Escolar Documentos
Profissional Documentos
Cultura Documentos
3, JULY 2014
747
I. INTRODUCTION
NSTALLATION of relatively small power sources embedded inside distribution networks, generally referred to as
distributed generation (DG), has extensively expanded in the last
decade and is expected to play a major role in future power
systems, as it enhances system reliability, reduces losses, and
shaves peak power, among other benets [1]. The spread of DG
also facilitates easier integration of renewable energy sources
such as wind power. Induction generators (IGs) are one of the
main technologies deployed in wind-based DGs, particularly
doubly fed IG (DFIG), which offer variable speed operation
accompanied by moderate converter sizes and hold the largest
market share for the currently installed wind capacity [2].
Despite various merits of DGs, their growth presents several
challenges to distribution system operation. A substantial portion
of these challenges appears as more rigorous requirements or
further complications for the existing distribution system protective relaying. For instance, DGs can cause mis-coordination
between overcurrent relays by increasing the fault current level,
1949-3029 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
748
0 coset=Ts
(1)
1s X
where Vm is the pre-fault voltage amplitude, s is the machine slip,
X 0 is the machine transient reactance, Xs is the stator leakage
reactance, Xms is the stator magnetizing reactance, T 0 is the
short-circuit transient time constant, which is inversely related to
the rotor resistance, ! 260 rad/s is the fundamental angular
frequency, is the fault inception angle, and Ts is the stator time
constant.
Although (1) is for a bolted fault at the SCIG terminal, it
describes the essential pattern of actual power system fault
currents fed by SCIGs as well. The only difference comes from
the fact that (1) is derived based on a 100% voltage dip
assumption, whereas actual power system faults always include
some levels of fault resistance, which leads to nonzero fault
voltage and keeps the IG from complete demagnetization. As a
result, unlike the current of (1), which eventually declines to zero,
SCIGs can sustain a small fault current in practice.
In the event of a voltage dip, large overcurrents are generated
in the rotor winding of an IG. In a DFIG, these overcurrents can
damage the rotor-side converter. Several methods, commonly
known as fault ride-through (FRT) techniques, have been proposed in the literature to protect the converters during such
conditions and enable the wind facility to meet the previously
discussed new grid code requirements [13]. Meanwhile, the
actual FRT practice in industrial applications remains the traditional crowbar circuit method, which diverts the rotor currents
through a short-circuit path, or a simple resistor [14]. Threephase short-circuits, the focus of this study, are among the most
severe faults that cause signicant voltage drops and subsequent
crowbar activation. When the rotor circuit is shorted and the
converters are eliminated from the gure, a DFIG is in essence an
SCIG and exhibits similar fault behavior.
Although the SCIG fault current expression of (1) ts DFIG
currents after three-phase short-circuits fairly well, a number of
its parameters may have different values for DFIGs. The most
critical of these parameters with respect to directional relaying is
the machine slip. The SCIG rotor speed is conned to a narrow
range close to the synchronous speed. Hence, the slip becomes
very small and the (1 s) term, which is multiplied with the
frequency of the sinusoidal term in (1), can be neglected. A
DFIG, however, accommodates different wind speeds by allowing signicant rotor speed deviations around the synchronous
speed, resulting in a 30% band for the slip. Consequently,
(1 s) is no longer a negligible term in (1) and the fault current
fundamental frequency ranges from 42 to 78 Hz for a 60-Hz
system.
To illustrate this issue, the simple test system in Fig. 1, which
includes a DFIG-based DG, was simulated with the PSCAD/
EMTDC program. The crowbar resistance of the DFIG is zero at
this stage. The effect of nonzero crowbar resistance is studied
later on. At t 7 s, a three-phase fault is placed on bus 4, i.e., the
Fig. 2. Three-phase DFIG fault current for two sub- and super-synchronous rotor
speeds.
feeder without the DG. The phase A current recorded by the relay
at the beginning of the feeder with the DG is plotted in Fig. 2 for a
sub- and a super-synchronous rotor speed, resulting in positive
and negative slips, respectively. The depicted waveshapes agree
with the general fault current pattern described in (1). In addition,
the dependence of the current frequency on the slip is evident.
B. Directional Relaying in Presence of DFIGs
The relay installed at the beginning of the feeder with the DG
in Fig. 1, denoted by DiR12, has to be directional in order to avoid
unnecessary tripping as a result of the DG contribution to the
faults on the other feeder. Following the common directional
relaying practice for three-phase short-circuits implemented in
commercial digital directional elements, such as in [15] and [16],
DiR12 is memory-polarized, i.e., the angle of each phase current
is compared with that of the pre-fault voltage in the same phase.
The results of this study are independent of the directional relay
characteristic angle (RCA); so, for the sake of simplicity, the
RCA is chosen to be zero degrees. DiR12 measures the voltage
phasor using discrete Fourier transform (DFT). Due to the unique
properties of a three-phase DFIG fault current, the performance
of DiR12 is inspected by three different current phasor measurement techniques (PMTs) developed so as to suppress the impact
of the fault currents decaying dc offset on the measured phasor:
1) the 1.25 cycles cosine ltering (CF) technique [17];
2) the one-cycle least error square (LES)-based technique
developed in [18], referred to as conventional LES (CLES)
in this paper;
3) the one-cycle-modied LES (MLES) method, discussed in
the Appendix.
The rst two techniques are termed common PMTs in this
paper, as they are widely used in modern commercial relays [17].
HOOSHYAR et al.: THREE-PHASE FAULT DIRECTION IDENTIFICATION FOR DISTRIBUTION SYSTEMS WITH DFIG-BASED WIND DG
749
Fig. 3. Phase difference between the memorized voltage and fault current for the
fault in Fig. 2, considering voltage frequency for all phasor measurements.
(a) s 24% and (b) s 20%.
Fig. 4. Phase difference between the memorized voltage and fault current for the
fault in Fig. 2, considering voltage and current frequencies for their respective
phasor measurements. (a) s 24% and (b) s 20%.
750
(2)
Fig. 6. Comparison of the phasor measured for substation and DFIG fault
currents. (a) Current of (2) for 90 , 40 ms, and Im 1. (b) Current
of (1) for identical ac and dc components, with 40 and 80 ms time constants,
respectively.
provide the accurate fundamental frequency phasor. For example, the current described by (2) is plotted in Fig. 6(a) for
90 , 40 ms, and Im 1. Fig. 6 also displays the
magnitude of the phasors obtained by the three current PMTs
mentioned earlier. For all three techniques, the calculated
phasor remains virtually xed at a very narrow margin of the
fundamental components amplitude following their initial
response time.
A DFIG fault current and its measured phasor, however,
exhibit a different pattern. As a representative case, Fig. 6(b)
shows the current described by (1) for identical unity ac and dc
component amplitudes and for dc and ac time constants equal to
40 and 80 ms, respectively. The ac component frequency is
60 Hz. The above PMTs are again employed to nd the current
phasor. The decaying nature of the ac component is directly
reected in the measured phasors. The declining phasors in
Fig. 6(b) are in clear contrast with the uniform pattern observed
for the phasors plotted in Fig. 6(a).
As dened by (3), 1 calculates the relative percentage
decline in the magnitude of the measured phasor for the fault
current in one phase:
jIf1 j jIf2 j if -ext
100
(3)
1
jIf2 j
If2
where If1 is the maximum of the measured fault current phasor
within the rst half-cycle after the initial response time of the
employed PMT. If2 is the minimum magnitude of the measured
fault current phasor in the second half-cycle after the response
time of the PMT applied to the current. if -max is the largest
magnitude for the current samples prior to If2 location and 4 ms
after the DD activation. if -max is supposed to be the extremum
HOOSHYAR et al.: THREE-PHASE FAULT DIRECTION IDENTIFICATION FOR DISTRIBUTION SYSTEMS WITH DFIG-BASED WIND DG
PARAMETERS
OF
751
TABLE I
(3) FOR THE CURRENTS SHOWN IN FIG. 6
Fig. 7. Frequency response of the sine and cosine digital lters. (a) MLES
method. (b) CLES method.
752
PERFORMANCE
OF THE
TABLE II
PROPOSED METHOD
FOR
DIFFERENT FAULTS
a
b
Fig. 9. Indices obtained for the currents described by (2) with respect to the fault
inception angle and dc offset time constant. (a) 1 and (b) 3 .
Fig. 11. Currents recorded at bus 844 for a fault on bus 842. (a) Phase A.
(b) Phase B. (c) Phase C.
HOOSHYAR et al.: THREE-PHASE FAULT DIRECTION IDENTIFICATION FOR DISTRIBUTION SYSTEMS WITH DFIG-BASED WIND DG
753
Fig. 12. Currents recorded at bus 832 for a fault on bus 802. (a) Phase A.
(b) Phase B. (c) Phase C.
Fig. 13. Currents recorded at bus 842 for a fault on bus 860 considering nonzero
resistance for the crowbar circuit. (a) Phase A. (b) Phase B. (c) Phase C.
A. Case Studies
754
Fig. 14. Currents recorded at bus 852 for a fault on bus 860. (a) Phase A.
(b) Phase B. (c) Phase C.
Fig. 15. Currents recorded by the relay at bus 854 for a fault next to the bus in the
downstream direction when an SG-based DG is behind the relay. (a) Phase A.
(b) Phase B. (c) Phase C.
HOOSHYAR et al.: THREE-PHASE FAULT DIRECTION IDENTIFICATION FOR DISTRIBUTION SYSTEMS WITH DFIG-BASED WIND DG
Nh
X
h2
Ih sinh!nT h
(4)
755
in
Nh h
X
Ih cosh sinh!nT
h1
Ih sinh cosh!nT
(5)
where the underlined terms are the unknowns. The next steps use
(2) for the samples inside a window to form a matrix equation
whose LES-based solution provides the above unknowns and, in
turn, the current phasor. These steps are similar to the CLES
technique [17], [18].
REFERENCES
[1] R. Dugan and T. McDermott, Distributed generation, IEEE Ind. Appl.
Mag., vol. 8, no. 2, pp. 1925, Mar./Apr. 2002.
[2] A. D. Hansen, Generators and power electronics for wind turbines,
in Wind Power in Power Systems, 2nd ed. Hoboken, NJ, USA: WileyBlackwell, 2012, pp. 73104.
[3] T. Seegers, K. Birt, R. Beazer, M. Begovic, K. Behrendt, S. Boutilier et al.
(Aug. 2004). Impact of distributed resources on distribution relay protection. Report of working group D3 of the line protection subcommittee, IEEE
Power System Relaying Committee [Online]. Available: www.pes-psrc.
org/Reports/wgD3ImpactDR.pdf.
[4] H. J. Laaksonen, Protection principles for future microgrids, IEEE Trans.
Power Electron., vol. 25, no. 12, pp. 29102918, Dec. 2010.
[5] E. Sortomme, S. S. Venkata, and J. Mitra, Microgrid protection using
communication-assisted digital relays, IEEE Trans. Power Del., vol. 25,
no. 4, pp. 27892796, Oct. 2010.
[6] T. K. Abdel-Galil, A. E. B. Abu-Elanien, E. F. El-Saadany, A. Girgis,
Y. A.-R. I. Mohamed, M. M. A. Salama, and H. H. M. Zeineldin.
(Jun. 2007). Protection coordination planning with distributed generation.
National Resources Canada [Online]. Available: http://canmetenergy.nrcan.
gc.ca/sites/canmetenergy.nrcan.gc.ca/les/les/pubs/2007-149e.pdf.
[7] S. H. Horowitz and A. G. Phadke, Nonpilot overcurrent protection of
transmission lines, in Power System Relaying, 3rd ed. Hoboken, NJ, USA:
Wiley, 2008, pp. 75100.
[8] I. Erlich and U. Bachmann, Grid code requirements concerning connection
and operation of wind turbines in Germany, in Proc. IEEE Power Eng. Soc.
General Meeting, San Francisco, CA, USA, Jun. 2005, vol. 2,
pp. 12531257.
[9] Schweitzer Engineering Laboratories (SEL). (Sep. 2012). Instruction
manual of SEL-700GW wind generator and intertie protection relay. SEL,
Pullman, WA, USA [Online]. Available: www.selinc.com/SEL-700GW.
[10] L. Y. Yu, I. Minceff, D. W. Hamilton, and G. W. Bottrell, Motor
contribution during three-phase short circuit fault, IEEE Trans. Ind. Appl.,
vol. IA-18, no. 6, pp. 593599, Nov./Dec. 1982.
[11] F. Sulla, Island operation with induction generatorsFault analysis
and protection, Ph.D. dissertation, Dept. Measurement Technology and
Industrial Electrical Engineering, Lund Univ., Lund, Sweden, 2009.
756