transformer Connections
Winding Connection
Sequence Network
Connections
Z0
Z1, Z2
Z1, Z2
Z0
53
Transformer Connections
Winding Connection
Z0
Z1, Z2
Z0
Z1, Z2
Z0
Z1, Z2
Z0
54
a
Ia
nIA
IA
B
b
Ib
nIB
IB
C
Ic
nIC
IC
3I0 = IA+IB+IC
55
Transformer Connections
A YG / YG connection provides a series
connection for zero sequence current
A / YG connection provides a zero sequence
(I0) current source for the YG winding
Auto transformer provides same connection as
YG / YG connection
Use 3R or 3X if a Y is connected to ground
with a resistor or reactor
57
T Network
Calculate corresponding T network
impedances:
ZH = (ZHL+ ZHM - ZML)/2
ZM = (- ZHL+ ZHM + ZML)/2
ZL = (ZHL- ZHM + ZML)/2
ZH
ZHL= ZH + ZL
ZHM = ZH + ZM
ZML= ZM+ ZL
ZM
ZL
59
Transformer Example
230 kV YG/115 kV YG/13.2 kV
Nameplate Impedances
ZHL= 5.0% @ 50 MVA
ZHM = 5.75% @ 250 MVA
ZML = 3.15% @ 50 MVA
60
Transformer Example
Convert impedances to per unit @ common
MVA Base (100)
ZHL= 5.0% @ 50 MVA = 5.0 / 50
= 0.10 pu
ZHM = 5.75% @ 250 MVA = 5.75 / 250
= 0.023 pu
ZML = 3.15% @ 50 MVA = 3.15 / 50
= 0.063 pu
61
Transformer Example
Convert impedances to T network equivalent
ZH = (ZHL+ ZHM - ZML)/2
= (0.1 + 0.023 - 0.063)/2 = 0.03 pu
ZM = (- ZHL+ ZHM + ZML)/2
= (-0.1 + 0.023 + 0.063)/2 = - 0.007 pu
ZL = (ZHL- ZHM + ZML)/2
= (0.1 - 0.023 + 0.063)/2 = 0.07 pu
62
Transformer Example
H , 230 kV
H
0.03
-0.007
L, 13.8 kV
M
M , 115 kV
0.03
0.07
L
+, - Sequence
-0.007 M
0.07
0 Sequence
63
Problem
Calculate pu impedances for generators and
transformers
Use 100 MVA base
Ignore all resistances
Problem
13.8 kV
230 kV
230 kV
13.8 kV
115 kV
Fault
65
Transmission Lines
R
jX
68
De _______
3(GMR
2)
GMD
cond
sep
or
Z0 = Ra + Re + j (Xa + Xe - 2Xd) /mile
71
72
Transmission Lines
Ra
j(Xa+Xd)
Z1
Ra
j(Xa+Xd)
Z2
Ra+Re j(Xa+Xe-2Xd)
Z0
73
23 Feet
J6 Configuration
23 Feet
75
76
j0.0743
Z1
0.0085
0.0356
j0.0743
j0.2311
Z2
Z0
78
79
Mutual Impedance
Result of coupling between parallel lines
Only affects Zero sequence network
Will affect ground fault magnitudes
Will affect ground current flow in lines
3I0, Line #1
Line #1
3I0, Line #2
Line #2
80
Mutual Impedance
ZM = Re + j 0.838 log De
/mile
GMDcircuits
or
ZM = Re + j (Xe 3Xd circuits) /mile
Re = 0.2862 @ 60 Hz
De = 2160 ( /f) = 2788 @ 60 Hz
Xe = 2.89 for 100 meter ohms average
ground resistivity
81
Mutual Impedance
GMDcircuits is the ninth root of all possible
distances between the six conductors,
approximately equal to center to center
spacing
GMDcircuits =
9(d
a1a2da1b2da1c2db1a2db1b2db1c2dc1a1dc1b2dc1c2)
Xd circuits = 0.2794 log GMDcircuits
82
Circuit #2
23 Feet
23 Feet
92 Feet
46 Feet
23 Feet
23 Feet
115 Feet
138 Feet
69 Feet
92 Feet
115 Feet
46 Feet
69 Feet
92 Feet
83
Z0 Line 2
Bus 2
Z01- ZM
ZM
Bus 1 Z02 - ZM
Bus 2
85
Garrison
Taft
Garrison
645 Amps
1980 Amps
645 Amps
1315 Amps
Garrison
920 Amps
920 Amps
Taft
Garrison
1370 Amps
260 Amps
87
Problem
Calculate Z1 and Z0 pu impedances for a
transmission line
Calculate R1, Z1, R0 and Z0
Calculate Z1 and Z0 and the angles for Z1
and Z0
Calculate Z0 mutual impedance between
transmission lines
Use 100 MVA base and 230 kV base
88
Problem
13.8 kV
230 kV
230 kV
13.8 kV
115 kV
Fault
89
91
92
Fault Studies
Fault Types:
3 Phase
One line to ground
Phase to phase
Phase to phase to ground
Fault Locations:
Bus fault
Line end
Line out fault (bus fault with line open)
Intermediate faults on transmission line
93
Fault
Vl = 1
Z1sl
Z1tl
Z1Ll
V1=1-I1Z1
Z1l
Z1Lr
I1
Z1h
Z1sr
Vr = 1
Z1m
95
Fault
Z2sl
Z2tl
Z2Ll
V2= -I2Z2
Z2l
Z2Lr
I2
Z2h
Z2sr
Z2m
96
Fault
Z0sl
Z0tl
V0= -I0Z0
Z0Ll
Z0l
Z0Lr
I0
Z0h
Z0sr
Z0m
97
Network Reduction
Fault
Simple 2 Source Power System Example
1PU
V1
V2
V0
I1
I2
Z1
I0
Z2
Z0
98
99
1PU
V1
V2
V0
I1=11.9
Z1
0.084
I2=0
I0=0
Z2
0.084
Z0
0.081
100
Vl = 1
Z1sl
Z1tl
Z1Ll
0.1
0.04
0.037
V1=1-I1Z1
Z1Lr
0.07
Z1l
Z1sr
Vr = 1
0.1
Vl = 1
V1=1-I1Z1
0.177
0.160
Vr = 1
I1
Ib
Va
Vb
Ia
103
104
106
1PU
V1
V2
V0
I1
I2
Z1
I0
Z2
Z0
107
Vl = 1
Z1sl
Z1tl
Z1Ll
V1=1-I1Z1
I1
Z2sl
Z2tl
Z2Ll
Z1l
Z1Lr
Z1h
Z1sr
Vr = 1
Z1m
V2= -I2Z2
Z2l
Z2Lr
I2 = -I1
Z2h
Z2sr
Z2m
108
Ic
Va
Ib
Vb
109
E
= ___1___
I0 = 0
(Z1 + Z2) (Z1 + Z2)
IA = I0 + I1 + I2 = 0
IB = I0 + a2I1 + aI2 = a2I1 - aI1
IB = (a2 - a) E = _-j 3 E_ = -j 0.866 E
(Z1 + Z2)
(Z1 + Z2)
Z1
IC = - IB
(assume Z1 = Z2)
110
111
112
V1
V2
V0
I1=4.02
I2=4.02
Z1
.084
Z2
.084
1PU
I0=4.02
Z0
.081
113
Vl = 1
V1=1-I1Z1
Z1sl
Z1tl
Z1Ll
Z1Lr
0.1
0.04
0.037
I1 0.037
V2= -I2Z2
Z2sl
Z2tl
Z2Ll
Z2Lr
0.1
0.04
0.037
I2 0.037
V0= -I0Z0
Z0sl
Z0tl
Z0Ll
Z0Lr
0.04
0.04
0.116
I0 0.116
0.07
Z1l
Z1h Z1m
0.03 -0.007
Z1sr
Vr = 1
0.1
0.07
Z2l
Z2h Z2m
0.03 -0.007
Z2sr
0.1
0.07
Z 0l
Z0sr
114
Va
Vb
Ia
115
118
1PU
V1
V2
V0
I1
I2
Z1
I0
Z2
Z0
119
Vl = 1
Z1sl
Z1tl
Z1Ll
V1=1-I1Z1
I1
Z2sl
Z2tl
Z2Ll
Z0Ll
Vr = 1
Z1m
Z 2l
Z2Lr
Z0tl
Z1h
Z1sr
V2= -I2Z2
I2
Z0sl
Z 1l
Z1Lr
Z2h
Z2sr
Z2m
V0= -I0Z0
Z 0l
Z0Lr
I0
Z0h
Z0sr
Z 0m
120
Vc
Ib
Va
Vb
121
Other Conditions
Fault calculations and symmetrical
components can also be used to evaluate:
Open pole or broken conductor
Unbalanced loads
Load included in fault analysis
Transmission line fault location
References
Circuit Analysis of AC Power Systems, Vol. 1 &
2, Edith Clarke
Electrical Transmission and Distribution
Reference Book, Westinghouse Electric Co.,
East Pittsburgh, Pa.
Symmetrical Components, Wagner and Evans,
McGraw-Hill Publishing Co.
Symmetrical Components for Power Systems
Engineering, J. Lewis Blackburn, Marcel
Dekker, Inc.
123
The end
Jon F. Daume
Bonneville Power Administration
Retired!
124
Theory Track
Transmission Protection Theory
Transmission System
Protection
Hands-On Relay School
Jon F. Daume
Bonneville Power Administration
March 14-15, 2011
1
Discussion Topics
Protection overview
Transmission line protection
Power Transfer
Vs
Vr
P = Vs Vr sin / X
Transmitted Power
Power Transfer
0.5
0
0
30
60
90
120
150
180
Angle Delta
Transmitted Power
1.2
Normal
1LG
0.8
LL
0.6
LLG
0.4
3 Phase
0.2
0
0
30
60
90
120
150
180
Angle Delta
6
Vs
Vr
Power Transfer
1.2
1
5
Power
0.8
4
0.6
P1
0.4
P2
A
6
0.2
1
0
0
30
60
90
Angle Delta
120
150
180
7
System Stability
10
Relay Reliability
Overlapping protection
Relay systems are designed with a high level
of dependability
This includes redundant relays
Overlapping protection zones
11
Relay Reliability
Relay dependability (trip when required)
Redundant relays
Remote backup
Dual trip coils in circuit breaker
Dual batteries
Digital relay self testing
Thorough installation testing
Routine testing and maintenance
Review of relay operations
12
Relay Reliability
Relay security (no false trip)
Careful evaluation before purchase
Right relay for right application
Voting
2 of 3 relays must agree before a trip
13
Transmission
Line Protection
14
Northwest
WECC
115 - 161
27400 miles
48030 miles
230
20850 miles
41950 miles
287 - 345
4360 miles
9800 miles
500
9750 miles
16290 miles
260 - 500 DC
300 miles
1370 miles
15
j(Xa+Xd)
16
17
18
Distance Relays
(21, 21G)
19
Distance Relays
Common protective relay for non radial
transmission lines
Fast and consistent trip times
Instantaneous trip for faults within zone 1
Operating speed little affected by changes
in source impedance
CT & PT Connections
V Phase
I Phase
21
3V0
3I0 = Ia + Ib + Ic
67N
I Polarizing
21
Instrument Transformers
Zsecondary = Zprimary x CTR / VTR
The PT location determines the point from
which impedance is measured
The CT location determines the fault
direction
Very important consideration for
Transformer terminated lines
Series capacitors
Saturated CT Current
150
100
50
0
-50
-100
-0.017
0.000
0.017
0.033
0.050
0.06
23
Westinghouse HZ
Later variation allowed for an offset circle
24
Impedance Characteristic
X
Directional
25
mho Characteristic
Most common distance element in use
Circular characteristic
Passes through RX origin
No extra directional element required
26
Zone 3
Zone 2
Zone 1
27
Typical Reaches
21 Zone 1 85-90%
21 Zone 2 125-180%, Time Delay Trip
21 Zone 3 150-200%, Time Delay Trip
67 Ground Instantaneous Overcurrent
67 Ground Time Overcurrent
67 Ground Time Permissive Transfer Trip Overcurrent
Typical Relay Protection Zones
28
Coordination Considerations,
Zone 1
Zone 1
Instantaneous trip
29
Coordination Considerations
Zone 2
125% or more of line impedance
Consider strong line out of service
Consider lengths of lines at next substation
Coordination Considerations
Zone 3
Greater than zone 2
Consider strong line out of service
Consider lengths of lines at next substation
Coordination Considerations
Zone 3 Special Applications
Starter element for zones 1 and 2
Provides current reversal logic for permissive
transfer trip (reversed)
May be reversed to provide breaker failure
protection
Characteristic may include origin for current
only tripping
May not be used
32
33
34
Apparent Impedance
3 Terminal lines with apparent
impedance
Fault resistance also looks like an
apparent impedance
Most critical with very short or
unbalanced legs
Results in
Short zone 1 reaches
Long zone 2 reaches and time delays
Apparent Impedance
Bus A
Zb = 1 Bus B
Za = 1 ohm
Ia = 1
Ic = Ia + Ib = 2
Z apparent @
Bus A = Za +
ZcIc/Ia
= 3 Ohms
Zc = 1
Ib = 1
Bus C
Apparent Impedance
36
Coordination Considerations
Zone 1
Set to 85 % of actual impedance to nearest
terminal
Zone 2
Set to 125 + % of apparent impedance to
most distant terminal
Zone 2 time delay must coordinate with all
downstream relays
Zone 3
Back up for zone 2
37
Load Encroachment
Z Load = kV2 / MVA
Long lines present biggest challenge
Heavy load may enter relay characteristic
38
Load Encroachment
NERC Loading Criteria
Applies to zone 2 and zone 3 phase distance
Other overreaching phase distance elements
Solutions
Dont use conventional zone 3 element
Use lens characteristic
Use blinders or quadrilateral characteristic
Tilt mho characteristic toward X axis
Utilize special relay load encroachment
characteristic
39
Load Encroachment
X
Zone 3
Zone 2
Zone 1
Load
Area
R
Load Consideration with Distance Relays
40
Lens Characteristic
41
Lens Characteristic
42
Tomato Characteristic
May be used as an external out of step
blocking characteristic
Reaches set greater than the tripping
elements
Generated by combining the total area of
two mho elements
43
Quadrilateral Characteristic
High level of freedom in settings
Blinders on left and right can be moved in
or out
More immunity to load encroachment (in)
More fault resistance coverage (out)
Quadrilateral Characteristic
X
Quadrilateral Characteristic
45
Zone 4
Zone 2
Zone 1
46
Fault Resistance
Most severe on short lines
Difficult for ground distance elements to
detect
Solutions:
Tilt characteristic toward R axis
Use wide quadrilateral characteristic
Use overcurrent relays for ground faults
47
Fault Resistance
X
Zone 3
Zone 2
Rf
Zone 1
R
Fault Resistance Effect on a Mho Characteristic
48
Negative inductance
Difficult problem for distance relays
Application depends upon location of
capacitors
49
Series Caps
Zl
21
Zc
Zl > Zc
21
50
Series Caps
Bypass MOD
Isolating MOD
Isolating MOD
Bypass Breaker
Discharge Reactor
Triggered Gap
Capacitor (Fuseless)
Damping Circuit
Platform
51
Coordination Considerations
Zone 1
80 to 90% of compensated line impedance
Must not overreach remote bus with caps in
service
Zone 2
125% + of uncompensated apparent line
impedance
Must provide direct tripping for any line fault
with caps bypassed
May require longer time delays
52
Power Swing
Power swings can cause false trip of 3
phase distance elements
Option to
Block on swing (Out of step block)
Trip on swing (Out of step trip)
Out of step tripping may require special breaker
Allows for controlled separation
Zone 2
t = 30 ms?
Zone 1
54
Ground Distance
Protection
and Kn
(21G)
55
Fault Types
3 Phase fault
Positive sequence impedance network only
Sequence Networks
57
58
Kn - Why?
Using phase/phase or phase/ground
quantities does not give proper reach
measurement for 1LG fault
Using zero sequence quantities gives the
zero sequence source impedance, not the
line impedance
Current compensation (Kn) does work for
ground faults
Voltage compensation could also be used
but is less common
59
Current Compensation, Kn
Kn = (Z0L - Z1L)/3Z1L
Z0L = Zero sequence transmission line impedance
Z1L = Positive sequence transmission line
impedance
Current Compensation, Kn
Current compensation (Kn) does work for
ground faults.
Kn = (Z0L Z1L)/3Z1
Kn may be a scalar quantity or a vector quantity
with both magnitude and angle
61
Ground Fault
Protection
(67N)
62
Ground Faults
Directional ground overcurrent relays
(67N)
Ground overcurrent relays
Time overcurrent ground (51)
Instantaneous overcurrent (50)
51 Time overcurrent
50 Instantaneous overcurrent
>125% Remote bus fault
Negative sequence
Requires 3 phase voltages and currents
More immune to mutual coupling problems
65
Current Polarizing
H1
CT
X1
Y1
H2
X2
Y2
X3
Y3
H3
H0X0
I Polarizing
66
Voltage Polarizing
Ea
Eb
Ec
3 VO Polarizing Potential
67
Mutual Coupling
Transformer affect between parallel lines
Inversely proportional to distance between
lines
68
Mutual Coupling
3I0, Line #1
Line #1
3I0, Line #2
Line #2
69
Garrison
Taft
Garrison
645 Amps
1980 Amps
645 Amps
1315 Amps
Garrison
920 Amps
920 Amps
Garrison
Taft
1370 Amps
260 Amps
70
Other Line
Protection Relays
71
Line Differential
87
87
72
Phase Comparison
Compares phase relationship at terminals
100% Channel dependant
Looped channels can cause false trips
74
Pilot Wire
Common on power house lines
Uses metallic twisted pair
Problems if commercial line used
Requires isolation transformers and protection
on pilot wire
Pilot Wire
76
Current Differential
Similar to phase comparison
Channel failure?
Distance relay backup or
Non directional overcurrent backup or
No backup must add separate back up
relay
Current Differential
Single pole capability
3 Terminal line capability
May include an external, direct transfer trip
feature
Immune to swings, load, series caps
78
Transfer Trip
79
80
Tone 1 Rcvd
Tone 2 Xmit
Tone 2 Rcvd
81
Zone 1 distance
Zone 2 distance time delay trip
Zone 3 distance time delay trip
Instantaneous ground trip
Time overcurrent ground trip
BFR-Ring bus, breaker & half scheme
Transformer relays on transformer
terminated lines
Line reactor relays
82
Permissive Relay
Tone 2 Xmit
Tone 2 Xmit
Tone 2 Rcvd
Tone 2 Rcvd
83
Permissive Keying
Zone 2 instantaneous
Permissive overcurrent ground (very
sensitive setting)
PCB 52/b switch
Current reversal can cause problems
84
I Fault, Line AB
Ic
Ib
I Fault, Line CD
Id
85
I Fault, Line AB
Ic
I Fault, Line CD
Id
86
Directional Comparison
Blocking
Overreaching relays
Delay for channel time
Channel failure can allow overtrip
Often used with On/Off carrier
87
Directional Comparison
Forward
Relay
TD
Reverse
Relay
Reverse
Relay
Forward
Relay
Block Xmit
Block Xmit
Block Rcvd
Block Rcvd
Time Delay
Time Delay
TD
88
89
Tone Equipment
Interface between relays and
communications channel
Analog tone equipment
Digital tone equipment
Security features
Guard before trip
Alternate shifting of tones
Parity checks on digital
90
Tone Equipment
Newer equipment has 4 or more
channels
2 for direct transfer trip
1 for permissive transfer trip
1 for drive to lock out (block reclose)
91
Telecommunications
Channels
Microwave radio
Analog (no longer available)
Digital
Multiplexed fiber
Long runs
SONET Rings
93
Telecommunications
Channels
Power line carrier current
On/Off Carrier often used with directional
comparison
Hard wire
Concern with ground mat interconnections
Limited to short runs
Leased line
Rent from phone company
Considered less reliable
94
More on Reclosing
Only reclose for one line to ground faults
Block reclose for time delay trip (pilot
schemes)
Never reclose on power house lines
Block reclosing for transformer fault on
transformer terminated lines
Block reclosing for bus faults
Block reclosing for BFR
Do not use them
97
Breaker Failure
Relay
(50BF)
98
Breaker Failure
Stuck breaker is a severe impact to
system stability on transmission systems
Breaker failure relays are recommended
by NERC for transmission systems
operated above 100 kV
BFRs are not required to be redundant by
NERC
99
PCB Trip
Coil #1
BFR Fault
BFR Retrip Detector
TD
PCB Trip
Coil #2
BFR Time
Delay, 8~
TD
Trip
86
Block Close
Typical Breaker Failure Scheme with Retrip
101
Failed Breaker:
0 Fault occurs
+1~ BFR FD PU
+8~ BFR Time Delay
+1~ BFR Trips 86 LOR
+2~ BU PCBs trip
+1~ Remote terminal clears
Remedial Action
Schemes (RAS)
aka: Special
Protection Schemes
103
107
Generator Dropping
Trip generators for loss of load
Trip generators for loss of transmission
lines or paths
Prevent overloading
108
Reactive Switching
On loss of transmission lines
Trip shunt reactors to increase voltage
Close shunt capacitors to compensate for loss
of reactive supplied by transmission lines
Close series capacitors to increase load
transfers
Utilize generator var output if possible
Static Var Compensators (SVC) provide high
speed adjustments
109
110
112
113
Chief Jo Brake
114
115
116
117
the end
Jon F. Daume
Bonneville Power Administration
retired
March 15, 2011
118
Symmetrical Faults
Faults
Shunt faults:
Three phase
Line to line
Line to ground
2 Line to ground
a
b
c
a
b
c
c
b
a
a
b
c
Faults
Series faults
One open phase:
a
b
c
a
b
c
2 open phases
Increased phase
impedance
a
b
c
5
Symmetrical Faults
L
i(t)
AC
2V sin( t + )
e(t ) =
Fault at t = 0
2V
t=0
7
Symmetrical Faults
For a short circuit at generator terminals at t=0
and generator initially open circuited:
di
e ( t ) = Ri + L
dt
(L is considered constant)
di
2VSin(t + ) = Ri + L
dt
by using Laplace transforms i(t) can be found
Symmetrical Faults
2V
[ Sin(t + ) Sin( )e t / T ]
i (t ) =
Z
Where:
Z = R 2 + (L) 2 = R 2 + X 2
= Tan
T=
i(t ) =
2I
= Tan
L
X
=
R R
ac
Where: Iac
X
R
Time Constant
[ Sin ( t + ) Sin ( ) e t / T ]
(Examples)
i(t ) =
2I
ac
[ Sin ( t + ) Sin ( ) e t / T ]
= = 90
e(t)
2V
= 90 o
t=0
2 I ac
Idc = 0
iac
10
i(t ) =
2I
2V
ac
[ Sin ( t + ) Sin ( ) e t / T ]
= 90 o
=0
e(t)
t=0
iac
2 I ac 0
2 I ac 0
idc
11
i(t ) =
= 90 o
=0
2I
ac
[ Sin ( t + ) Sin ( ) e t / T ]
iac
2 I ac 0
2 I ac 0
2 2 I ac 0
idc
i (t )
t
12
Symmetrical Faults
Iac and Idc are independent after t = 0
2V
[ Sin(t + / 2) + e t / T ]
i (t ) =
Z
I
RMS
dc
ac
= 2I
+I
aco
dc
t T
e
Substituting:
2t T
2
2
T
I
(max)= (I
+ 2I )e
= I 1+ 2e
RMS
ac
ac
ac
13
Asymmetry Factor
IRMS(max) = K() Iac
Asymmetry Factor = K()
4 x
r
K ( ) = 1 + 2e
Where:
= number of cycles T = X / 2 fR
(Example 7.1)
14
Example 7.1
R = 0.8
CB
+
AC
XL = 8
Fault at t = 0
V = 20 kVLN
= 0.5 cycles
Example 7.1
a.
b.
I AC (0) =
20
0.8 + 8
2
K ( 0 .5 ) = 1 + 2 e
= 2.488kARMS
4 ( .5
10
= 1.438
K ( 3 ) = 1 + 2e
4 ( 3
10
= 1.023
AC Decrement
In the previous analysis we treated the
generator as a constant voltage behind a
constant impedance for each phase. The
constant inductance is valid for steady state
conditions but for transient conditions, the
generator inductance is not constant.
The equivalent machine reactance is made
up of 2 parts:
a) Armature leakage reactance
b) Armature reaction
17
(See Phasor Diagram)
AC Decrement
R
XL
EI
XAR
Load
I=IL
+
EI
XL
XAR
Armature Reaction
Field
Flux
Load
Loaded Generator
EI
Resultant
Field
jILXAR(t)
ET
IL
jILXL
19
I=0
+
E = E = E = ET0
XL
XAR=0
ET0
Unloaded Generator
Armature Reaction = 0
Field
Flux
Resultant
Field
t=0E
ET0
20
I=0
+
E = E = E = ET0
XL
XAR
Faulted Generator
t=0
Armature Reaction = 0
Field
Flux
Resultant
Field
ET0 = 0
21
I = I
XL
+
E = E = E = ET0
XAR=0
Armature Reaction = 0
Field
Flux
Resultant
Field
t=0+
E = jIXL
ET = 0
I
22
I = I
XL
+
E = E = E = ET0
XAR
Armature Reaction = 0
t 3Cyc.
Field
Flux
Resultant
Field
E = jI(XL + XAR)
ET = 0
I
23
I=I
XL
+
E = E = E = ET0
XAR
Armature Reaction = 0
t =
Field
Flux
Resultant
Field
E = jI(XL + XAR)
ET = 0
I
24
AC Decrement
As fault current begins to flow, armature reaction will
increase with time thereby increasing the apparent
reactance. Therefore, the ac component of the fault
current will decrease with time to a steady state
condition as shown in the figure below.
2I2I"
2I '
2I
25
AC Decrement
For a round rotor machine we only need to
consider the direct axis reactance.
2I"=
2I '=
2I =
2E"
X "d
2E'
X 'd
2E
X
d
Subtransient
Transient
Synchronous
(steadystate)
26
AC Decrement
Can write the ac decrement equation
i (t ) = 2 ( I " I ' )e
ac
T "d
E " = E '= E = ET
Td:
27
AC Decrement
i (t ) = 2 ( I " I ' )e
ac
T "d
For t = 0
ac and dc Decrement
Transform ac decrement equation to phasor form
_
t
t
I ac = ( I " I ' )e T " d + ( I ' I )e T ' d + I ] /
dc decrement equation:
I dc =
2 I " Sin ( ) e
29
Example 7.2
R=0
CB
+
AC
V = 1.05 pu
Fault at t = 0
30
Example 7.2
1 t .035 1
1 t 2 1
1
+
I AC ( t ) = 1.05
e
e
1.1
.24 1.1
.15 .24
I DC ( t ) max = 2 I " e
.2
I Base
500
=
= 14.434 KA
20 3
E " 1.05
I"=
=
= 7.0 puI DC
= 101kA
x" d .15
I DC ( t ) max = 2 (7)e
.2
= 9.9e
.2
a
b
31
Example 7.2
Part c: Find IRMS at interruption (3 cycles)
3
t=
= 0.05 sec .
60
1 .05 .035 1
1 .05 2 1
1
I AC ( t ) = 1.05
+
+
e
e
1.1
.24 1.1
.15 .24
.05
.2
= 7.71 pu
32
Example 7.2
Part d: Find IMomentary(max) at t = cycle
.5
t=
= .0083 sec
60
1 .0083 .035 1
1 .0083 2 1
1
+
I AC ( t ) = 1.05
+
e
e
1.1
.24 1.1
.15 .24
I DC = 9.9e
.0083
.2
= 9.5 pu
d
33
Turbine
Gen.
Energy
34
35
New representation:
IF
IG
Bus 2
IM
Bus 1
IG1
IF1
IM1
IG2
IF = IG1 + IM1
IL
IF2=0
36
Example 7.3
For the system of Slide 35 and 36 the generator is operating
at 100 MVA, .95 PF Lagging 5% over rated voltage
Part a: Find Subtransient fault current magnitude.
From Slide 36
VF
1.05
1.05
I F1"=
=
=
= j 9.08 pu
(.15)(.505) j .116
Z TH
j
.655
Part b: Neglecting load current, find Generator and
motor fault current.
.505
I G 1 " = j 9.08
= j 7 pu
.655
37
Example 7.3
Part c: Including load current, find Generator and
motor current during the fault period.
I Load
S * 1/ cos .95 1/ 18 o
o
= * =
=
=
.
952
/
18
= IG2 = I M 2
o
1.05
1.05 / 0
V
38
Z Bus Method
For Z bus method of fault studies the
following approximations are made:
Neglect load current
Model series impedance only
Model generators and synchronous
motors by voltage behind a reactance for
the positive sequence system
39
2
J 0 . 305
J 0 . 15
AC
J 0 .2
IF
-VF
+
AC
Eg
-
+
AC
40
Z Bus Method
For the circuit of Figure 7.4d (Slide 36 & 40)
Y 11 Y 12 E
I1
I = Y Y E
21 22
2
Injected
node
currents
[matrix
1
2
Node
voltages
Y-bus]
nodal
admittance
Premultiplying both sides by the inverse of [Y-bus}
E1 Z 11
E = Z
2 21
Z 12 I 1
Z 22 I 2
-IF1
0
For a fault
at Bus 1
E1 = Z11 ( I F 1 )
VF
E1
=
I F1 =
Z11
Z11
41
Z-Bus Method
For a fault at Bus 1
E 1 = Z 11 ( I
IF1
I
F 1
VF
E1
=
=
Z 11
Z 11
=
V
Z
F 1
F
11
where:
Z-Bus Method
For N bus system, fault on Bus n
-VF
E1 Z 11
E Z
2 21
E3 Z 31
=
E N Z n1
. .
E N Z N 1
I Fn
VF
=
Z nn
Z 12
Z 22
Z 13
Z 23
Z 1n
Z 2n
Z 32
Z 33
Z 3n
Z n2
.
Z n3
.
Z nn
,
ZN2
Z N3
Z Nn
. Z 1N 0
. Z 2 N 0
. Z 3N 0
. Z nN I Fn
.
. .
. Z NN 0
Z-Bus Method
After IFn is found the voltage at any bus can be
found from:
E1 = Z1n (-Ifn) E2 = Z2n(-Ifn) Etc.
If voltage at each bus is found, current through
any branch can be found:
I12 = (E1 - E2) / 12 Etc/
Note: 12 is series impedance between Bus1
and Bus 2, not from Z-Bus.
(Example 7.4)
44
Example 7.4
For the system of Figure 7.3 (Slide 40) using the Z-bus
method find:
a) Z bus
b) IF and I contribution from Line for Bus 1
fault
c) IF and I contribution from Line for Bus 2
fault
1
2
Y12 = -j3.28
Y10 = -j6.67
Y20 = -j5
IF
45
Example 7.4
j 9.95 j 3.28
[YBus ] =
j
3
.
28
j
9
.
95
[Z Bus ] = [Ybus ]
j .1156
=
j .046
E1 j .1156
E = j .046
2
j .046
j .139
j .046 I 1 -IF
j .139 I 2 0
E1 = ( j .1156) I 1
-VF
-IF
VF
IF "=
= j 9.08
j .1156
46
Example 7.4
Find: Line current
E1 j .1156
E = j .046
2
j .046 I 1
j .139 I 2
I 21
E 2 E1 .632 0
=
=
= j 2.07
Z 21
j .305
b
47
Example 7.4
1
2
Y12 = -j3.28
Y10 = -j6.67
Y20 = -j5
IF
Find IF and I contribution from Line for Bus 2 fault
E1 j .1156
=
-VF E 2 j .046
IF2
j .046 I 1
j .139 I 2
1.05
=
= j 7.55 pu
j .139
- I F2
Z-Bus Method
[Z-Bus] = [Y-Bus]-1
Will not cover formation of [Z-Bus] or [Y-Bus]
[Z-Bus] can be considered a fictitious circuit
which has the appearance of a rake. See
Figure 7.6 on Page 371.
49
VF
Z nn
E1 = VF ( Z 1n )( I n )
Etc.
50
Class Problem 1
For the given Bus Impedance matrix(where
subtransient reactances were used) and a
pre-fault voltage of 1 p.u.:
a. Draw the rake equivalent circuit
b. A three-phase short circuit occurs at bus
2. Determine the subtransient fault
current and the voltages at buses 1, 2,
and 3 during the fault.
51
Symmetrical Components
52
Symmetrical Components
Symmetrical Components is often referred to
as the language of the Relay Engineer but it
is important for all engineers that are
involved in power.
The terminology is used extensively in the
power engineering field and it is important
to understand the basic concepts and
terminology.
53
Symmetrical Components
Used to be more important as a calculating
technique before the advanced computer age.
Is still useful and important to make sanity
checks and back-of-an-envelope calculation.
We will be studying 3-phase systems in
general. Previously you have only considered
balanced voltage sources, balanced impedance
and balanced currents.
54
Symmetrical Components
Ib
bb
Ia
a
Vb
Va
ZY
ZY
n
Vc
Vb
ZY
Va
Vc
Ic
Balanced load supplied by balanced voltages results
in balanced currents
This is a positive sequence system,
In Symmetrical Components we will be studying
55
unbalanced systems with one or more dissymmetry.
Symmetrical Components
For the General Case of 3 unbalanced voltages
VC
6 degrees of freedom
VA
VB
Can define 3 sets of voltages designated as positive
sequence, negative sequence and zero sequence
56
Symmetrical Components
Common a operator identities
a =1/120o
a2 = 1/240o
a3 = 1/0o
a4 = 1/120o
1+a+a2 = 0
(a)(a2) = 1
57
Symmetrical Components
Positive Sequence
2 degrees of freedom
VC1
VA1
120o
120o
120o
VA1 = VA1
VB1 = a2 VA1
VC1 = a VA1
VB1
a is operator 1/120o
58
Symmetrical Components
Negative Sequence
2 degrees of freedom
VB2
VA2
120o
120o
120o
VC2
VA2 = VA2
VB2 = aVA2
VC2 = a2 VA2
a is operator 1/120o
59
Symmetrical Components
Zero Sequence
2 degrees of freedom
VA0
VB0
VC0
60
Symmetrical Components
Reforming the phase voltages in terms of the symmetrical
component voltages:
VA = VA0 + VA1 + VA2
VB = VB0 + VB1 + VB2
VC = VC0 + VC1 + VC2
What have we gained? We started with 3 phase voltages
and now have 9 sequence voltages. The answer is that the 9
sequence voltages are not independent and can be defined
in terms of other voltages.
61
Symmetrical Components
Rewriting the sequence voltages in term of the Phase A
sequence voltages:
VA = VA0 + VA1 +VA2
Drop A
VB = VA0 + a2 VA1 + aVA2
VC = VA0 + aVA1 +a2 VA2
VA = V0 + V1 +V2
VB = V0 + a2 V1 + aV2
VC = V0 + aV1 +a2 V2
V0
VB = 1
a2
V1
VC
a2
V2
[VP] =
[A]
[VS]
62
Symmetrical Components
We shall consistently apply:
[VP] = Phase Voltages
[VS] = Sequence Voltages
1 1 1
[A] = 1 a2 a
1 a a2
[VP] = [A][VS]
Pre-multiplying by [A]-1
[A]-1[VP] = [A]-1[A][VS]= [I][VS]
[VS] = [A]-1 [VP]
63
Operator a
a = 1 /120o = - .5 + j .866
a2 = 1 / 240o = - .5 - j.866
a3 = 1 / 360o = 1
a4 = 1 / 480o = 1 / 120o = a
a5 = a2 etc.
1 + a + a2 = 0
a - a2 = j 3
1 - a2 = 3 /30o
1/a = a2 Relationships of a can greatly expedite calculations
( Find [A]-1)
64
Inverse of A
1 1
[A] = 1 a 2
1 a
a
2
a
1 1
T
Step 1:
[
A] = 1 a 2
Transpose
1 a
1
a
a 2
2
2
2
a a aa
1 aa
2
2
a 1
2 a a a 1
2
2
a 1 a 1
3 a a
65
Inverse of A
1
2
2
2
a a aa
1 aa
2
2
a 1
2 a a a 1
2
2
1
a
a
3 aa
a a a a a a
2
2
a 1 1 a
2 a a
2
2
1
a
a
3 aa
66
Inverse of A
a a a a a a
2
2
a 1 1 a
2 a a
2
2
1
a
a
3 aa
1 1
[A] = 1 a 2
1 a
a
2
a
a 1
a 1 a a 1
=
=a 2
=a
2
2
a 1
aa
aaa
2
1 a 1 1 a 1
2
= =a
=
2
aa
a 1 a a
67
Inverse of A
[A]
1 1
1
= 1 a
3
2
1 a
1
2
a
a
68
Symmetrical Components
Previous relationships were developed for voltages.
Same could be developed for currents such that:
IA
[IP] = IB
IC
I0
[IS] = I1
I2
1 1 1
[A] = 1 a2 a
1 a a2
[A]-1
1 1 1
= 1/3 1 a a2
1 a2 a
69
Significance of I0
I0
I1
I2
1 1 1
= 1/3 1 a a2
1 a2 a
IA
IB
IC
I0 = 1/3 ( IA + IB + IC)
IA
In = IA + IB + IC = 3 I0
IC
In
IB
70
Example 8.1
277 / 0 o 277 a
o
[V P ] = 277 / 120 = 277a 2 b
277 / 120 o 277a c
Find [VS] (Sequence
voltages)
1 1
V0
277
1
[VS ] = V1 = [ A] [VP ] = 1 a
3
V2
1 a 2
1 1 0 0
o
2 2
a a = 277/ 0 1
a a 0 2
71
Example 8.2
Y connected load with reverse sequence
10 / 0 o
1 a
o
[I P ] = 10/ 120 = (10) a b
10 / 120 o
a 2 c
Find IS
(Sequence Currents)
1 1
10
1
[I S ] = [ A] [I P ] = 1 a
3
1 a 2
1 1 0 0
2
a
a =
0
1
a a 2 10 / 0 o 2
72
Ia = 10 /
0o
Example 8.3
I0
[I S ] = I 1 = [ A]1 [I P ]
I 2
Ic = 10
/120o
In
Ib =
o
1 1
10
[I S ] = 1 a
3
1 a 2
1 1 a
a 2 0 b
a a c
2
o
a
3.33 / 60 0
1+ a
10
10
o
[I S ] = 2 = 2 = 6.67 / 0 1
3
3
2
o
2
1
a
a
3
.
33
/
60
+
I n = 3 I 0 = 10 / 60 o
73
ZY
VC
VB
IB
ZY
n
ZY
Zn
.
VA = IAZy + (IA + IB +IC) Zn = (ZY + Zn)IA + ZnIB + ZnIC
VB = ZnIA + (ZY + Zn)IB + ZnIC
VC = ZnIA + ZnIB +(ZY + Zn)IC
74
V = Z
Z
Z
Z
I
+
n
Y
n
n
B
B
VC Zn
Zn
ZY +Zn IC
[VP] = [ZP] [IP]
(1)
Transform to sequence reference frame. We know:
[VP] = [A] [VS] and [IP] = [A] [IS], Substitute in(1)
[A][VS] = [ZP][A][IS] premultiply both sides by [A]-1
[VS] = [A]-1[ZP][A][IS] = [ZS][IS]
where: [ZS] = [A]-1[ZP][A]
75
3
Z20 Z21 Z22 1 a2 a Zn
Zn ZY +Zn1 a a2
0
ZY + 3 Z n
[Z S ] = 0
0
0
ZY
0
0
Z Y
0
1
2
76
0
ZY
0
0 I0
0 I 1
Z Y I 2
77
V0
I0
3 Zn
ZY
V1
I1
ZY
V2
I2
ZY
Sequence circuits
V0
I0
ZY
open
V1
I1
V2
I2
Z/3
Z/3
79
Z 00 Z 01 Z 02
1 1 1 Z AA Z AB Z AC 1 1 1
1
Z
1 a 2 a
2
=
Z
Z
1
a
a
Z
Z
Z
11
12
BB
BC
10
BA
3
Z 20 Z 21 Z 22
1 a 2 a Z CA Z CB Z CC 1 a a 2
If there is symmetry: ZAA = ZBB = ZCC and ZAB = ZBC = ZCA
we could perform multiplication and get:
0
0
Z AA + 2 Z AB
[Z S ] = 0
Z AA Z AB
0
0
0
Z AA Z AB
We see that: Z11 = Z22 and Z00 > Z11
80
IB
VA
VB
n
IC
ZBC
VC
VAA
ZAA
VBB
ZCA
ZBB
VAA
VB
ZCC
V A V A' Z AA
V V = Z
B'
BA
B
VC VC ' Z CA
VC
Z AB
Z BB
Z CB
VA
Z AC I A
Z BC I B
Z CC I C
81
Z0
[Z S ] =
Z1
Z 2
82
I0
Z0
V 0
o n0
V1
I1
Z1
V 1
o n1
V2
I2
Z2
o n2
V 2
83
84
ZAC
ZCA
+ EC
-
IC
ZBC
n
ZCB
EA +
ZAB
EB
ZK
ZK
ZBA
IA
eA = Em Cos t
eB = Em Cos(t 120o)
eC = Em Cos(t + 120o)
In phasor form:
EA= ERMS / 0 = E
EB = ERMS /-120o = a2 E
o = a E
E
=
E
/120
C
RMS
IB
B
85
[E ] = [ A] [E ]
1
Sg
Pg
[E ]
Pg
1 1
1
= 1 a
3
2
1 a
E a
= a 2 E b
aE c
1 E
a 2 a 2 E =
a aE
0 0
E
1
0 2
ZAC
ZCA
+ EC
-
IC
EA
ZBC
n
ZCB
IA
ZK
ZAB Z
BA
EB
ZK
IB
87
ZR + ZN
ZK + ZN
ZQ + Z N
ZQ + Z N I A
Z R + Z N IB
Z K + Z N I C
[E PG ] = [Z PG ][I P ]
ZG0
[Z SG ] = [ A]1 [Z PG ][ A] = 0
0
Z G1
0
0 0
0 1 uncoupled
Z G 2 2
Where: ZG0 = ZK + ZR + ZQ
ZG1 = ZK + a2 ZR + a ZQ
ZG2 = ZK + a ZR + a2 ZQ
88
V0
+
EG1
ZG1
I1
V1
ZG2
I2
Generator
Terminal
Voltages
V2
89
90
Example 8.6
- [ EP ] +
[ IP ]
Z L = 1.0 / 85o
Load
Z = 30 / 40o
Unbalanced Source
277 / 0o a
o
[EP ] = 260/ 120 b
295/ 115o c
ZY =
= 10 / 40 o = 7.66 + j 6.43
Z L = 1/ 85 o = .087 + j .996
Z 0 = Z 1 = Z 2 = Z Y + Z L = 7.747 + j 7.426 = 10.72 / 43.7 o
91
Example 8.6
- [ EP ] +
[ IP ]
277 / 0o
o
[EP ] = 260/ 120
295/ 115o
1 1
[E S ] = [ A]1 [E P ] = 1 1 a
3
1 a 2
Z L = 1.0 / 85o
Load
Z = 30 / 40o
2
o
o
a 260 / 120 = 277.1/ 1.77 1
92
I0
10.72
/43.7o
+
15.91
/62.1o
Example 8.6
I1
10.72
/43.7o
+
277.1 /1.77o
I2
+
9.22
/216.6o
I0 = 0
10.72
/43.7o
277 / 1.77 o
I1 =
10.72 / 43.7 o
I 1 = 25.84 / 45.5 o A
9.22 / 216.6 o
I2 =
10.72 / 43.7 o
I 2 = 0.86 / 172.9 o A
93
Example 8.6
0
o
[I S ] = 25.84/ 45.5 1
o
0.86 / 172.9 2
Amps
25.17 / 46.7 o a
o
[I P ] = [ A][I S ] = 25.72/ 196.4 b
26.64 / 73.8 o c
Amps
Ic
Ia
Ib
I
C
IB
IA
Ic
Ia
Ib
IC
IB
IA
I0
96
IA Q
Ic
P0
Ib
Ic/n
IB
Ic/n
IC
Ia Ib/n
IA Q
Ic/n
Ic
Ib
Ia
Ib/n
IB
I
Ic/
n
C
Ia + Ib + Ic = 0 Ia/n + Ib/n + Ic/n is not necessarily 0,
but IA + IB + IC = 0
No zero sequence current
flow
P0
Q0
Z0
n0
98
Ia
Ib
Ic
IA
IB
IC
Ia + Ib + Ic = 0
P0
IA + IB + IC = 0
No zero sequence current
flow
Q0
Z0
n0
99
Power
In
Sequence
Networks
For a single phase circuit we know that:
S = EI* = P + jQ
In a 3-phase system we can add the power in
each phase such that:
SP = EAIA* + EBIB* + ECIC*
Written in matrix form
[S P ] = [E A
EB
I A *
E C ] I B *
I C *
100
[IP] = [A][IS]
[IP]* = [A]*[IS]*
Class Problem 2
One line of a three-phase generator is open
circuited, while the other two are shortcircuited to ground. The line currents are:
Ia=0, Ib= 1500/90 and Ic=1500/-30
a. Find the symmetrical components of
these currents
b. Find the ground current
102
Class Problem 3
The currents in a delta load are:
Iab=10/0, Ibc= 20/-90 and Ica=15/90
Calculate:
a. The sequence components of the delta
load currents
b. The line currents Ia, Ib and Ic which feed
the delta load
c. The sequence components of the line
currents
103
Class Problem 4
The source voltages given below are applied
to the balanced-Y connected load of 6+j8
ohms per phase:
Vag=280/0, Vbg= 290/-130 and Vcg=260/110
The load neutral is solidly grounded.
a. Draw the sequence networks
b. Calculate I0, I1 and I2, the sequence
components of the line currents.
c. Calculate the line currents Ia, Ib and Ic
104
Unsymmetrical Faults
105
VB
V
A
n
C
Symmetrical Components Reference Frame
n0
n1
n2
I0
I1
I2
V0
V1
V2
106
Assumptions Continued
Synchronous machines represented by constant
voltage behind reactance(x0, x1. x2)
Non-rotating loads neglected
Small machines neglected
Effect of Y transformers may be included
108
IF0
Zero
System
f1
f2
IF1
EF1
Positive
System
IF2
EF2
Negative
System
n2
n0
n1
The sequence networks are connected together from
knowledge of the type of fault and fault impedance
Example 9.1
110
Example 9.1
Bus 1
Bus 2
X1=X2 =20
AC
100MVA
13.8kV
X=0.15pu
X2 = 0.17pu
X0 =0.05pu
100MVA
13.8:138kV
X = 0.1pu
X0 = 60
AC
100MVA
138:13.8kV
X = 0.1pu
100MVA
13.8kV
X=0.20pu
X2 = 0.21pu
X0 =0.05pu
Xn = 0.05pu
(138)2
100
190.4
Z1 = Z 2 =
j 60
j 20
= j 0.315 pu
= j 0.105 pu Z 0 =
190.4
190.4
111
Example 9.1
1
j.05
J0.315
AC
J0.1
J0.1
.
AC
J0.1
j.15
AC
1
j.15
J0.1
J0.105
J0.1
AC
+
AC
1.05 /
1
j.17
n0
1.05 / 0o
0o
J0.1
n1
J0.105
J0.1
.
J0.2
AC
AC
2
.
J0.21
AC
AC
.
AC
AC
112
n2
Example 9.1
Reduce the sequence networks to their
thevenin equivalents as viewed from Bus 2
1
j.05
AC
J0.315
J0.1
J0.1
.
AC
J0.1
AC
j.15
n
0
113
Example 9.1
1
j.15
J0.1
J0.105
J0.1
AC
+
AC
1.05 /
0o
1.05 / 0o
.
J0.2
AC
AC
n1
Positive Sequence Thevenin Equivalent
from Bus 2
f1
Z thev
j (.455)(.2)
=
= j .139
.655
J0.139
+
1.05 / 0 o
n1
114
Example 9.1
1
j.17
J0.1
J0.105
J0.1
2
.
J0.21
AC
AC
.
AC
AC
n2
Negative Sequence Thevenin Equivalent
from Bus 2
f2
Z thev
j (.475)(.21)
=
= j .146
.685
J0.146
n2
115
I FA
[I FP ] = 0
0
IF
B
IFC
1 1
[I FS ] = [ A]1 [I FP ] = 1 1 a
3
1 a 2
EFA = IFA ZF
EF0 + EF1 + EF2 = (IF0 + IF1 + IF2) ZF
1 I FA
I FA
1
a 2 0 = I FA
a 0
I FA
116
f1
IF1
EF Zero
0
System
n0
f2
IF2
EF1 Positive
System
n1
EF2 Negative
System
n2
117
EF0
EF1
EF2
IF0
Zero
System
n0
IF1 f1
Positive
System
n1
IF2
f2
Negative
System
3 ZF
n2
118
Example 9.3
For the system of Example 9.1 there is a bolted SingleLine-to-Ground fault at Bus 2.
Find the fault currents in each phase and the phase
voltages at the fault point.
f1
f0
IF0
IF1
J0.25
n0
IF 0 = IF1 = IF 2
J0.139
+
1.05 / 0 o
n1
f2
IF2
J0.146
n2
1.05 / 0 o
=
= j1.96
j .25 + j .139 + j .146
119
Example 9.3
IF0 = IF1 = IF2 = -j1.96
f1
f0
EF0
J0.25
n0
EF1
J0.139
+
1.05 / 0 o
n1
f2
EF2
J0.146
n2
120
Example 9.3
[I FP ] = [ A][I FS ]
I FA 1 1
I = 1 a 2
FB
I FC 1 a
1 j1.96 j 5.88 pu a
0
a j1.96 =
b
0
a 2 j1.96
c
[E FP ] = [ A][E FS ]
E FA 1 1
E = 1 a 2
FB
E FC 1 a
0
1 .491
a
a .777 = 1.179 / 231o pu b
2
o
a .286 1.179 / 128.7 pu c
Example 9.3a
Bus 1
IL
Bus 2
AC
AC
IF
I F 0 j1.96
I = j1.96
F1
I F 2 j1.96
I FA j 5.88 pu
I =
0
FB
0
I FC
SLG
Fault
.
Zero Sequence
1
j.05
AC
J0.315
J0.1
I L0 = 0
J0.1
2(f0)
-j1.96
AC
J0.1
.
AC
j.15
n
0
I L0 =0
123
Positive Sequence
1
j.15
J0.1
J0.105
e j30 : 1
AC
+
AC
1.05 /
j.455
I T1
2
f1
j .2
-j1.96
n1
.2
= ( j1.96)
= j .6
.655
I L1
e j30 : 1
SLG
1.05 / 0o
0o
n1
IT 1
J0.1
.
J0.2
AC
AC
I T1
f1 -j1.96
n1
I L1 = 0.6 / 60
124
Negative Sequence
1
j.17
J0.1
J0.105
J0.1
e -j30 : 1
AC
SLG
.
J0.21
AC
.
AC
n2
j.475 2
I T2
j .2
f2 -j1.96
n2
IT 2
.21
= ( j1.96)
= j .6
.685
I L2
I T2
e -j30 : 1
f2 -j1.96
n2
I L 2 = 0.6/ 120o
125
Example 9.3a
Bus 1
IL
Bus 2
AC
AC
IF
0 . 0
[I LS ] = .6/ 60 o 1
.6 / 120 o 2
1 1
[I PL ] = [ A][I PS ] = 1 a 2
1 a
SLG
Fault
0
1
j1.039 pu a
a .6 / 60 o =
0
b
a 2 .6 / 120 o j1.039 pu c
126
0
[I FP ] = I FB
I FB
IFB
EF
nA
EF
B
IFC
EF
ZF
1 1
[I FS ] = [ A]1 [I FP ] = 1 1 a
3
1 a 2
E FA
[E FP ] = E FB
E FB I FB Z F
1 1
[EFS ] = 1 1 a
3
1 a 2
0
1 0
1
2
a
I FB =
j 3 I FB
3
a I FB
j 3 I FB
IF0 = 0
IF1 = IF2
I F 1 = j 3 I FB so I FB =
EFA
1
EFA + 2 EFB I FB Z F
= 1 E E a2 I Z
a 2
EFB
FB
FB F
3 FA
EFA EFB aI FB Z F
a EFB I FB Z F
a2 a
EF1 EF 2 =
IFBZF = ( j 3)IFBZF = j 3IFBZ F= IF1 ZF
3
0
1
2
127
IF1
j 3
f0
EF0
IF0
Zero
System
n0
IF1
f1
EF1 Positive
System
n1
IF2
f2
EF Negative
System
2
n2
128
Example 9.4
EF 0 = 0
129
Example 9.4
I FA 1 1
I = 1 a 2
FB
I FC 1 a
1 0
0
0
a
a j 3.69 = j 3 ( j 3.69) = 6.39 pu b
2
a j 3.69 j 3 ( j 3.69) 6.39 pu c
E FA 1 1
E = 1 a 2
FB
E FC 1 a
1 0 1.07 pu a
a .537 = .537 pu b
2
a .537 .537 pu c
130
IFC
ZF
EF
E FA
E FA
[E FP ] = E FB = ( I FB + I FC )Z F
E FC ( I FB + I FC )Z F
1 EFA EFA / 3 + 2 I F 0 Z F
a 2 3I F 0 Z F = EFA / 3 I F 0 Z F
a 3I F 0 Z F EFA / 3 I F 0 Z F
0
1
2
3ZF
f0
EF0
IF0
Zero
System
n0
IF1
f1
EF1 Positive
System
n1
IF2
f2
EF2 Negative
System
n2
132
Example 9.5
For the system of Example 9.1 there is a 2-line-toground bolted fault at Bus 2.
a) Find the fault currents in each phase
b) Find the neutral current
c) Fault current contribution from motor and generator
Neglect delta-wye transformers
Bus 1
IL
Bus 2
AC
AC
IF
.
2LG
Fault
133
Example 9.5
f1
f0
IF0
J0.25
n0
IF1 =
f2
IF1
J0.139
+
1.05 / 0 o
-
n1
IF2
J0.146
n2
1.05
= j 4.547 pu
(.146)(.25)
j .139 + j
.146 + .25
I F 0 = ( I F 1 )
.146
= j1.674 pu
.146 + .25
134
Example 9.5
1 1
[I FP ] = 1 a 2
1 a
This image cannot currently be display ed.
1 j1.674
0
a
a j 4.547 = 6.9 / 158.7 o pu b
2
o
a j 2.873 6.9 / 21.3 pu c
135
Example 9.5
I GF 0 = 0
j.455 2 j .2
I T1
-j4.547
f1
I GF !
.2
= ( j 4.547 )
= j1.39
.655
n1
2 j .2
I T2
J2.87
f2 3
n2
I GF 2
.21
= ( j 2.8773)
= j .88
.685
Example 9.5
1 1
[I GFP ] = 1 a 2
1 a
1 0 j .51 pu
a j1.39 = 1.98 / 172.6 o pu
1 1
[I MFP ] = 1 a 2
1 a
1 j1.674 j .504 pu
o
2
o
a j1.99 5.0 / 26.9 pu
137
Example 9.6
Find the fault current contribution from the generator
considering the delta-wye transformer phase shift.
Example 9.5 results
1
j.05
AC
I L0 = 0
J0.315
J0.1
J0.1
2
X
J0.1
2LG .
J1.674 j.1
5
AC
AC
n
0
-j1.39 1
j.15
AC
J0.105
e -j30 : 1
AC
J0.1
1.39/ -60o
AC
1.05 /
-j1.39 2
J0.1
X
-j3.16
.
j30
e :1
2LG J0.2
+
0o
1.05 /
0o
AC
n1
138
Example 9.6
Example 9.5 results
j.88
j.17
.88/ 60o
J0.1
J0.105
e j30 : 1
AC
j.88
e -j30 : 1
J0.1
2
X
2LG
AC
J1.99
AC
Bus 1
.
J0.21
IGP
AC
1 1
[I GP ] = 1 a 2
1 a
n2
IL
Bus 2
X
2LG
Fault
1 0 j .51 pu a
.
o.
2
o
a j .88 1.98 / 7 pu c
M
AC
139
T1
Bus 1
Class Problem 5
Bus 3 T3
LINE 1-3
G1
G3
AC
AC
LINE 1-2
Bus 2
LINE 2-3
T4
T2
G4
G2
The system data in p.u. based on SB = 100MVA, VB = 765kV for the lines are:
G1: X1=X2=.18, X0=.07
T1: X=.1
T2: X=.1
T3: X=.24
T4: X=.15
a)
X0=.17
X0=.17
From the perspective of Bus 1, draw the zero, positive and negative sequence networks.
140
141
142
143
144
146
147
148
149
150
Questions
151