FM Global

Property Loss Prevention Data Sheets

7-32
January 2010
Page 1 of 50

FLAMMABLE LIQUID OPERATIONS

Table of Contents
Page
1.0 SCOPE ................................................................................................................................................... 3
1.1 Changes ............................................................................................................................................ 3
2.0 LOSS PREVENTION RECOMMENDATIONS ....................................................................................... 3
2.1 General Flammable and Combustible Liquid Occupancies ............................................................ 3
2.1.1 Construction and Location .................................................................................................... 3
2.1.2 Equipment and Processes .................................................................................................... 5
2.1.3 Occupancy ............................................................................................................................. 8
2.1.4 Ignition Source Control .......................................................................................................... 9
2.1.5 Operation and Maintenance ................................................................................................ 14
2.1.6 Training ................................................................................................................................ 15
2.1.7 Human Element ................................................................................................................... 15
2.1.8 Protection ............................................................................................................................ 16
2.2 Piping Systems .............................................................................................................................. 19
2.2.1 Construction and Location .................................................................................................. 19
2.2.2 Equipment and Processes .................................................................................................. 24
2.2.3 Operation and Maintenance ................................................................................................ 28
2.3 Flammable and Combustible Liquid Transfer Systems ................................................................. 29
2.3.1 Equipment and Processes .................................................................................................. 29
3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................. 36
3.1 Application of Recommendations .................................................................................................. 36
3.1.1 General ................................................................................................................................ 36
3.1.2 Fire Hazard .......................................................................................................................... 37
3.1.3 Piping Systems/Transfer Systems ...................................................................................... 37
3.1.4 Room Explosion Hazard ..................................................................................................... 37
3.1.5 Equipment Explosion Hazard .............................................................................................. 39
4.0 REFERENCES ..................................................................................................................................... 40
4.1 FM Global ...................................................................................................................................... 40
4.2 NFPA Standards ............................................................................................................................ 40
4.3 Others ............................................................................................................................................ 40
APPENDIX A GLOSSARY OF TERMS ..................................................................................................... 41
APPENDIX B DOCUMENT REVISION HISTORY ..................................................................................... 43
APPENDIX C CHARACTERISTICS OF FLAMMABLE AND COMBUSTIBLE LIQUID FIRES
AND EXPLOSIONS ............................................................................................................. 43
C.1 Characteristics and Types of Flammable and Combustible Liquid Fires ..................................... 43
C.1.1 Pool Fires ............................................................................................................................ 43
C.1.2 Unconfined Spill Fires ......................................................................................................... 43
C.1.3 Spray Fires .......................................................................................................................... 44
C.2 Fire Control and Extinguishment .................................................................................................. 44
C.3 Characteristics of Flammable/Combustible Liquid Vapor-Air Explosions ..................................... 45
C.4 Explosion Control and Protection ................................................................................................. 45
C.5 Equipment Explosion (Deflagration) Venting Design .................................................................... 46
C.5.1 Vent Sizing for a Pred Greater Than 1.5 psig (0.1 bar g) (High Strength Equipment) ....... 46
C.5.2 Vent Sizing for a Pr of 1.5 psig (0.1 bar g) or Less (Low Strength Equipment) .............. 47
C.5.3 Venting of Gases/Vapors Other Than Those Specified and Mists ..................................... 47
C.5.4 Vent Mass and Location ..................................................................................................... 48
C.5.5 Vent Discharge Arrangement .............................................................................................. 48

2010 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.

7-32

Flammable Liquid Operations

Page 2

C.5.6
C.5.7
C.6 Sight
C.6.1
C.6.2
C.6.3

FM Global Property Loss Prevention Data Sheets

Effect of Turbulence ............................................................................................................ 48


Effect of High Initial Pressures ........................................................................................... 49
Glasses ................................................................................................................................ 49
Properties of Glass ............................................................................................................. 49
Types of Glass .................................................................................................................... 50
Sight Glass Design ............................................................................................................. 50

List of Figures
Fig. 1. Preferred locations for processes containing flammable or combustible liquids. (Table 1) ............... 4
Fig. 2a. Location of hazardous area rated electrical equipment for up to 70 gal (265 l) of
flammable/combustible liquid in open equipment. .......................................................................... 10
Fig. 2b. Location of hazardous area rated electrical equipment for up to 70 gal (265 l) of
flammable/combustible liquid in closed equipment. ....................................................................... 11
Fig. 3a. Location of hazardous area rated electrical equipment for more than 70 gal (265 l) of
flammable/combustible liquid in open equipment. .......................................................................... 12
Fig. 3b. Location of hazardous area rated electrical equipment for more than 70 gal (265 l) of
flammable/combustible liquid in closed equipment. ....................................................................... 13
Fig. 4. Buried-pipe entrance into building. ................................................................................................... 20
Fig. 5. Preferred arrangement for above grade pipe entrance into building. .............................................. 21
Fig. 6. Welding neck type flange. ................................................................................................................ 23
Fig. 7. Slip-on type flange. ........................................................................................................................... 23
Fig. 8. Compressed inert-gas transfer method. ........................................................................................... 31
Fig. 9. Hydraulic transfer method. ................................................................................................................ 33
Fig. 10. Railcar loading/unloading station-bonding arrangement to prevent sparks due to stray currents. . 36
Fig. 11. Sprinklered vs. Unsprinklered Flammable/Combustible Liquid Fires. ............................................ 45
Fig. 12. Maximum Pressure Developed During Venting of Gases, With and Without Vent Ducts. ............ 49

List of Tables
Table
Table
Table
Table

1.
2.
3.
4.

Construction For Flammable and Combustible Liquid Occupancies (notes 1 & 2). ...................... 4
Sprinkler Protection for Occupancies Utilizing Flammable/Combustible Liquids. ........................ 17
Space Separation for Flammable/Combustible Liquid Loading/Unloading Stations. ................... 34
The volume of a stoichiometric vapor-air mixture that may be produced from either 1 gallon or
1 liter of some common flammable liquids. (Note: these values are based on complete
vaporization of the liquid.) ............................................................................................................. 39
Table 5. Heat of Combustion for Representative Materials. ....................................................................... 43
Table 6. Explosion Venting Constants. ....................................................................................................... 46
Table 7. Venting Constants for Other Vapors and Gases. ......................................................................... 48

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

7-32
Page 3

1.0 SCOPE
This loss prevention data sheet provides recommendations for the prevention of and protection against fires
and explosions in occupancies handling, processing, or transferring flammable or combustible liquids. Data
sheets covering specific occupancies may supersede this data sheet. Additional recommendations may be
needed to provide adequate prevention and protection features for a chemical process plant with the potential
for hazardous chemical reactions, three dimensional fires, or operating pressures in excess of 100 psig (7
bar g). Refer to Section 3.1 for guidelines on applying recommendations.
International standards may be applied when required, instead of referenced United States standards (i.e.,
ASTM, ASME, etc.).
NFPA 30, Flammable and Combustible Liquids Code, also covers this material.
1.1 Changes
January 2010. Minor editorial changes were made. Added references to Data Sheet 4-12, Foam-Water
Sprinkler Systems.
2.0 LOSS PREVENTION RECOMMENDATIONS
2.1 General Flammable and Combustible Liquid Occupancies
2.1.1 Construction and Location
Isolate flammable and combustible liquids by distance or construction so that they do not expose important
buildings or facilities, and in turn are protected from fires originating elsewhere. The extent of isolation
depends on such factors as the quantity of flammable or combustible liquid, the consequences of failure of
safeguards, and whether the hazard is one of fire only or of both fire and explosion.
2.1.1.1 Flammable and combustible liquid operations that create a fire and/or an explosion hazard should
be located as follows to reduce the exposure to important buildings or facilities, and to limit exposure to the
flammable/combustible liquid operations from fires originating elsewhere (listed in order of preference; see
Figure 1, Table 1):
a) Detached outside location at least 75 ft (23 m) away from an important building or facility. A 50 ft (15 m)
separation is acceptable when only a fire hazard exists or an explosion hazard exists with less than
1500 gal (6000 l) of liquid. (Fig. 1, Location 1)
b) Along an exterior wall of an important building (preferably at a corner to limit exposure and increase
available vent area). (Fig. 1, Location 2)
c) Inside an important building on the first floor, either at an exterior corner or along an exterior wall. Avoid
locations in basements, below-grade spaces or on upper floors of multistory buildings. If such locations
are unavoidable, the floor of the room should be completely cut off (i.e., no openings in the floor to the floor
or space below, to prevent liquid or vapor escape) and liquid tight. An acceptable alternative for rooms
with small spaces below is to completely fill in the space with a noncombustible material (e.g., fiberglass,
mineral wool, earth). (Fig. 1, Locations 3 and 4)
2.1.1.2 Avoid below grade locations for equipment and piping containing flammable and combustible liquids
to help ensure adequate access for manual fire fighting efforts.
2.1.1.3 To limit the potential fire and explosion hazards created by flammable/combustible liquid occupancies,
apply the construction features listed in Table 1 to both the exposing building/room and exposed important
buildings. Table 1 applies if both the exposing building/room and the exposed building are adequately
sprinklered and adequate damage limiting construction, designed in accordance with Data Sheet 1-44,
Damage-Limiting Construction, is provided when an explosion hazard exists.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 4

FM Global Property Loss Prevention Data Sheets

Table 1. Construction For Flammable and Combustible Liquid Occupancies (notes 1 & 2).

Fig. 1. Preferred locations for processes containing flammable or combustible liquids. (Table 1)

Location

Hazard
Type
refer to
Section 3.1
for
definitions

Quantity of
Flammable
Liquid gal
(1)
> 1500 (6)

Explosion
< 1500 (6)

1
(note 5)

> 1500 (6)


Fire
< 1500 (6)

2
(note 6)

Distance
x
ft (m)
>75 (23)
10-75
(3-23)
> 50 (15)
10-50
(3-15)
> 50 (15)
< 50 (15)
> 25 (8)
< 25 (8)

Cutoff Room/Building
Construction
(note 3)
A

Roof
(note 4)

PV

PV

PV

PR

PV

LW

PV

PV

PV

PR

PV

LW

LW
FR
LW
FR

LW

LW

PV
Explosion

Any

Abutting

DNA

PV
PR

3&4

Explosion
Fire

Any

Inside

PV
NC

PR
FR

Construction of Main Buildings


Exposed Wall
C

Any

Vertical Exposure
Horizontal
Protection:
Exposure
PR and 1 hour fire
Protection:
rated for 10 ft (3 m) PR for length of
above exposure.
exposing wall A
plus 10 ft
Vertical Exposure
(3 m) beyond
Protection: Any

PR
FR

DNA

1. This table assumes adequate sprinkler protection is provided in the Main Building and the exposure. Table also assumes damage limiting
construction is designed in accordance with Data Sheet 1-44, Damage-Limiting Construction.
2. If sprinkler protection is not provided in the exposing building (i.e., low value building), use Data Sheet 1-20, Protection Against Exterior
Fire Exposure, (applies to Location 1 only). Use the following exposure rating in Data Sheet 1-20: Exposure A for quantities greater
than 1500 gal (6000 l). Exposure B for quantities less than 1500 gal (6000 l). Construction features for the exposing building still apply
when an explosion hazard exists.
3. The types of construction are defined as follows:
LWlight weight/noncombustible;
FR1 hour fire rated;
PRpressure resistant.
NCnoncombustible;
PVpressure venting;
4. Pressure resistant construction should also be provided for floors that have spaces below. Roof construction should meet the requirements
listed in Data Sheet 1-44, Damage-Limiting Construction.
5. For <10 ft (3 m) with an explosion hazard, use Location 2, Explosion Hazard.
6. For abutting structures with a fire hazard only, use Location 1, Fire Hazard, <50 ft/<25 ft (15 m/8 m). Sprinklered and adequate damage
limiting construction, designed in accordance with Data Sheet 1-44, Damage-limiting Construction, is provided when an explosion hazard
exists.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

7-32
Page 5

If the exposing building is not sprinklered (low value building, Location 1 only) and the quantity of flammable
or combustible liquid in the building is more than 1500 gal (6000 l), apply spacing and construction
recommendations listed in Data Sheet 1-20, Protection Against Exterior Fire Exposure, using exposure A
(Tables 2 through 7). Construction features shown in Table 1 still apply to the exposing building when an
explosion hazard exists.
If the exposing building is not sprinklered (low value building, Location 1 only) and quantity of flammable or
combustible liquid in the building is less than 1500 gal (6000 l), apply spacing and construction
recommendations listed in Data Sheet 1-20, using exposure B. Construction features shown in Table 1
still apply to the exposing building when an explosion hazard exists.
2.1.1.4 For interior locations with flammable/combustible liquids having a flash point below 200F (93C),
provide at least a one hour fire-rated partition to cut off the flammable liquid occupancy from surrounding
occupancies (Table 1). Other recommendations may exist for specific occupancies (covered by occupancy
specific data sheets).
If unheated combustible liquids with flash points above 200F (93C) are in use, the water supply is adequate,
and no high-value occupancies are exposed, a curb surrounding the combustible liquid operation is
acceptable in lieu of a fire rated partition. The curbing should be designed for a spill from largest vessel or
container plus a 2 in. (51 mm) freeboard in accordance with Data Sheet 7-83, Drainage Systems For
Flammable Liquids, (criteria for areas with containment but no drainage).
2.1.1.5 When a flammable/combustible liquid occupancy creates a room explosion hazard (see Section 3.1.4),
provide damage limiting construction as recommended in Table 1 and Data Sheet 1-44, Damage-Limiting
Construction. If a mist explosion hazard exists, refer to Data Sheet 1-44, to design the explosion venting.
When damage limiting construction is not possible for small rooms that create a severe exposure to high value
adjoining occupancies, consider an explosion suppression system. Install the system in accordance with
Data Sheet 7-17, Explosion Protection Systems.
2.1.1.6 Provide emergency drainage and/or containment for all flammable/combustible liquid areas protected
by water fire suppression systems. Determine the need for drainage and/or containment using Data Sheet
7-83, Drainage Systems For Flammable Liquids. The design of the drainage/containment system or a possible
alternative to adequate drainage should be in accordance with Data Sheet 7-83. Curbs and floors in
flammable/combustible liquid areas should be watertight. The surface grade around flammable/combustible
liquid areas should direct possible liquid releases away from important buildings.
Arrange drainage systems to prevent flammable vapors from backing up into buildings or rooms that are
tied into those systems. One method of accomplishing this is the use of trapped drains. Provide this
arrangement for all buildings/rooms with drains that are tied into a drainage system that can handle
flammable/combustible liquids regardless of the occupancy in that room/building.
2.1.2 Equipment and Processes
Equipment that handles flammable and/or combustible liquids should be designed to: 1) Confine the liquids
and vapors within the equipment, 2) Keep escaping material to a minimum and prevent its spread, and 3)
Drain escaping liquids to a safe location.
2.1.2.1 Equipment and tanks should be closed or have a minimum of exposed flammable/combustible liquid
surface area and quantity.
2.1.2.2 Equipment should be constructed of materials that are compatible with the liquids in use and
surrounding environmental conditions, resistant to physical damage (e.g., impact), and are resistant to high
exposing temperatures (e.g., flammable liquid fire). Avoid glass and plastic equipment (e.g., tanks or vessels).
Metal equipment with a glass or plastic lining is acceptable. The equipment should be designed for the
maximum hydrostatic head plus the usual corrosion and wear factors. The equipment should also be
designed for use with flammable/combustible liquids.
2.1.2.3 Equipment containing flammable and combustible liquids should utilize indirect measurement or
observation instruments (e.g., thermocouple to measure temperature, sensor to measure pressure or liquid
level, etc.) to reduce or eliminate leakage in the event of instrument failure. When direct measurement or
observation instruments (e.g., gauges, meters, liquid level indicatorsglass type, sight glasses [see Appendix
C, Section C.6], rotameters, sample tubes, etc.) are used the following safeguards should be applied:

2010 Factory Mutual Insurance Company. All rights reserved.

7-32
Page 6

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

a) Direct measurement instruments that use glass for containment (e.g., sight glasses, liquid level
indicatorglass type, rotameter) should be used only as a last resort and avoided entirely on processes
that contain flammable gases or flammable/combustible liquids above their normal atmospheric boiling
point. Locate sight glasses above liquid level. Sight glasses and liquid level indicators should be Factory
Mutual Research Approved (see Appendix A for definition). Follow the manufacturers recommendations
for mounting and maintenance.
b) The instruments materials of construction should be compatible with the materials being handled. Rate
glass for the temperature, pressure and chemical service conditions under which it will operate.
c) The instruments strength should be equal to or greater than the equipment to which they are attached.
d) Use restricted orifices in piping connecting the instruments to the equipment. Provide self-closing
faucets on draw-off/sample lines (sample tubes).
e) Avoid sudden temperature changes (e.g., addition of a very high or low temperature liquid to the inside
or outside of a vessel) on instruments with glass components (e.g., sight glasses).
f) Inspect all instruments on a regular schedule. Determine inspection frequency by the severity of local
conditions.
g) Inspect sight glasses at least once a week. Record sight glass inspections. When surface damage is
detected, replace the glass immediately. If sight glasses are exposed to frequent changes in temperature
and pressure, replace at regular intervals as determined by processing conditions.
h) Rotameters should be armored and arranged so only a sample of the flow is directed through the glass
reading chamber instead of the entire stream. Vents on air releases used in conjunction with some
metering devices should be piped to outdoor locations to prevent the release of flammable or combustible
liquids in the event of meter failure.
i) Conduct instrument maintenance, including tightening bolts and replacement, only when the associated
equipment or piping has been shut down and depressurized. Equipment containing flammable liquids
or gases should be emptied and purged.
2.1.2.4 Flammable or combustible liquid handling and processing equipment that, under normal operating
conditions, have the potential for a vapor-air explosion or mist explosion within the equipment (i.e., equipment
explosion hazardsee Section 3.1.5) should be protected by one of the following methods (listed in order
of preference):
a) Provide explosion venting designed to limit the pressure developed by an explosion to approximately
133% of the equipments yield strength (stress). If damage to the equipment creates a significant exposure
(i.e., high value equipment or difficult to replace), design the explosion venting to limit the pressure
development to approximately two thirds (23) of the equipments yield strength (stress) to prevent
permanent equipment deformation. Equipment explosion venting calculations are presented in the
Appendix C, Section C.5. The initial pressure of the equipment must be considered when calculating the
needed vent size.
b) Design the equipment to contain the maximum expected pressure due to a vapor-air explosion. The
maximum pressure should not exceed 133% of the equipments yield strength (stress). To prevent
permanent equipment damage, the maximum pressure should not exceed two thirds (23) of the
equipments yield strength (stress). Most vapor-air explosions will produce a maximum pressure of
approximately nine times the initial absolute pressure in the equipment (this applies to equipment operating
at atmospheric or at elevated initial pressures).
c) Provide a gas inerting system designed in accordance with Data Sheet 7-59, Inerting and Purging of
Tanks, Process Vessels, and Equipment, that is arranged to prevent the creation of a flammable vapor-air
mixture. The inerting system should have a reliable inert gas supply. Equipment operators should be well
trained on the importance and function of the inerting system.
d) An explosion suppression system, designed in accordance with Data Sheet 7-17, Explosion Protection
Systems, should be provided on high value equipment, equipment that exposes high value processes,
or equipment with frequent explosions, when either explosion venting, containment, or inerting cannot be
provided.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

7-32
Page 7

2.1.2.5 Provide purging or ventilation systems for equipment with a vapor-air explosion hazard to reduce
the risk of creating a vapor-air mixture in the flammable (explosive) range (not needed on inerted equipment).
Design purging systems in accordance with Data Sheet 7-59, Inerting and Purging of Tanks, Process Vessels,
and Equipment. Ventilation systems should be designed in accordance with Data Sheet 6-9, Industrial Ovens
and Dryers. Utilize purging to avoid passing through the flammable (explosive) range of the flammable vapor
during start-up or shutdown operations. Design ventilation systems to limit flammable vapor concentrations
to less than 25% of the lower flammable (explosive) limit (these systems are normally found in ovens and
dryers).
2.1.2.6 Supports for important equipment or equipment containing flammable/combustible liquids
(e.g., mixing tanks, storage tanks) that are blocked from ceiling sprinkler discharge (i.e., equipment that is
wider than 3 ft (0.9 m) or 10 ft2 (0.9 m2) in area) should be protected against potential failure due to the high
temperatures created by pool fires. Use automatic water spray or sprinklers, arranged to protect the supports,
in rooms without a room explosion hazard. Use reinforced concrete or protected steel supports when a room
explosion hazard exists or as an alternative to water spray or sprinklers.
2.1.2.7 Tanks, mixers and other equipment to which flammable or combustible liquids are transferred should
be arranged to prevent accidental overflow. One or a combination of the following methods or equivalent
should be used (listed in order of preference):
a) Provide a trapped overflow drain leading back to the source of supply or to a point of safe discharge.
The capacity of the overflow drain should be at least equal to that of the fill pipe.
b) A liquid level-limit switch arranged to stop the liquid flow by closing a valve or stopping the pump should
be provided. An audible alarm may be used as a first warning that is followed by shutdown of the liquid
flow. The liquid level-limit switch should be Approved. This arrangement is acceptable if the equipment
normally operates under pressure so that an overflow drain is not practical but overflow is possible during
filling because of open manholes or sampling connections. This may also be used in conjunction with an
overflow drain (provide an alarm to prevent overflow).
The use of weigh tanks, measuring tanks, and dispensing meters to accurately provide a measured quantity
of liquid to a tank will assist in the prevention of overflows. Arrange weigh tanks and measuring tanks to
prevent overflow (using either a or b). The use of a dispensing meter does not eliminate the need to follow
recommendations a and b above.
2.1.2.8 Provide overflow protection and emergency bottom drains for open top tanks to prevent overflow
due to sprinkler discharge and hose streams, and to remove the exposed flammable/combustible liquid from
a fire area. The overflow protection and emergency bottom drains should be designed in accordance with
Data Sheet 7-9, Dip Tanks, Flow/Roll Coaters, and Oil Cookers. Sprinkler discharge overflow protection may
be omitted if the exposure created by spilling flammable/combustible liquids is limited, and one of the
following is provided:
a) The tank or equipment is equipped with automatic closing covers or normally closed covers.
b) The liquid in the tank has a flash point above 200F (93C).
c) The tank has a capacity of less than 100 gal (380 l) and there is less than 20 ft2 (1.9 m2) of exposed
surface.
Provide at least 6 in. (150 mm) of freeboard on tanks without overflow protection.
2.1.2.8.1 Emergency bottom drains may be omitted if the exposure created by burning flammable/combustible
liquids is limited, and one of the following exists:
a) The liquid has a flash point greater than 200F (93C).
b) The tank has a capacity of less than 500 gal (1900 l) and is located on the first floor.
c) The tank has a capacity of less than 150 gal (600 l) and is located on an upper floor.
2.1.2.9 Equipment heating should be provided by steam, hot water, organic heat transfer fluid (see Data
Sheet 7-99/12-19, Heat Transfer By Organic and Synthetic Fluids) or other means not requiring an open flame.
Arrange heating equipment for automatic control. Provide a high temperature interlock arranged to provide
an audible alarm and shut down the heating equipment. Equipment and process temperatures should be
continuously monitored by the operator. Maximum equipment temperatures should be below the liquids
autoignition or autodecomposition temperature.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32
Page 8

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

2.1.2.10 Flammable/combustible liquid storage should be cut off from points of use (e.g., manufacturing area).
The quantity of flammable/combustible liquids in areas where they are used should be limited to one shifts
needs (approximately 100 gal (400 l) or as specified by other specific data sheets).
2.1.2.11 Use drum pumps (preferred, easy control of liquid discharge) or self-closing faucets (gravity driven,
less control with failure of faucet), where permitted, for drums arranged for dispensing flammable and
combustible liquids. Use drip cans below faucets with on-side dispensing operations of Class I flammable
liquids (in areas where the ambient temperature can approach 100F (38C) include Class II combustible
liquids). A shallow metal drip pan is acceptable for use with Class II and III combustible liquids except as noted
above. The drum pumps, self-closing faucets, and drip cans should be Approved.
2.1.2.12 Provide safety bungs on drums of Class I liquids arranged for upright dispensing with a drum pump
that is not equipped with pressure and vacuum relief vents. If ambient temperatures can approach 100F
(38C), safety bung use should include Class II liquids. Also provide safety bungs on drums of Class I, II and
III liquids arranged for on-side dispensing. Safety bung use for Class III liquids is intended to prevent possible
spillage during on-side dispensing. Safety bungs prevent the creation of vacuum during dispensing, prevent
the release of flammable/combustible liquids and their vapors, allow the release of excess internal pressure
that can be created when the drum is exposed to a fire (i.e., prevent a BLEVE), and prevent the flashback
of released vapor. Attach safety bungs only to the 2 in. (51 mm) drum opening to ensure its proper operation.
Provide safety bungs on intermittent drum storage of flammable or combustible liquids located in a dispensing
area if the stored drums will be exposed to a spill from the dispensing drum and sprinkler protection in the
area is not adequate for drum storage (Data Sheet 7-29, Flammable Liquid Storage in Portable Containers)
or sprinkler operation may be delayed (e.g., locations under 20 ft [6 m] high ceilings). Store the drums on
the floor, upright and a maximum of one high. If the dispensing area is adequately curbed and drained so a
spill will not expose the stored drums, safety bungs are not needed on the stored drums. Drums stored in
adequately protected dedicated storage areas do not need safety bungs.
2.1.2.13 Use Approved safety cans for handling small quantities of Class I, II, and IIIA liquids. Class IIIB
liquids can be handled in nonrated containers.
2.1.2.14 Use Approved flammable liquid storage cabinets for storing small quantities (type, quantity and
container size is limited by Approval Standard) of Class I, II, and IIIA liquids in manufacturing areas or areas
that are not designed for flammable or combustible liquid use. Provide mechanical ventilation in cabinets
where flammable vapors may be present (e.g., open containers, dispensing in cabinet). To maintain cabinet
integrity, the ventilation ducts should have a fire resistance similar to the cabinet. If ventilation is not needed,
keep the two ventilation openings closed to ensure the cabinets fire rating is maintained.
2.1.2.15 Flammable/combustible liquids should be transferred in closed systems. Arrange liquid pumping
and piping systems in accordance with recommendations listed in Sections 2.2 and 2.3.
2.1.3 Occupancy
2.1.3.1 Ventilation
Ventilation systems are designed to confine, dilute and remove the maximum normal amount of flammable
vapor released from equipment and handling of flammable and combustible liquids during normal operations.
Adequately designed low level ventilation will reduce the chances of a flammable vapor-air mixture
accumulating in the process area. Excessive vapor release caused by equipment failure (pipe break, release
from a relief valve), accidental discharge of heated flammable/combustible liquids (drum or tank spill), or
an uncontrolled chemical reaction (venting a reactor) cannot be adequately safeguarded by the ventilation
rates provided below. Designing a ventilation system to remove a large vapor release is outside the scope of
this document.
2.1.3.1.1 Continuous low level mechanical ventilation designed to provide 1 cfm/ft2 (0.3 m3/min/m2) of floor
area should be provided in rooms or buildings where Class I liquids or liquids with a flash point up to 300F
(149C) that are heated above their flash point are used.
2.1.3.1.2 In addition to providing the design in Recommendation No. 2.1.3.1.1, the exhaust ventilation should
confine flammable vapor concentrations exceeding 25% of the lower explosive limit to within 2 ft (0.6 m)
of points of release (e.g., open mixing or dip tanks, dispensing stations).

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations


FM Global Property Loss Prevention Data Sheets

7-32
Page 9

2.1.3.1.3 Exhaust air should be removed through a system of blowers, fans and ductwork terminating out
of doors away from air inlets, doorways and other openings. Exhaust ducts should be constructed of
noncombustible materials. Run the ducts as directly as possible to the outdoors with a minimum of bends.
Protect long runs of ventilation ducts with the potential for accumulation of combustible deposits in
accordance with Data Sheet 7-78, Industrial Exhaust Systems. Exhaust systems for small rooms may consist
of a fan installed at floor level arranged to exhaust out of doors (i.e., installed in exterior wall).
The ventilation system should take suction within 12 in. (0.3 m) of the floor. Locate intake openings at open
tank lips, near equipment or dispensing, and in any pits located within the cutoff room or within 25 ft (8 m)
of the operations that produce vapors.
Ventilation systems that are arranged to recirculate air into the room should be provided with an Approved
combustible gas detector arranged to stop recirculation, and return to full exhaust when the vapor
concentration reaches 25% of its lower explosive limit (LEL).
2.1.3.1.4 At a minimum, interlock exhaust fans with equipment power supplies. However, if flammable or
combustible liquids are kept in the room or building during idle periods, the exhaust ventilation should operate
continuously and be monitored (provide visual or audible ventilation failure alarm at occupied locations).
2.1.3.1.5 Provide make-up air inlets in exterior walls. Air inlets should be remote from exhaust outlets so that
air will sweep through the hazardous area. If gas or oil make-up air heaters are provided, they should be
indirect-fired and properly safeguarded.
If make-up air is taken from other plant areas, those areas should be free of flammable or combustible liquids.
Install automatic closing fire dampers or doors at make-up air inlet openings in interior fire walls or partitions.
The dampers or doors should have a fire rating equal to that of the walls.
2.1.3.1.6 For unheated liquids with a flash point greater than 100F (38C) and heated liquids with a flash
point greater than 300F (149C), provide natural draft ventilation arranged to provide 1 ft2 (0.1 m2) of free
inlet and outlet opening per 500 ft2 (47 m2) of floor area.
2.1.4 Ignition Source Control
A basic design goal for occupancies that contain flammable and combustible liquids is the elimination and
careful control of all potential ignition sources. Prevention measures should prevent contact of an ignition
source with any flammable vapor-air mixture.
2.1.4.1 Provide hazardous location rated electrical equipment in accordance with Data Sheet 5-1, Electrical
Equipment in Hazardous (Classified) Locations, and the NFPA National Electric Code, Article 500, when
handling: a) Class I liquids, or b) Class II or III liquids heated above their flash point (including possible ambient
temperatures). Electrical equipment should be Approved. Class I Division 1 and Class I Division 2 areas
should be defined as follows:
a) Areas with less than 5 gal (19 l) of flammable/combustible liquid in a single container or piece of
equipment generally do not require rated electrical equipment (limited exposure).
b) Areas with 5 gal to 70 gal (19 l to 265 l) of flammable/combustible liquids in a single container or piece
of equipment should use either Figure 2a or 2b.
c) Areas with more than 70 gal (265 l) of flammable/combustible liquids, in a single container or piece
of equipment, with low pressures (less than 100 psig [7 bar g]) should use either Figure 3a or 3b. Electrical
equipment with contacts (e.g., make-and-break or sliding contacts: motors, switches, breakers, etc.)
should be avoided directly above and 10 ft (3 m) beyond the Class I Division 1 area. Provide light fixtures
with lenses to enclose bulb Protect all equipment against physical damage. If electric equipment with
contacts is located above a Class I Division 1 area, the contacts should be fully enclosed in a metal
housing.
d) Buildings or rooms where an explosion hazard has been determined to exist should use Figure 3a to
define Class I Division 1 areas. The remainder of the room or building should be defined as a Class I
Division 2 area (floor to ceiling).
Processes using flammable/combustible liquids at high pressures are not covered by this recommendation.
These occupancies require a full review of processing conditions to determine areas requiring hazardous
area rated electrical equipment.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 10

FM Global Property Loss Prevention Data Sheets

1. Class I, Division 1 within 5 ft (1.5 m) of Flammable Vapor Release


2. Class I, Division 2
3.
Separation Between Pit and
Point of Vapor Liberation
05 ft (01.5 m)
520 ft
(1.56 m)

Is Ventilation
Provided in
Pit?
Yes/No
No
Yes

> 20 ft (6 m)

Yes/No

Electrical
Equipment
Needed in Pit
Class I
Division 1
Class I
Division 1
Class I
Division 2
Ordinary

4. Ordinary Electric Equipment


Fig. 2a. Location of hazardous area rated electrical equipment for up to 70 gal (265 l) of flammable/combustible liquid
in open equipment.

The use of all nonrated equipment (including maintenance equipment, battery operated equipment, etc.)
unless it is recognized as being intrinsically safe, should be strictly prohibited in rated areas unless the area
has been purged of all flammable and combustible liquids as well as their vapors. An alternative is to provide
a pressurized or purged enclosure for the electric equipment designed in accordance with Data Sheet 5-1,
Electrical Equipment in Hazardous (Classified) Locations.
Standard electrical equipment is acceptable in: a) areas handling unheated Class II or III liquids, or b)
above-grade areas with flammable liquid piping (no associated equipment such as pumps, valves, connect
and disconnect points, filters, tanks, etc.).
2.1.4.2 Equipment handling Class I liquids or Class II and III liquids heated above their flash points should
be electrically bonded and grounded in accordance with Data Sheet 5-8, Static Electricity, Data Sheet 5-10,
Protective Grounding for Electric Power Systems and Equipment, and NFPA National Electric Code, Articles
250 and 500. Proper grounding and bonding of equipment reduces the potential for buildup of electric charge
on separated pieces of equipment due to static accumulations or stray electric currents.
2.1.4.3 Prohibit smoking or the use of open flames in all rooms or buildings requiring hazardous location
rated electrical equipment (i.e., Class I Division 1 or 2). Post signs to define hazardous areas and state
restrictions for the area.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 11

1. Class I, Division 2
2.
Separation Between Pit and
Point of Vapor Liberation
015 ft
(05 m)

Is Ventilation
Provided in
Pit?
No
Yes

> 15 ft (5 m)

Yes/No

Electrical
Equipment
Needed in Pit
Class I
Division 1
Class I
Division 2
Ordinary

3. Ordinary Electric Equipment


Fig. 2b. Location of hazardous area rated electrical equipment for up to 70 gal (265 l) of flammable/combustible liquid
in closed equipment.

2.1.4.4 When heating rooms or buildings containing a flammable or combustible liquid occupancy, use a
system that does not introduce an ignition source (e.g., steam or hot water, organic heat transfer oil, or
hazardous location rated electric heating). Direct natural gas/fuel oil-fired make-up air heaters are acceptable
if the heating unit is located outside the room or building and there is no air recirculation. Heating equipment
temperatures should be below the auto-ignition point of the liquids present in the room. If Class I liquids
are present, the heaters should be at least 4 ft (1.2 m) above the floor level.
2.1.4.5 Arrange all equipment that may produce sparks (electrical, static, mechanical, or friction), open flames,
or hot surfaces to prevent or strictly limit contact with flammable/combustible liquids or their vapors.
Equipment that, over time, may produce sparks or hot spots due to wear (e.g., rotating equipment such as
motors, agitators, pumps, etc.) should be maintained on a strict schedule.
Equipment or piping that create hot surfaces (e.g., steam pipe) should be avoided in areas with piping systems
containing unusually low ignition temperature liquids, such as carbon disulfide.
2.1.4.6 Industrial trucks should be properly rated and Approved for use in areas requiring Class I Division
1 or 2 electrical equipment. Refer to Data Sheet 7-39, Industrial Trucks, to select the appropriate truck rating.
2.1.4.7 Avoid hot work of any kind in areas handling, processing or storing flammable liquids. Hot Work
provides an ignition source in an area where fuel is available in significant quantities and in a readily ignitable
form. Ideally, relocate any hot work to a nonhazardous location. When relocation is not possible, a
documented Hot Work Permit System is needed.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 12

FM Global Property Loss Prevention Data Sheets

1. Class I,, Division 1 within 5 ft (1.5 m) of Flammable Vapor Release


2. Class I, Division 2
3.
Separation Between Pit and
Point of Vapor Liberation
05 ft
(01.5 m)
525 ft
(1.58 m)

Is Ventilation
Provided in
Pit?
Yes (always
needed)
No
Yes

25 ft
(8 m)

No
Yes

Electrical
Equipment
Needed in Pit
Class I
Division 1
Class I
Division 1
Class I
Division 2
Class I
Division 2
Ordinary

4. No Equipment With Make-and-Break or Sliding Contacts


(e.g., motors, switches, receptacles, cutouts, etc.)
Equipment Protected Against Physical Damage
Lighting Equipment Provided With a Lens to Enclose the Bulb
Fig. 3a. Location of hazardous area rated electrical equipment for more than 70 gal (265 l) of flammable/combustible
liquid in open equipment.

Use a documented permit system to strictly control all hot work operations. The permit is issued only after
a complete review of all proposed work, the hazards in the area, and all precautions needed to prevent a fire
or explosion. If all of the requirements cannot be met, then the permit should not be issued and the work
should not be allowed.
Precautions are listed on the FM Global Hot Work Permit itself. Some of the minimum requirements include:
a) Automatic sprinkler protection should be in service. Charged small hose or fire extinguishers should
be available at work area.
b) Remove flammable and combustible liquid storage from the area. All combustibles within 35 ft (11 m)
of the work should be removed or covered with a fire-resistive tarpaulin (see Data Sheet 1-0, Safeguards
During Construction, Alteration and Demolition).
c) Drain all equipment or piping in the area of flammable and combustible liquids. Equipment or pipe to
be worked on should be steam cleaned or provided with an inert atmosphere to prevent creation of a
flammable atmosphere (see Data Sheet 7-59, Inerting and Purging of Tanks, Process Vessels, and

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 13

1. Class I, Division 2
2. Ordinary Electric Equipment
3.
Separation Between Pit and
Point of Vapor Liberation
025 ft
(08 m)

Is Ventilation
Provided in
Pit?
No
Yes

> 25 ft (8 m)

Yes/No

Electrical
Equipment
Needed in Pit
Class I
Division 1
Class I
Division 2
Ordinary

Fig. 3b. Location of hazardous area rated electrical equipment for more than 70 gal (265 l) of flammable/combustible
liquid in closed equipment.

Equipment). Piping supplying the area with flammable and combustible liquids should be shut off at the
source (valve should be locked shut to prevent unexpected opening). If the piping is to be worked on, it
should be blanked off. Check equipment or piping with an Approved portable oxygen analyzer (see Data
Sheet 5-49, Gas and Vapor Detectors and Analysis Systems) before and during the hot work. This is to
ensure that sufficient oxygen to support combustion is not present inside the equipment or piping.
d) All permanent storage tanks or piping that cannot be moved or drained must be protected against
physical contact and heat from hot work equipment. Preferably all equipment that is within reach of the
hot work equipment (grinder, welding rod holder, cutting torch, etc.) will be drained, purged and inerted. If
this is not possible due to the quantities of flammable liquids involved, physical protection can be provided
by placing welding curtains and temporary barriers between the equipment and the hot work. A careful
review of the area is required to ensure that no vents or other openings are near the hot work that could
allow fumes and sparks from the hot work to meet.
e) Keep mechanical ventilation in the room/building in operation. Use a portable combustible gas analyzer
before and during the work. If any detectable readings are obtained, then work cannot begin or continue
until the source is found and suitably mitigated such that the concentration is maintained below 10% of
the LEL.
f) Provide a continuous fire watch both during and at least 60 minutes after work. Check the area at least
hourly for up to three hours after the end of hot work operations.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 14

FM Global Property Loss Prevention Data Sheets

Avoid the use of nonrated electrical equipment in areas containing flammable liquids. If such equipment must
be temporarily introduced, view this as hot work and follow the permit precautions. As with other hot work,
if the precautions cannot be taken, the permit should not be issued and the nonrated electrical equipment
should not be used.
For situations where the above steps are not applicable or unusual circumstances are present, consult a
specialist in flammable/combustible liquid handling before any hot work is performed.
2.1.5 Operation and Maintenance
Thorough operator training and a complete maintenance program are fundamental components of any
process that utilizes flammable/combustible liquids. Both items will contribute to reducing the potential for a
fire or explosion as well as reduce the frequency and severity of such occurrences. As the complexity of
flammable/combustible liquid processes increase, the need for high levels of operator training and strict
equipment maintenance programs becomes essential to the proper operation of the process. Tailor training
programs and maintenance schedules to meet each locations specific needs.
2.1.5.1 A series of routine checkpoints with normal condition limits should be inspected by the operator for
prompt detection of abnormal conditions. Determine the frequency of the checks by the process conditions
and severity of the consequences due to a process upset. Check all safety devices and process control
features at the beginning of each shift
2.1.5.2 All emergency shutoff valves for piping systems containing flammable and combustible liquids should
be clearly labeled with a sign indicating what is controlled.
2.1.5.3 Equipment (tanks, drums, etc.) containing flammable and combustible liquids should be clearly labeled
indicating the content of the equipment and the type of hazard they present (e.g., flammable, combustible).
Piping containing flammable and combustible liquids should be labeled and color coded. Piping containing
specific flammable and combustible liquids should indicate the liquid name and direction of flow. Identification
is particularly important where piping passes through walls, at valves and fittings, and at points of use. An
acceptable piping identification system is described in ANSI A13.1, Scheme for Identifications of Piping
Systems. Pipe labeling and coding will reduce mix-ups during liquid transfer, prevent mistakes during
maintenance operations, and reduce confusion during emergency responses.
2.1.5.4 Provide a raw materials inspection program to ensure delivery of expected materials and prevent
the introduction of foreign or incompatible materials into a storage or distribution system.
2.1.5.5 Management should strictly control all changes or new installations in processes or areas containing
flammable and combustible liquids. Conduct a full review of all planned changes by qualified loss prevention
consultants as well as other authorities having jurisdiction before the project begins.
2.1.5.6 Establish a complete preventive maintenance program designed to ensure that equipment is operating
as it has been engineered to operate. Refer to Data Sheet 9-0/17-0, Maintenance, to evaluate existing
programs or as a guide to develop new programs. This program should also include regular documented
testing of safety devices and process control features in accordance with the manufacturers
recommendations.
Preventive maintenance programs for equipment and areas containing flammable or combustible liquids
should include: mechanical and electrical equipment, piping systems (e.g., connect/disconnect points, pumps,
flanged fittings, flexible pressure hoses, swing joints, etc.), system control devices (e.g., valves, computer
controllers, etc.), and emergency control or relief devices (e.g., emergency shutoff valves, float valves,
pressure relief devices, etc.). Follow preventive maintenance schedules closely to prevent the creation of an
ignition source (e.g., equipment breakdown and overheating, improperly sealed hazardous area rated electric
equipment) or the release of flammable or combustible liquid (e.g., pipe joint failure).
Conduct frequent inspections to detect and repair leakage. Use a flammable-vapor detector to locate small
leaks (detector should be Approved). Prohibit the use of open flames or spark-producing devices.
2.1.5.7 Perform maintenance or repair operations only on equipment that has been depressurized, shut down
and drained of any flammable/combustible liquids. This includes tightening or loosening bolts or flanges,
packing glands, or making new connections. Piping should be depressurized, drained, flushed, purged and
inerted before it is opened or tapped. Bolts for flanges or for connections to flanged fittings should be
tightened with a torque wrench to ensure proper tightness without overstressing. Prohibit the use of power

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 15

tools unless the precautions listed in Recommendation No. 2.1.4.7 are strictly followed. Use Approved safety
tools in areas where a flammable atmosphere may exist.
2.1.5.8 Relocate equipment needing repair or maintenance that requires use of a cutting torch or other hot
work operation preferably to a nonhazardous location. Regardless of where the work is done, the equipment
should be drained, flushed, purged, and inerted as necessary to eliminate all flammable and combustible
liquids and their vapors. Use an Approved combustible vapor analyzer (see Data Sheet 5-49, Gas and Vapor
Detectors and Analysis Systems) before and during work to make certain equipment that is not inerted has
been fully purged and remains purged of any flammable vapors. Check equipment that is inerted before
and during work with an Approved oxygen analyzer to ensure a flammable atmosphere is not present. Follow
Recommendation No. 2.1.4.7 and Data Sheet 7-59, Inerting and Purging of Tanks, Process Vessels, and
Equipment, to ensure all flammable vapors and potential ignition sources have been eliminated.
2.1.5.9 Use an equipment isolation procedure to supervise valves controlling flammable and combustible
liquids that are shut off for repair or other maintenance procedures. Equipment isolation procedures should
be strictly controlled to ensure equipment repairs/maintenance are complete before flammable/combustible
liquids are introduced.
2.1.5.10 Remove unused piping or tanks. Cap open end pipes promptly. Unused equipment that is not
removed should be completely drained and purged of all flammable/combustible liquids and their vapors.
The equipment should also be disconnected from any surrounding active equipment and clearly labeled as
shutdown to reduce the chances of accidental use.
2.1.5.11 Protect flammable and combustible liquid handling and transfer equipment against external corrosion.
Protective coatings for buried tanks and piping should be carefully applied and inspected before they are
covered. Conduct regular inspections of the equipment to investigate external corrosion. Increase the
inspection frequency of equipment located in corrosive atmospheres.
2.1.6 Training
2.1.6.1 Create a training program for all employees (including operators, emergency organization members,
and security personnel) who have access to or work in areas containing or processing flammable/combustible
liquids. Design and supervise the training programs to address the complexity of process operations and
the hazard level present at a facility. The training should include proper handling, equipment operation, and
emergency procedures as well as the consequences of failing to follow the procedure. Provide training for
all new employees. Refresher programs should also be provided, as needed, for current employees. The
program should at least include:
a) The hazards created by the materials in use.
b) The proper operation or shutdown of the equipment under normal and emergency conditions. Critical
procedures should be printed and posted for convenient reference.
c) Proper material handling procedures (i.e., bonding/grounding, self-closing faucets, safety bungs, etc.).
d) Flammable/combustible liquid piping system operation and shutdown including the location of all local
and remote shutoff valves.
e) Proper flammable/combustible liquid transfer procedures.
f) The location, proper type and proper use of fire extinguishers for the hazard present.
g) Fixed extinguishing systems operation and function.
2.1.7 Human Element
2.1.7.1 Establish an emergency response plan at locations handling or processing flammable/combustible
liquids. Design the plan to control the extent of damage due to fires or explosions by at least ensuring prompt
fire department notification, shutdown of fuel supply, and availability of provided fire protection features. The
plan should also include spill response procedures aimed at limiting spill size (e.g., prompt shutdown of liquid
flow), containing released liquid (e.g., use of sand bags), and elimination of all ignition sources that may be
exposed by the spill, or flammable vapors, until the spill is cleaned up. The actual extent of the emergency
response plan, including spill response procedures, will depend on the hazards present, facility size,
availability of emergency response personnel from surrounding communities (e.g., fire department, spill
response teams, etc.), and local, state or federal regulations.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 16

FM Global Property Loss Prevention Data Sheets

The facilitys emergency organization members and the local fire department should be familiar with the
location of flammable/combustible liquid processes as well as the emergency response plan. Use emergency
response drills to reinforce the employee training programs (including emergency organization) and assist
the fire department in pre-fire planning.
2.1.7.2 Arrange security rounds to include areas handling flammable and combustible liquids during idle
periods. Train security personnel to ensure all equipment and valves that contain or control flammable and
combustible liquids are shut down (including pumps, emergency shutoff valves, mixers, etc.).
2.1.7.3 Establish excellent housekeeping standards for areas storing or handling flammable and combustible
liquids. Clean up spills promptly. Keep waste materials in Approved oily waste cans. Remove waste daily.
Maintain adequate aisles to permit unobstructed movement of personnel and access for fire fighting.
2.1.8 Protection
2.1.8.1 Provide automatic sprinkler protection over all areas storing, processing, or transferring flammable
and/or combustible liquids. Extend the sprinkler protection to the physical limits of the area. The physical limits
are defined by at least one hour rated fire walls and curbs. Sprinkler systems over areas defined by curbs
only (see Recommendation No. 2.1.1.4) should extend over and 20 ft (6 m) beyond the curbed area. The
sprinkler system should be either a standard closed head, preaction or deluge type. Preaction systems are
preferred over dry systems for unheated locations. Install the sprinkler system in accordance with Data Sheet
2-8N, Installation of Sprinkler Systems (NFPA).
2.1.8.2 Provide sprinkler protection under any obstruction to water distribution that exceeds 3 ft (0.9 m) in
width or diameter and 10 ft2 (0.9 m2) in area (e.g., under large tanks or pieces of equipment, below grated
mezzanines) to ensure adequate cooling for steel structures. Spacing below mezzanines should be 100 ft2
(9 m2) per head.
2.1.8.3 Automatic sprinkler protection may be omitted in building areas that contain no combustibles (including
combustible construction) other than flammable or combustible liquid piping if all of the following exist:
a) The piping is welded with no flanged joints or has threaded joints that meet the criteria listed in
Recommendation No. 2.2.1.3.6. Evaluate fire protection requirements for external pipe racks in
accordance with Data Sheet 7-14, Fire & Explosion Protection for Flammable Liquid, Flammable Gas, &
Liquefied Flammable Gas Processing Equipment & Supporting Structures.
b) There are no valves, pumps, or other accessories that are known to be potential leakage points.
c) The piping system consists solely of ferrous piping installed as recommended in Section 2.2 of this
document.
Automatic sprinkler protection may also be omitted in low value buildings (including pump houses, etc.) with
flammable and combustible liquid processes that have adequate space separation (see Section 2.1.1) from
important buildings and structures.
2.1.8.4 Sprinkler spacing should be a maximum of 100 ft2 (9 m2) when protecting liquids with a flash point
less than 200F (93C) or greater than 200F (93C) and heated to its flash point. A maximum spacing of
130 ft2 (12 m2) when protecting liquids with a flash point greater than or equal to 200F (93C).
2.1.8.5 Automatic sprinkler systems (i.e., wet, preaction, or deluge) should be hydraulically designed as
indicated in Table 2. If a dry sprinkler system is provided, increase the sprinkler operating areas by 50%.
These tables apply to ordinary manufacturing occupancies that use flammable and/or combustible liquids (no
liquid quantity limitations) with no potential for a three dimensional fire. Refer to Data Sheet 7-14, Fire &
Explosion Protection for Flammable Liquids, Flammable Gas, & Liquefied Flammable Gas Processing
Equipment & Supporting Structures, for plants or buildings that are dedicated to flammable/combustible liquid
processing (i.e., plants with processes that involve chemical reactions, chemical plants, etc.), any process
that creates the potential for three dimensional flammable/combustible liquid fires, or processes that operate
at high pressures (pressures approximately 100 psig [7 bar g] or greater). Sprinkler protection
recommendations provided in other data sheets that address specific occupancies that use flammable/
combustible liquids supersede the recommendations in this document.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 17

Table 2. Sprinkler Protection for Occupancies Utilizing Flammable/Combustible Liquids.


Room/
Liquid
Equipment
Heated
Explosion
Liquid Flash
To/Above
Hazard
Point,
o
F (oC)
Flash Point
(note 1)
Any liquid with an associated room/
equipment explosion hazard or
nitrocellulose lacquer
< 100 (38)

100200
(38-93)

DNA

No

Yes

No

No

No

Yes

No

No

No

> 200 (93)

Sprinkler
Temperature
Rating
o
F (oC)

Density
gpm/sq ft
(mm/min)

286 (141)

Duration
(note 3),
min

1000 (3800)

120

500 (1900)

60

Area of
Demand,
ft2 (m2)
6000 (560)

0.30 (12)
165 (74)
286 (141)
165 (74)
286 (141)
165 (74)
286 (141)
165 (74)
286 (141)
165 (74)
286 (141)
165 (74)

Hose
Streams
(note 2),
gpm
(1/hr)

8000 (740)
0.30 (12)
0.30 (12)
0.25 (10)
0.25 (10)
0.20 (8)

4000
6000
4000
6000
4000
6000
4000
6000
3000
4000

(370)
(560)
(370)
(560)
(370)
(560)
(370)
(560)
(280)
(370)

1. See Sections 3.1.4 and 3.1.5 for definition of room/equipment explosion hazard.
2. Hose stream demands may need to be increased if shielded areas exist.
3. Water supply durations may need to be increased when local conditions delay fire fighting efforts (e.g., lack of drainage, inaccessible
areas, etc.).

Sprinkler protection for flammable/combustible liquid processes and transfer systems may be designed for
the surrounding occupancy when one of the following applies:
a) The aggregate area of an open tank and its drainboard is less than 20 ft2 (2 m2).
b) The total liquid surface area of an open tank does not exceed 10 ft2 (1 m2).
c) The aggregate liquid capacity within the fire area is less than 70 gal (265 l). The flammable or
combustible liquid should be kept in flammable liquid storage cabinets.
d) The area contains properly arranged ferrous piping (no valves, manifolds, pumps, or other accessories).
2.1.8.6 Sprinklers provided below open grate mezzanines (no flammable or combustible liquids located
above the mezzanine) should be hydraulically designed to provide the same density as recommended for the
ceiling over half the recommended area (or the entire mezzanine area; whichever is smaller). These
sprinklers should be balanced with the ceiling demand at the point of connection. If flammable liquids are
located above the mezzanine, a three dimensional fire potential exists and Data Sheet 7-14, Fire & Explosion
Protection for Flammable Liquid, Flammable Gas, & Liquefied Flammable Gas Processing Equipment &
Supporting Structures, should be used for system design.
2.1.8.7 Spacing of detectors for interior deluge systems (either pilot head, electric, or pneumatic) should
be in accordance with Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA), (pilot headssame spacing
as sprinklers, electric or pneumatic devices under smooth ceilingsfollow spacing requirements listed in
the Approval Guide for the particular model) or as recommended in data sheets that cover the specific
occupancy. Exterior deluge system design should be in accordance with Data Sheet 7-14.
Detector spacing for preaction systems (either pilot head, electric, or pneumatic) should be as follows:
a) Pilot head spacing should be the same as the sprinkler spacing. Preaction sprinkler systems that use
pilot heads should be considered dry systems for design purposes regardless of detector spacing.
b) Electric or pneumatic detector spacing should be the greater of one-half the listed linear detector
spacing or the full sprinkler spacing. Preaction systems with this detector spacing may be considered wet
systems for design purposes. Preaction systems with a detector spacing greater than the above spacing
should be considered dry systems for design purposes. The spacing should never exceed the devices
listed spacing (e.g., Approval Guide, a publication of FM Approvals, listing).

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 18

FM Global Property Loss Prevention Data Sheets

2.1.8.8 Sprinkler piping, valves, and fittings exposed by occupancies that create an explosion hazard should
be protected in accordance with Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA), and Data Sheet
7-14, Fire & Explosion Protection for Flammable Liquid, Flammable Gas, & Liquefied Flammable Gas
Processing Equipment & Supporting Structures.
2.1.8.9 Automatic sprinkler protection may be supplemented with a fixed special protection system (local or
total floodinggaseous, dry chemical, water spray) to limit the exposure created by a potential flammable/
combustible liquid fire. A special protection system should be provided to:
a) Limit fire damage and downtime for high value processes.
b) Limit exposure to high value surrounding occupancies that are susceptible to smoke and water damage.
c) Provide local protection for open tanks that are not accessible to fire fighting with portable extinguishers.
d) Limit the exposure created by inadequate space separation between important buildings or processes
and flammable/combustible liquid operations (e.g., loading and unloading stations, piping systems, etc.).
The special protection system should be Approved and designed in accordance with the applicable data sheet.
2.1.8.10 When an open (deluge) or closed-head AFFF (aqueous film forming foam) sprinkler system is
provided as an alternative to a standard sprinkler or deluge system, the following design criteria should be
used (not acceptable in areas with a three dimensional fire potential or warehouse/storage areas):
a) Closed or open-head AFFF sprinkler systems should be hydraulically designed to provide either the
density listed in Table 2 or the minimum required density provided in the Approval Listing, whichever is
larger. The AFFF concentrate injection percentage should be in accordance with the Approval Listing.
The closed-head systems should be designed to deliver this density over the demand area listed in Table 2.
This protection is acceptable with or without adequate drainage (except when superseded by a specific
occupancy data sheet).
b) Exterior hose stream demand and water supply duration should be as recommended in Table 2.
c) Areas with adequate drainage in accordance with Data Sheet 7-83, Drainage Systems for Flammable
Liquids, should have at least a 10-minute supply of AFFF concentrate provided. Areas without adequate
drainage should have at least a 20-minute supply of AFFF concentrate provided. The supply should be
based on the sprinkler system design requirements, hose stream design requirements and the required
concentrate injection percentage provided in parts (a) and (b) above.
d) Adequate containment designed in accordance with Data Sheet 7-83, should be provided when
adequate drainage is available. If adequate drainage is not available, containment should be designed
to hold sprinkler and hose stream discharge for the full 20-minute foam concentrate duration.
e) The AFFF concentrate should be compatible and Approved for the flammable or combustible liquid
being protected. The AFFF delivery system (proportioning equipment, sprinklers) should be Approved.
f) The AFFF system should be installed in accordance with Data Sheet 4-12, Foam-Water Sprinkler
Systems.
2.1.8.11 Portable extinguishers should be provided for areas (interior and exterior) utilizing or handling
flammable and combustible liquids. Extinguishers should be either carbon dioxide, dry chemical, or AFFF
type. Refer to Data Sheet 4-5, Portable Extinguishers, to determine effective sizes and locations for the
extinguishers. Extinguishers should be Approved. Protect extinguishers located outside against freezing.
2.1.8.12 Provide small hose (1-12 in. [38 mm]) stations with combination spray/solid stream nozzles in areas
utilizing or handling flammable and combustible liquids. Space hose stations to allow full coverage of the
area being protected. Add a water demand of 50 gpm (11 m3/h) to the sprinkler demand for a single hose
station (100 gpm [23 m3/h] should be added for more than one hose station).
2.1.8.13 Manual protection consisting of yard hydrants should be located within 200 ft (60 m) of all outside
flammable and combustible liquid handling and process areas (e.g., pump houses, loading and unloading
stations, valve-manifold houses, process structures, etc.). Provide manual foam protection for critical process
or handling areas containing liquids with flash points below 200F (93C). Manual foam protection can be
provided by a fixed water spray system, fixed monitor nozzles, or mobile monitor and hose nozzles. Design
the system in accordance with Data Sheet 4-7N, Low Expansion Foam Systems .

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 19

2.2 Piping Systems


2.2.1 Construction and Location
2.2.1.1 Location and Arrangement
2.2.1.1.1 Locate flammable and combustible liquid piping systems outside (above or below ground) of
important buildings and structures. Arrange points of entry to buildings or structures to minimize inside piping
and to ensure a direct route to the point of use. Avoid piping flammable and combustible liquids through
or under buildings or process structures that do not use the liquids (e.g., reduce pipe length by taking a short
cut through a building).
2.2.1.1.2 Pipe routes should prevent or limit fire exposure to piping systems created by other plant
occupancies.
2.2.1.1.3 Protect piping against mechanical damage. Do the following to prevent or limit mechanical damage
to piping:
a) Provide adequate clearance for aboveground pipe that passes over roadways or railroad sidings. The
amount of clearance provided should be posted on signs at each crossing point.
b) Locate buried piping at least 1 ft (0.3 m) from building foundations, railroad tracks or other facilities
subject to vibration and settling. Enclose piping that passes below building footings or railroad tracks in
a larger pipe.
c) Mark buried piping routes to permit visual determination of their location.
d) Interior pipe risers within 6 ft (1.8 m) of the floor that are exposed to vehicles or mobile equipment
should be installed inside reinforced concrete columns, between flanges of steel columns, in a securely
anchored larger pipe, or provided with some other type of guard that will prevent contact with the mobile
equipment. Locate pipe risers in areas not exposed to mobile equipment or vehicles as close as possible
to walls or columns.
2.2.1.1.4 Protect interior and exterior piping (above or below ground) against external corrosion. Cover buried
pipe with noncorrosive backfill, or for ease of replacement and maintenance, place in covered masonry
trenches or split-tile ducts. Evaluate environmental conditions for aboveground installations to ensure
adequate precautions have been taken to prevent corrosion (e.g., exposure to weather conditions or corrosive
atmospheres).
2.2.1.1.5 Support exterior aboveground piping on noncombustible structures that are adequately protected
against vehicle impact damage. Piping may also be located on noncombustible building walls and above
noncombustible roofs. Place piping supported by a wall below window level. Piping runs above roofs should
have welded joints and avoid having known leakage points (e.g., flanged fittings, valves, meters, etc.).
Roofs supporting piping that contains known leakage points should be arranged to promptly direct any liquid
release to a properly arranged collection point through a dedicated collection and removal system (e.g., metal
collection pan below leakage points attached to a metal trough which directs a spill to a collection tank;
enclose entire piping system in a sealed metal duct arranged to direct spills to a containment tank). The liquid
collection and removal system should prevent damage to the roof covering due to liquid contact and prevent
the released liquid, or its vapors, from entering the building.
2.2.1.1.6 Avoid passing exterior pipe routes through service tunnels, sewer manholes, or other underground
pits.
2.2.1.1.7 Locate interior pipe routes either overhead or in covered (removable steel plates) trenches in the
floor. Avoid basement areas, vacant spaces below grade, and concealed or other inaccessible locations
within plant buildings. Place overhead piping as close as possible to ceilings and beams or along walls at
least 6 ft (2 m) above floor level. If a floor trench is used, do the following to prevent the collection of flammable
vapor or flammable/combustible liquid in the trench:
a) Provide drainage in accordance with Data Sheet 7-83, Drainage Systems for Flammable Liquids. The
trench may be used to direct the liquid to a collection point that does not expose the building (e.g., pitch
the trench to an exterior collection point so a spill that collects in the trench will be directed out of the
building).

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 20

FM Global Property Loss Prevention Data Sheets

b) Provide positive exhaust ventilation throughout the trench when the piping system is transporting liquids
with a flash point below 100F. Alternatives to providing ventilation are filling the trench with sand (this
will eliminate the need for drainage as well).
c) If the trench passes below a cutoff wall (e.g., enters a flammable liquid room from an adjacent area),
cut the trench off at the wall with a liquid tight noncombustible barrier. The section of trench outside the
area using the flammable/combustible liquids does not require drainage or ventilation if it is welded piping
only (no leakage pointsvalves, flanged joints, etc.). Protect the section of trench inside the room or
trench areas containing potential leakage points as stated in parts (a) and (b) above.
2.2.1.1.8 If piping is located inside a building and is below grade (e.g., basement areas) or is inaccessible
(e.g., vacant below grade spaces) provide one of the following:
a) Enclose the pipe in a larger pipe throughout its entire length (Fig. 4). Weld the larger pipe at joints.
Provide a means of checking for leaks (e.g., provide a low point drain that is accessible for inspection at
regular intervals).

Fig. 4. Buried-pipe entrance into building.

b) Enclose the pipe in sealed ductwork throughout its entire length. Arrange the ductwork to permit
inspection for leaks and allow drainage of potential leaks to a collection location (e.g., tank or flammable/
combustible liquid drainage system).
c) Basements or below grade spaces containing flammable or combustible liquid piping should be
provided with automatic sprinkler protection (Table 3), adequate drainage (per Data Sheet 7-83, Drainage
Systems for Flammable Liquids), and a low level continuous mechanical exhaust ventilation system for
the entire space. Design the ventilation system to provide 0.5 cfm/ft2 (0.15 m3/min/m2). Natural ventilation
is acceptable for pipe containing liquids with a flash point greater than 100F (38C).

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 21

2.2.1.1.9 Piping should enter buildings above grade. Buried piping should be brought above grade before
entering a building as shown in Figure 5. The piping should be adequately protected against damage due to
building settlement. Where flammable or combustible liquid piping enters a building below grade, seal all
other nearby openings in the foundation.
2.2.1.1.10 Enclose piping in a pipe sleeve where the piping passes through exterior walls and foundations.
Seal the opening between the sleeve and the pipe. Extend the sleeve to the exterior of the wall or foundation
at least 2 in. (51 mm) or 18 in. (460 mm) respectively. (Figs. 4 & 5)

Fig. 5. Preferred arrangement for above grade pipe entrance into building.

2.2.1.1.11 Arrange piping system to permit drainage of its content during maintenance operations (repairs,
cutting and welding, etc.). This can be accomplished by pitching pipe back toward the supply, providing low
point drains, and providing flanged connections at various locations to permit disconnection and blanking
of the pipe.
2.2.1.2 Pipe Materials
2.2.1.2.1 Choose flammable and combustible liquid pipe materials using The American Society of Mechanical
Engineers (ASME) Standard B31.3-1990 or latest edition, Chemical Plant and Petroleum Refinery Piping,
as a basic guideline. Consider the following factors when choosing a pipe material:
a) Chemical compatibility with the liquid to be handled.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 22

FM Global Property Loss Prevention Data Sheets

b) Operating environment.
c) Operating strength (i.e., design for maximum expected pressure and temperature).
d) Resistance to mechanical shock (e.g., impact damage).
e) Resistance to thermal shock (e.g., quick cooling or heating due to expected and unexpected process
conditions).
f) Resistance to high exposure temperatures (e.g., high melting point or noncombustible material that
will resist softening or decomposition when heated by an exposure fire).
2.2.1.2.2 Avoid materials such as cast irons, high silicon irons, plastics (thermoplastic, thermoset), glass,
and aluminum in flammable and combustible liquid piping systems due to their potential for failure (low impact
strength, low pressure ratings, low resistance to thermal shock, and low melting point). Seamless copper
or brass pipe and tubing is acceptable for use with flammable and combustible liquids in sprinklered locations
subject to the design conditions provided in ASME B31.3-1990 or latest edition.
2.2.1.2.3 Underground pipe should meet the above requirements (i.e., compatible with liquid in use, adequate
strength for maximum expected operating conditions, high impact strength, and high resistance to thermal
shock) but may be a low melting point material (e.g., plasticthermoplastic, thermoset) since there is no
potential for a fire exposure.
2.2.1.2.4 Consider seamless steel pipe for interior piping systems that operate under severe cyclic conditions
(i.e., pressure cycles, thermal cyclesfor example a hydraulic system) and create a significant exposure
to the facility.
2.2.1.2.5 Use stainless steel, nickel alloy, lined (glass, rubber, lead, plastic, etc.) steel pipe, or other similar
material when process conditions require high purity levels or create severely corrosive conditions. These
materials provide a high resistance to heat and mechanical damage. Lined pipe may fail internally with impact
or thermal shock, but the steel pipe shell will still contain the pipe contents.
2.2.1.2.6 Provide flexible all-metal seamless hose in piping systems exposed to vibration, settling or thermal
change. The installation should be in accordance with Section 2.2.2.1.
2.2.1.3 Pipe Joints
2.2.1.3.1 Piping systems containing flammable and combustible liquids should have welded joints. Provide
a limited number of flanged joints to permit pipe system dismantling for equipment maintenance or removal.
Welded joints connecting pipe lengths and fittings should be butt welded in accordance with ANSI/ASME
B16.25, Butt Welding Ends, and ASME B31.3, Chemical Plant and Petroleum Refinery Piping, Chapter 5.
Welding should be done by qualified welders under close supervision, with all hot work safeguards observed.
The flanged joints should be provided at connections to system accessories (e.g., pumps, valves, tanks,
etc.) and at various points in-line (e.g., entrance to a room or building).
2.2.1.3.2 Design flanged joints in accordance with ANSI/ASME B16.5, Pipe Flanges and Flanged Fittings,
and ASME B31.3. Provide the following for flanged joints:
a) Flanges should be constructed of forged or cast steel. Do not use cast iron flanges. Bronze flanges
are acceptable in sizes of 2 in. (50 mm) or less in sprinklered areas.
b) Flanges should be welding-neck type (flange is butt welded to pipe endsee Fig. 6). A double welded
slip-on type flange (flange slips over pipe end and is welded outside and insidesee Fig. 7) is acceptable
for use in systems that are noncyclic and have operating pressures less than 100 psig (7 bar g).
c) Design flanges on lined pipe (i.e., plastic, glass, etc., in steel pipe) to prevent leakage in the event of
lining failure (e.g., fire exposure to pipe melts plastic lining).
d) Consider high integrity or protected flanges (i.e., flanges designed or protected to prevent leakage or
full failure) when the exposure created by leakage (fire or explosion) is significant (e.g., spray fire exposure
to high value occupancies, flange failure would create explosion potential).
2.2.1.3.3 Bolting materials for flanges should be alloy steel conforming to ASTM A193, Alloy Steel Bolting
Materials for High Temperature Service, Grade B-7 or equivalent. Nuts should be alloy steel conforming to
ASTM A194, Carbon and Alloy Steel Nuts for Bolts for High Pressure and High Temperature Service. Bolt and
nut dimensions and threads should conform to nationally recognized codes. Existing installations with carbon

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 23

Fig. 6. Welding neck type flange.

Fig. 7. Slip-on type flange.

steel and wrought iron bolts are acceptable in sprinklered areas or in outside areas with limited exposures.
Make the effort to replace the bolts during maintenance of the joints or if the bolts are corroded.
2.2.1.3.4 Gaskets for use with flanged joints should be compatible with the flange type being used. Consider
the following factors when choosing a gasket material:
a) Chemical compatibility with the liquid in use.
b) Strength and temperature limitations (adequate for maximum possible system pressure and
temperature as well as system pressures when exposed by external fire).
c) Resistance to leakage or total failure.
d) Resistance to cold flow.
e) Resistance to decomposition or melting with an external fire exposure (e.g., noncombustible, high
melting pointgreater than 1200F [650C]).
2.2.1.3.4.1 Use one of the following types of gasket for flammable and combustible liquid service:
a) Spiral-wound stainless steel, Monel, copper, Inconel 600, or equivalent metallic gasket with graphite,
ceramic, or equivalent filler.
b) Metal ring-joint gasket consisting of dead-soft aluminum, Monel, copper, or equivalent.
c) Graphite gasket without organic fillers or resins.
2.2.1.3.4.2 Other gasket materials consisting of fiber-sheet, paper, vegetable fiber, plastic, cork, lead, rubber,
Teflon, or equivalent are tolerable in existing systems located in sprinklered areas if all of the following are
true:
a) The operating pressure is less than 100 psig (7 bar g).
b) The system is noncylic.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 24

FM Global Property Loss Prevention Data Sheets

c) The potential exposure created by a gasket failure is limited.


d) The joints are outside and either underground or aboveground with limited exposure.
2.2.1.3.5 Join nonferrous metallic piping with flanged, brazed or flared connections. Brazing alloys should
have a minimum melting point of 1000F (535C). Do not use fillet-brazed joints or soldered joints.
2.2.1.3.6 Avoid threaded joints. New systems containing liquids with flash points of 200F (93C) and above
or existing systems (any flash point) with threaded joints can be considered tolerable when all of the following
are true:
a) The exposure created by leakage is minimal.
b) The piping system has an operating pressure less than 100 psig (7 bar g).
c) The piping system has limited leakage (constant repairs for leakage would indicate that a change in
joint type is needed).
d) Operating conditions are not cyclic.
e) Operating conditions do not create corrosion problems.
If the piping creates a significant exposure, severe cyclic conditions exist or corrosion problems exist, replace
the threaded connections with butt welded joints. Piping systems with high pressures (greater than 100 psig
[7 bar g]) or leakage problems should have the threaded joints seal welded. A combination of leakage
problems and high system pressures in a piping system should have threaded joints replaced with butt welded
joints.
2.2.2 Equipment and Processes
2.2.2.1 Flexibility and Support of Piping Systems
2.2.2.1.1 Design flammable and combustible liquid piping systems to provide adequate expansion and
flexibility to handle thermal expansion and contraction due to internal operating conditions (e.g., system
temperature changes) and external conditions (e.g., environmental effects) or other movements (e.g., fluid
hammer effects, settlement, vibration). Provide system flexibility to prevent: a) failure of piping or supports
from overstress or fatigue b) leakage at joints and c) creation of damaging stresses in piping, valves or other
connected equipment.
2.2.2.1.2 Evaluate piping system flexibility in accordance with ASME B31.3, Section 319. Provide system
flexibility by the use of pipe bends, welding elbows, pipe hangers, flexible hose connectors and other flexible
designs. Do not use expansion slip joints.
2.2.2.1.3 Provide pipe hangers to support and secure piping systems in accordance with the rules listed in
Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA), or ASME B31.3, Section 321. Consider the
following when designing and installing hangers:
a) Design pipe hangers to support the full weight of the system including all live loads (e.g., content, snow),
dead loads (e.g., pipe, valves, insulation), and test loads (e.g., test liquid weight).
b) Design pipe hangers for expected dynamic effects (e.g., hydraulic shock, wind loads, vibration) and
potential thermal expansion and contraction loads.
c) Arrange pipe hangers to prevent excessive vibration and strain on connecting equipment.
d) Limit horizontal pipe spans to reduce stress on pipe walls. Long horizontal spans should be supported
from cables or trusses.
e) Arrange hangers to prevent stress on joints and pipe sagging.
f) Hangers and anchoring devices should consist of high melting point, noncombustible materials, or be
insulated against possible exposure fires.
g) Follow closely manufacturers recommendations for supporting specialty piping.
2.2.2.1.4 Provide flexible hose connectors in piping systems to prevent dangerous stresses due to vibration,
settling, or thermal change. Provide the following material and installation features to ensure adequate hose
strength/durability and protection against physical damage:

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 25

a) Flexible hose should be constructed of high strength, noncombustible material that is resistant to
decomposition or melting when exposed to an exposure fire, and compatible with the liquid in use. All-metal
construction consisting of materials such as steel, Monel, stainless steel, brass, bronze, or an equivalent
material are preferred. Reinforced rubber hose with a synthetic liner and a metal-braid covering is
acceptable when needed to meet operational requirements. Do not use soft rubber, plastic, or other
unreinforced or unprotected combustible tubing.
b) The hose should be bent only in one plane without subjecting it to tensile, torsional, or excessive
bending stresses.
c) Protect the hose against mechanical damage.
d) Hose joints should comply with all rigid pipe joint recommendations (Section 2.2.1.3).
e) Hose and fittings should have a bursting strength that is greater than the maximum expected working
pressure with a safety factor of at least 4.
2.2.2.1.5 Arrange piping systems located in areas exposed by earthquakes in accordance with Data Sheet
1-2, Earthquakes.
2.2.2.2 Heating and Insulating Piping Systems
2.2.2.2.1 Arrange pipe heating systems to prevent: 1) local overheating, 2) the creation of an ignition source
for the pipe content or surrounding combustibles, and 3) overpressurization of piping sections that may be
isolated between valves. Operate heating systems at the minimum temperature needed to meet process
requirements. Heated pipe sections that may be isolated between valves while the heating system is active
should have a pressure relief device provided to prevent overpressurization. Liquid trapped in an isolated
section of heated pipe can produce significant pressures due to liquid expansion and/or vapor liberation.
Relief valves should be piped to a location that does not create an exposure to important plant facilities or
buildings.
2.2.2.2.2 Provide pipe heating by one of the following methods or an equivalent: a) steam-tracing, b) electric
heating cable, or c) impedance heating (i.e., pass a low voltage alternating current through the pipe). Do
not use open flames. Data Sheet 9-18/17-18, Prevention of Freeze-ups, should be used to develop freeze-up
prevention plans.
2.2.2.2.3 Steam-tracing should be arranged as follows:
a) Provide the minimum steam pressure needed to make the liquid fluid.
b) Provide a steam regulator.
c) Install a pressure relief valve downstream of the regulator. Set the relief valve to open at a pressure
just above the regulator.
d) Enclose the pipe and steam-tracing in insulation.
2.2.2.2.4 An electric heating cable system should be arranged as follows:
a) Heating cable should be fastened along the pipe or spirally wound around the pipe. Enclose the pipe
and cable in insulation.
b) Heating cable should be continuous (no splices). Electrical connections should be visible for inspection.
c) Provide individual thermostat controls for each cable section. Fuses or fused disconnect switches of
as low a rating as practical should also be provided.
d) Electrical equipment (thermostats, plug assemblies, and switches) exposed to various weather
conditions should be enclosed in weatherproof housings. All sparking equipment (i.e., equipment with
make-and-break contacts) should be well separated from the pipeline and locations requiring hazardous
area rated electrical equipment.
e) All electric heating cable equipment should be Approved.
2.2.2.2.5 An impedance heating system should be arranged as follows:

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 26

FM Global Property Loss Prevention Data Sheets

a) Systems should be installed and tested as complete units by the manufacturer or other qualified
installer. The installation should conform to the requirements of the authority having jurisdiction and Article
427Fixed Electric Heating Equipment For Pipelines and Vessels, of the National Electric Code (1990
or current edition).
b) Piping sections that are heated should be insulated from unheated sections with electrically
nonconductive fittings to confine the current paths and to eliminate any current leakage at hazardous
locations.
c) Provide an automatic high-temperature-limit cutoff switch in each circuit of each system to prevent
overheating of liquid in event of failure of the operating temperature control thermostat.
d) Enclose all parts of the piping and fittings in electrical and thermal insulating material to prevent
accidental grounding of the system. Provide a ground fault interrupt (GFI) device for the power supply
of all impedance heating systems.
e) Locate all sparking equipment (e.g., switches, transformers, contacts) well away from the pipeline and
areas requiring electrical equipment rated for hazardous locations.
f) Test the heating system periodically to ensure its continued proper operation. All maintenance on the
system should be conducted by trained employees or contractors.
2.2.2.2.6 Insulation provided on the piping system should be noncombustible. Provide nonabsorbent
insulation (e.g., closed cell cellular glass) near flanged fittings or other potential leakage points (e.g., valves,
pumps). Any type of insulation (e.g., calcium silicate, glass fiber batts, mineral wool, etc.) is acceptable over
welded pipe.
2.2.2.3 Piping System Control Valves and Safety/Emergency Shutoff Valves
2.2.2.3.1 Flammable and combustible liquid piping systems should be provided with adequate valving to
ensure proper system control, regulation, isolation, and ability to shut down all fluid flow in the event of a
fire.
2.2.2.3.2 Select control valves and safety/emergency shutoff valves using the following criteria:
a) The valve should be compatible with the liquid in use (including the packing and lubricants).
b) Valve bodies should be cast steel construction. Bronze is acceptable for valves 2 in. (50 mm) or smaller
installed in sprinklered areas. Use stainless steel, Monel, lined-steel, or an equivalent when process
conditions require the use of special materials. Cast iron bodies and yokes are not acceptable.
c) Rate the valve for the maximum expected system pressures and temperatures.
2.2.2.3.3 Consider the following for the selection and arrangement of process control valves:
a) Valve should provide positive indication of its status (i.e., open or closed, direction of flow).
b) Valves may be either manually operated at point of use or remotely operated depending on complexity
of the system. Remotely operated valves should fail in a safe position.
c) Arrange valves to ensure adequate control of liquid direction and flow rate. The valve arrangement
should also minimize the potential for improper system operation (e.g., allowing liquid flow to the wrong
tank, permitting too high a liquid flow rate, etc.). Proper valve operation can be accomplished through the
use of check lists for manual system operation and through process control systems for remote operation.
Thorough employee training is needed for either approach.
d) Arrange control valves to isolate important equipment to permit maintenance operations or
replacement.
e) Control valves that may be exposed to severe fire conditions (e.g., valves located in a flammable liquid
room) where loss of their function could significantly increase the exposure (e.g., valve controlling
flammable liquid flow from the bottom of a tank where valve failure would release the tank contents) should
be a Approved firesafe shutoff valve.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 27

2.2.2.3.4 Safety/emergency shutoff valves should be either diaphragm, solenoid, or fusible-element (weight
or spring operated) type. Positive displacement pumps may also be used as a safety/emergency shutoff.
The valves should be Approved. Valves that may be exposed to a flammable/combustible liquid fire should
be Approved fire safe shutoff valves.
2.2.2.3.5 Arrange safety/emergency shutoff valves to permit complete shutdown of liquid flow during a fire
and to limit the quantity of liquid released in the event of accidental escape. In general this can be
accomplished by isolating the liquid supply and shutting off liquid at the various points of use. The actual
number and location of safety/emergency shutoff valves will vary depending on the piping system size,
complexity and potential exposure created by a release. All piping systems containing flammable/combustible
liquids should at least have safety/emergency shutoff valves in the following locations:
a) On discharge lines of interior or exterior tanks (aboveground or underground), arranged for transfer
by gravity, centrifugal pump, inert gas pressure, or other means that provide continuous pressure on the
system.
b) On bottom-discharge lines of exterior aboveground tanks feeding a positive displacement pump when
multiple tanks are located in the same area (e.g., two or more tanks in a diked area or a single tank in
a diked area that is not accessible during a fire) to permit supply shutdown in the event of a leak at the
pump. A single exterior tank (e.g., single tank in a diked area that is accessible) feeding a positive
displacement pump may have a manually operated valve on the bottom-discharge line.
c) On bottom-discharge lines of interior tanks feeding positive displacement pumps to permit supply
shutdown in the event of a leak at the pump.
d) At points of use such as dispensing operations or delivery lines to equipment. Valves may be located
on each feed pipe to a piece of equipment/dispensing operation or on the supply pipe to a manifold feeding
equipment/dispensing operation. A single valve located at the entrance point to a building or cutoff room
is also acceptable.
2.2.2.3.6 Safety/emergency shutoff valves or positive displacement pumps should be arranged for automatic
and manual operation. In locations that are constantly attended and where leakage will be quickly discovered,
manual operation is acceptable. Arrange both automatic and manual valve operation to shut down all
flammable/combustible liquid flow in and to the area affected (i.e., shutdown valves at supply tank and at
points of use).
2.2.2.3.7 Automatic operation of safety/emergency shutoff valves and/or positive displacement pumps should
be accomplished by one of the following methods:
a) Thermal actuation by use of heat detectors (e.g., HADs) located above the points of use (including
potential leak points, such as pumps, that create a significant exposure), fusible link operated valves, or
use of thermoplastic tubing for air supply to a pneumatic valve (loss of air supply will cause valve to close,
thermoplastic tubing will melt when exposed to a fire). Fusible link operated valve placement should ensure
it will be exposed to a fire caused by a flammable/combustible liquid release. If the valves placement
limits its exposure to a potential fire, the valve should either be arranged to ensure its operation (e.g., in
addition to link at valve, provide a second link over expected leak points with a cable attached to the valve
handle which is arranged to close when the cable releases) or be replaced with a valve that can be remotely
operated.
b) Actuation by operation of a fire protection system such as automatic sprinklers and special protection
systems (water spray, gaseous extinguishing system, etc.). Safety/emergency shutoff valves may be tied
into pressure switches, waterflow alarms, or fire detection systems. Arrangements should be made to
permit protection system alarm testing without unwanted production shutdown.
c) Release of a dead-man type control or self-closing valve. These types of controls require constant
attendance by the operator and will close automatically when the operator leaves. Provide self-closing
valves at dispensing operations upstream of any flexible hose.
d) Actuation by abnormal system conditions such as high/low pressure and excess flow. Use this
arrangement to reduce a flammable/combustible liquid release before ignition when the expected fire or
explosion exposure is excessive. Provide this type of actuation system in addition to a method listed
above (ac).

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 28

FM Global Property Loss Prevention Data Sheets

2.2.2.3.8 Manual operation of safety/emergency shutoff valves and/or positive displacement pumps should
be accomplished by providing one or more stop buttons or switches located within the flammable/combustible
liquid operation area (arranged for easy access by the operators and at points of egress from the building
or structure) and at accessible remote locations (e.g., control room, security station, etc.).
2.2.2.3.9 Provide check valves in piping arranged to feed tanks, receivers, or other vessels when: a) the
liquid flow is in one direction only and b) the vessel can supply a leak in the feed pipe by reverse flow. Install
the check valve as close to the vessel as possible. Check valves used on systems with materials that may
impair their proper operation (e.g., paint, printing ink) should be physically checked regularly.
2.2.2.3.10 Provide hydraulic accumulators or safety relief valves on pipelines that can be valved off with
liquid trapped between valves to prevent damage or overpressure from thermal expansion of the liquid. Pipe
the relief valve discharge to a properly arranged collection point.
2.2.3 Operation and Maintenance
2.2.3.1 Piping systems should be inspected and tested in accordance with ASME B31.3, Chapter VI.
Inspections should include all pipe joints (welded and flanged) and pipe supports. Conduct all testing before
painting, insulating, or burying of the pipe system.
2.2.3.2 Conduct pressure testing on all piping systems before introduction of flammable/combustible liquids.
Hydrostatic testing should be conducted, using water as a test liquid, for systems that will not be adversely
affected by water and with design pressures greater than 1 psig (0.07 bar g). Systems that are incompatible
with water or that have a design pressure less than 1 psig (0.07 bar g) should be pneumatically tested using
compressed air or inert gas (generally, pneumatic testing should be avoided when possible due to the high
release energy potential created by compressed gas).
2.2.3.3 The following should be provided to conduct a hydrostatic leak test on the piping system:
a) Vent the piping to permit removal of air within the system.
b) Relief valves, rupture disks, pumps, vessels of appreciable volume, and other portions of the system
rated below the test pressure should be blanked off or removed.
c) Reinforce piping supports if the test liquid is heavier than the liquid the system was designed to contain.
d) Pressurize the test liquid to 1.5 times the systems design pressure. Consider normal operating
temperatures when picking a test pressure.
e) Hold the test pressure for at least 30 minutes.
f) While pressurized, the system should be visually inspected for leaks.
g) All leaks should be repaired and the system retested until the test pressure can be held for the stated
time period.
2.2.3.4 Provide the following to conduct a pneumatic leak test on the piping system. Conduct pneumatic
tests with caution due to the high release energy potential present in compressed gases.
a) Relief valves, rupture disks, pumps, tanks, and other portions of the piping system rated below the
test pressure should be blanked off or removed.
b) A pressure relief device set for the test pressure plus the lesser of 50 psig (3 bar g) or 10% of test
pressure should be provided on the piping system.
c) Provide a test pressure of 110% of the design pressure or a minimum of 3 psig (0.2 bar g). The system
should be raised to the test pressure in small increments, to locate large leaks at low pressures.
d) Hold the test pressure for 30 minutes.
e) After the test period, reduce the pressure to the design pressure and inspect for leaks using a solution
of soap and water.
f) All leaks should be repaired and the system retested until the test pressure can be held for the stated
time period.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 29

2.3 Flammable and Combustible Liquid Transfer Systems


2.3.1 Equipment and Processes
2.3.1.1 Transfer by Pumping
2.3.1.1.1 Arrange pumping systems to pressurize the piping system only when there is a demand for liquid
at the point of use. Avoid piping systems that are pressurized when not in use.
2.3.1.1.2 Arrange pumps to shut down when safety/emergency shutoff valves are actuated.
2.3.1.1.3 Arrange pumping systems to provide the minimum pressure required for system operation.
2.3.1.1.4 Use a positive displacement pump when possible to permit complete shutoff of liquid flow. A
centrifugal pump is acceptable but can only be arranged to shut off pumping. Liquid flow may continue by
siphoning or gravity flow.
2.3.1.1.5 Consider the following factors when choosing pump construction features:
a) Pumps should be cast steel construction. The pump, packing, and trim should be compatible with the
liquid being handled.
b) Studs used to attach packing glands to pumps should have the nuts on the outside ends to indicate
the amount of thread engaged. Avoid cap screws.
c) The pump casing, impeller, and other moving parts should be constructed of nonsparking materials if
the pump is to operate dry at frequent intervals.
d) Provide pumps with high integrity seals (dual seals) or use seal-less type pumps when the exposure
created by a leak at the pump is significant or the frequency of leakage is high.
2.3.1.1.6 Install a pressure relief valve downstream of positive displacement pumps. It should have adequate
capacity to prevent excessive pressure build-up in the system. Pipe the relief valve discharge back to the
supply source or to the suction side of the pump. Systems containing liquids with a closed-cup flash point of
0F (-18C) or less should have relief valves discharge back to the supply source to prevent possible
overheating due to the churning action of the pump.
2.3.1.1.7 Arrange submerged or vertical-shaft centrifugal pumps to prevent dry operation of rotating parts
in the vapor space of a tank. Using the pumped liquid to cool the pump and bearings is acceptable.
2.3.1.1.8 Pumps should be located as follows (listed in order of preference):
a) Outdoor locations.
b) Noncombustible pump house.
c) Cutoff room in a main building.
Pumps located near outdoor storage tanks should be placed outside of containment dikes to limit the exposure
to the tank from the pump.
2.3.1.1.9 Pumps located on open pads or in pump houses, without water spray protection should be spaced
to limit exposure to important buildings as follows:
a) High pressure (approx. >100 psig [7 bar g]) or high flow rate (approx. >100 gpm [23 m3/h]) pumps
should be spaced in accordance with Data Sheet 1-20, Protection Against Exterior Fire Exposure, (using
Exposure B in Tables 2 through 7).
b) Low pressure (approx. <100 psig [7 bar g]) or low flow rate (approx. <100 gpm [23 m3/h]) pumps should
be spaced in accordance with Data Sheet 1-20 (using Exposure C in Tables 2 through 7).
2.3.1.1.10 Pumps located on open pads protected with a water spray system should be spaced to limit
exposure to important buildings as follows:
a) High pressure or high flow rate pumps should be 50 ft (15 m) away from a building. Within 50 ft (15 m)
the exposed wall should be at least one hour fire rated.
b) Low pressure or low flow rate pumps should be 25 ft (8 m) away from a building. Within 25 ft (8 m)
the exposed wall should be at least one hour fire rated.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 30

FM Global Property Loss Prevention Data Sheets

2.3.1.1.11 Pumps located in pump houses protected with a water spray system should be spaced to limit
the exposure to important buildings using Table 1, Construction for Flammable or Combustible Liquid
Occupancies, (for high pressure or high flow rate pumps use the >1500 gal [6000 l] section; for low pressure
or low flow rate pumps use the <1500 gal [6000 l] section).
2.3.1.1.12 Protect pumps located in pump houses or cutoff rooms in accordance with Sections 2.1.1 (Location
and Construction), 2.1.3.1 (Ventilation), 2.1.4 (Ignition Source Control), 2.1.5 (Operations and Maintenance),
2.1.6 (Training), 2.1.7 (Human Element), and 2.1.8 (Protection). Evaluate pump rooms or pump houses for
a room explosion hazard based on the material being pumped.
2.3.1.2 Gravity Transfer
2.3.1.2.1 Use gravity transfer operations for flammable and combustible liquid transfer when other methods
are not compatible with the liquids in use (e.g., some volatile liquids may cause vapor lock when pumped)
or for small systems (limited exposure).
2.3.1.2.2 Arrange gravity transfer operations to permit isolation of the supply in the event of a leak or fire.
Gravity transfer does not allow easy fluid flow control since the driving force is gravity, rather than a pump.
2.3.1.2.3 Use safety/emergency shutoff valves to isolate the liquid supply. Locate the valves as close to the
source as possible.
2.3.1.3 Inert-Gas Transfer
2.3.1.3.1 Gas transfer systems should use inert gas (e.g., nitrogen, carbon dioxide) to avoid the potential
for more violent vapor-air explosions and increased flammable liquid explosive limits that would occur with
the use of air. Do not use air.
2.3.1.3.2 Tanks for inert gas transfer systems should be constructed, installed, and tested in accordance
with ASME or other recognized codes for unfired pressure vessels.
2.3.1.3.3 The gas pressure should be the minimum needed to force the liquid through the transfer system
at a rate to meet the operating demands.
2.3.1.3.4 Provide the following minimum equipment on an inert gas transfer system (Fig. 8):
a) Provide an accessible manual shutoff valve on the gas supply line.
b) Provide a pressure regulator in the gas supply line set at the minimum needed pressure.
c) Provide a check valve on the gas supply line and the tank fill line to prevent the backflow of liquid.
d) A two-way, three port power operated directional control valve (e.g., solenoid valve; energized valve
permits gas flow to pressurize tank, de-energized valve permits release of tank pressure to vent) or
equivalent should be provided on the gas supply line downstream of the check valve.
e) A pressure relief valve set at a slightly higher pressure than the regulator should be provided
downstream of the regulator or on the tank.
f) Provide the process supply line with a safety/emergency shutoff valve.
g) Provide the tank fill line with a power operated control valve (e.g., solenoid, motor, air operated).
h) Provide a liquid level control on the tank to prevent overflow.
i) Vent lines for the storage tank (pressure relief line, directional valve vent line) should be provided with
flame arresters for liquids with a flash point below 100F (38C).

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 31

Fig. 8. Compressed inert-gas transfer method.

2.3.1.3.5 The inert gas transfer system should be interlocked to operate as follows:
a) During normal operation the safety/emergency shutoff valve should be open, the fill line control valve
should be shut, and the directional valve on the gas supply line should be arranged to allow gas flow
into the storage tank.
b) During filling operations the safety/emergency shutoff valve should be closed, the fill line control valve
should be open, and the directional valve on the gas supply line should be arranged to vent the tank
pressure.
c) During fire or leakage conditions the safety/emergency shutoff valve should be closed, the fill line control
valve should be closed, and the directional valve on the gas supply line should be arranged to vent the
tank pressure.
Arrange the inert gas transfer system to prevent valve operation before confirmation of proper valve position
(e.g., interlock valves on large systems electrically or provide clear procedures for manual valve operation
on small systems). Arrange the control valves to operate automatically (i.e., interlock with safety/emergency
shutoff valve) in the event of a fire or leakage.
2.3.1.4 Hydraulic Transfer
2.3.1.4.1 Liquids that are not miscible in water and present hazards that may not be controlled with other
liquid transfer arrangements should be hydraulically transferred (e.g., carbon disulfide, which has a very low
flash point and ignition temperature). Liquids may be either heavier or lighter than water.
2.3.1.4.2 Tanks for hydraulic transfer systems should be constructed, installed, and tested in accordance
with ASME or other recognized code for unfired pressure vessels.
2.3.1.4.3 Use a double tank arrangement (water tank and flammable liquid tank) to permit recovery and re-use
of the water. A single tank arrangement is acceptable when other water recovery equipment is available (e.g.,
water treatment plant). (Fig. 9)
2.3.1.4.4 Arrange the hydraulic transfer system to operate on demand instead of continuous operation.
2.3.1.4.5 Supply the following minimum equipment for a double tank hydraulic transfer system (Fig. 9):
a) Provide a positive displacement pump to deliver water to the flammable/combustible liquid storage tank.
Place a foot valve on the suction supply line for the pump.
b) Provide a check valve on the water delivery line and the flammable/combustible liquid tank fill line.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 32

FM Global Property Loss Prevention Data Sheets

c) A pressure relief valve set just above the system operating pressure should be provided downstream
of the pump or on the tank. The pressure relief valve should be piped back to the water tank.
d) A power operated control valve (e.g., solenoid, motor, air operated) should be provided on the process
supply line and the flammable/combustible liquid tank fill line.
e) Provide the water storage tank with a vent line. The vent line should be supplied with a flame arrester
for liquids with a flash point below 100F (38C).
f) A second water line with a control valve should be provided between the two tanks to permit water to
return to the storage tank when the flammable/combustible liquid tank is being filled.
g) Provide a liquid level control on the flammable/combustible liquid storage tank to prevent overflow.
2.3.1.4.6 Supply the following minimum equipment for a single tank hydraulic transfer system (Fig. 9):
a) Provide an accessible manual control valve on the water supply line.
b) Provide a pressure regulator on the water supply line.
c) Provide a check valve on the tank fill line and the water delivery line (upstream of the two way valve).
d) Provide a two-way, three port power operated valve on the water supply line (valve permits water
delivery to tank or water removal from tank).
e) A pressure relief valve set just above the operating pressure should be provided downstream of the
regulator or on the tank.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 33

Fig. 9. Hydraulic transfer method.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 34

FM Global Property Loss Prevention Data Sheets

f) Provide a power operated control valve on the fill line and the process supply line.
g) Provide a liquid level control on the tank to prevent overflow.
2.3.1.4.7 The double and single tank hydraulic transfer systems should be interlocked to operate as follows:
a) During normal operation, the control valve on the process supply line is open and the control valve
on the tank fill line is closed. For the single tank system, the two-way valve is arranged to permit water
flow when needed. For the double tank system, the valve on the water return line is closed and the pump
is arranged to operate when flow is needed.
b) During flammable/combustible liquid tank filling operations, the control valve on the process supply
line is closed and the control valve on the fill line is open. For the single tank system, the two-way valve
on the water supply line allows water flow out of the tank. For the double tank system, the pump is off
and the control valve on the water return line is open.
c) During a fire or leak, the control valves on the process supply line and the fill line are closed. For the
single tank system, the two-way valve is in the same position as described in part (b). For the double
tank system, the pump is off.
Arrange the hydraulic transfer system to prevent valve or pump operation before confirmation of proper valve
position (e.g., interlock the control valves and the pump). The valves and pump should operate automatically
in the event of leakage or fire (i.e., interlock with safety/emergency shutoff valve at the point of liquid use).
2.3.1.4.8 Arrange hydraulic transfer systems to prevent water flow into the process supply line. Double tank
systems should use the same size tanks (limits water quantity). Single tank systems should use float operated
control valves on the discharge lines (float will close when tank is full of water).
2.3.1.4.9 For flammable or combustible liquids that are lighter than water, the water supply line should be
extended to the bottom of the liquid supply tank and the discharge and fill lines should be at the top of the
liquid supply tank. For flammable or combustible liquids that are heavier than water, the water supply line
should be at the top of the supply tank and the discharge and fill lines should extend to the bottom of the
supply tank.
2.3.1.5 Loading and Unloading Stations
2.3.1.5.1 Rail cars and trucks used for flammable and combustible liquids should meet Department of
Transportation (DOT) or equivalent specifications.
2.3.1.5.2 Separate loading and unloading stations from important buildings and facilities to limit the potential
exposure from a liquid spill and fire. When possible provide at least 50 ft (15 m) separation or the minimum
distances listed in Table 3.
Table 3. Space Separation for Flammable/Combustible Liquid Loading/Unloading Stations.
Space Separation
Exposed Wall Construction
Combustible or With Unprotected
Openings
Noncombustible, Blank or With
Protected Openings

Flash Point
100oF (38oC)
and Below

Flash Point
Greater Than
100oF (38oC)

50 ft (15 m)

25 ft (8 m)

25 ft (8 m)

15 ft (5 m)

2.3.1.5.3 An automatic water spray special protection system, designed in accordance with Data Sheet 4-1N,
Water Spray Fixed Systems (NFPA), should be provided for loading/unloading stations when the station
exposes high value plant facilities (i.e., inadequate separation) or if the station is vital to plant production.
2.3.1.5.4 Supply loading and unloading stations with either curbing, drainage, grading, or a combination to
direct a potential liquid spill to a collection location that is accessible to fire fighting and liquid recovery
operations, but does not expose important buildings or facilities.
2.3.1.5.5 Supply loading and unloading stations with adequate control and safety/emergency shutoff valves
to permit control of normal operations as well as isolation of the rail car or truck and plant piping systems

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 35

in the event of a leak or fire. Provide safety/emergency shutoff valves on all bottom discharge lines of rail
cars or trucks and on the plant side of flexible piping. Arrange the valves for automatic operation in the event
of a fire as well as remote manual operation and protection from physical damage (e.g., internal tank valve
with a shear fitting downstream).
2.3.1.5.6 Use top loading and unloading of rail cars and trucks when possible. Bottom loading and unloading
is tolerable when:
a) Space separation is provided as recommended.
b) A liquid spill will not expose important buildings or facilities.
c) Safety/emergency shutoff valves are provided on discharge lines of the rail car or truck.
2.3.1.5.7 Use positive displacement pumps for top unloading operations to prevent siphoning. Place the pump
on a noncombustible platform above the liquid level and arrange it to shut down automatically or manually
(from a remote location) in the event of a fire or leak.
2.3.1.5.8 Provide overflow protection for the rail car/truck or the storage tank. Arrange liquid level controls
to automatically shut down filling operations when the tank is full. This control system may be used alone or
in conjunction with meters, scales or manual observation.
2.3.1.5.9 Use steel pipe and swing joints or metal type flexible hose when needed for connections to rail
cars, tank trucks or barges. Metal reinforced rubber hose is acceptable if required by process conditions and
if resistant to the materials being handled and rated for system pressure.
2.3.1.5.10 Provide the following at tank truck loading and unloading stations:
a) Conduct all loading and unloading operations on level surfaces.
b) Provide bonding and grounding in accordance with Data Sheet 5-8, Static Electricity. Connect bonding
wires before opening tank domes.
c) Set the trucks hand brake and block the wheels before connecting to fixed piping.
d) Post warning signs indicating the tank truck is connected to the piping system.
2.3.1.5.11 Provide the following at rail car loading and unloading stations (Fig. 10):
a) Conduct all loading and unloading operations on level tracks in a private siding on plant property or
equivalent location with permanent piping to storage tanks.
b) Provide stray current protection by bonding the fill pipe (or pipes) to at least one rail and to the rack
structure (if metallic). In areas with excessive stray currents, provide all pipes entering the rack area with
insulating flanges to electrically isolate the rack piping from the pipelines (Fig. 10).
c) Accurately align rail cars with loading/unloading connection points to avoid excessive stress on the
connections.
d) Protect rail cars against other moving railcars by providing derailers at least one car length away at
the open end of the siding. The use of existing railroad switches is acceptable if they can be locked in the
closed position.
e) Set the brakes and block the wheels before connecting to the fixed piping system.
f) Warning signs indicating the rail car is connected to the fixed piping system should be posted until
the rail car is disconnected.
2.3.1.5.12 Vents on rail cars and trucks should be provided with flame arresters for liquids with flash points
below 100F (38C).
2.3.1.5.13 Protect loading and unloading stations against uncontrolled ignition sources in accordance with
Section 2.1.4.
2.3.1.5.14 Label all piping clearly to avoid intermixing materials.
2.3.1.5.15 All loading and unloading operations should be constantly attended.
2.3.1.5.16 Liquids that require heating for transfer purposes should be delivered in rail cars or trucks that
are equipped with heating coils. Use the minimum steam pressure necessary to bring the liquid to a fluid state.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 36

FM Global Property Loss Prevention Data Sheets

Fig. 10. Railcar loading/unloading station-bonding arrangement to prevent sparks due to stray currents.

Control the steam with a regulator set to the minimum pressure needed. Install a pressure relief valve
downstream of the regulator set to a slightly higher pressure.
3.0 SUPPORT FOR RECOMMENDATIONS
3.1 Application of Recommendations
3.1.1 General
A flammable or combustible liquid is defined as any material that in its normal state is a liquid and will burn.
The ability of a liquid to burn is generally tied to the existence of a flash point (closed cup or open cup).
However, a flash point alone will not always indicate if a liquid is capable of sustaining combustion. Some
liquid solutions (e.g., 15% ethyl alcohol in water) may have a closed cup flash point but do not have a fire point
(i.e., the liquid solution cannot produce enough flammable vapor to permit sustained combustionthe vapor
mixture produced has a very low heat of combustion and slow heat release rate).
The recommendations in this data sheet (general, piping system, transfer system) are not intended for liquids
or liquid solutions that do not have a fire point (Note: These liquid solutions may be labeled as a flammable
or combustible liquid in accordance with state or federal regulations). Materials that are unstable or very
reactive may not be adequately protected by the recommendations in this data sheet.
Flammable liquids are easily ignited (vapors can be present at room temperature) and difficult to extinguish.
Combustible liquids require heating for ignition and are easier to extinguish by cooling the liquid below its
fire point with sprinkler discharge. Flammable and combustible liquids have a high heat of combustion, and

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 37

once ignited will produce a high heat release rate (i.e., fires will produce high temperatures in a short period
of time). They are fluid and can spread rapidly when a leak or rupture involves a tank or piping system.
Vapors from flammable and combustible liquids can form explosive mixtures with air. Some liquids are
unstable or very reactive (e.g., burn when exposed to air without an ignition source, susceptible to
spontaneous heating, react violently with other materials including water). These characteristics combine to
create a significant fire and/or explosion hazard.
The actual hazard associated with a particular process containing or using flammable or combustible liquids,
in addition to the characteristics of the particular liquid, also depends on conditions such as:
a) Quantity of liquid.
b) The confinement of the liquid (open or closed containers, piping systems).
c) The potential for leakage or overflow.
d) Separation from important structures or buildings.
e) Control of ignition sources.
f) Available fire protection.
Each process or occupancy should be evaluated separately to determine the actual exposure created by
the flammable or combustible liquid.
3.1.2 Fire Hazard
A flammable or combustible liquid will always create a fire hazard. However, the exposure created by the
hazard is considered limited for occupancies with all the following qualities:
a) Quantities of flammable or combustible liquids less than approximately 70 gal (265 l) in one fire area.
b) A low susceptibility to water damage.
c) No vapor-air explosion hazard.
Recommendations covering location, construction and mechanical ventilation for flammable and combustible
liquid processes generally do not need to be applied to occupancies that meet the above conditions.
Automatic sprinkler protection, proper equipment, proper handling procedures, and control of ignition sources
should be provided in any area handling flammable and combustible liquids regardless of quantity.
3.1.3 Piping Systems/Transfer Systems
Piping system recommendations should be applied to all piping systems containing flammable or combustible
liquids based on the potential exposure created by the system. For additional recommendations concerning
cutting oils and hydraulic fluids refer to Data Sheet 7-37, Cutting Oils, and Data Sheet 7-98, Hydraulic Fluids,
respectively.
3.1.4 Room Explosion Hazard
The potential for a vapor-air explosion hazard exists in a room containing flammable or combustible liquids
when their release into the room will produce sufficient flammable vapor to create a vapor-air mixture above
the lower explosive limit. The ability of a liquid to produce enough vapor to create an explosion hazard
depends on many variables, such as the physical characteristics of the liquid (e.g., vapor pressure), the
operating temperature and pressure of the process containing the liquid, and the ventilation system
arrangement within the room.
Liquids with high vapor pressures at room temperature (i.e., low atmospheric boiling points) have a high
vaporization rate without heating, while liquids with lower vapor pressures require heating to produce similar
vaporization rates. The ventilation system must be arranged to sweep across the floor to prevent the
accumulation of flammable vapor-air mixtures. Improperly designed, high level ventilation may actually
facilitate the formation of a flammable vapor-air mixture within the room.
The severity of a vapor-air explosion within a room depends on several items, such as: 1) the materials
physical characteristics such as reactivity (Kg) and fundamental burning velocity, 2) the percent of the rooms
volume occupied by the vapor and 3) the vapors concentration. The largest pressure increase during an

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 38

FM Global Property Loss Prevention Data Sheets

explosion is normally produced by vapor-air mixtures, with concentrations just above stoichiometric. At
present, there is no methodology to quantify the relationship between explosion severity and either the fraction
of the rooms volume occupied by the vapor-air mixture, or the vapor concentration if other than worst case.
In general, explosions involving vapor-air mixtures occupying less than the full room volume or lean vapor-air
mixtures produce lower pressure increases than explosions involving full room volumes or vapor-air mixtures
of worst case concentrations.
At present, there is no simple method for predicting the potential for creating an explosion hazard or predicting
the severity of an explosion hazard. However, various materials and process conditions can be divided into
two general categories, those that may create a severe explosion hazard and those that may create a weak
explosion hazard. A severe explosion hazard exists if there is a potential for creating a large quantity of
flammable vapor in a relatively short time frame. A weak explosion hazard exists when there is a potential
for creating a limited quantity of flammable vapor due either to low vaporization rates or limited liquid
quantities.
Severe Explosion Hazards
The following materials and/or process conditions may produce a severe room explosion hazard in
occupancies where flammable/combustible liquids are handled/processed:
1. Flammable liquids with atmospheric boiling points below 100F (38C) (i.e., liquids with high vapor
pressuresClass 1A liquids).
2. Liquids with closed cup flash points up to 300F (149C) that are handled or can be heated, due to
improperly arranged heating system (e.g., electric heating system without a high temperature shutoff), to or
above their atmospheric boiling points.
3. A significant fraction (10% or more) of the rooms volume occupied by a single piece of equipment that
presents an equipment explosion hazard. This includes equipment that is not properly designed to vent or
contain an explosion, equipment designed to vent an explosion into the room or equipment without venting
that is provided with an inert gas system. Equipment that is adequately designed to vent an explosion to an
area outside the room or to contain an explosion does not create a room explosion hazard.
In either of the first two cases, there must be enough liquid/vapor released to fill a significant portion of the
rooms volume with a stoichiometric vapor-air mixture. Research indicates that this level be at least 10%
of the rooms volume. The size of a liquid/vapor release should be limited to a single credible event (i.e., either
base release amount on the largest container or a justifiable release scenario). Rooms containing these
materials or process conditions would need damage limiting construction designed in accordance with Data
Sheet 1-44, Damage-Limiting Construction, to prevent excessive damage to the building, equipment and
stock. If the potential liquid/vapor release amount cannot reach this limit, ignition of the vapor-air mixture will
likely produce a weak explosion as described in Weak Explosion Hazards.
The volume of a stoichiometric vapor-air mixture that can be produced by completely vaporizing one gallon
of flammable/combustible liquid, Vs (ft3/gal), can be calculated using the following equation:
English Units:
Vs (cu ft/gal) = 8.33 S.G.
0.075 V.D.
where: 8.33
0.075
S.G.
V.D.
Cst

100
Cst

is the weight of 1 gal of water (lb/gal)


is the weight of 1 cu ft of air (lb/cu ft)
is the specific gravity of the liquid (water=1)
is the vapor density of the liquid, (air=1)
is the liquids stoichiometric vapor concentration (vol. %)

To calculate the volume of a stoichiometric vapor-air mixture that can be produced from one liter of
flammable/combustible liquid, Vs (m3/l), multiply the answer to the above equation by 0.00748. (Note: this
conversion factor has the following units[gal/l] [m3/ft3].)
This calculation has been done for some common flammable liquids. The results are provided in Table 4. If
a liquid being evaluated is not in the table, the above equation should be used to determine how much vapor
will be created.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 39

Table 4. The volume of a stoichiometric vapor-air mixture that may be produced from either 1 gallon or 1 liter of some
common flammable liquids. (Note: these values are based on complete vaporization of the liquid.)
Material
Acetone
Benzene
Ethyl Acetate
Ethyl Alcohol
Ethyl Ether
Heptane
Isopropyl Alcohol
Methyl Alcohol
Methyl Butyl Ketone
Methyl Ethyl Ketone
Pentane
Toluene
Vinyl Acetate
Xylene

Cst (% by Volume)
5.0
2.7
4.0
7.1
3.4
1.9
4.5
12.0
2.4
3.7
2.6
2.3
4.5
2.0

Vs (cu ft/gal)
890
1325
835
785
880
1170
945
675
1060
965
1025
1405
745
1355

Vs (cu m/l)
6.7
9.9
6.3
5.9
6.6
8.8
7.1
5.1
7.9
7.2
7.7
10.5
5.6
10.1

Loss history has also shown that a severe room explosion hazard can be created with liquids having flash
points between 300F (149C) and 425F (218C) that are heated to their atmospheric boiling point and
pressurized. These materials have the potential for creating an aerosol mist that can explode. Data Sheet
7-99/12-19, Heat Transfer by Organic and Synthetic Fluids, provides further discussion about these types of
materials and mist explosions in general.
Weak Explosion Hazards
The following material properties and/or process conditions may produce a weak explosion hazard in
occupancies where flammable/combustible liquids are handled/processed:
1. Liquid with a closed-cup flash point of 20F (-7C) or less.
2. Liquid with a closed-cup flash point of 100F (38C) or less (Class 1B and 1C liquids) which is handled
at or can be heated to more than 60F (33C) above its flash point. Heat sources may include chemical
reactions or poorly controlled heating systems (e.g., electric heater without high temperature shutoff).
3. A small fraction (less than 10%) of the rooms volume occupied by a single piece of equipment that presents
an equipment explosion hazard. This includes equipment that is not properly designed to vent or contain
an explosion, equipment designed to vent an explosion into the room or equipment without venting that is
provided with an inert gas system. Equipment that is adequately designed to vent an explosion to an area
outside the room or to contain an explosion does not create a room explosion hazard.
While the above conditions should be expected to cause explosive vapor-air concentrations in the proximity
of the released liquid, they generally will produce vapor-air mixtures with most of the volume near the lean
limit of the explosive range. Only a small percentage (less than 10%) of the rooms volume may contain a
stoichiometric mixture. These conditions generally produce easily controlled pressure increases that may
not need damage limiting construction designed in accordance with Data Sheet 1-44, Damage-Limiting
Construction. However, fully enclosed rooms (i.e., no venting-windows or vent panels) and rooms with
load-bearing walls can still experience significant damage (i.e., wall collapse).
3.1.5 Equipment Explosion Hazard
The potential for a vapor-air explosion within a piece of equipment exists whenever the contained
flammable/combustible liquid is handled at or can be heated to a temperature above its closed-cup flash
point. The potential for a mist explosion within a piece of equipment exists whenever the contained flammable/
combustible liquid is present as an aerosol mist (e.g., spray washers used to clean metal parts). A mist may
be created in equipment whenever the liquid is sprayed depending on the type of spray nozzle and operating
pressure. The liquid does not have to be heated to form a mist. Depending on the operating temperature and
pressure, the material, and the nature of the operation, the hazard (vapor-air or mist explosion) can be
continuous or intermittent.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 40

FM Global Property Loss Prevention Data Sheets

Equipment containing liquids that can undergo violent chemical reactions should be evaluated using Data
Sheet 7-49/12-65, Emergency Venting of Vessels. Equipment protection against a vapor-air/mist explosion
hazard should always be considered since improperly designed or protected equipment will be significantly
damaged by an internal vapor-air explosion.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-0, Safeguards During Construction, Alteration and Demolition.
Data Sheet 1-2, Earthquakes.
Data Sheet 1-20, Protection Against Exterior Fire Exposure.
Data Sheet 1-44, Image-Limiting Construction.
Data Sheet 2-8N, Installation of Sprinkler Systems (NFPA).
Data Sheet 3-10, Installation/Maintenance of Private Fire Service Mains and their Appurtenances.
Data Sheet 4-1N, Fixed Water Spray Systems for Fire Protection.
Data Sheet 4-5, Portable Extinguishers.
Data Sheet 4-7N, Low Expansion Foam Systems.
Data Sheet 4-12, Foam-Water Sprinkler Systems.
Data Sheet 5-1, Electrical Equipment in Hazardous (Classified) Locations.
Data Sheet 5-8, Static Electricity.
Data Sheet 5-10, Protective Grounding for Electric Power Systems and Equipment.
Data Sheet 5-49, Gas and Vapor Detectors and Analysis Systems.
Data Sheet 6-9, Industrial Ovens and Dryers.
Data Sheet 7-9, Dip Tanks, Flow/Roll Coaters, and Oil Cookers.
Data Sheet 7-14, Fire & Explosion Protection for Flammable Liquid, Flammable Gas, & Liquefied Flammable
Gas Processing Equipment & Supporting Structures.
Data Sheet 7-17, Explosion Protection Systems.
Data Sheet 7-29, Flammable Liquid Storage in Portable Containers.
Data Sheet 7-37, Cutting Oils.
Data Sheet 7-39, Industrial Trucks.
Data Sheet 7-49, Emergency Venting of Vessels.
Data Sheet 7-59, Inerting and Purging of Tanks, Process Vessels, and Equipment.
Data Sheet 7-78, Industrial Exhaust Systems.
Data Sheet 7-83, Drainage Systems for Flammable Liquids.
Data Sheet 7-98, Hydraulic Fluids.
Data Sheet 7-99, Heat Transfer By Organic and Synthetic Fluids.
Data Sheet 9-0/17-0, Maintenance and Inspection.
Data Sheet 9-18/17-18, Prevention of Freeze-ups.
4.2 NFPA Standards
NFPA 30, Flammable and Combustible Liquids Code, 1996.
NFPA 68, Guide for Venting of Deflagrations, 1988.
National Electric Code, Article 427, Fixed Electric Heating Equipment for Pipelines and Vessels.
National Electric Code, Article 500.
4.3 Others
American Society of Mechanical Engineers (ASME) Standard B31.3-1990, Chemical Plant and Petroleum
Refinery Piping.
American Society of Mechanical Engineers (ASME) Standard B16.5, Pipe Flanges and Flanged Fittings.
ANSI A13.1, Scheme for Identifications of Piping Systems.
ANSI/ASME B16.25, Butt Welding Ends.
ANSI/ASME B16.5, Pipe Flanges and Flanged Fittings.
ASTM A193, Alloy Steel Bolting Materials for High Temperature Service.
ASTM A194, Carbon and Alloy Steel Nuts for Bolts for High Pressure and High Temperature Service.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 41

APPENDIX A GLOSSARY OF TERMS


Approved: references to Approved in this data sheet means the product and services have satisfied the
criteria for Factory Mutual Research Approval. Refer to the Approval Guide for a complete listing of products
and services that are Factory Mutual Research Approved.
Flammable Liquids: are defined as liquids having closed-cup flash points below 100F (38C) and vapor
pressures not exceeding 40 psia (3 bar a) at 100F (38C) (thus excluding liquefied petroleum gases, liquefied
natural gases and liquefied hydrogen). Flammable liquids are referred to as Class I liquids, and are
subdivided as follows:
Class IA liquidsflash points below 73F (23C) and boiling points below 100F (38C). Examples are
acetaldehyde, ethyl ether, ethyl chloride, isoprene, pentane and methyl formate. Class IA liquids are the
most hazardous from the fire protection standpoint due to their low boiling points and high volatility.
Class IB liquidsflash points below 73F (23C) and boiling points at or above 100F (38C). Examples
are acetone, carbon disulfide, benzene, cyclohexane, ethyl acetate, 100% ethyl alcohol, gasoline, heptane,
octane, toluene and methyl alcohol.
Class IC liquidsflash points at or above 73F (23C) and below 100F (38C). Examples are styrene,
methyl isobutyl ketone, isobutyl alcohol and turpentine.
Combustible Liquids: liquids having closed-cup flash points at or above 100F (38C). They are referred to
as either Class II or Class III liquids and are subdivided as follows:
Class II liquidsflash points at or above 100F (38C) and below 140F (60C). Examples include Nos. 1-3
fuel oils, kerosene, n-decane, hexyl alcohol, and stoddard solvent.
Class IIIA liquidsflash points at or above 140F (60C) and below 200F (93C). Examples include aniline,
benzaldehyde, butyl cellosolve, nitrobenzene and pine oil.
Class IIIB liquidsflash points at or above 200F (93C). Examples include animal oils; ethylene glycol;
glycerine; lubricating, quenching, and transformer oils; triethanolamine; benzyl alcohol; hydraulic fluids
and vegetable oils.
Flash Point: a liquids flash point is the minimum temperature at which sufficient vapor is liberated to form
a vapor-air mixture that will ignite and propagate a flame away from the ignition source (flash fire not
continuous combustion). Evaporation will take place below the flash point, but the quantity of vapor released
is not sufficient to produce an ignitable vapor-air mixture. A flash point can be determined by using either
a closed or open cup test apparatus. The closed cup test will produce lower flash points than open cup tests
because it provides greater vapor containment (i.e., increases vapor accumulation). The closed cup flash
point is used to classify liquids because it is conservative (i.e., produces lowest flash point for liquid) and it
represents the condition in which most liquids are handled (i.e., most liquids are contained in closed
containers or equipment).
Vapor Pressure: a liquids vapor pressure is a measure of the pressure created by its vapor at a specific
temperature. The vapor pressures for flammable or combustible liquids provide a basis for comparing the
volatility of the liquids at various temperatures (i.e., provides a measure of the tendency of the liquids to
vaporize). Flammable or combustible liquids with a high vapor pressure at room temperature are more
hazardous than liquids with lower vapor pressures because they will produce more flammable vapor without
heating. Vapor pressure data is often not available.
Boiling Point: a liquids boiling point is the temperature at which its vapor pressure is equal to the atmospheric
pressure on the liquid. The boiling point is measured at an atmospheric pressure of 14.7 psia (approximately
1 bar a). The boiling point of a flammable or combustible liquid permits the comparison of liquid volatility
without knowing the vapor pressures. Liquids with low boiling points are very volatile.
Fire Point: a liquids fire point is the lowest temperature at which a liquid in an open container will give off
enough vapor to ignite and continue to burn. Fire points are generally slightly higher than the open cup flash
point for a particular liquid. Liquids can have flash points without having fire points. A liquid without a fire
point will not burn (e.g., 15% ethanol-water solution: closed cup flash point 107F (42C), no fire point; 15%
acetone-water solution: closed cup flash point 49F (9C), no fire point).

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 42

FM Global Property Loss Prevention Data Sheets

Flammable (Explosive) Limits/Flammable (Explosive) Range: the terms flammable and explosive are used
interchangeably since unconfined vapors mixed in air will burn while confined vapors will produce an
explosion.
Flammable or combustible liquids do not burn, their vapors do. The flammable vapors produced by most
liquids require oxygen to burn. Combustion is an oxidation reaction between a fuel and an oxidizernot
always oxygen. Combustion will occur only when an adequate concentration of fuel (flammable vapor) and
an oxidizer are present. Combustion in air (approximately 21% oxygen) can take place over a range of vapor
concentrations (expressed in terms of percentage by volume of vapor in air). The minimum vapor
concentration in air that, when ignited, will propagate a flame is the lower flammable limit. The maximum
vapor concentration in air that when ignited will propagate a flame is the upper flammable or explosive limit.
The range of vapor concentrations between the lower and upper flammable limits is the flammable range.
The flammable range for a vapor can be altered by changes in oxygen concentration, pressure changes or
temperature changes. An increase in oxygen concentration or pressure will increase the upper flammable
limit and have a minimal effect on the lower limit. An increase in temperature will increase the upper limit and
reduce the lower limit. Overall, an increase in oxygen concentration, pressure or temperature will increase
the hazard created by a flammable or combustible liquid by increasing its vapors flammable range.
Vapor Density: is the weight of a volume of pure vapor or gas (with no air present) compared to the weight
of an equal volume of dry air at the same temperature and pressure. It is calculated as the ratio of the
molecular weight of the gas to the average molecular weight of air, 29. A vapor density figure less than one
indicates the vapor is lighter than air. A figure greater than one indicates the vapor is heavier than air.
Flammable and combustible liquids produce vapors that are heavier than air. The vapors will collect at floor
level and exhibit fluid properties (i.e., they will flow to low points and accumulate). Flammable vapor, if not
removed by ventilation, can flow to an ignition source and flash back to the vapor source.
Specific Gravity: the specific gravity of a substance is the ratio of the weight of the substance to the weight
of the same volume of another substance. The specific gravity for flammable and combustible liquids is
provided using water as a basis. Specific gravities less than one indicate the liquid will float on water while
specific gravities greater than one indicate the liquid will sink in water. This information permits a determination
of what effect water will have on a flammable or combustible liquid fire. Liquids heavier than water will sink
indicating water would extinguish a fire involving this liquid (cover liquid and smother fire). Liquids lighter than
water will float indicating the fire would not be extinguished but could be spread by water if adequate drainage
is not provided.
Water Soluble (Miscible) Flammable and Combustible Liquids: when water soluble (miscible) flammable or
combustible liquids are mixed with water a homogeneous solution is formed. The flash point, fire point, heat
of combustion, and heat release rate of the solution will be different from the pure flammable or combustible
liquid. The flash point and fire point of the solution will increase as the water concentration increases. At
a certain water concentration (varies for different flammable or combustible liquids) the fire point will no longer
exist and the solution will no longer present a fire hazard (e.g., 15% ethyl alcohol in water, 15% acetone
in water).
However, the solution will still produce a closed cup flash point creating the potential for confusion in deciding
the hazard presented by the liquid (e.g., 15% ethyl alcohol in water has a closed cup flash point of
approximately 107F [42C], 15% acetone in water has a closed cup flash point of approximately 44F [7C]).
The heat of combustion and heat release rate for a solution will decrease as the water concentration
increases showing a reduction in the overall fire hazard (i.e., a fire involving the solution will produce less
heat at a slower rate than pure flammable or combustible liquid).
The above factors indicate that fires involving water soluble flammable or combustible liquids can be
extinguished by diluting the liquid with water (need approximately 4 gal [15 l] of water to dilute 1 gal [4 l] of
ethyl alcohol to extinguishment). Also, solutions of water and a soluble flammable or combustible liquid may
present a significantly reduced fire hazard (or no fire hazard) due to quicker fire extinguishment with water
(e.g., need approximately 1-12 gal [6 l] of water to dilute 1 gal [4 l] of a 50% ethyl alcohol/water solution to
extinguishment) and reduced thermal damage potential (e.g., a 20% ethyl alcohol/water solution produces a
heat of combustion that is much less than that produced by paper products, and the heat release rate will
be low indicating this solution presents an insignificant fire hazard).

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 43

APPENDIX B DOCUMENT REVISION HISTORY


January 2010. Minor editorial changes were made. Added references to Data Sheet 4-12, Foam-Water
Sprinkler Systems.
May 2008. Minor editorial changes were made.
September 2000. This revision of the document has been reorganized to provide a consistent format.
May 1998. Reformatted.
November 1993. Minor Technical Revision.
July 1993. Minor Technical Revision.
March 1993. Major Technical Revision.
APPENDIX C CHARACTERISTICS OF FLAMMABLE AND COMBUSTIBLE LIQUID FIRES AND
EXPLOSIONS
C.1 Characteristics and Types of Flammable and Combustible Liquid Fires
A flammable or combustible liquid fire is the combination of flammable vapor and air with the evolution of
heat and light (i.e., an exothermic oxidation reaction) without significant pressure development. The fire
hazard created by flammable/combustible liquids is more severe than the hazard created by other combustible
materials (e.g., wood, paper, etc.) due to their: a) high heats of combustion, b) high heat release rates and
c) fluid properties. The following comparison of heats of combustion for flammable/combustible liquids and
other combustible material (Table 5) illustrates one measure of fire hazard severity.
The severity of a fire is also dependent on the heat release rate. A heat release rate generally depends on
the heat of combustion, arrangement or geometry (e.g., exposed surface area), and combustion efficiency
of the material. The heat release rate for a flammable/combustible liquid fire is greater than that of other
combustibles because they have a high heat of combustion, favorable geometry, and a good combustion
efficiency. The fluid properties of flammable/combustible liquids tend to create large surface areas when the
liquids are released (e.g., unconfined liquid spill will spread over a large floor area; pressurized liquids can
be released in the form of small drops or a mist). These properties also influence fire spread since a fire will
expand over the full area of a spill or spray.
Table 5. Heat of Combustion for Representative Materials.
Material
Petroleum-Based Flammable/Combustible Liquids
Pure Alcohols
Distilled Whiskey (100 proof)
Plastic Commodities
Polystyrene
Class III Commodities

Heat of Combustion Btu/lb (kcal/kg)


>20,000 (11,000)
13,000-14,000 (7,000-8,000)
5,000 (3,000)
>10,000 (5,500)
17,000-18,000 (9,000-10,000)
6,000-9,000 (3,000-5,000)

C.1.1 Pool Fires


Flammable or combustible liquids that are confined to open tanks or diked areas can create a pool fire. The
confined liquid has a depth and controlled surface area. The heat release rate for this arrangement is limited
by the exposed surface area of the liquid. The length of time the fire can burn is controlled by the liquid depth.
This type of fire can release up to 10,000 Btu/min/ft2 (27,000 kcal/min/m2) (assuming perfect combustion
efficiency) of surface area. Approximately 1 gal (4 l) of liquid will be consumed each minute for each 12 ft2
(1 m2) of surface area and approximately 1 in. (25 mm) of liquid will be consumed every seven minutes.
C.1.2 Unconfined Spill Fires
A flammable or combustible liquid released on a level surface without confinement will spread out over the
surface and form a thin film. The area of the spill will depend on the amount of liquid released and the type
of surface it is released on. A fire involving this spill can release 10,000 Btu/min/ft2 (27,000 kcal/min/m2) of
surface area. The fire duration depends on the quantity of liquid spilled.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 44

FM Global Property Loss Prevention Data Sheets

C.1.3 Spray Fires


Flammable or combustible liquid spray fires result from leaks under pressure, as from hydraulic oil lines or
liquid transfer piping. The spray (e.g., mist of small liquid droplets) is easily ignited, even at temperatures
below the flash point of the liquid, in the same manner as fuel-oil discharge from a domestic oil burner. The
liquid will burn nearly as fast as it is released producing heat release rates much greater than a pool or spill
fire. A spray fire can produce approximately 120,000 Btu/gal (8,000 kcal/l). The duration of the fire depends
on the fuel supply available and how quickly the fuel supply can be shut off.
C.2 Fire Control and Extinguishment
The damage from a flammable/combustible liquid fire, as from other burning materials, is primarily from heat.
The heat released from this type of fire can affect large areas (e.g., spill or pool fire) or can affect a limited
area with extreme temperatures (e.g., spray fire). The best heat absorbing medium known is water. The best
way to deliver water to a fire is the wet pipe automatic sprinkler system, which is considered the basic
fire-control safeguard for flammable or combustible liquids. The purpose of special protection systems is
to supplement the sprinkler system and reduce damage or downtime below that obtainable with sprinkler
protection alone.
The principal effect of sprinkler water on flammable/combustible fires is one of cooling. Each gallon (3.8 l)
of water, heated to its boiling point and converted to steam, will absorb 8000 Btu (2000 kcal). For maximum
cooling, vaporization should occur close to the burning surface. Droplet size and velocity are critical because
the spray must penetrate a zone of flame and rising heat waves. Sprinkler discharge can extinguish a pool
fire involving unheated liquids with a flash point over 200F (93C) by cooling the liquid below its fire point.
Sprinkler protection may not extinguish a fire involving liquids with a flash point below 200F (93C) but will
hold temperatures at levels that will not cause major damage to buildings or equipment. (Fig. 11). Fires
involving water soluble liquids or liquids heavier than water can be extinguished by sprinkler discharge (i.e.,
dilute liquid to a concentration where it no longer has a fire point or smother fire by water floating on surface
of liquid).
Sprinkler protection alone will not ensure control or extinguishment of a flammable or combustible liquid fire.
The fires size must be limited by providing curbing to stop fuel spread, which will limit the number of sprinklers
that will operate. In addition, the fuel supply must be controlled and drainage provided to limit the fire
duration, which limits the needed water supply duration.
Special protection systems (e.g., water spray, foam, gaseous, and dry chemical) are designed to extinguish
a fire or provide localized cooling of equipment and buildings.
Water spray protection systems deliver large amounts of water to a specific area that allows increased cooling
(i.e., larger water droplets delivered at a higher velocity than available from ceiling sprinklers). These systems
can extinguish fires in liquids with flash points above 150F (66C), some viscous liquids with lower flash
points, water soluble liquids and liquids heavier than water. These systems also are suitable for providing
exposure protection for equipment, building or facilities.
Foam protection systems extinguish fires by blanketing the liquid and smothering the fire. The blanket persists
for some time, reducing the likelihood of reflashing. The foam used must be compatible with the burning
liquid. Foam may be delivered to a fire manually or automatically. Aqueous film forming foams (AFFF) may
be delivered with open or closed head sprinkler systems.
Gaseous protection systems extinguish flammable/combustible liquid fires by either reducing the oxygen
content over the liquid or by interfering with the combustion reaction. The gaseous agent can be delivered
by direct local application or by total flooding of the room or enclosure. No cleanup of the extinguishing agent
is required after discharge.
Dry chemical protection systems extinguish flammable/combustible liquid fires by coating the liquid surface
and smothering the fire. The dry chemical agent can be delivered by direct local application or by total
flooding of the room or enclosure.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 45

Fig. 11. Sprinklered vs. Unsprinklered Flammable/Combustible Liquid Fires.

C.3 Characteristics of Flammable/Combustible Liquid Vapor-Air Explosions


A vapor-air explosion is the rapid combustion of a flammable vapor and air (i.e., exothermic oxidation reaction)
which produces heat, light and an increase in pressure. A vapor-air explosion can occur when flammable
vapor and air are present, in a confined space, within the vapors flammable (explosive) range and the mixture
becomes ignited. If unvented, the developed pressure may reach six to nine times the initial absolute
pressure.
Boiling-liquid expanding-vapor explosions (BLEVE) occur when a confined liquid is heated above its
atmospheric boiling point by an exposure fire and suddenly released by rupture of the closed container. Part
of the heated liquid immediately flashes to vapor and is ignited by the exposure fire, releasing heat at a lower
rate than the vapor-air explosion but for a longer period of time.
C.4 Explosion Control and Protection
Explosion damage is largely the result of pressure created by rapidly expanding gases in a confined space.
Conditions under which explosive mixtures may accumulate should be eliminated or carefully controlled by
provision of adequate ventilation to dilute the vapors, by use of an inert atmosphere, or by other means.
The effects of an explosion are reduced by explosion vents or damage-limiting building construction.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 46

FM Global Property Loss Prevention Data Sheets

Explosion-protection systems are available that detect an incipient explosion and, by suppressing and/or
venting action, prevent the full impact of the explosion from developing. They are adaptable to vapor-air
explosion hazards in equipment and in small rooms.
Boiling-liquid expanding-vapor explosions can be prevented by reducing heat input to the closed container
or by bleeding off excess pressure from the container. Heat input rates can be reduced by insulation, by
burying or mounding the vessel, or by automatic sprinklers or water spray. Excessive pressure can be
prevented by atmospheric vent pipes, relief valves, bursting disks, or safety bungs.
C.5 Equipment Explosion (Deflagration) Venting Design
C.5.1 Vent Sizing for a Pred Greater Than 1.5 psig (0.1 bar g) (High Strength Equipment)
The following vent sizing equation (1) (reprinted from NFPA 68, Guide for Venting of Deflagrations1988
edition) should be used to estimate the vent area needed for high strength equipment.
h
e(gPstat)
Av = dVf Pred

(Note: the above equation must only be used with metric units)
With:
Av
Pred
Pstat
V
e
d,f,g,h

=
=
=
=
=
=

Vent Area, m2
Reduced Explosion Pressure, bar g
Static Venting Pressure, bar g
Vessel Volume, m3
2.718 (base of natural logarithm)
Constants as Defined in Table 6

To convert m2 to ft2 multiply by 10.76 ft2/m2


To convert bar g to psig multiply by 14.5 psig/bar g
To convert m3 to ft3 multiply by 35.31 ft2/m2
The constants, d, f, g and h, used in Equation (1) depend on the type of gas/vapor present. The data and
equation were developed based on four gases: methane, propane, coke gas and hydrogen. The composition
limits for the coke gas were:
4555%
610%
2533%
4.6%
0.1%
23%

Hydrogen
Carbon Monoxide
Methane
Nitrogen
Carbon Dioxide
Unspecified Hydrocarbons

There are no available data to indicate whether the constants, determined for coke gas, vary significantly
within these limits.
The table below, Table 6, indicates the constants to be used for each gas:
Table 6. Explosion Venting Constants.
Gas
Methane
Propane
Coke Gas
Hydrogen

d
0.105
0.148
0.150
0.279

f
0.770
0.703
0.695
0.680

g
1.23
0.942
1.38
0.755

2010 Factory Mutual Insurance Company. All rights reserved.

h
-0.823
-0.671
-0.707
-0.393

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 47

Equation (1) is valid only for vessels with a length to diameter ratios of 5 or less and for the following ranges
of Pred and vessel volume (V):
0.1 bar g Pstat 0.5 bar g
Pstat+0.1 bar g Pred 2 bar g
1 cu m V 1000 cu m
Pred is the maximum pressure that will be developed during the vented explosion and is the highest pressure
that can be sustained by the equipment being protected. To prevent deformation of cylindrical equipment,
Pred should be based on two-thirds of the equipments yield strength (stress). For rectangular or square
equipment, the above criteria may be used, however, some additional bracing may be needed to prevent
deformation. If deformation is acceptable, but not rupture of the equipment, then Pred should be based on
two-thirds of the equipments ultimate strength (stress). (Note: the minimum listed ultimate strength for a
material should always be used for this type of evaluation or design.)
Determination of Pred based on the above criteria is best left to the equipment designer or a structural
engineer. Lacking any data, use of twice the normal vessel design pressure (such as ASME rating) would
be acceptable.
Pstat is the set or relieving pressure of the deflagration vent. It should be at least 0.1 bar below the maximum
desired pressure during venting, Pred.
C.5.2 Vent Sizing for a Pr of 1.5 psig (0.1 bar g) or Less (Low Strength Equipment)
The design criteria provided in Data Sheet 1-44, Damage-Limiting Construction, should be used to estimate
the vent area needed for low strength equipment. The nomenclature listed in the data sheet represent the
following:
Pr = Maximum Vented Explosion Pressure, psf (kPa) (Note: this is equivalent to Pred for high strength
equipment.)
Pv = Vent Release Pressure, psf (kPa)
Av = Vent Area, ft2 (m2)
As = Internal Surface Area, ft2 (m2)
Limitations listed in Data Sheet 1-44 should be strictly followed.
Pr is the maximum pressure that will be developed during the vented explosion and is the highest pressure
that can be sustained by the equipment being protected. To prevent deformation of cylindrical equipment,
Pr should be based on two-thirds of the equipments yield strength (stress). For rectangular or square
equipment, the above criteria may be used, however, some additional bracing may be needed to prevent
deformation. If deformation is acceptable, but not rupture of the equipment, then Pr should be based on
two-thirds of the equipments ultimate strength (stress). (Note: the minimum listed ultimate strength for a
material should always be used for this type of evaluation or design.)
Determination of Pr based on the above criteria is best left to the equipment designer or a structural engineer.
Lacking any data, use of twice the vessel design pressure would be acceptable.
Pv is the set or relieving pressure of the deflagration vent. It should be at least 50 psf (2.4 kPa) below the
maximum desired pressure during venting, Pr. Ideally Pv should be 20 psf (0.96 kPa) or less.
Vent mass criteria listed in Data Sheet 1-44 are applicable for buildings and rooms only. The criteria listed
in Appendix C, Section C.5.4 should be used for equipment design.
C.5.3 Venting of Gases/Vapors Other Than Those Specified and Mists
Deflagration testing is used to compare the relative reactivity or hazard of various gases or vapors. When
tested under similar conditions of turbulence, igniter strength and vessel size, the rate of pressure rise is a
good measure of the ease of venting. Larger rates of pressure rise will require larger vent areas. A common
measure of this factor is Kg (bar-m/sec) which is the rate of pressure rise normalized to vessel size.
If vent size calculations for high strength equipment are necessary for gases or vapors other than the standard
gases listed above, an acceptable choice would be to use Equation (1) with the venting constants for
hydrogen (i.e., worst case). Using Figure 10 and Table 5 in Data Sheet 1-44 would be the worst case for
low strength equipment). A second alternative would be to refer to Data Sheet 1-44, Table 1, which lists many

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 48

FM Global Property Loss Prevention Data Sheets

common gases and vapors. Based on the classification in Table 1, Equation (1) and Table 7 of this document,
may be used with the venting constant for the comparable standard gas.
Table 7. Venting Constants for Other Vapors and Gases.
Data Sheet 1-44 Table Number
3
4
5

Use Venting
Constants For
Methane
Propane
Hydrogen

For high or low strength equipment containing gases or vapors that are not listed in Data Sheet 1-44, tests
should be conducted to determine the Kg for the new gas or vapor and compare it with Kg for any of the
standard gases (conducted with the exact same vessel and conditions). Then either use Equation (1) and the
venting constant for the comparable standard gas (high strength equipment) or the appropriate table in Data
Sheet 1-44 for the comparable standard gas (low strength equipment). For additional details of classifying
a particular gas/vapor refer to NFPA 68, Guideline for Venting of Deflagrations, Appendix A.
All mist explosion hazards should be evaluated as follows:
For high strength equipment use Equation (1) and the constants for propane in Table 6.
For low strength equipment use Table 4 in Data Sheet 1-44.
C.5.4 Vent Mass and Location
The deflagration vent for low or high strength equipment should be of low mass per unit area. The vent should
be less than 2.5 lb/ft2 (12.5 kg/m2), to minimize inertia effects and delay in vent opening. The vent should
open reliably and should not present a missile hazard. Vents should be centrally located for equipment with
a single vent (i.e., use largest side of equipment and avoid small ends) or symmetrically arranged for multiple
vents (i.e., provide several equally sized vents spaced evenly on equipment).
C.5.5 Vent Discharge Arrangement
Vents should be arranged to discharge to a safe location, preferably outdoors. For equipment located inside
buildings or rooms, a vent pipe/duct may sometimes be used to direct discharge to a safe outdoor location.
Vent pipes/ducts will, however, increase the vented explosive pressure experienced by the equipment due
to: 1) the force needed to overcome the inertia of the air column in the pipe/duct, 2) the back-flow of
combustion products created by escaping unburned gases igniting in the pipe/duct, and 3) friction losses
due to the gas flow through the pipe/duct (minimal effect). This increase in pressure will require a similar
increase in the strength of the equipment (Pred or Pr).
Vent pipe/ducts on high strength equipment should be as short and straight as possible; preferably limit length
to less than 10 ft (3 m) and avoid elbows or direction changes. Use Figure 12 to determine the increase
in Pred to account for the effect of the vent pipe/duct. Failure to account for the vent pipe/duct effect may lead
to equipment rupture during an explosion.
Vent pipe/ducts should not be provided on low strength equipment. The vent pipe/duct effect will increase
Pr beyond the definition of low strength equipment (i.e., Pr greater than 1.5 psig [0.1 bar g] so design for high
strength equipment). Vent pipe/ducts with a length to diameter ratio (L/D) of 1 or less can be used on any
equipment (high or low strength) without increasing Pr or Pred. Pipe/ducts with a diameter equal to or greater
than its length will not generally produce an increase in the maximum pressure experienced by the
equipment.
C.5.6 Effect of Turbulence
Equation (1) and the venting constants were based on quiescent mixtures in the test vessel. In some process
equipment, the vapor space may be turbulent due to flow into and out of the vessel (e.g., gas injection into
a reactor). If such conditions are likely, limited test data indicates Equation (1) and venting constants for
hydrogen will provide acceptable venting for gases other than high Kg gases like hydrogen.

2010 Factory Mutual Insurance Company. All rights reserved.

Flammable Liquid Operations

7-32

FM Global Property Loss Prevention Data Sheets

Page 49

Fig. 12. Maximum Pressure Developed During Venting of Gases, With and Without Vent Ducts.

Sizing vents for turbulent conditions of high Kg gases like hydrogen is not practical and other steps should
be taken to protect vessels containing these materials (e.g., inerting the vapor space).
The effect of ventilation induced turbulence within a piece of equipment may be disregarded when applying
Equation (1) or Data Sheet 1-44.
C.5.7 Effect of High Initial Pressures
The vent area equations are based on gases at initial pressures around atmospheric. Usually they are
considered valid up to 1.2 bar a (17.4 psia) initial pressures. Initial pressures beyond 1.2 bar a (17.4 psia)
cannot be handled by Equation (1) of this document, or Data Sheet 1-44.
C.6 Sight Glasses
C.6.1 Properties of Glass
All glass has a tensile strength of approximately 10,000 psi (70 MPa) and a compression strength of
approximately 100,000 psi (700 MPa). The maximum allowable working tensile stress is approximately 1,000
psi (7 MPa) for ordinary glass, and 2,000 to 4,000 psi (15 to 30 MPa) for high-strength glass. A lower factor
of safety is possible with high-strength glass because of its superior resistance to fatigue and thermal shock.
Surface scratches or chips will reduce the strength of glass to a small fraction of its original value. Thermal
shock, either by a wide difference of temperature on either side of a piece of glass or by a rapid change
of temperature, can cause failure. Repetitive cycling of temperatures and pressures over extended periods
of time also appears to have a harmful effect on the strength of the glass.

2010 Factory Mutual Insurance Company. All rights reserved.

7-32

Flammable Liquid Operations

Page 50

FM Global Property Loss Prevention Data Sheets

C.6.2 Types of Glass


Glass for observation ports is specially manufactured in accordance with the intended application, as follows:
1. Ordinary heat-treated soda-lime glass is suitable only for operations at normal atmospheric pressures
and temperatures.
2. Specially heat-treated soda-lime glass is suitable for pressures of approximately 150 to 300 psig
(10-20 bar g) and temperatures up to 400F (204C).
3. Annealed borosilicate glass is used at temperatures and pressures similar to those for ordinary
heat-treated soda-lime.
4. Tempered borosilicate glass is used for higher temperatures than the annealed glass, but is is more subject
to chemical deterioration.
5. High-silica glass is suitable for operations at high temperatures but only at low pressures.
C.6.3 Sight Glass Design
Glasses are usually circular. Older designs use a single glass mounted between two bolted flanges with
gaskets to separate the glass from metal surfaces.
Newer Approved designs are available. One incorporates two tempered borosilicate glass pressure disks
and an inside shield disk to protect against chemical deterioration, all sealed into one lens. The lens is bonded
in a special holder to reduce lens pressures and stresses.
Another Approved design incorporates two tempered borosilicate glass pressure disks, with or without an
inside shield disk, bonded into a lens assembly. A soft gasket fits around the glass circumferentially. A set
screw and metal-compression-ring arrangement presses against the gasket, which in turn holds the glass in
place by circumferential forces. This is intended to minimize tensile stress in the glass.

2010 Factory Mutual Insurance Company. All rights reserved.