ALTERATIONS

NO.

DESCRIPTION

1 Added owners approval date for Rev.0.

PCM

AUTHOR.

BY

DATE

Owner

VIVEK

24th Sept 09

CHECK

Choong

REFERENCE PLANS
NO.

TITLE

PLAN NO.

PLAN BY

This document and the information which it contains are confidential and are the property of Keppel-FELS Ltd. It is loaned to you for the limited purpose of
assisting you with operation and maintenance of the equipment which you have purchased from Keppel-FELS Ltd. It remains the property of Keppel-FELS Ltd. It
may not be reproduced in whole or in part without Keppel-FELS prior written consent. It may not be disclosed to persons not having need of disclosure for the loan
and it is to be returned to Keppel-FELS Ltd upon completion of the use for which it was loaned.
PRINT RECORD

DATE PRINTED 11/08 29/09


REVISION
0
1
Alpha Star Ltd
4
4
ABS Site
2
2
QA
2
2
PJS
5
5
PJS(C)
5
5

29-Sep-09

Keppel FELS Limited


50, Gul Road
Singapore 629351

Tel: (65) 68637200


Fax: (65) 68631739

Printed from GEMS


No Signature Required

JOB:

DATE :

28th May 2009

SCALE :

N.T.S

DESIGNED BY :

Keppel FELS

HULL/JOB NO :

B309

DRAWN BY :

JAI

COST CODE NO: -

CHECKED BY :

YANG

APPROVED BY :

APPROVED BY :
OWNER
CLASS

1
QGOG

DSS 38 - DP2 DRILLING


SEMI-SUBMERSIBLE
FOR 9000 FEET WATER DEPTH

TITLE:

TEST MEMO FOR


MAIN GENERATOR

CHOONG

DATE :

14-AUG-09

SHEET 1 OF 46 SHEETS
K-FELS
DRAWING NO :
OWNER
DRAWING NO :

TM-M001

ALT. NO.

A4 (285 X 199)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

1.0

Page 2 of 46
Alt. 1
Date: 24-Sep-09

REFERENCE

No.

Description

1.1

Main specification for construction and outfitting of the DSS 38 - DP2, deep water of 9000
feet development Semi Submersible.
ME 20-710G9B-T1Electro Motive Diesel engine - Operation and Maintenance Manual.

1.2
1.3
1.4
1.5

KFELS
Commissioning
Supervisor

Keppel FELS drawing no. M101-10 Machinery Arrangement Generator Room No.1
(Stbd/Lower & Tween Deck).
Keppel FELS drawing no. M101-11 Machinery Arrangement Generator Room No.2
(Port/Lower & Tween Deck).
Keppel FELS drawing no. M201-05 Ventilation Arrangement and Details Generator
Room No.1 (Stbd/Lower & Tween Deck).

1.6

Keppel FELS drawing no. M201-06 Ventilation Arrangement and Details Generator
Room No.2 (Port/Lower & Tween Deck).

1.7

KEPPEL FELS drawing no. P107 Piping Diagram - Fuel Oil System

1.8

Keppel FELS drawing no. P113-1 Piping Diagram Central Cooling System (Sea Water).

1.9

Keppel FELS drawing no. P114 Piping Diagram Engine Exhaust System.

1.10

Keppel FELS drawing no. P116-1 Piping Diagram Rig Air System

1.11

Keppel FELS drawing no. P117 Piping Diagram Starting Air System

1.12

Keppel FELS drawing no. P118-1 Piping Diagram Lube Oil System

1.13

Keppel FELS drawing no. P118-2 Piping Diagram Waste Oil System

1.14

Keppel FELS drawing no. E052, One Line Diagram 480VAC Main Switchboard A-B.

1.15
1.16

Keppel FELS drawing no.E059 One Line Diagram 220 / 127 VAC Main Switchboard
- 2.
Keppel FELS drawing no. E051, One Line Diagram 11 KVAC Main Switch board.

1.17

Keppel FELS drawing no. E301, Schematic & Arrangement Main Generator controls

2.0

3.0

PURPOSE
2.1

To ensure proper installation of main generators.

2.2

To demonstrate operational capabilities of main generators.

2.3

To demonstrate proper functioning of control and safety devices.

SYSTEM DESCRIPTION
3.1 System:
The purpose of the main generators is to supply power to the whole rig. The system consists of Ten
generator sets and a main switchboard. In order for the generator sets to function properly, the starting air
system, sea water cooling system, ventilation system inside engine room, fuel oil system and lube oil system
play an integral part.
3.2

Mechanical:
It consists of Ten (10) (ME 20-710G9B-T1) x EMD diesel engines with NOV Baylor generator ( Model no
855ZXT rated 3580 eKW ) as prime mover of the system, design output of each generator set is 3560 eKW
@ 900 rpm. The diesel engine and the alternator are coupled by flexible coupling.

3.3

Piping:
It consists of starting air piping, diesel piping, lube oil & waste oil piping, exhaust piping and cooling water
piping system.

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

3.4

4.0

Page 3 of 46
Alt. 1
Date: 24-Sep-09

Electrical & Instrumentation:


The output power from generator is 4450 KVA, which is distributed throughout rig by 11 KVAC Main
Switchboard and 480VAC Main Switchboard A-B. The Generators are designed for a power factor of 0.8.

EQUIPMENT REQUIRED

No.

Description

KFELS
Commissioning
Supervisor

4.1

Voltmeters*: 0-1500 volt, 0-1000 volt, 0-250 volt, 0-25 volt (2% accuracy)

4.2

Ammeter *

4.3

Ohmmeter *

4.4

Insulation resistance tester *

4.5

Thermometer *

4.6

Tachometer *

4.7

Stopwatch

4.8

Load banks for load testing the generators ( 10680 KW, 13350 KVA)

4.9

Walkie Talkie

*NOTE: All test instruments shall bear certificate of calibration dated within 12 months of test.
5.0

PRE-OPERATIONAL CHECK

No.

Description

5.1

Pre-operational checks shall be conducted by vendor service engineer as per manufacturers


standard.
Verify all major items listed on FAT PAIRS and Punch lists are closed by QGOG.
All necessary adjustments for alignment and crankshaft deflection of each generator have
completed and the readings are within tolerance of manufacturer recommended values and
accepted by QGOG/ABS and recorded by KFELS QA.
Crank case and alternator of each unit is inspected by QGOG, it is clean, no foreign materials
found and moisture free.
Crankshaft has been turned by turning device and found no mechanical interference.

5.2
5.3

5.5

5.6

Turbochargers have been checked.


Record data found on the equipment nameplates in Table 1.0 and verify them against design
data.
Engine isolation height to be measured for all the engines before starting the test.
The main generators have been installed as per KFELS drawing no. M101-10 Machinery
Arrangement Generator Room No.1 and M101-11 Machinery Arrangement Generator
Room No 2. Mounting and alignment of generator sets are accepted by QGOG/ABS and
documented by KFELS QA.
Pipe works for cooling water system have been installed as per KFELS drawing P113-1
Piping Diagram Central Cooling System (Sea water), hydro-tested, reinstalled, and accepted
by QGOG/ABS and documented by KFELS QA.
Jacket water with recommended additives for each engine is filled up to required level.
The fuel oil piping system from the service tank to generator and return line has been installed
as per KFELS drawing no. P107 Piping Diagram - Fuel Oil System, hydro-tested, reinstalled,
accepted by QGOG/ABS and documented by KFELS QA.

TM-M001 R1 Main Generator

KFELS
Commissioning
Supervisor

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 4 of 46
Alt. 1
Date: 24-Sep-09

No.

Description

5.7

The lube oil piping system has been installed as per KFELS drawing no. P118-1 Piping
Diagram - Lube Oil System and P118-2 Piping Diagram Waste Oil System, hydro-tested,
reinstalled, accepted by QGOG/ABS and documented by KFELS QA.
Lube oil sump low level alarm is tested before filling lube oil and documented by KFELS
QA. Engine lube oil sump is filled up with manufacturer recommended lube oil.
Pre-lube oil pump is operated and checking has been done for leaks within the skid.
Lubrication NDE/DE Alternator shall be connected to 230 V UPS and 480 VAC Main.
Starting Air system test is installed as per KFELS drawing no P116-1 Rig Air System and
P117 Starting Air system, hydro tested, reinstated, accepted by QGOG/ABS and documented
by KFELS QA.
The electrical system has been installed as per KFELS drawing no. E051 One line diagram
11KVAC Main Switchboard, E052, One line diagram - 480VAC Main Switchboard A-B,
E059, One line diagram - 220 / 127 VAC Main Switchboard 1-2., E301 Schematic &
Arrangement Main Generator controls. Continuity checks and megger checks have been
done and the installation is accepted by QGOG/ABS and documented by KFELS QA.
Entire switchboard and transformers have been thoroughly cleaned and all foreign materials
removed. Commissioning team has completed the pre-commissioning of all AC modules.
All preservation items such as silicon packages within engine and switchboard have been
removed. All non-essential items blocking the passages and equipment inside engine room
have been removed.
All penetrations for instruments, pipe works have completed before diesel filling into the FO
(day) tanks as per KFELS drawing no. H701-03 Settling & Day Tank Detail in Aux Mech
Room No-1 (Stbd). All fuel tanks and temporary tanks are cleaned and free from foreign
matters.
Permanent FO tanks to be properly treated and witness by QGOG.
Starting air system is ready and operational. Check air pressure on the receiver after charging
is 145 psi.
Portable fire extinguishers are readily available inside the engine room if C02 fire fighting
system is not ready.
Insulation Resistance inspected and verified by vendor:
a) Stator insulation resistance not less than 1.6 M ohms, Actual value:

5.8

5.9

5.10

5.11

5.12
5.13
5.14

b) Rotor insulation resistance not less than 1.6 M ohms, Actual value:
c) Field insulation resistance not less than 1 M ohms, Actual value:
d) PMG Stator insulation resistance not less than 1.6 M ohms, Actual value:
e) PMG Rotor insulation resistance not less than 1.6 M ohms, Actual value:
f) Cable insulation resistance not less than 1000 M ohms, Actual value:

5.15
5.16
5.17

g) Insulation resistance between switchboard bus bars not less than 1.6 M ohms, Actual
value:
h) Insulation resistance between transformer difference phases not less than 1.6 M ohms,
Actual value:
Filters and strainers are checked.
Generator space heaters should be powered for at least 24 hours prior to operation as per
manufacturers recommendation.
Important:
Confirmation of generator breaker setting and generator breaker operational test are to be
satisfactorily carried out including, but not limited to overload protection, prime mover
shutdown, under voltage protection and reverse power protection before start of item
6.3, 6.4.

TM-M001 R1 Main Generator

KFELS
Commissioning
Supervisor

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

6.0

Page 5 of 46
Alt. 1
Date: 24-Sep-09

TEST PROCEDURE
All works are to be suspended on the Main Switchboard before the Engine start up.
All non-essential personnel need to vacate from the Main voltage switchboard room during the testing.
Note: Operation of the governor will comply to Part 4-3-4/ 3.19.1
Ensure generator being loaded / unloaded is on the opposite bus as load to allow the full amount of current to
pass through the tie breaker.

No.

Description

6.1

Start-Up and Shut-Down


A brief start up and shut down will be demonstrated under this
test. Verify all the gauges, instruments on the control panel are
working.
Start diesel engine according to manufacturers procedure
(refer to Reference Document #1). Adjust it to rated speed of
900 rpm.
Note: Ensure breaker is in open position.
Demonstrate the shut down by turning the engine control
switch to Off/Reset. Again restart the engine and demonstrate
the shut down by Emergency-stop switch at medium voltage
room and local engine panel.
Check engine and all auxiliary equipment for signs of defects
and discrepancies (e.g. abnormal noise, vibration, leakage,
etc.). Record and rectify any inadequacies found.
Lubrication of alternator bearings shall be continuously
checked during the commissioning test.
Repeat step 6.1.1 to 6.1.4 for all generator sets.

6.1.1

6.1.2

6.1.3

6.1.4
6.1.5

6.2

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

Shutdown and Alarm Setting Tests

No.

Description

6.2.1

Simulate over speed trip through generator control panel.


Verify the engine trip when over speed simulated. Record the
results. Repeat this at diesel generator local control panel and
at EGCP-3.
Simulate low lube oil pressure by isolating the pressure
transducer from line pressure.

6.2.2

KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor

6.2.3

Simulate high jacket water temperature by removing


temperature sensor from the engine and exposing it to higher
temperature. 96.1C <205F>. Verify the alarm and record
the results.

6.2.4

Switchboard vendor to confirm all control panel


Configuration menus for all generators are set for correct
generator parameters.

TM-M001 R1 Main Generator

KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 6 of 46
Alt. 1
Date: 24-Sep-09

No.

Description

KFELS
QGOG
ABS (where
Commissioning Representative applicable)
Supervisor

6.2.5

All switch board insulation tests and generators control panel


settings for both Hard & Soft shutdowns are set same for all
the generators and verified by vendor in the following
electrical test memo:
11KVAC Main Switchboard Test Memo TM-E001, 480VAC
Switchboard Test Memo TM-E004, 480VAC Emergency
Switchboard Test Memo TM-E005 and 480VAC MCC Test
Memo TM-E006.
Also, check whether they comply with ABS requirements.

6.2.6

Repeat the steps 6.2.1 to 6.2.5 for all the 10 generators and
record the results in Table 2.1 to 2.10.

Alarm Test
6.2.7

6.3

Simulation of all alarm conditions shall be conducted by the


service engineer and recorded in the corresponding Table 2.1
to 2.10 by KFELS QA. Verify each alarm circuit and alarm
indication on generator instrumentation panel.

Load Test and Endurance Trial

No.

Description

KFELS
Commissioning
Supervisor

Carry out the following procedures and record data in Table 3.1 ~ 3.10.
Engine power = 3730 bKW, Generator design output = 3560 ekW.
Load bank = 3 x 3560= 10680 kW, (13350kVA), 11 KVA for parallel operation.
6.3.1

Start generator #1 with no load connected.

6.3.2

Preset the load at 10% full load. Start the unit and let the
controller warm up the engine at idle speed. Raise the
engine to full speed till we reach the operating
temperature.

6.3.3

Increase the load from 0% to 100% at 25% intervals and


run the generator for 15 min and till temperature settles at
each load setting before each 25% increase. For 100%
load, run the generator for 3 hrs.
Increase the load to 110% (or maximum fuel rack position)
and run the generator for 1 hr.
Record all results in Table 3.1 to 3.10.

6.3.4

Measure the diesel level in the Fuel Oil Tank before and
after the 100% load test to determine the specific fuel
consumption. Record the results in Table 1.0.

6.3.5

Check for tightness and integrity for all expansion joints,


silencers, pipe hangers of engine exhaust system.

6.3.6

Reduce the load in decrement and allow the engine to cool


down before shut down.

6.3.7

Repeat 6.3.1 to 6.3.6 for the rest of the generators.

TM-M001 R1 Main Generator

QGOG
ABS (where
Representative applicable)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

6.4

Page 7 of 46
Alt. 1
Date: 24-Sep-09

Parallel Tests
The following tests will demonstrate the capabilities of generator sets to share the load on the bus bar.
Carry out the following procedures and record data in Table 4.1 ~ Table 4.13.
Automatic synchronizing shall be function tested during the test.
Load on any generator is not to differ more than 15% of the rated output of the generator during these tests as per
ABS requirement:
1) Part 4-3-4 Section 3.21.2 on Steady State Condition
2) Part 4-3-4 Section 3.21.3 on Parallel Operation
3) Part 4-3-4 Section 3.21.3a on Reactive Load Sharing
Note: Load percentage described below is the percentage of rated output power of one generator unit.

No.

Description

6.4.
1

Run generator no. 1, close breaker to the main switch board bus
and increase load gradually to 100%.

6.4.
2

Start generator no. 2, synchronize and parallel with the bus. Load
up to 7120kW (2 generators running full load)
Observe the load sharing at 2x50% (7120/2=3560 kW).
Record load and current on each generator in Table 4.1 for
2x50% load. <Generator 1& 2 in parallel>

6.4.
3

Start generator no. 3, synchronize and parallel with the bus.


Observe the load sharing at 3x33.33% (10680/3=3560 kW).
Record load and current on each generator in Table 4.2 for
3x33.3% load. <Generator 1, 2 & 3 in parallel>

6.4.
4

Start generator no. 4, synchronize and parallel with the bus.


Observe the load sharing at 4x25% (10680/4= 2670 kW).
Record load and current on each generator in Table 4.3 for 4 x
25% load. <Generator 1, 2 ,3 & 4 in parallel>

6.4.
5

Start generator no. 5, synchronize and parallel with the bus.


Observe the load sharing at 5x20% (10680/5= 2136 kW).
Record load and current on each generator in Table 4.4 for
5x20% load. <Generator 1, 2, 3, 4 & 5 in parallel>

6.4.
6

Start generator no. 6, synchronize and parallel with the bus.


Observe the load sharing at 6x16.67% (10680/6= 1780 kW).
Record load and current on each generator in Table 4.5 for
6x16.67% load. <Generator 1, 2, 3, 4, 5 & 6 in parallel>

6.4.
7

Start generator no. 7, synchronize and parallel with the bus.

6.4.
8

Start generator no. 8, synchronize and parallel with the bus.


Observe the load sharing at 8x 12.5% (10680/8= 1335 kW).
Record load and current on each generator in Table 4.7 for 8x
12.5% load. <Generator 1, 2, 3, 4, 5, 6, 7 & 8 in parallel>

Observe the load sharing at 7x 14.28% (10680/7= 1525.7 kW).


Record load and current on each generator in Table 4.6 for 7x
14.28% load. <Generator 1, 2, 3, 4, 5, 6 & 7 in parallel>

TM-M001 R1 Main Generator

KFELS
Commissioning
Supervisor

QGOG
ABS
Representative (Where
applicable)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

No.

Description

6.4.
9

Start generator no. 9, synchronize and parallel with the bus.


Observe the load sharing at 9x 11.11% (10680/9=1186.6 kW).
Record load and current on each generator in Table 4.8 for 9x
11.11% load. <Generator 1, 2, 3, 4, 5, 6, 7, 8 & 9 in parallel>

6.4.
10

Start generator no. 10, synchronize and parallel with the bus.

6.4.
11

Remove load from generator no. 1 and disconnect it from the bus.
Record load and current on each generator in Table 4.10 for 9x
11.11% load. <Generator 2 to 10 in parallel>

6.4.
12

Remove load from generator no. 2 and disconnect it from the bus.
Record load and current on each generator in Table 4.11 for 8x
12.5% load. <Generator 3 to 10 in parallel>

6.4.
13

Remove load from generator no. 3 and disconnect it from the bus.
Record load and current on each generator in Table 4.12 for 7x
14.28% load. <Generator 4 to 10 in parallel>

6.4.
14

Remove load from generator no. 4 and disconnect it from the bus.
Record load and current on each generator in Table 4.13 for
6x16.67%. <Generator 5 to 10 in parallel>

6.4.
15

Remove load from generator no. 5 and disconnect it from the bus.
Record load and current on the remaining generator 4 in Table
4.14 for 5x20% load.<Generator 6 to 10 in parallel>

6.4.
16

Remove load from generator no. 6 and disconnect it from the bus.
Record load and current on each generator in Table 4.15 for 4x
25% load. <Generator 7 to 10 in parallel>

6.4.
17

Remove load from generator no. 7 and disconnect it from the bus.
Record load and current on each generator in Table 4.16 for
3x33.3%. <Generator 8 to 10 in parallel>

6.4.
18

Remove load from generator no. 8 and disconnect it from the bus.
Record load and current on the remaining generator in Table 4.17
for 2x50% load.<Generator 9&10 in parallel >

6.4.
20

Remove the load from the generators slowly and shut down the
generators.

6.4.
21

During load test of Generator no. 4 and 5 in section 6.3,


observe the load sharing at 2x50% (each generator running at
max. load of 3560 kW, total 7120 KW).

Observe the load sharing at 10x 10% (10680/10= 1068 kW).


Record load and current on each generator in Table 4.9 for 10x
10% load. <Generator 1, 2, 3, 4, 5, 6, 7, 8, 9 & 10 in parallel>

Record load and current on each generator in Table 4.18 for


2x50% load. <Generator 4& 5 in parallel>
6.4.
22

During load test of Generator no. 6 and 7 in section 6.3,


observe the load sharing at 2x50% (each generator running at
max. load of 3560 kW, total 7120 KW).
Record load and current on each generator in Table 4.19 for
2x50% load. <Generator 6& 7 in parallel>

TM-M001 R1 Main Generator

Page 8 of 46
Alt. 1
Date: 24-Sep-09

KFELS
Commissioning
Supervisor

QGOG
ABS
Representative (Where
applicable)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 9 of 46
Alt. 1
Date: 24-Sep-09

No.

Description

6.4.
23

The reactive loads of the individual generating sets are not to


differ from their proportionate share of the combined reactive
load by more than 10% of the rated reactive output of the largest
generator, or 25% of the smallest generator, which ever is less.

6.5

KFELS
Commissioning
Supervisor

QGOG
ABS
Representative (Where
applicable)

Reverse Power Test

No.

Description

6.5.1

Carry out the following procedures and record data in


Table 5.1

6.5.2

Start generators 1 and 2 with no load connected.

6.5.3

Synchronize and parallel run these two generators.

6.5.4

Regulate the loading on generator 2 until a reverse power


of 10% is reached on generator 1. Verify that reverse
power relay is tripping-out before 10% reverse power.
Increase the relay setting if necessary.

6.5.5

Record time taken for circuit breaker to trip with 10%


reverse power (about 10 seconds).

6.5.6

Repeat steps 6.5.2 to 6.5.5 for remaining generators #6 to


#10. Record the result in Table 5.2.

TM-M001 R1 Main Generator

KFELS
Commissioning
Supervisor

QGOG
ABS
Representative (Where
applicable)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

6.6

Page 10 of 46
Alt. 1
Date: 24-Sep-09

Block Load Test


These tests are to be recorded on a chart recorder.

No.

Description

6.6.1

Start generator #1 with no load connected.

6.6.2

Increase load abruptly to 50% (of rated output). Verify that


momentary speed variation does not exceed 10% of engine
rated speed and the voltage variation are within the range of
minus (-) 15% to plus (+) 20% of rated voltage. The
Voltage is to be restored within plus or minus 3% of the
rated voltage in not more than 1.5 seconds.
Record data in Table 6.0.

6.6.3

Increase load abruptly from 50% to 100% (of rated output).


Verify that momentary speed variation does not exceed 10%
of engine rated speed and the voltage variation are within
the range of minus (-) 15% to plus (+) 20% of rated voltage.
The Voltage is to be restored within plus or minus 3% of
the rated voltage in not more than 1.5 seconds.
Record data in Table 6.0.

6.6.4

Decrease load abruptly from 100% to 0% (of rated output).


Verify that momentary speed variation does not exceed 10%
of engine rated speed and the voltage variation are within
the range of minus (-) 15% to plus (+) 20% of rated voltage.
The Voltage is to be restored within plus or minus 3% of
the rated voltage in not more than 1.5 seconds.
Record data in Table 6.0.

6.6.5

Shutdown the generator.

6.6.6

Repeat steps 6.6.1 to 6.6.5 for the rest of the generator sets.

6.7

Description

6.7.1

Check whether the Engine vibration isolator height is


within the allowable tolerance. Result shall be witnessed
by KFELS/QGOG/ABS.
Alignment of Engine and alternator to be checked after
engine test has been completed.
Post test check shall be conducted by service engineer as
per manufacturers standard. Record if any abnormalities.

6.7.3

6.7.4

QGOG
ABS (where
Representative applicable)

Post Test Check

No.

6.7.2

KFELS
Commissioning
Supervisor

Multilin settings shall be recorded by vendor and attached


to test memo results.

TM-M001 R1 Main Generator

KFELS
Commissioning
Supervisor

QGOG
ABS (where
Representative applicable)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 11 of 46
Alt. 1
Date: 24-Sep-09

DATA SHEET
Table 1.0

ENGINE DATA

Make/Model
Engine rated power
Generator Model
Generator rated power
Generator set output
Specific fuel consumption

Description

Gen.Set
No.1

:
:
:
:
:
:

Gen.Set
No.2

EMD / ME 20-710G9B-T1
3730 bkW @ 900 rpm
855ZXT
3580 ekW (11KVA/3ph/60Hz)
3560 ekW (11KVA/3ph/60Hz)

Gen.Set
No.3

Gen.Set
No.4

Gen.Set
No.5

Gen.Set
No.6

Gen.Set
No.7

Tag No.

Engine S.No.
Alternator
S.No.
Output
Power (kW)
Specific Fuel
Consumption
(g/kWh)
Cooler No.
Governor
Alternator
lubricating
unit (Drive
End)
Alternator
lubricating
Unit(Non
Drive End)
Note: All engine/generator tests will be performed utilizing fuel conforming to Grade DF-2

TM-M001 R1 Main Generator

Gen.Set
No.8

Gen.Set
No.9

Gen.Set
No.10

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.1

Page 12 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.1


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.2

Page 13 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.2


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.3

Page 14 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.3


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.4

Page 15 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.4


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.5

Page 16 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.5


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.6

Page 17 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.6


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.7

Page 18 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.7


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.8

Page 19 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.8


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.9

Page 20 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.9


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 2.10

Page 21 of 46
Alt. 1
Date: 24-Sep-09

SHUTDOWN AND ALARM TESTS FOR ENGINE/GENERATOR SET NO.10


Rated Speed - 900 rpm
Design
Trip Set
Point

Min Max
Set Point

215 F

190-212 F

Low Oil Pressure

27 PSIG

40-100 PSIG

High Crankcase Pressure

1 H2O

0.8-1.3
H2O

Low Engine Coolant Level

[switch]

[switch]

Low Oil Level (External Tank)

[switch]

[switch]

High Oil Temperature

210 F

200215 F

Low Turbo soak back Oil Pressure

6 PSIG

830 PSIG

Low Pre Lube Oil Pressure

10 PSIG

15-30 PSIG

High Intake Air Filter Restriction

14 H2O

6-10 H2O

Emergency Stop

[switch]

[switch]

80 F

85-100 F

Description
High Jacket Water Temperature

Low Lube Oil Temperature


Over speed Shutdown (RPM )

990

Observed Set
Alarm
point

220 F

X
X

899-902

Engine Over crank (Failed to Start)

3 attempts

3 attempts

Intake Air Shut off Valve Tripped

[switch]

[switch]

Engine Mode Selector Not in Remote


Auto

[switch]

[switch]

Generator Lock-Out Relay Shutdown

[switch]

[switch]

High Cylinder Temperature

1200 F

8501100 F

Low Oil Pressure

37 PSIG

40100
PSIG

205 F

190 212 F

35 PSIG

4060 PSIG

25 PSIG

30-60 PSIG

25 PSIG

30-60 PSIG

20 PSIG

5-15 PSIG

10 PSIG

4-7 PSIG

270 F

200-260 F

High Generator Stator Temperature

284 F

270-280 F

High Generator Bearing Temperature

194 F

180-190 F

Low Starting Air Pressure

70 PSIG

75-125 PSIG

High Generator Air Inlet

140 F

113-130 F

Generator Coolant leak

[switch]

High Jacket Water Temperature


Low Fuel Pressure
Low Jacket Water Pressure, Right
Bank
Low Jacket Water Pressure, Left
Bank
High Lube Oil Filter Differential
Pressure
High Fuel Oil Filter Differential
Pressure
High Engine Main Bearing
Temperature

Shutdown

X
X
X
X
290 F

X
X
X

Note: Observed set point should be +/- 5% of Design set point or +/-1 % unit whichever is greater.

TM-M001 R1 Main Generator

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.1

Page 22 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 1


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Table 3.2

Non-Drive (oF)

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 2

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 23 of 46
Alt. 1
Date: 24-Sep-09

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Table 3.3

Non-Drive (oF)

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 3

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 24 of 46
Alt. 1
Date: 24-Sep-09

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Table 3.4

Non-Drive (oF)

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 4

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Page 25 of 46
Alt. 1
Date: 24-Sep-09

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.5

Page 26 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 5


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

9.

Actuator (mA)

10.

Field
excitation

Analogue
Digital

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.6

Page 27 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 6


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

9.

Actuator (mA)

10.

Field
excitation

Analogue
Digital

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.7

Page 28 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 7


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue L2

5.

L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

9.

Actuator (mA)

10.

Field
excitation

Analogue
Digital

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.8

Page 29 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 8


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.9

Page 30 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 9


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 3.10

Page 31 of 46
Alt. 1
Date: 24-Sep-09

LOAD AND ENDURANCE TEST FOR ENGINE/GENERATOR NO 10


0

Load (%)
Power Factor
Duration (min)
1.

Engine Speed (rpm)

2.

Engine Frequency (Hz)

3.

Engine % load meter reading

4.

Alternator voltage (V)

0.8

25
0.8

50
0.8

75
0.8

100
0.8

100
0.8

100
0.8

110
0.8

15

15

15

60

60

60

15

L1
Analogue

5.

L2
L3

Alternator
current (A)

L1
Digital

L2
L3

6.

Alternator
output
(kW)

Analogue
Digital

7.

Alternator output (kVA)

8.

Alternator
output
(kVAR)

Analogue
Digital

9.

Actuator (mA)

10.

Field
excitation

Current (A)
A1 (oC)
A4 (oC)

11.

Winding temp.
(from swbd)
(max)

B2 (oC)
B5 (oC)
B3 (oC)
B6 (oC)

12.

Bearing temp.
(max)

13.

Power (Kw)

15.

Lube oil pressure (Psig)

16.

Lube oil temperature (F)

17.

Fuel Pressure (Psig)

18.

Fuel oil temperature (F)

19.

Inlet air temperature (oF)

20.

Fuel filter diff. pressure (Psig)

21.

Jacket water outlet temperature (F)

22.

Jacket water pressure (Psig)

23.

Post turbo exhaust temperature (F)

24.

Ambient temperature (oC)

25.

Exhaust gas color to check @ 100%


load for feel of proper combustion

N/A

N/A

N/A

N/A

N/A

26.

Fuel Rack setting @ 100% load

N/A

N/A

N/A

N/A

N/A

Non-Drive (oF)

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 4.0

Page 32 of 46
Alt. 1
Date: 24-Sep-09

PARALLEL LOAD TEST

All Load Test are to be made with load bank set at 0.8 power factor.
Table 4.1

GEN NO.2 PARALLEL TO GEN NO. 1


Item

Total Load On Line /


Actual Load
Gen. Set No.1
(50% of 7120=3560 kW)
Gen. Set No.2

(kW)

Remarks

2x50% (7120 kW/8900 KVA Total)

(kW)
(A)

(A)

GEN NO.3 PARALLEL TO BUS

Item

Units

Total Load On Line /


Actual Load

(kW)

Gen. Set No.1

(kW)

(33.33%x10680=3560 kW)
Gen. Set No.2

Actual Load

Remarks

3x33.33% (10680 kW/13350 KVA Total)

(A)
(kW)

(33.33%x10680=3560 kW)
Gen. Set No.3

(A)
(kW)

(33.33%x10680=3560 kW)

Table 4.3

Actual Load

(kW)

(50% of 7120=3560 kW)


Table 4.2

Units

(A)

GEN NO.4 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

4x25% (10680 kW /13350 KVA Total)

Gen. Set No.1

(kW)

(25%x10680=2670 kW)
Gen. Set No.2
(25%x10680=2670 kW)
Gen. Set No.3
(25%x10680=2670 kW)
Gen. Set No.4
(25%x10680=2670 kW)

TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 4.4

Page 33 of 46
Alt. 1
Date: 24-Sep-09

GEN NO.5 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

5x20% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.2

(A)
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.3

(A)
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.4

(A)
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.5
(20%x 10680 kW =2136 kW)
Table 4.5

Remarks

(A)
(kW)
(A)

GEN NO.6 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

6x16.67% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

(16.67%x10680= 1780 kW)


Gen. Set No.2
(16.67%x10680= 1780 kW)
Gen. Set No.3
(16.67%x10680= 1780 kW)
Gen. Set No.4
(16.67%x10680= 1780 kW)
Gen. Set No.5
(16.67%x10680= 1780 kW)
Gen. Set No.6
(16.67%x10680= 1780 kW)

TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 4.6

Page 34 of 46
Alt. 1
Date: 24-Sep-09

GEN NO.7 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

7x 14.28% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.2

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.3

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.4

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.5

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.6

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.7

(A)
(kW)

(14.28% x10680=1525.7 kW)

Table 4.7

Remarks

(A)

GEN NO.8 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

8x 12.5% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

(12.5%x10680=1335 kW)
Gen. Set No.2
(12.5%x10680=1335 kW)
Gen. Set No.3
(12.5%x10680=1335 kW)
Gen. Set No.4
(12.5%x10680=1335 kW)
Gen. Set No.5
(12.5%x10680=1335 kW)
Gen. Set No.6
(12.5%x10680=1335 kW)
Gen. Set No.7
(12.5%x10680=1335 kW)

TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Item

Page 35 of 46
Alt. 1
Date: 24-Sep-09

Actual Load

Remarks

Units

Actual Load

Remarks

Total Load On Line /


Actual Load

(kW)

9x 11.11% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

Gen. Set No.8

(kW)

(12.5%x10680=1335 kW)
Table 4.8

Units

(A)

GEN NO.9 PARALLEL TO BUS


Item

(11.11%x10680=1186.6 kW)
Gen. Set No.2
(11.11%x10680=1186.6 kW)
Gen. Set No.3
(11.11%x10680=1186.6 kW)
Gen. Set No.4
(11.11%x10680=1186.6 kW)
Gen. Set No.5
(11.11%x10680=1186.6 kW)
Gen. Set No.6
(11.11%x10680=1186.6 kW)
Gen. Set No.7
(11.11%x10680=1186.6 kW)
Gen. Set No.8
(11.11%x10680=1186.6 kW)
Gen. Set No.9
(11.11%x10680=1186.6 kW)

TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 4.9

Page 36 of 46
Alt. 1
Date: 24-Sep-09

GEN NO.10 PARALLEL TO BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

10x 10% (10680 kW/13350 KVA Total)

Gen. Set No.1

(kW)

(10%x10680=1068 kW)
Gen. Set No.2

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.3

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.4

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.5

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.6

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.7

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.8

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.9

(A)
(kW)

(10%x10680=1068 kW)
Gen. Set No.10
(10%x10680=1068 kW)

Table 4.10

Remarks

(A)
(kW)
(A)

GEN NO.1 DISCONNECTED FROM BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

9x 11.11% (10680 kW/13350 KVA Total)

Gen. Set No.2

(kW)

(11.11%x10680=1186.6 kW)
Gen. Set No.3
(11.11%x10680=1186.6 kW)
Gen. Set No.4
(11.11%x10680=1186.6 kW)
Gen. Set No.5
(11.11%x10680=1186.6 kW)
TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)
(kW)
(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Item

Page 37 of 46
Alt. 1
Date: 24-Sep-09

Actual Load

Remarks

Units

Actual Load

Remarks

Total Load On Line /


Actual Load

(kW)

8x 12.5% (10680 kW /13350 KVA Total)

Gen. Set No.3

(kW)

Gen. Set No.6

(kW)

(11.11%x10680=1186.6 kW)
Gen. Set No.7

Gen. Set No.8

(A)
(kW)

(11.11%x10680=1186.6 kW)
Gen. Set No.9

(A)
(kW)

(11.11%x10680=1186.6 kW)
Gen. Set No.10
(11.11%x10680=1186.6 kW)

(A)
(kW)
(A)

GEN NO.2 DISCONNECTED FROM BUS


Item

(12.5%x10680=1335 kW)
Gen. Set No.4

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.5

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.6

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.7

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.8

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.9

(A)
(kW)

(12.5%x10680=1335 kW)
Gen. Set No.10
(12.5%x10680=1335 kW)

Table 4.12

(A)
(kW)

(11.11%x10680=1186.6 kW)

Table 4.11

Units

(A)
(kW)
(A)

GEN NO.3 DISCONNECTED FROM BUS


Item

Total Load On Line /


Actual Load

TM-M001 R1 Main Generator

Units

Actual Load

(kW)

7x 14.28% (10680 kW /13350 KVA Total)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Item

Page 38 of 46
Alt. 1
Date: 24-Sep-09

Actual Load

Remarks

Units

Actual Load

Remarks

Total Load On Line /


Actual Load

(kW)

6x16.67% (10680 kW/13350 KVA Total)

Gen. Set No.5

(kW)

Gen. Set No.4

(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.5

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.6

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.7

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.8

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.9

(A)
(kW)

(14.28% x10680=1525.7 kW)


Gen. Set No.10

(A)
(kW)

(14.28% x10680=1525.7 kW)


Table 4.13

Units

(A)

GEN NO.4 DISCONNECTED FROM BUS


Item

(16.67%x10680= 1780 kW)


Gen. Set No.6

(kW)

(16.67%x10680= 1780 kW)


Gen. Set No.7

(A)
(kW)

(16.67%x10680= 1780 kW)


Gen. Set No.8

(A)
(kW)

(16.67%x10680= 1780 kW)


Gen. Set No.9

(A)
(kW)

(16.67%x10680= 1780 kW)


Gen. Set No.10

(A)
(kW)

(16.67%x10680= 1780 kW)


Table 4.14

(A)

(A)

GEN NO.5 DISCONNECTED FROM BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

5x20% (10680 kW/13350 KVA Total)

Gen. Set No.6

(kW)

(20%x 10680 kW =2136 kW)

TM-M001 R1 Main Generator

(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Item

Page 39 of 46
Alt. 1
Date: 24-Sep-09

Actual Load

Remarks

Units

Actual Load

Remarks

Total Load On Line /


Actual Load

(kW)

4x25% (10680 kW/13350 KVA Total)

Gen. Set No.7

(kW)

Gen. Set No.7

Units
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.8

(A)
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.9

(A)
(kW)

(20%x 10680 kW =2136 kW)


Gen. Set No.10

(kW)

(20%x 10680 kW =2136 kW)

Table 4.15

(A)

(A)

GEN NO.6 DISCONNECTED FROM BUS


Item

(25%x10680=2670 kW)
Gen. Set No.8

(A)
(kW)

(25%x10680=2670 kW)
Gen. Set No.9

(A)
(kW)

(25%x10680=2670 kW)
Gen. Set No.10

(kW)

(25%x10680=2670 kW)

Table 4.16

(A)

(A)

GEN NO.7 DISCONNECTED FROM BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

3x33.33% (10680 kW/13350 KVA Total)

Gen. Set No.8

(kW)

(33.33%x10680=3560 kW)
Gen. Set No.9
(33.33%x10680=3560 kW)
Gen. Set No.10
(33.33%x10680=3560 kW)

TM-M001 R1 Main Generator

(A)
(kW)
(A)
(kW)
(A)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 4.17

Page 40 of 46
Alt. 1
Date: 24-Sep-09

GEN NO.8 DISCONNECTED FROM BUS


Item

Units

Actual Load

Total Load On Line /


Actual Load

(kW)

2x50% (7120 kW/8900 KVA Total)

Gen. Set No.9

(kW)

(50% of 7120=3560 kW)


Gen. Set No.10

(A)
(kW)

(50% of 7120=3560 kW)


Table 4.18

Remarks

(A)

GEN NO.5 PARALLEL TO GEN NO. 4

Note : This test can be performed during load test of Gen Set No.4 and No.5.
Item
Total Load On Line /
Actual Load
Gen. Set No.4
(50% of 7120=3560 kW)
Gen. Set No.5

(kW)

Actual Load

Remarks

2x50% (7120 kW/8900 KVA Total)

(kW)
(A)
(kW)

(50% of 7120=3560 kW)


Table 4.19

Units

(A)

GEN NO.7 PARALLEL TO GEN NO. 6

Note : This test can be performed during load test of Gen Set No. 6 and No.7.

Item
Total Load On Line /
Actual Load
Gen. Set No.6
(50% of 7120=3560 kW)
Gen. Set No.7
(50% of 7120=3560 kW)

TM-M001 R1 Main Generator

Units
(kW)
(kW)
(A)
(kW)
(A)

Actual Load
2x50% (7120 kW/8900 KVA Total)

Remarks

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 5.0

Page 41 of 46
Alt. 1
Date: 24-Sep-09

REVERSE POWER TEST

5.1
Item

Description

1.

Load connected (kW)

2.

Load at tripping (kW)

3.

Percentage reverses
power before tripping
(%)

4.

Time taken before


tripping (seconds)

5.

Remarks

Gen. Set #1

Gen. Set #2

Gen. Set #3

Gen. Set #4

Gen. Set #5

Gen. Set #6

Gen. Set #7

Gen. Set #8

Gen. Set #9

Gen. Set #10

5.2
Item

Description

1.

Load connected (kW)

2.

Load at tripping (kW)

3.

Percentage reverses
power before tripping
(%)

4.

Time taken before


tripping (seconds)

5.

Remarks

TM-M001 R1 Main Generator

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 6.0

Page 42 of 46
Alt. 1
Date: 24-Sep-09

BLOCK LOAD TEST

Common Data
Engine Rated Speed :
Output Power (100%) :
Output Power (50%):

900 rpm
3560 ekW (11KVA/3ph/60Hz)
1780 ekW (11KVA/3ph/60Hz)

Load
Condition

Status

Voltage

Dev

Freq.

Dev

Control
Panel

(%)

(Hz)
Analog
Panel
Meter

(%)

(V)

Generator
No. 1

Generator
No.2

Generator
No.3

Generator
No.4

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Final

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

TM-M001 R1 Main Generator

Time taken to Steady State


Condition (sec)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Load
Condition

Page 43 of 46
Alt. 1
Date: 24-Sep-09

Status

Voltage

Dev

Freq.

Dev

Control
Panel

(%)

(Hz)
Analog
Panel
Meter

(%)

(V)

Generator
No.5

Generator
No.6

Generator
No.7

Generator
No.8

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

TM-M001 R1 Main Generator

Time taken to Steady State


Condition (sec)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Load
Condition

Page 44 of 46
Alt. 1
Date: 24-Sep-09

Status

Voltage

Dev

Freq.

Dev

Control
Panel

(%)

(Hz)
Analog
Panel
Meter

(%)

(V)

Generator
No.9

Generator
No.10

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

0%

Initial

0% to 50%

Momentary

50%

Final

50%

Initial

50% to 100%

Momentary

100%

Final

100%

Initial

100% to 0%.

Momentary

0%

Final

TM-M001 R1 Main Generator

Time taken to Steady State


Condition (sec)

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

Table 7.0

Page 45 of 46
Alt. 1
Date: 24-Sep-09

Instrumentation (ALL WORKING CORRECTLY)


Results
Gen.
Set
No.1

Gen.
Set
No.2

Gen.
Set
No.3

Gen.
Set
No.4

Gen.
Set
No.5

Gen.
Set
No.6

Gen.
Set
No.7

Gen.
Set
No.8

Gen.
Set
No.9

Gen.
Set
No.10

KFELS
Comm.
Supervisor

Temperature
meter (0 - 100
C)
Ammeter
Kilowatt meter
Running Hour
timer
kVAR meter
Voltmeter
Ammeter
Selector
Switch
Voltmeter
Selector
Switch
Selector
Switch
Heater On
Lamp (Blue)
Heater Switch
Speed
Adjustment
Potentiometer
Voltage
Adjustment
Potentiometer
All Control
Panel Bearings

8.0

TEST ACCEPTANCE

The units and system covered under this test memo have been tested accordingly and found to be satisfactory in
accordance with test procedures.

REPRESENTATIVES
ABS
Electro Motive Diesel
QGOG
KFELS Commissioning
Supervisor

TM-M001 R1 Main Generator

NAME

SIGNATURE

DATE

Project: B309
Doc. No. : TM-M001
Title: Test Memo For Main Generator

9.0

Page 46 of 46
Alt. 1
Date: 24-Sep-09

COMMENTS

SL. NO.

TM-M001 R1 Main Generator

COMMENTS / OBSERVATIONS

SIGNATURE