DRAFT
REYQ8-48PY1
R-410A Heat Recovery 50Hz
Si37-701
Part 4 Function............................................................................ 95
1. Function General...................................................................................96
1.1 Symbol ...................................................................................................96
1.2 Operation Mode......................................................................................98
2. Basic Control.........................................................................................99
2.1 Normal Operation ...................................................................................99
2.2 Compressor PI Control.........................................................................100
Table of Contents
Si37-701
2.3
2.4
2.5
2.6
3. Special Control....................................................................................111
3.1
3.2
3.3
3.4
3.5
3.6
3.7
5. Other Control.......................................................................................132
5.1 Backup Operation.................................................................................132
5.2 Demand Operation ...............................................................................132
5.3 Heating Operation Prohibition ..............................................................132
ii
Table of Contents
Si37-701
Table of Contents
Si37-701
iv
Table of Contents
Si37-701
6.
7.
8.
9.
Index
............................................................................................. i
Table of Contents
Introduction
Si37-701
1. Introduction
1.1
Safety Cautions
Cautions and
Warnings
Be sure to read the following safety cautions before conducting repair work.
The caution items are classified into
Warning and
Caution. The
Warning
items are especially important since they can lead to death or serious injury if they are not
followed closely. The
Caution items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
vi
Si37-701
Introduction
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
vii
Introduction
Si37-701
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly.
For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
viii
Si37-701
Introduction
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
Type of
Information
Note
Description
A note provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Note:
Caution
Warning
Reference
Caution
Warning
ix
Introduction
1.2
Si37-701
PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2007 VRVIII series Heat Recovery System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII series R-410A Heat
Recovery System.
Aug., 2007
After Sales Service Division
Si37-701
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units ..............................................................................................3
2.2 Outdoor Units ...........................................................................................4
General Information
Si37-701
Power
Supply
Model Name
Ceiling Mounted
Cassette Type
(Double Flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
Ceiling Mounted
Cassette Type
(Multi Flow)
FXFQ
25M
32M
40M
50M
63M
80M
600600 Ceiling
Mounted Cassette
Type
FXZQ
Ceiling Mounted
Cassette Corner Type
FXKQ
63MA
FXDQPVE
20P
25P
32P
FXDQPVET
20P
25P
32P
125M
100M 125M
VE
FXDQNAVE
V1B
VE
FXDQNVET
20N
25N
32N
40N
50N
63N
Ceiling Concealed
(Duct) Type (Aus.
exclusive use)
FXDYQ
80M
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M 125M
Ceiling Mounted
Duct Type
FXMQ
Ceiling Suspended
Type
FXHQ
32MA
V1
200MA 250MA
63MA
100MA
FXAQ
FXLQ
Concealed Floor
Standing Type
FXNQ
VE
BS Units
Type
Heat Recovery Series
BSVQ
Model Name
160P
100P
Power Supply
V1
250P
Outdoor Units
Normal Series
Series
Heat Recovery
REYQ
8P
26P
44P
10P
28P
46P
12P
30P
48P
Model Name
14P
16P
32P
34P
Power Supply
18P
36P
20P
38P
22P
40P
24P
42P
Y1(E)
General Information
Si37-701
External Appearance
2. External Appearance
2.1
Indoor Units
FXMQ40~125M
FXMQ200 250M
BS Units
BSVQ100P
BSVQ160P
BSVQ250P
General Information
External Appearance
2.2
Si37-701
Outdoor Units
REYQ8P, 10P, 12P, 14P, 16P
REYQ26P, 28P
REYQ30P, 32P
26, 28 HP
73.0, 78.5 kW
30, 32 HP
85.0, 90.0 kW
REYQ42P, 44P
REYQ46P, 48P
42, 44 HP
118 ~ 124 kW
46, 48 HP
130, 135 kW
General Information
Si37-701
System Number
Capacity of units
8HP
1
10HP
1
12HP
1
14HP
1
16HP
1
10
Single Unit
12
14
16
Multiple Use
System Number
Capacity of units
18HP
2
20HP
2
22HP
2
24HP
2
26HP
2
28HP
2
30HP
2
32HP
2
34HP
3
36HP
3
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
Note:
General Information
16
For multiple connection of 18HP system or more, an optional Daikin Outdoor Unit Multi
Connection Piping Kit is required.
Model Selection
Si37-701
4. Model Selection
VRV III Heat Recovery Series
Connectable indoor units number and capacity
8HP
10HP
12HP
14HP
16HP
18HP
20HP
System name
HP
REYQ8P
REYQ10P
REYQ12P
REYQ14P
REYQ16P
REYQ18P
REYQ20P
Outdoor unit 1
REYQ8P
REYQ10P
REYQ12P
REYQ14P
REYQ16P
REMQ8P
REMQ8P
Outdoor unit 2
REMQ10P
REMQ12P
Outdoor unit 3
13
16
19
22
26
29
32
10.0~26.0
12.5~32.5
15.0~39.0
17.5~45.5
20.0~52.0
22.5~58.5
25.0~65.0
22HP
24HP
26HP
28HP
30HP
32HP
34HP
System name
HP
REYQ22P
REYQ24P
REYQ26P
REYQ28P
REYQ30P
REYQ32P
REYQ34P
Outdoor unit 1
REMQ10P
REMQ12P
REMQ10P
REMQ12P
REMQ14P
REMQ16P
REMQ8P
Outdoor unit 2
REMQ12P
REMQ12P
REMQ16P
REMQ16P
REMQ16P
REMQ16P
REMQ10P
Outdoor unit 3
REMQ16P
35
39
42
45
48
52
55
27.5~71.5
30.0~78.0
32.5~84.5
35.0~91.0
37.5~97.5
40.0~104.0
42.5~110.5
36HP
38HP
40HP
42HP
44HP
46HP
48HP
System name
HP
REYQ36P
REYQ38P
REYQ40P
REYQ42P
REYQ44P
REYQ46P
REYQ48P
Outdoor unit 1
REMQ8P
REMQ10P
REMQ12P
REMQ10P
REMQ12P
REMQ14P
REMQ16P
Outdoor unit 2
REMQ12P
REMQ12P
REMQ12P
REMQ16P
REMQ16P
REMQ16P
REMQ16P
Outdoor unit 3
REMQ16P
REMQ16P
REMQ16P
REMQ16P
REMQ16P
57.5~149.5
60.0~156.0
REMQ16P
REMQ16P
58
61
45.0~117.0
47.5~123.5
64
50.0~130.0
52.5~136.5
55.0~143.0
General Information
Si37-701
Model Selection
Power
Supply
Model Name
Ceiling Mounted
Cassette Type
(Double Flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
Ceiling Mounted
Cassette Type
(Multi Flow)
FXFQ
25M
32M
40M
50M
63M
80M
600600 Ceiling
Mounted Cassette
Type (Multi Flow)
FXZQ
Ceiling Mounted
Cassette Corner Type
FXKQ
63MA
FXDQPVE
20P
25P
32P
FXDQPVET
20P
25P
32P
125M
100M 125M
VE
FXDQNAVE
FXDQNVET
20N
25N
32N
40N
50N
63N
Ceiling Concealed
(Duct) Type (Aus.
exclusive use)
FXDYQ
80M
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M 125M
Ceiling Mounted
Duct Type
FXMQ
Ceiling Suspended
Type
FXHQ
32MA
V1B
VE
V1
200MA 250MA
63MA
100MA
FXAQ
FXLQ
Concealed Floor
Standing Type
FXNQ
VE
P20
type
2.2
kW
0.8HP
P25
type
2.8
kW
1HP
P32
type
3.5
kW
1.25HP
P40
type
4.5
kW
1.6HP
P50
type
5.6
kW
2.0HP
P63
type
7.0
kW
2.5HP
P80
type
9.0
kW
3.2HP
P100
type
11.2
kW
4HP
P125
type
14.0
kW
5HP
P200
type
22.4
kW
8HP
P250
type
28.0
kW
10HP
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
General Information
Model Selection
Si37-701
Object
Connection of equalizer oil pipe
Equalizer oil pipe for multioutdoor-unit system
Workability
Differences
New model (P Model)
z NONE
(No particular changes in
terms of service)
z NONE
General Information
Si37-701
Part 2
Specifications
1. Specifications ........................................................................................10
1.1 Outdoor Units .........................................................................................10
1.2 Indoor Units ............................................................................................21
1.3 BS Units .................................................................................................47
Specifications
Specifications
Si37-701
1. Specifications
1.1
Outdoor Units
m/h
r.p.m
REYQ8PY1(E)
19,400
76,800
22.5
22.4
21,500
85,300
25.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801300765
Cross Fin Coil
Hermetically Sealed Scroll Type
7.88+10.53
3720, 2900
kW
1.0+4.5
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Casing Color
mm
Soft Start
Propellor Fan
kW
0.352
I/s
3,166
m/min
190
Drive
Direct Drive
Liquid Pipe
9.5 C1220T (Brazing Connection)
Suction Gas Pipe
19.1 C1220T (Brazing Connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
15.9 C1220T (Brazing Connection)
Pressure Equalizer Tube
Mass (Weight)
kg
311
High Pressure Switch, Fan Driver Overload Protector, Over
Safety Devices
Current Relay, Inverter Overload Protector
Defrost Method
Deicer
Capacity Control
%
20~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
10.3
Control
Electronic Expansion Valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Standard Accessories
Clamps
Drawing No.
4D057563
REYQ10PY1(E)
24,300
96,200
28.2
28.0
27,100
107,000
31.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801300765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.34+10.53
6300, 2900
2.2+4.5
Soft Start
Propellor Fan
0.352
3,166
190
Direct Drive
9.5 C1220T (Brazing Connection)
22.2 C1220T (Brazing Connection)
19.1 C1220T (Brazing Connection)
331
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
14~100
R-410A
10.6
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D057564
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
10
Specifications
Si37-701
Specifications
Model Name
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ12PY1(E)
29,000
115,000
33.7
33.5
32,300
128,000
37.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801300765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.34+10.53
6300, 2900
REYQ14PY1(E)
35,500
141,000
41.3
40.0
38,700
154,000
45.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801300765
Cross Fin Coil
Hermetically Sealed Scroll Type
16.90+16.90
7980, 7980
kW
3.3+4.5
3.8+3.8
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft Start
Propellor Fan
kW
0.352
I/s
3,500
m/min
210
Drive
Direct Drive
Liquid Pipe
12.7 C1220T (Brazing Connection)
28.6 C1220T (Brazing Connection)
Suction Gas Pipe
Connecting
Pipes
High and Low Pressure Gas Pipe
19.1 C1220T (Brazing Connection)
Pressure Equalizer Tube
Mass (Weight)
kg
331
High Pressure Switch, Fan Driver Overload Protector, Over
Safety Devices
Current Relay, Inverter Overload Protector
Defrost Method
Deicer
Capacity Control
%
14~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
10.8
Control
Electronic Expansion Valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Standard Accessories
Clamps
Drawing No.
4D057565
Soft Start
Propellor Fan
0.752
3,916
235
Direct Drive
12.7 C1220T (Brazing Connection)
28.6 C1220T (Brazing Connection)
22.2 C1220T (Brazing Connection)
339
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
10~100
R-410A
11.1
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D057566
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
11
Specifications
Si37-701
Model Name
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ16PY1(E)
40,000
159,000
46.5
45.0
43,000
171,000
50.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801300765
Cross Fin Coil
Hermetically Sealed Scroll Type
16.90+16.90
7980, 7980
kW
4.4+4.4
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
kW
I/s
m/min
Drive
Liquid Pipe
Suction Gas Pipe
Connecting
Pipes
High and Low Pressure Gas Pipe
Pressure Equalizer Tube
Mass (Weight)
kg
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Refrigerant
Charge
kg
Control
Refrigerator Oil
Standard Accessories
Drawing No.
Soft Start
Propellor Fan
0.752
4,000
240
Direct Drive
12.7 C1220T (Brazing Connection)
28.6 C1220T (Brazing Connection)
22.2 C1220T (Brazing Connection)
339
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Deicer
10~100
R-410A
11.1
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes, Clamps
4D057567
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
12
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ18PY1(E)
REMQ8PY1(E)+REMQ10PY1(E)
43,600
173,000
50.7
50.4
48,600
193,000
56.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53)+16.90
(6300, 2900), 7980
REYQ20PY1(E)
REMQ8PY1(E)+REMQ12PY1(E)
48,300
192,000
56.2
55.9
53,800
213,000
62.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53)+16.90
(6300, 2900), 7980
kW
(2.2+4.5)1+4.71
(3.5+4.5)1+4.71
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.751)
I/s
3,000+3,083
m/min
180+185
Drive
Direct drive
Liquid Pipe
15.9 C1220T (Brazing connection)
Suction Gas Pipe
28.6 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
22.2 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
204+254
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
9~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
8.2+9.0
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057568
Soft start
Propellor fan
(0.751)+(0.751)
3,000+3,333
180+200
Direct drive
15.9 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
204+254
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
7~100
R-410A
8.2+9.1
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057569
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
13
Specifications
Si37-701
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ22PY1(E)
REMQ10PY1(E)+REMQ12PY1(E)
53,200
211,000
61.9
61.5
59,300
235,000
69.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53)2
(6300, 2900)2
REYQ24PY1(E)
REMQ12PY1(E)+REMQ12PY1(E)
58,000
230,000
67.4
67.0
64,500
256,000
75.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53)2
(6300, 2900)2
kW
(3.5+4.5)1+(2.2+4.5)1
(3.5+4.5)2
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.751)
I/s
3,083+3,333
m/min
185+200
Drive
Direct drive
Liquid Pipe
15.9 C1220T (Brazing connection)
Suction Gas Pipe
28.6 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
28.6 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
254+254
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
7~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
9.0+9.1
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057570
Soft start
Propellor fan
0.752
3,333+3,333
200+200
Direct drive
15.9 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
254+254
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
6~100
R-410A
9.1+9.1
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057571
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
14
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ26PY1(E)
REMQ10PY1(E)+REMQ16PY1(E)
63,100
250,000
73.4
73.0
70,100
278,000
81.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)
(6300, 2900, 2900)+(6300, 2900)
REYQ28PY1(E)
REMQ12PY1(E)+REMQ16PY1(E)
67,900
270,000
79.0
78.5
75,300
299,000
87.5
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)
(6300, 2900, 2900)+(6300, 2900)
kW
(3.2+4.5+4.5)1+(2.2+4.5)1
(3.2+4.5+4.5)1+(3.5+4.5)1
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.352)
I/s
3,083+3,833
m/min
185+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
34.9 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
28.6 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
254+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
6~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
9.0+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057572
Soft start
Propellor fan
(0.751)+(0.352)
3,333+3,833
200+230
Direct drive
19.1 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
254+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
6~100
R-410A
9.1+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057808
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
15
Specifications
Si37-701
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ30PY1(E)
REMQ14PY1(E)+REMQ16PY1(E)
73,500
292,000
85.5
85.0
81,700
324,000
95.0
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)2
(6300, 2900, 2900)2
REYQ32PY1(E)
REMQ16PY1(E)+REMQ16PY1(E)
77,800
309,000
90.5
90.0
86,000
341,000
100
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)2
(6300, 2900, 2900)2
kW
(3.2+4.5+4.5)1+(1.9+4.5+4.5)1
(3.2+4.5+4.5)2
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.352)+(0.352)
I/s
3,833+3,833
m/min
230+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
34.9 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
28.6 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
334+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
5~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
11.7+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057809
Soft start
Propellor fan
(0.352)2
3,833+3,833
230+230
Direct drive
19.1 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
334+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
5~100
R-410A
11.7+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057810
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
16
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ34PY1(E)
REMQ8PY1(E)+REMQ10PY1(E)+REMQ16PY1(E)
82,600
328,000
96.0
95.4
92,000
365,000
107
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)+16.90
(6300, 2900, 2900)+(6300, 2900)+7980
REYQ36PY1(E)
REMQ8PY1(E)+REMQ12PY1(E)+REMQ16PY1(E)
87,700
348,000
102
101
97,200
386,000
113
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)+16.90
(6300, 2900, 2900)+(6300, 2900)+7980
kW
(3.2+4.5+4.5)1+(2.2+4.5)1+4.71
(3.2+4.5+4.5)1+(3.5+4.5)1+4.71
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.751)+(0.352)
I/s
3,000+3,083+3,833
m/min
180+185+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
34.9 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
28.6 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
204+254+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
5~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
8.2+9.0+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057811
Soft start
Propellor fan
(0.751)+(0.751)+(0.352)
3,000+3,333+3,833
180+200+230
Direct drive
19.1 C1220T (Brazing connection)
41.3 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
204+254+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
5~100
R-410A
8.2+9.1+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057812
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
17
Specifications
Si37-701
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ38PY1(E)
REMQ10PY1(E)+REMQ12PY1(E)+REMQ16PY1(E)
92,900
368,000
108
107
102,000
406,000
119
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)2
(6300, 2900, 2900)+(6300, 2900)2
REYQ40PY1(E)
REMQ12PY1(E)+REMQ12PY1(E)+REMQ16PY1(E)
97,200
386,000
113
112
108,000
427,000
125
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+1680930765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)+(13.34+10.53)2
(6300, 2900, 2900)+(6300, 2900)2
kW
(3.2+4.5+4.5)1+(3.5+4.5)1+(2.2+4.5)1
(3.2+4.5+4.5)1+(3.5+4.5)2
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.751)+(0.352)
I/s
3,083+3,333+3,833
m/min
185+200+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
41.3 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
34.9 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
254+254+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
5~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
9.0+9.1+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057813
Soft start
Propellor fan
(0.752)+(0.352)
3,333+3,333+3,833
200+200+230
Direct drive
19.1 C1220T (Brazing connection)
41.3 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
254+254+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
4~100
R-410A
9.1+9.1+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057814
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
18
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ42PY1(E)
REMQ10PY1(E)+REMQ16PY1(E)+REMQ16PY1(E)
102,000
406,000
119
118
114,000
450,000
132
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)2+(13.34+10.53)
(6300, 2900, 2900)2+(6300, 2900)
REYQ44PY1(E)
REMQ12PY1(E)+REMQ16PY1(E)+REMQ16PY1(E)
108,000
427,000
125
124
119,000
471,000
138
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
1680930765+16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)2+(13.34+10.53)
(6300, 2900, 2900)2+(6300, 2900)
kW
(3.2+4.5+4.5)1+(2.2+4.5)1
(3.2+4.5+4.5)2+(3.5+4.5)1
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.751)+(0.352)2
I/s
3,083+3,833+3,833
m/min
185+230+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
41.3 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
34.9 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
254+334+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
4~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
9.0+11.7+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057815
Soft start
Propellor fan
(0.751)+(0.352)2
3,333+3,833+3,833
200+230+230
Direct drive
19.1 C1220T (Brazing connection)
41.3 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
254+334+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
4~100
R-410A
9.1+11.7+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057816
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
19
Specifications
Si37-701
Y1 Type
Y1E Type
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
m/h
r.p.m
REYQ46PY1(E)
REMQ14PY1(E)+REMQ16PY1(E)+REMQ16PY1(E)
113,000
447,000
131
130
124,000
495,000
145
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801240765+16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)3
(6300, 2900, 2900)3
REYQ48PY1(E)
REMQ16PY1(E)+REMQ16PY1(E)+REMQ16PY1(E)
117,000
464,000
136
135
129,000
512,000
150
Ivory White 5Y7.5/1
Light Camel 2.5Y6.5/1.5
16801240765+16801240765+16801240765
Cross fin coil
Hermetically sealed scroll type
(13.34+10.53+10.53)3
(6300, 2900, 2900)3
kW
(3.2+4.5+4.5)2+(1.9+4.5+4.5)1
(3.2+4.5+4.5)3
kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW
Casing Color
mm
Soft start
Propellor fan
kW
(0.352)+(0.352)2
I/s
3,833+3,833+3,833
m/min
230+230+230
Drive
Direct drive
Liquid Pipe
19.1 C1220T (Brazing connection)
Suction Gas Pipe
41.3 C1220T (Brazing connection)
Connecting
Pipes
High and Low Pressure Gas Pipe
34.9 C1220T (Brazing connection)
Pressure Equalizer Tube
19.1 C1220T (Brazing connection)
Mass (Weight)
kg
334+334+334
High
pressure
switch,
fan driver overload protector,
Safety Devices
overcurrent relay, inverter overload protector
Defrost Method
Deicer
Capacity Control
%
4~100
Refrigerant Name
R-410A
Refrigerant
Charge
kg
11.7+11.7+11.7
Control
Electronic expansion valve
Refrigerator Oil
Refer to the nameplate of compressor
Installation
manual, Operation manual, Connection pipes,
Standard Accessories
Cramps
Drawing No.
4D057817
Soft start
Propellor fan
(0.352)3
3,833+3,833+3,833
230+230+230
Direct drive
19.1 C1220T (Brazing connection)
41.3 C1220T (Brazing connection)
34.9 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
334+334+334
High pressure switch, fan driver overload protector,
overcurrent relay, inverter overload protector
Deicer
4~100
R-410A
11.7+11.7+11.7
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes,
Cramps
4D057818
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference
: 0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
REYQ8PY1E.
20
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
1.2
Specifications
Indoor Units
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXCQ40MVE
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AB1
Sirocco Fan
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
305990600
2101.5
20.145
2D17K1AA1
Sirocco Fan
101
151
151
201
116/83
7/5
247/177
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
150/108
9/6.5
318/230
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
150/108
9/6.5
318/230
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
200/150
12/9
424/318
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
Temperature Control
kg
220V
dBA
240V
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panels
(Option)
FXCQ32MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AB1
Sirocco Fan
FXCQ25MVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AA1
Sirocco Fan
I/s
m/min
cfm
Drive
Mass (Weight)
FXCQ20MVE
VP25
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
VP25
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
26
32/27
34/29
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
26
34/28
36/30
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
26
34/28
36/30
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
31
34/29
37/32
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBC32G-W1
BYBC32G-W1
White (10Y9/0.5)
531,030680
Resin Net
(with Mold Resistant)
8
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
White (10Y9/0.5)
White (10Y9/0.5)
531,030680
531,030680
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
8
8
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation,
Pattern for Installation,
Washer for Hanging
Washer for Hanging
Brackets, Clamp Metal,
Brackets, Clamp Metal,
Drain Hose, Insulation for
Drain Hose, Insulation for
Fitting, Washer Fixing
Fitting, Washer Fixing
Plates, Sealing Pads,
Plates, Sealing Pads,
Clamps, Screws, Washers. Clamps, Screws, Washers.
C: 3D039413
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
VP25
Dia. 32
( External
Internal Dia. 25 )
BYBC32G-W1
Panel Color
Dimensions: (HWD)
VP25
Dia. 32
( External
Internal Dia. 25 )
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
BYBC50G-W1
White (10Y9/0.5)
531,245680
Resin Net
(with Mold Resistant)
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
21
Specifications
Si37-701
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXCQ125MVE
8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3051,665600
2101.5
20.287
3D17K2AA1
Sirocco Fan
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3051,665600
2101.5
20.287
3D17K2AB1
Sirocco Fan
201
301
501
851
200/150
12/9
424/318
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
32
34/29
37/32
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
275/216
16.5/13
582/459
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
35
37/32
39/34
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
433/350
26/21
918/741
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
47
39/34
41/36
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
550/416
33/25
1,165/883
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
48
44/38
46/40
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBC63G-W1
BYBC125G-W1
BYBC125G-W1
Temperature Control
kg
220V
dBA
240V
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panels
(Option)
FXCQ80MVE
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
3051,175600
2101.5
20.184
2D17K2AA1VE
Sirocco Fan
FXCQ63MVE
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
305990600
2101.5
20.145
2D17K1AA1
Sirocco Fan
I/s
m/min
cfm
Drive
Mass (Weight)
FXCQ50MVE
BYBC50G-W1
Panel Color
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
White (10Y9/0.5)
531,245680
Resin Net
(with Mold Resistant)
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
White (10Y9/0.5)
White (10Y9/0.5)
531,430680
531,920680
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
9.5
12
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation,
Pattern for Installation,
Washer for Hanging
Washer for Hanging
Brackets, Clamp Metal,
Brackets, Clamp Metal,
Drain Hose, Insulation for
Drain Hose, Insulation for
Fitting, Washer Fixing
Fitting, Washer Fixing
Plates, Sealing Pads,
Plates, Sealing Pads,
Clamps, Screws, Washers. Clamps, Screws, Washers.
C: 3D039413
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
22
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
White (10Y9/0.5)
531,920680
Resin Net
(with Mold Resistant)
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXFQ40MVE
FXFQ50MVE
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan
301
301
301
301
216/166
13/10
459/353
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
30/27
Fuse
Electronic Expansion Valve
R-410A P Series
216/166
13/10
459/353
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
30/27
Fuse
Electronic Expansion Valve
R-410A P Series
250/183
15/11
530/388
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
31/27
Fuse
Electronic Expansion Valve
R-410A P Series
266/183
16/11
565/388
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
32/27
Fuse
Electronic Expansion Valve
R-410A P Series
BYCP125D-W1
BYCP125D-W1
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
kg
dBA
Model
Decoration
Panels
(Option)
FXFQ32MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan
I/s
m/min
cfm
Drive
Mass (Weight)
5 Sound Level (H/L) (220V-240V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
FXFQ25MVE
BYCP125D-W1
Panel Color
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
White (10Y9/0.5)
White (10Y9/0.5)
45950950
45950950
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
5.5
5.5
Operation manual,
Operation manual,
Installation manual, Paper
Installation manual, Paper
pattern for installation, Drain pattern for installation, Drain
hose, Clamp metal, Washer hose, Clamp metal, Washer
fixing plate, Sealing pads,
fixing plate, Sealing pads,
Clamps, Screws, Washer for Clamps, Screws, Washer for
hanging bracket, Insulation hanging bracket, Insulation
for fitting.
for fitting.
C: 3D038812
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
BYCP125D-W1
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
23
Specifications
Si37-701
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXFQ80MVE
FXFQ100MVE
FXFQ125MVE
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
246840840
2101.2
0.454
QTS46D14M
Turbo Fan
8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
246840840
2101.2
0.454
QTS46D14M
Turbo Fan
10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
288840840
2121.2
0.544
QTS46C17M
Turbo Fan
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
288840840
2121.2
0.544
QTS46C17M
Turbo Fan
301
301
1201
1201
I/s
m/min
cfm
308/233
18.5/14
653/494
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
25
33/28
Fuse
Electronic Expansion Valve
R-410A P Series
333/250
20/15
706/530
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
25
36/31
Fuse
Electronic Expansion Valve
R-410A P Series
433/350
26/21
918/741
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
29
39/33
Fuse
Electronic Expansion Valve
R-410A P Series
500/400
30/24
1,059/847
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
29
42/36
Fuse
Electronic Expansion Valve
R-410A P Series
BYCP125D-W1
BYCP125D-W1
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
5 Sound Level (H/L) (220V-240V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
kg
dBA
Model
Decoration
Panels
(Option)
FXFQ63MVE
BYCP125D-W1
Panel Color
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
White (10Y9/0.5)
White (10Y9/0.5)
45950950
45950950
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
5.5
5.5
Operation manual,
Operation manual,
Installation manual, Paper
Installation manual, Paper
pattern for installation, Drain pattern for installation, Drain
hose, Clamp metal, Washer hose, Clamp metal, Washer
fixing plate, Sealing pads,
fixing plate, Sealing pads,
Clamps, Screws, Washer for Clamps, Screws, Washer for
hanging bracket, Insulation hanging bracket, Insulation
for fitting.
for fitting.
C: 3D038812
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
24
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
BYCP125D-W1
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
551
551
551
150/116
9/7
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
18
30/25
32/26
47
Fuse
Electronic Expansion Valve
R-410A M(A) Series
158/125
9.5/7.5
335/265
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
18
32/36
34/28
49
Fuse
Electronic Expansion Valve
R-410A M(A) Series
Liquid Pipes
Gas Pipes
mm
mm
Drain Pipe
mm
kg
220V
dBA
240V
dBA 220V
Sound Power
Safety Devices
Refrigerant Control
Connectable outside unit
Model
Decoration
Panels
(Option)
3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan
150/116
9/7
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
18
30/25
32/26
47
Fuse
Electronic Expansion Valve
R-410A M(A) Series
FXZQ32M8V1B
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan
Temperature Control
Mass (Weight)
FXZQ25M8V1B
2,000
7,900
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan
I/s
m/min
cfm
Drive
Piping
Connections
FXZQ20M8V1B
Panel Color
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
BYFQ60BW1
BYFQ60BW1
BYFQ60BW1
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outside temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outside temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
3 Indoor temp. : 20CDB / outside temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
Specifications
25
Specifications
Si37-701
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
Sound Power
Safety Devices
Refrigerant Control
Connectable outside unit
Model
Panel Color
Decoration
Dimensions: (HWD)
Panels
(Option)
Air Filter
FXZQ50M8V1B
4,000
15,900
4.7
4.5
4,300
17,000
5.0
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan
5,000
19,900
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan
551
551
I/s
m/min
cfm
183/133
11/8
388/282
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene/Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
233/166
14/10
494/353
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene/Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
FXZQ40M8V1B
kg
220V
dBA
240V
dBA 220V
mm
Weight
kg
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outside temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
26
18
18
36/28
41/33
36/28
41/33
53
58
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
R-410A M(A) Series
R-410A M(A) Series
BYFQ60BW1
BYFQ60BW1
White (Ral 9010)
White (Ral 9010)
55700700
55700700
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
2.7
2.7
Operation Manual, Installation Manual, Paper Pattern for
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Installation, Drain Hose, Clamp Metal, Washer Fixing Plate,
Sealing Pads, Clamps, Screws, Washer for Hanging
Sealing Pads, Clamps, Screws, Washer for Hanging
Bracket, Insulation for Fitting.
Bracket, Insulation for Fitting.
C: 3D038929A
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outside temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outside temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
FXKQ25MAVE
FXKQ32MAVE
FXKQ40MAVE
FXKQ63MAVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AN1V1
Sirocco Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AN1V1
Sirocco Fan
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AP1V1
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
2151,310710
3111.75
0.226
4D12H1AJ1V1
Sirocco Fan
151
151
201
451
I/s
m/min
cfm
183/150
183/150
216/166
Air Flow Rate (H/L)
11/9
11/9
13/10
388/318
388/318
459/353
Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor
Thermostat
Microprocessor
Thermostat
Microprocessor
Thermostat
Temperature Control
for Cooling and Heating
for Cooling and Heating
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Liquid Pipes
mm
6.4 (Flare Connection)
6.4 (Flare Connection)
6.4 (Flare Connection)
Gas Pipes
mm
12.7 (Flare Connection)
12.7 (Flare Connection)
12.7 (Flare Connection)
Piping
Connections
VP25
VP25
VP25
Drain Pipe
mm
External Dia. 32
External Dia. 32
External Dia. 32
Internal Dia. 25
Internal Dia. 25
Internal Dia. 25
Mass (Weight)
kg
31
31
31
220V
38/33
38/33
40/34
5 Sound Level (H/L)
dBA
240V
40/35
40/35
42/36
Fuse,
Fuse,
Fuse,
Safety Devices
Thermal Fuse for Fan Motor Thermal Fuse for Fan Motor Thermal Fuse for Fan Motor
Refrigerant Control
Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Units
R-410A P Series
R-410A P Series
R-410A P Series
Model
Decoration
Panels
(Option)
BYK45FJW1
Panel Color
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
White (10Y9/0.5)
701,240800
Resin Net
(with Mold Resistant)
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
BYK45FJW1
BYK45FJW1
White (10Y9/0.5)
White (10Y9/0.5)
701,240800
701,240800
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
8.5
8.5
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation, Drain Pattern for Installation, Drain
Hose, Clamp Metal,
Hose, Clamp Metal,
Insulation for Fitting, Sealing Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Pads, Clamps, Screws,
Washers, Positioning Jig for Washers, Positioning Jig for
Installation, Insulation for
Installation, Insulation for
Hanger Bracket, Air Outlet
Hanger Bracket, Air Outlet
Blocking Pad.
Blocking Pad.
C: 3D038813A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
300/250
18/15
635/530
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyethylene Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
34
42/37
44/39
Fuse,
Thermal Fuse for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYK71FJW1
White (10Y9/0.5)
701,440800
Resin Net
(with Mold Resistant)
9.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
27
Specifications
Si37-701
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
mm
mm
m
FXDQ20NAVE
FXDQ25NAVE
FXDQ32NAVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
621
621
621
I/s
m/min
cfm
Pa
158/125
9.5/7.5
335/265
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
158/125
9.5/7.5
335/265
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C: 3D051253
175/141
10.5/8.5
371/300
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
28
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller this pressure means High static
pressure - Standard static pressure.
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
mm
mm
m
FXDQ40NAVE
FXDQ50NAVE
FXDQ63NAVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
200900620
3121.5
0.176
Sirocco Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
200900620
3121.5
0.176
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
2001100620
3121.5
0.227
Sirocco Fan
621
1301
1301
I/s
m/min
cfm
Pa
175/141
10.5/8.5
371/300
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
27
34/30
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
208/166
12.5/10.0
441/353
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
28
35/31
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C: 3D051253
275/216
16.5/13.0
583/459
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
31
36/32
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller this pressure means High static
pressure - Standard static pressure.
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
29
Specifications
Si37-701
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
mm
mm
m
FXDQ20NVET
FXDQ25NVET
FXDQ32NVET
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
621
621
621
m/min
Pa
9.5/7.5
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
9.5/7.5
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
10.5/8.5
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D049693
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Piping
Gas Pipes
mm
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
30
Specifications
Si37-701
Specifications
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
mm
mm
m
FXDQ40NVET
FXDQ50NVET
FXDQ63NVET
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
200900620
3121.5
0.176
Sirocco Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
200900620
3121.5
0.176
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
2001100620
3121.5
0.227
Sirocco Fan
621
1301
1301
m/min
Pa
10.5/8.5
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
12.5/10.0
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
16.5/13.0
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
27
34/30
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
28
35/31
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D049693
31
36/32
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Piping
Gas Pipes
mm
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
Specifications
31
Specifications
Si37-701
Slim Ceiling Mounted Duct Type (PVE: with Drain Pump PVET: without Drain Pump)
FXDQ20PVE
FXDQ20PVET
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
FXDQ25PVE
FXDQ25PVET
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
FXDQ32PVE
FXDQ32PVET
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200900620
2121.5
0.176
Sirocco Fan
621
621
621
I/s
m/min
cfm
Pa
133/106
9.5/7.5
282/226
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
133/106
9.5/7.5
282/226
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
133/106
10.5/8.5
282/226
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C: 3D052136
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Model
kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
mm
mm
m
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
32
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller this pressure means High static
pressure - Standard static pressure.
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
FXDYQ80MV1
kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Type
Motor Output
Fan
mm
mm
m
W
l/s
cfm
Pa
Temperature Control
Sound Absorbing Thermal Insulation Material
6 Air Filter
Piping
Connections
Liquid Pipes
Gas Pipes
mm
mm
Drain Pipe
mm
Mass (Weight)
7 Sound Level (240V)
kg
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3601,168869
2181.5
0.284
Twin Sirocco Fan
290
590
1250
130 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
FXDYQ100MV1
FXDYQ125MV1
10,000
12,500
39,600
49,500
11.6
14.5
11.2
14.0
10,800
13,800
42,700
54,600
12.5
16.0
Galvanized Steel Plate
Galvanized Steel Plate
3601,478899
3601,478899
2181.5
3181.5
0.435
0.435
Twin Sirocco Fan
Twin Sirocco Fan
490
490
815
925
1726
1959
130 5
100 5
Direct Drive
Direct Drive
Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
7
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote controller this pressure means High static
pressure - Standard static pressure.
Air filter is not a standard accessory. A suitable field supplied filter must be installed in the return air duct.
The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
FXDYQ145MV1
14,500
57,700
16.9
16.2
15,900
63,100
18.5
Galvanized Steel Plate
3601,478899
3181.5
0.435
Twin Sirocco Fan
655
1070
2266
130 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
33
Specifications
Si37-701
Model
FXDYQ180MV1
kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Type
Motor Output
Fan
mm
mm
m
W
l/s
cfm
Pa
Temperature Control
Sound Absorbing Thermal Insulation Material
6 Air Filter
Liquid Pipes
mm
Piping
Gas
Pipes
mm
Connections
Drain Pipe
mm
Mass (Weight)
kg
7 Sound Level (240V)
dBA
Safety Devices
Refrigerant Control
Standard Accessories
17,700
70,300
20.6
20.0
19,300
76,400
22.4
Galvanized Steel Plate
5001,210910
2222.0
0.443
Twin Sirocco Fan
700
1,180
2500
150 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Drawing No.
FXDYQ200MV1
19,800
78,500
23.0
22.4
21,500
85,300
25.0
Galvanized Steel Plate
5001,210910
3222.0
0.443
Twin Sirocco Fan
750
1,200
2542
180 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
FXDYQ250MV1
24,800
98,300
28.8
28.0
27,000
107,500
31.5
Galvanized Steel Plate
5001,410910
3222.0
0.54
Twin Sirocco Fan
1,100
1,400
2965
200 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference;
34
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
501
501
501
150/108
9/6.5
318/230
158/116
9.5/7
335/247
Pa
88-39-20
88-39-20
64-39-15
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
39/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
39/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
40/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
kg
220V
dBA
240V
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel
(Option)
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan
150/108
9/6.5
318/230
Temperature Control
FXSQ32MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan
pressure
Drive
Mass (Weight)
FXSQ25MVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan
I/s
m/min
cfm
4 External static
Piping
Connections
FXSQ20MVE
Panel Color
Dimensions: (HWD)
Weight
mm
kg
Standard Accessories
Drawing No.
BYBS32DJW1
BYBS32DJW1
BYBS32DJW1
White (10Y9/0.5)
55650500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
White (10Y9/0.5)
55650500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
C: 3D039431
White (10Y9/0.5)
55650500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
High static pressure-Standard -Low static pressure.
Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
35
Specifications
Si37-701
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number of
Units
Fan
pressure
Drive
mm
mm
m
651
851
1251
250/183
15/11
530/388
350/258
21/15.5
741/547
Pa
88-49-20
88-59-29
88-49-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
40/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
31
41/36
43/38
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
41
42/35
44/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel
(Option)
Panel Color
Dimensions: (HWD)
Weight
mm
kg
Standard Accessories
Drawing No.
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
3001,000800
3141.75
0.221
2D18H2A
Sirocco Fan
191/150
11.5/9
406/318
kg
220V
dBA
240V
FXSQ63MVE
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
300700800
3141.75
0.132
D18H2A
Sirocco Fan
Mass (Weight)
FXSQ50MVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
300700800
3141.75
0.132
D18H2A
Sirocco Fan
I/s
m/min
cfm
Temperature Control
Gas Pipes
Piping
Connections
Drain Pipe
FXSQ40MVE
BYBS45DJW1
BYBS45DJW1
BYBS71DJW1
White (10Y9/0.5)
55800500
3.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
White (10Y9/0.5)
55800500
3.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
C: 3D039431
White (10Y9/0.5)
551,100500
4.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
36
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
High static pressure-Standard -Low static pressure.
Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number of
Units
Fan
mm
mm
m
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan
2251
2251
2251
450/358
27/21.5
953/759
466/366
28/22
988/777
633/466
38/28
1,341/988
Pa
113-82
107-75
78-39
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
VP25
(External Dia. 32 Internal Dia. 25)
52
46/41
48/43
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
White (10Y9/0.5)
551,500500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
White (10Y9/0.5)
551,500500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
C: 3D039431
White (10Y9/0.5)
551,500500
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
Piping
Connections
Drain Pipe
kg
220V
dBA
240V
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel
(Option)
FXSQ125MVE
10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan
pressure
Drive
FXSQ100MVE
8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan
l/s
m/min
cfm
4 External static
Mass (Weight)
FXSQ80MVE
Panel Color
Dimensions: (HWD)
Weight
mm
kg
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
6
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
High static pressure-Standard.
Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
37
Specifications
Si37-701
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
FXMQ50MAVE
FXMQ63MAVE
FXMQ80MAVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan
8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AA1VE
Sirocco Fan
1001
1001
1001
1601
I/s
m/min
cfm
233/191
14/11.5
494/406
233/191
14/11.5
494/406
233/191
14/11.5
494/406
325/266
19.5/16
688/565
Pa
157-118 4
157-118 4
157-118 4
157-108 4
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
6.4 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
External Static
Pressure 50Hz
Drive
Temperature Control
FXMQ40MAVE
mm
VP25
mm
External Dia. 32
Internal Dia. 25
kg
44
39/35
220V
dBA
240V
41/37
Fuse,
Thermal Fuse for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Mass (Weight)
7 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
6
7
38
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
VP25
Dia. 32
( External
Internal Dia. 25 )
45
42/38
44/40
Fuse,
Thermal Fuse for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
FXMQ200MAVE
FXMQ250MAVE
12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3901,110690
3162.0
0.319
2D11/2D3AF1VE
Sirocco Fan
19,800
78,500
23.0
22.4
21,500
85,300
25.0
Galvanized Steel Plate
4701,3801,100
3262.0
0.68
D13/4G2DA12
Sirocco Fan
24,800
98,300
28.8
28.0
27,100
107,000
31.5
Galvanized Steel Plate
4701,3801,100
3262.0
0.68
D13/4G2DA12
Sirocco Fan
2701
4301
3802
3802
483/383
29/23
1,024/812
600/483
36/29
1,271/1,024
966/833
58/50
2,047/1,765
1,200/1,033
72/62
2,542/2,189
Pa
157-98 4
191-152 4
221-132 4
270-147 4
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
19.1(Brazing Connection)
VP25
External Dia. 32
Internal Dia. 25
63
43/39
45/41
VP25
External Dia. 32
Internal Dia. 25
65
45/42
47/44
PS1B
PS1B
137
48/45
49/46
Fuse,
Thermal Protector for Fan
Motor
Electronic Expansion Valve
R-410A P Series
137
48/45
49/46
Fuse,
Thermal Protector for Fan
Motor
Electronic Expansion Valve
R-410A P Series
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
Piping
Connections
Drain Pipe
mm
mm
kg
220V
dBA
240V
FXMQ125MAVE
10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
3901,110690
3162.0
0.319
2D11/2D3AG1VE
Sirocco Fan
I/s
m/min
cfm
External Static
Pressure 50Hz
Drive
Mass (Weight)
FXMQ100MAVE
Safety Devices
Fuse,
Fuse,
Thermal Fuse for Fan Motor Thermal Fuse for Fan Motor
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
6
7
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Operation Manual,
Installation Manual, Sealing
Pads, Connection Pipes,
Screws, Clamps.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
39
Specifications
Si37-701
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXHQ32MAVE
FXHQ63MAVE
FXHQ100MAVE
3,200
12,600
3.7
3.6
3,400
13,600
4.0
White (10Y9/0.5)
195960680
2121.75
0.182
3D12K1AA1
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
White (10Y9/0.5)
1951,160680
3121.75
0.233
4D12K1AA1
Sirocco Fan
10,000
39,600
11.6
11.2
10,800
42,700
12.5
White (10Y9/0.5)
1951,400680
3121.75
0.293
3D12K2AA1
Sirocco Fan
621
621
1301
I/s
m/min
cfm
200/166
12/10
424/353
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
24
36/31
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
291/233
17.5/14
618/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
28
39/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
C: 3D038815A
416/325
25/19.5
883/688
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
33
45/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Piping
Gas Pipes
mm
Connections
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
40
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXAQ25MAVE
FXAQ32MAVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
White (3.0Y8.5/10.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan
2,500
9,900
2.9
2.8
2,800
10,900
3.2
White (3.0Y8.5/10.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
White (3.0Y8.5/10.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan
401
401
401
I/s
m/min
cfm
125/75
7.5/4.5
265/159
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
133/83
8/5
282/177
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
150/91
9/5.5
318/194
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ20MAVE
Liquid Pipes
Gas Pipes
mm
mm
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
VP13
(External Dia. 18 Internal Dia. 13)
11
35/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
VP13
(External Dia. 18 Internal Dia. 13)
11
36/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
C: 3D039370B
VP13
(External Dia. 18 Internal Dia. 13)
11
37/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length:7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
41
Specifications
Si37-701
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
mm
mm
m
FXAQ50MAVE
FXAQ63MAVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
White (3.0Y8.5/10.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
White (3.0Y8.5/10.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
White (3.0Y8.5/10.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan
431
431
431
I/s
m/min
cfm
200/150
12/9
424/318
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
250/200
15/12
530/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
316/233
19/14
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
9.5 (Flare Connection)
15.9 (Flare Connection)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ40MAVE
Liquid Pipes
Gas Pipes
mm
mm
Drain Pipe
mm
Mass (Weight)
kg
dBA
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
VP13
(External Dia. 18 Internal Dia. 13)
14
39/34
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
VP13
(External Dia. 18 Internal Dia. 13)
14
42/36
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
C: 3D039370B
VP13
(External Dia. 18 Internal Dia. 13)
14
46/39
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
42
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing Color
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
W
I/s
m/min
cfm
FXLQ20MAVE
FXLQ25MAVE
FXLQ32MAVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Ivory White (5Y7.5/1)
6001,000222
3141.5
0.159
D14B20
Sirocco Fan
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Ivory White (5Y7.5/1)
6001,000222
3141.5
0.159
D14B20
Sirocco Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Ivory White (5Y7.5/1)
6001,140222
3141.5
0.200
2D14B13
Sirocco Fan
151
116/100
Air Flow Rate (H/L)
7/6
247/212
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
151
116/100
7/6
247/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
25
35/32
37/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
C: 3D038816A
251
133/100
8/6
282/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
30
35/32
37/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
43
Specifications
Si37-701
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
W
I/s
m/min
cfm
FXLQ40MAVE
FXLQ50MAVE
FXLQ63MAVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Ivory White (5Y7.5/1)
6001,140222
3141.5
0.200
2D14B13
Sirocco Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Ivory White (5Y7.5/1)
6001,420222
3141.5
0.282
2D14B20
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Ivory White (5Y7.5/1)
6001,420222
3141.5
0.282
2D14B20
Sirocco Fan
251
183/141
Air Flow Rate (H/L)
11/8.5
388/300
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
351
233/183
14/11
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
36
39/34
41/36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
C: 3D038816A
351
266/200
16/12
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
21 O.D (Vinyl Chloride)
36
40/35
42/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
44
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
Specifications
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
W
I/s
m/min
cfm
FXNQ20MAVE
FXNQ25MAVE
FXNQ32MAVE
2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
610930220
3141.5
0.159
D14B20
Sirocco Fan
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
610930220
3141.5
0.159
D14B20
Sirocco Fan
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
6101,070220
3141.5
0.200
2D14B13
Sirocco Fan
151
116/100
Air Flow Rate (H/L)
7/6
247/212
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
151
116/100
7/6
247/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
19
35/32
37/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
C: 3D038817A
251
133/100
8/6
282/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
23
35/32
37/34
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
Specifications
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
45
Specifications
Si37-701
Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
mm
mm
m
W
I/s
m/min
cfm
FXNQ40MAVE
FXNQ50MAVE
FXNQ63MAVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
6101,070220
3141.5
0.200
2D14B13
Sirocco Fan
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
6101,350220
3141.5
0.282
2D14B20
Sirocco Fan
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
6101,350220
3141.5
0.282
2D14B20
Sirocco Fan
251
183/141
Air Flow Rate (H/L)
11/8.5
388/300
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber / Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
351
233/183
14/11
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
27
39/34
41/36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
C: 3D038817A
351
266/200
16/12
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
21 O.D (Vinyl Chloride)
27
40/35
42/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
2
3
4
5
46
difference: 0m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si37-701
1.3
Specifications
BS Units
Model
Power Supply
Total Capacity Index of Indoor Unit
No. of Connectable Indoor Units
Casing
Dimensions: (HWD)
mm
Sound Absorbing Thermal Insulation
Material
Liquid Pipes
Indoor
Unit
Gas Pipes
Piping
Liquid Pipes
Connection
Outdoor Suction Gas Pipes
Unit
Discharge Gas
Pipes
Weight
kg
Standard Accessories
Drawing No.
Note:
BSVQ100PV1
BSVQ160PV1
BSVQ250PV1
14
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057926
14
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057927
15
Installation manual, Attached pipe
Insulation pipe cover, Clamps
C: 4D057928
1 If the total capacity of all indoor units connected to the system is less than 7.1 kW, connect the attached pipe to the field pipe.
(Braze the connection between the attached pipe and field pipe.)
2 Use the field flanged pipe.
Also, with a 200 class indoor unit, connect the attached reducer to the field pipe. (Braze the connection between the attached pipe and
field pipe.)
3 Use the attached pipe.
Components
Note:
Specifications
Number of connectable
indoor units
13 (20)
16 (25)
19 (30)
22 (35)
26 (40)
29 (36)
32 (40)
35 (44)
39 (48)
42 (52)
Same number of
45 (56)
BS units
48 (60)
52 (64)
55 (55)
58 (58)
61 (61)
64 (64)
Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from
double outdoor units, 130% from triple outdoor units.
47
Specifications
48
Si37-701
Specifications
Si37-701
Part 3
Refrigerant Circuit
1. Refrigerant Circuit .................................................................................50
1.1
1.2
1.3
1.4
1.5
1.6
1.7
Refrigerant Circuit
49
Refrigerant Circuit
Si37-701
1. Refrigerant Circuit
1.1
No. in
refrigerant
Symbol
Name
system
diagram
1
M1C Inverter compressor (INV)
2
M2C
Standard compressor 1
(STD1)
M1F
Inverter fan
M2F
Inverter fan
5(6)
7(8)
9
10(11)
12
13
14
15
16
17(18)
19
20
21
22
23
24
25
26
27
28
29
30
31
32(42)
33
34
35(45)
Y1E
(Y3E)
Y2E
(Y5E)
(Liquid pipe)
Pressure
regulating valve
(Refrigerant regulator)
Refrigerant regulator
Capillary tube
Capillary tube
Capillary tube
R1T
Thermistor (Outdoor air: Ta)
R8T
Thermistor (Suction pipe: TsA)
(R10T)
Thermistor (INV discharge
R31T
pipe: Tdi)
Thermistor (STD1 discharge
R32T pipe: Tds1)
R4T
Thermistor (Heat exchanger
(R12T) deicer: Tb)
36(46)
R2T
Thermistor (Heat exchanger
(R11T) gas pipe Tg)
37(47)
R7T
Thermistor (Heat exchanger
(R15T) liquid pipe Tf)
38(48)
R5T
Thermistor (Subcooling heat
(R13T) exchanger gas pipe: Tsh)
39
40(50)
50
R6T
R9T
(R14T) Thermistor (Liquid pipe Tsc)
Major Function
Inverter compressor is operated on frequencies between 52Hz and 210Hz by using
the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
REYQ8, 10, 12P : 37 steps
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
PI control is applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
This is used to open/close refrigerant charge port.
This opens in cooling operation.
Used to prevent the low pressure from transient falling.
This is used to collect refrigerant to the refrigerant regulator.
This is used to collect refrigerant to the refrigerant regulator.
This is used to discharge refrigerant from the refrigerant regulator.
Bypass the high pressure gas to the refrigerant regulator.
This is used to switch outdoor heat exchanger to evaporator or condenser.
This is used to switch dual pressure gas pipe to high pressure or low pressure.
Used to detect high pressure.
Used to detect low pressure.
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
Apply subcooling to liquid refrigerant.
Surplus refrigerant is held according to the operation conditions.
Used to return the refrigerating oil separated through the oil separator to the INV compressor.
Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
This is used to discharge refrigerant from the refrigerant regulator.
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
Used to detect suction pipe temperature.
Used to detect discharge pipe temperature. Used for compressor temperature
protection control.
Used to detect liquid pipe temperature of air heat exchanger. Used to make judgments
on defrosting operation.
This detects temperature of gas pipe for air heat exchanger. Used to exercise the
constant control of superheated degree when an evaporator is used for outdoor unit
heat exchanging.
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve. Used to make judgments on the recover or discharge
refrigerants to the refrigerant regulator.
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger. Used to exercise the constant control of superheated degree at the outlet
of supercooled heat exchanger.
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.
Refrigerant Circuit
Si37-701
Refrigerant Circuit
50
Left
26
Stop
Valve
48
46
Heat exchanger 2
11
45
47
18
6
4
Dual Pressure
Gas Pipe
19
Stop
Valve
23
S2PH
34
STD
29
Suction
Pipe
42
Stop
Valve
40
39
Right
26
7
38
Gauge Port
36
24
10
Heat exchanger 1 35
37
17
S1NPH 20
25
13
3
31
12
27
22 S1PH
33
16
INV
14
15
28
Gauge Port
30
32
Refrigerant Circuit
21
S2NPL
51
Refrigerant Circuit
1.2
Si37-701
REYQ14P, 16P
No. in
refrigerant
Symbol
system
diagram
Name
Major Function
M1C
M2C
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
M2F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
5(6)
Y1E
(Y3E)
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
7(8)
Y2E
(Y5E)
Y4E
10(11)
Y5S
Solenoid valve (Main bypass1
(Y10S) (Main bypass2))
12
Y4S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
13
Y3S
14
Y1S
15
Y7S
16
Y6S
17(18)
Y2S
(Y9S)
19
Y8S
This is used to switch dual pressure gas pipe to high pressure or low pressure.
20
21
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
22(23)
24
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
25
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
26
27
Refrigerant regulator
28
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
29
Capillary tube
30
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
31(41)
R8T
Thermistor (Suction pipe: TsA) Used to detect suction pipe temperature.
(R10T)
32
R31T
33
R32T
35(45)
R4T
Thermistor (Heat exchanger
(R12T) deicer: Tb)
Used to detect liquid pipe temperature of air heat exchanger. Used to make judgments
on defrosting operation.
36(46)
R2T
Thermistor (Heat exchanger
(R11T) gas pipe Tg)
This detects temperature of gas pipe for air heat exchanger. Used to exercise the
constant control of superheated degree when an evaporator is used for outdoor unit
heat exchanging.
37(47)
R7T
Thermistor (Heat exchanger
(R15T) liquid pipe Tf)
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve. Used to make judgments on the recover or discharge
refrigerants to the refrigerant regulator.
38(48)
R5T
Thermistor (Subcooling heat
(R13T) exchanger gas pipe: Tsh)
This detects temperature of gas pipe on the evaporator side for the subcooling heat
exchanger. Used to exercise the constant control of superheated degree at the outlet
of supercooled heat exchanger.
39
40(50)
52
R6T
R9T
Thermistor (Liquid pipe Tsc)
(R14T)
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.
Refrigerant Circuit
Si37-701
Refrigerant Circuit
REYQ14P, 16P
(14HP, 16HP Single Type)
(INV Unit 2)
Liquid
Pipe
50
Left
26
Stop
Valve
48
46
Heat exchanger 2
11
45
47
18
Dual Pressure
Gas Pipe
19
Stop
Valve
23
S2PH
33
2 INV2
28
9
Suction
Pipe
41
Stop
Valve
40
Liquid Pipe
39
Right
26
7
38
36
24
10
Heat exchanger 1 35
Gauge Port
37
17
S1NPH
25
13
20
30
12
27
22 S1PH
32
16
1 INV1
14
15
28
Gauge Port
29
31
Refrigerant Circuit
21
S2NPL
53
Refrigerant Circuit
1.3
Si37-701
No. in
refrigerant
Symbol
system
diagram
54
Name
Major Function
M1C
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y3E
Y2E
Y6S
10
Y5S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
11
Y4S
12
Y1S
13
Y7S
14
Y8S
15
Y3S
16
Y2S
This is used to switch dual pressure gas pipe to high pressure or low pressure.
17
18
19
S1PH
22
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
23
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
24
25
Refrigerant regulator
26
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
29
Capillary tube
30
R1T
31
R8T
32
R31T
35
R4T
This detects temperature of some of the liquid pipes for air heat exchanger.
36
R2T
37
R7T
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve.
38
R5T
This detects temperature of gas pipe on the evaporator side for the subcooling heat
exchanger.
39
R6T
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
40
R9T
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.
Refrigerant Circuit
Si37-701
Refrigerant Circuit
REMQ8PY1
40
Stop Valve
Liquid Pipe
39
24
7
38
36
22
35
37
15
30
17 S1NPH
Stop Valve
Equalizing Pipe
23
11
10
16
Stop Valve
Dual Pressure
Gas Pipe
19 S1PH
25
32
14
1
12
INV
13
26
29
S2NPL
18
Gauge Port
Stop Valve
Suction Pipe
31
Refrigerant Circuit
55
Refrigerant Circuit
1.4
Si37-701
No. in
refrigerant
Symbol
system
diagram
56
Name
Major Function
M1C
M2C
Standard compressor 1
(STD1)
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y3E
Y2E
Y6S
10
Y5S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
11
Y4S
12
Y1S
13
Y7S
14
Y8S
15
Y3S
16
Y2S
This is used to switch dual pressure gas pipe to high pressure or low pressure.
17
18
19
S1PH
20
S2PH
22
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
23
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
24
25
Refrigerant regulator
26
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
27
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
29
Capillary tube
30
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
31
R8T
32
R31T
33
R32T
35
R4T
36
R2T
37
R7T
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve.
38
R5T
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger.
39
R6T
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
40
R9T
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.
Refrigerant Circuit
Si37-701
Refrigerant Circuit
REMQ10PY1, 12PY1
40
Stop Valve
Liquid Pipe
39
24
7
38
22
35
36
37
15
23
S1NPH 17
Stop Valve
Equalizing Pipe
11
30
10
16
Stop Valve
Dual Pressure
Gas Pipe
19 S1PH
20 S2PH
32
33
25
12
14
1
INV
S1
13
27
29
26
18 S2NPL
Stop Valve
Gauge Port
31
Suction Pipe
Refrigerant Circuit
57
Refrigerant Circuit
1.5
Si37-701
No. in
refrigerant Symbol
system
diagram
58
Name
Major Function
M1C
M2C
M3C
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
M2F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y3E
Y2E
Y6S
10
Y5S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
11
Y4S
12
Y1S
13
Y7S
14
Y8S
15
Y3S
16
Y2S
This is used to switch dual pressure gas pipe to high pressure or low pressure.
17
18
19
S1PH
20
S2PH
21
S3PH
22
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
23
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
24
25
Refrigerant regulator
26
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
27
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
28
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD2
compressor.
29
Capillary tube
30
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
31
R8T
32
R31T
33
R32T
Thermistor (STD1 discharge pipe: Tds1) Used to detect discharge pipe temperature.
34
R33T
35
R4T
36
R2T
37
R7T
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve.
38
R5T
This detects temperature of gas pipe on the evaporator side for the subcooling heat
exchanger.
39
R6T
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
40
R9T
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.
Refrigerant Circuit
Si37-701
Refrigerant Circuit
REMQ14PY1, 16PY1
Stop Valve
Liquid Pipe
40
39
24
7
38
9
22
35
36
37
6
15
4
5
17
Stop Valve
Equalizing Pipe
30
S1NPH
23
11
10
Stop Valve
Dual Pressure
Gas Pipe
16
19 S1PH
20 S2PH
21 S3PH
33
34
32
INV
S1
25
S2
27
12
28
13
26
29
18 S2NPL
Stop Valve
Gauge Port
31
Suction Pipe
Refrigerant Circuit
59
Refrigerant Circuit
1.6
Si37-701
BSVQ100,160,250PV1
No.
1
Name
Electronic expansion valve (EVH)
Symbol
Y4E
2
3
Y5E
4
5
Y3E
Y2E
Y1E
6
Capillary tube
Note : Factory set of all EV opening : 60pls
Liquid
Function
Opens while in heating operation or all indoor units are in cooling
operation. (Max : 760pls)
Opens while in cooling operation. (Max : 760pls)
Opens while in heating operation or all indoor units are in cooling
operation. (Max : 480pls)
Opens while in cooling operation. (Max : 480pls)
Used to subcool liquid refrigerant of heating indoor unit while in cool/
heat simultaneous operation. (Max : 480pls)
Used to bypass high pressure gas to low pressure side.
Liquid
Dual pressure
Indoor
side
Outdoor
side
Gas
Suction
60
Refrigerant Circuit
Si37-701
1.7
Refrigerant Circuit
Indoor Units
FXCQ, FXFQ, FXZQ, FXKQ, FXDQ, FXDYQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ
Gas-side
piping
Fan
Liquid-side
piping
Filter
No.
Refrigerant Circuit
Name
Electronic
expansion valve
Suction air
thermistor
Liquid pipe
thermistor
Gas pipe
thermistor
Electronic
expansion valve Filter
Symbol
Y1E
Function
Used to control superheated degree of gas when
cooling and subcooled degree when heating.
R1T
R2T
R3T
61
Si37-701
Plan
18
10
19
17
13
11
14
16
23
15
12
22
33
34
Front View
40
4
3
36
5
9
38
6
20
8
21
46
37
47
31
48
32
42
39
45
1
2
62
35
Refrigerant Circuit
Si37-701
2.2
REYQ14P, 16P
Plan
10
17
19
13
18
14
11
16
15
23
12
22
32
33
Front View
40
36
3
5
9
38
6
20
46
21
47
30
48
37
41
39
45
31
1
2
Refrigerant Circuit
35
63
2.3
Si37-701
REMQ8P
Plan
31
10
25 REFRIGERANT REGULATOR
11
18
40
19
38
32
Front View
4
16
15
17
36
30
37
14
39
35
12
13
Note:
64
Si37-701
2.4
REMQ10P, 12P
Plan
31
10
25 REFRIGERANT REGULATOR
11
18
20
40
19
38
33
31
Front View
4
16
15
17
36
37
30
39
14
35
12
13
Note:
Refrigerant Circuit
2.5
Si37-701
REMQ14P, 16P
Plan
31
10
25 REFRIGERANT REGULATOR
19
11
20
7
21
8
18
34
40
33
32
38
Front View
4
16
15
17
6
36
30
37
39
35
3
12
13
Note:
66
Refrigerant Circuit
Cooling
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Cooling
Unit
Thermostat "OFF"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
Suction
Pipe
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
67
68
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Suction
Pipe
Dual
Pressure
Gas Pipe
Liquid
Pipe
Stop Valve
EVJ
Stop Valve
Stop Valve
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Heating Operation
Refrigerant Circuit
Refrigerant Circuit
Heating
Unit
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "ON"
Operation
"ON"
Thermostat "ON"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
69
70
Cooling
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVHS
EVSC
EVH
EVL
EVH
EVHS
EVSC
BS Unit
EVLS
Cooling
Unit
Thermostat "OFF"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Operation
"OFF"
EVH
EVLS
EVL
EVHS
EVSC
BS Unit
EVLS
EVH
EVL
EVHS
EVSC
BS Unit
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Indoor Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Indoor Unit
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
71
72
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "ON"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Heating
Unit
Heating
Unit
Operation
"OFF"
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tb
Tf
EVT
Tf
EVT
Tb
TL
Ta
In operation
of defrosting
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
73
74
Heating
Unit
Heating
Unit
Operation
"OFF"
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tdi
INV
S2NPL
Tsh
Tb
Tf
EVT
Tf
EVT
Tb
TL
Ta
In operation
of defrosting
Tsh
STD
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Cooling
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Cooling
Unit
Thermostat "OFF"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
INV
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
REYQ14P, 16P
Cooling Operation
75
76
Cooling
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
INV
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Heating Operation
Refrigerant Circuit
Refrigerant Circuit
Heating
Unit
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "ON"
Operation
"ON"
Thermostat "ON"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
INV
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
77
78
Cooling
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Cooling
Unit
Thermostat "OFF"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
INV
S2NPL
Tsh
INV
Tdi
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
INV
S2NPL
Tsh
INV
Tdi
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
79
80
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "ON"
Operation
"ON"
Cooling
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
Tdi
INV
S2NPL
Tsh
INV
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
Tsh
INV
S2NPL
In operation
of defrosting
Tsh
INV
Tdi
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
SVG
Right
Left
Si37-701
Refrigerant Flow for Each Operation Mode
81
82
Heating
Unit
Operation
"OFF"
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVL
EVH
EVHS
EVSC
BS Unit
Heating
Unit
Thermostat "OFF"
Operation
"ON"
Heating
Unit
Thermostat "ON"
Operation
"ON"
Indoor Unit
Stop Valve
EVJ
Stop Valve
Dual
Pressure
Gas Pipe
Liquid
Pipe
Suction Pipe
SVP
Equalizing
Pipe
Equalizing
Pipe
Tsc
TS_A
S1NPH
Liquid
Pipe
TS_A
20SB
In operation
of defrosting
Tsh
Tdi
INV
S2NPL
Tsh
INV
HPS
20SA
Tg
Tdi
HPS
20SA
Tg
Tsc
Ta
Tf
Tf
EVT
Tb
TL
Tb
EVT
EVM
SVE
EVM
SVE
SVO
Refrigerant
Regulator
SVL
Right
Left
Refrigerant Circuit
Refrigerant Circuit
Operation "ON"
Theromstat "ON"
Cooling
Unit
Operation "ON"
Theromstat "OFF"
Cooling
Unit
Operation "OFF"
Cooling
Unit
Indoor Unit
EVH
EVHS
EVLS
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Tsc
SVP
Suction Pipe
Stop Valve
EVJ
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
TL
Tf
SVE
EVT
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Si37-701
Refrigerant Flow for Each Operation Mode
REYQ18P, 20P
Cooling Operation
83
84
Operation "ON"
Theromstat "ON"
Heating
Unit
Operation "ON"
Theromstat "OFF"
Heating
Unit
Operation "OFF"
Heating
Unit
Indoor Unit
EVH
EVHS
EVLS
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
Tf
SVE
EVT
TL
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Heating Operation
Refrigerant Circuit
Refrigerant Circuit
EVH
EVLS
EVL
EVLS
EVHS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Operation "ON"
Theromstat "ON"
Heating
Unit
Operation "ON"
Theromstat "ON"
Heating
Unit
Operation "OFF"
Theromstat "ON"
Cooling
Unit
Indoor Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
TL
Tf
SVE
EVT
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Si37-701
Refrigerant Flow for Each Operation Mode
85
86
EVH
EVLS
EVL
EVLS
EVHS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Operation "OFF"
Cooling
Unit
Operation "ON"
Theromstat "OFF"
Cooling
Unit
Operation "ON"
Theromstat "ON"
Cooling
Unit
Indoor Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
Tf
SVE
EVT
TL
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Refrigerant Circuit
Refrigerant Circuit
EVH
EVLS
EVL
EVLS
EVHS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Theromstat "OFF"
Heating
Unit
Operation "ON"
Theromstat "OFF"
Heating
Unit
Operation "ON"
Theromstat "ON"
Heating
Unit
Indoor Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
Tf
SVE
EVT
TL
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Si37-701
Refrigerant Flow for Each Operation Mode
87
88
EVH
EVLS
EVL
EVLS
EVHS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Operation "ON"
Theromstat "ON"
Heating
Unit
Operation "ON"
Heating
Unit
Operation "ON"
Theromstat "ON"
Cooling
Unit
Indoor Unit
Tsc
SVP
Suction Pipe
Stop Valve
EVJ
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
Tf
SVE
EVT
TL
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Refrigerant Circuit
Refrigerant Circuit
EVH
EVLS
EVL
EVLS
EVHS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Operation "OFF"
Heating
Unit
Operation "ON"
Theromstat "OFF"
Heating
Unit
Operation "ON"
Theromstat "ON"
Heating
Unit
Indoor Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
INVFAN
Tsh
Tf
SVE
EVT
TL
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
S1NPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
S2NPL
S1
Tb
Tds1
HPS
INVFAN
In operation
of defrosting
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Si37-701
Refrigerant Flow for Each Operation Mode
89
90
Heating
Unit
Heating
Unit
Heating
Unit
Indoor Unit
EVH
EVHS
EVLS
EVL
EVLS
EVHS
EVSC
EVH
EVL
EVLS
EVSC
EVH
EVL
EVHS
EVSC
BS Unit
Tsc
SVP
EVJ
Suction Pipe
Stop Valve
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
SENPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
SENPL
INVFAN
In operation
of defrosting
Tsh
TL
Tf
SVE
EVT
SVT
Tb
EVM
SVO
Refrigerant
Regulator
SVL
SVG
Tsc
EVJ
Suction Pipe
Stop Valve
SVP
Equalizing Pipe
Stop Valve
Liquid Pipe
Stop Valve
SENPH
TS_A
Gauge
Port
20SB
Tdi
HPS
20SA
INV
Tg
SENPL
S1
Tb
Tds1
HPS
INVFAN
Tsh
Tf
EVM
SVT
SVE
EVT
TL
SVO
Refrigerant
Regulator
SVL
SVG
Refrigerant Circuit
Si37-701
Tsc
Right
TL
EVT
Tsh
SVE
Tg
Tb
20SA
Tf
Pressure
regulating valve
EVM
SVL
Ta
SENPH
Equalizing
Pipe
SVP
Refrigerant
Regulator
HPS
Tdi
SVG
INV
SVO
SENPL
TS_A
Suction Pipe
2. Discharge of refrigerant
Discharge refrigerant from refrigerant regulator by opening of SVC when the load of the
outdoor unit is large.
Liquid
Pipe
Tsc
Right
TL
EVT
Tsh
SVE
Tg
Tb
20SA
Tf
Pressure
regulating valve
EVM
SVL
Ta
SENPH
Equalizing
Pipe
SVP
Refrigerant
Regulator
HPS
Tdi
SVG
INV
SVO
Suction Pipe
TS_A
SENPL
Refrigerant Circuit
91
Si37-701
In cooling
operation
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
EVHS
Dual
Pressure
Gas Pipe
EVH
EVL
Cooling
Unit
Suction
Pipe
EVLS
In equalization
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
(Close)
EVHS (Open)
Dual
Pressure
Gas Pipe
EVH (Close)
EVL (Close)
Suction
Pipe
EVLS (Close)
To heating
operation
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
EVHS
Dual
Pressure
Gas Pipe
EVH
EVL
Heating
Unit
92
Suction
Pipe
EVLS
Refrigerant Circuit
Si37-701
In heating
operation
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
EVHS
Dual
Pressure
Gas Pipe
EVH
EVL
Heating
Unit
Suction
Pipe
EVLS
In equalization
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
(Close)
EVHS (Close)
Dual
Pressure
Gas Pipe
EVH (Close)
EVL (Close)
To cooling
operation
Suction
Pipe
In
equalization
EVLS (Open)
Indoor Unit
BS Unit
Liquid
Pipe
EVSC
EVHS
Dual
Pressure
Gas Pipe
EVH
EVL
Cooling
Unit
Refrigerant Circuit
Suction
Pipe
EVLS
93
94
Si37-701
Refrigerant Circuit
Si37-701
Part 4
Function
1. Function General...................................................................................96
1.1 Symbol ...................................................................................................96
1.2 Operation Mode......................................................................................98
2. Basic Control.........................................................................................99
2.1
2.2
2.3
2.4
2.5
2.6
3. Special Control....................................................................................111
3.1
3.2
3.3
3.4
3.5
3.6
3.7
5. Other Control.......................................................................................132
5.1 Backup Operation.................................................................................132
5.2 Demand Operation ...............................................................................132
5.3 Heating Operation Prohibition ..............................................................132
Function
95
Function General
Si37-701
1. Function General
1.1
Symbol
20SA
Symbol
Electric symbol
Description or function
REYQ8~16P REMQ8~16P
Y2S
(Heat
exchanger1)
Y9S
(Heat
exchanger2)
Y3S
20SB
Y8S
Y2S
DSH
DSHi
DSHs
EV
Y1E
Y3E
EVM
EVT
Y1E (Main1)
Y3E (Main2)
Y2E
(Subcooling1)
Y5E
(Subcooling2)
EVJ
Y4E
Y2E
HTDi
HTDs
Pc
S1NPH
S1NPH
Pe
S2NPL
S2NPL
SH
SHS
Y6S
SVE
Y5S
(Bypass1)
Y10S
(Bypass2)
SVP
Y4S
Y5S
SVL
Y3S
Y4S
SVG
Y1S
Y1S
SVO
Y7S
Y7S
SVT
Y6S
Y8S
96
Function
Si37-701
Symbol
Ta
TsA
Tb
Tg
Tf
Tsh
Tl
Tsc
Function General
Electric symbol
Description or function
REYQ8~16P REMQ8~16P
R1T (A1P)
R8T (Suction
pipe1)
R10T (Suction
pipe2)
R4T
(Deicer1)
R12T
(Deicer2)
R2T
(Gas pipe1)
R11T
(Gas pipe2)
R7T
(Liquid pipe1)
R15T
(Liquid pipe2)
R5T
(Gas pipe1)
R13T
(Gas pipe2)
R6T
(Liquid pipe1)
R14T
(Liquid pipe2)
R9T, R14T
R1T (A1P)
R8T
R4T
R2T
R7T
Temperature of liquid pipe between heat exchanger and main electronic expansion
valve
R5T
R6T
R9T
Temperature of liquid pipe between liquid shutoff valve and supercooled heat
exchanger
Tc
TcS
Target temperature of Tc
Te
TeS
Target temperature of Te
Tfin
R1T (A3P)
Tp
Tdi
Tds
R32T
Function
R32T, R33T
97
Function General
1.2
Si37-701
Operation Mode
Thermostat ON
Operation in
stop mode
Indoor unit
stop or
thermostat
OFF
Operation
mode
changeover
Pressure egualization
prior to startup
Restart
stanby
Thermostat ON
Malfunction/
Stanby
Rotation
Malfunction/
Stanby
Heating
startup
Thermostat ON
After completion of
startup control
Malfunction/
Stanby
Pump-down
residual
operation
Operation
mode
changeover
Normal operation
Large capacity
Compressor PI control
startup
Motorized valve PI control
Protection control
in
operation
Malfunction/
Stanby
Oil return IN
conditions are met
Yes
Oil return
operation
No
Defrost IN
conditions are met
Yes
Defrosting
operation
No
Operation mode
changeover
Yes
Operation mode
changeover
Mode
changeover
No
Malfunction/Stand by
Oil return, Defrost and Mode changeover move on to the next process after the completion of
above function in progress even if the thermostat is OFF during the operation.
98
Function
Si37-701
Basic Control
2. Basic Control
2.1
Normal Operation
Symbol
Compressor 1
(Electric
Symbol)
M1C
Compressor 2
M2C
Compressor 3
M3C
M1F
M2F
Y1E
Electronic expansion valve
(Main)
EVM
Y3E
EVT
Y2E
Y5E
PI control
PI control
PI control
EVJ
Y4E
80 pls
80 pls
80 pls
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON for refrigerant
recovery
ON for refrigerant
recovery
ON for refrigerant
discharge
OFF
ON for refrigerant
recovery
ON for refrigerant
recovery
ON for refrigerant
discharge
Y2S
Four way valve
(Heat exchanger switch)
20SA
Y9S
20SB
SVP
Y5S
Y10S
Y4S
SVL
Y3S
SVG
Y1S
SVO
Y7S
OFF
ON for refrigerant
recovery
ON for refrigerant
recovery
ON for refrigerant
discharge
SVT
Y6S
ON for oil level control ON for oil level control ON for oil level control
Y8S
Normal cooling
Remote controller setting
OFF
Remote controller setting
Normal opening *1
0 pls
0 pls
Normal heating
Remote controller setting
OFF
LL
Normal opening *2
192 pls
192 pls
Function
Normal cooling
760 pls (fully opened)
760 pls (fully opened)
480 pls (fully opened)
480 pls (fully opened)
0 pls
99
Basic Control
2.2
Si37-701
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te set value (Make this setting while in Setting
mode 2.)
Te setting
L
M (Normal)
H
(factory
setting)
3
6
7 8 9 10 11
[Heating operation]
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Te set value (Make this setting while in Setting
mode 2.)
Tc setting
L
M (Normal)
H
(factory
setting)
43
46
48
Outdoor Unit 1
Priority 1
Priority 2
Priority 1
Outdoor Unit 2
Priority 2
Priority 1
Priority 2
Outdoor Unit 1
Priority 1
Priority 3
Priority 2
Outdoor Unit 2
Priority 2
Priority 1
Priority 3
Outdoor Unit 3
Priority 3
Priority 2
Priority 1
Priority 1
Priority 2
Priority 3
100
Function
Si37-701
Basic Control
Operating Priority and Rotation of Compressors (For multi standard connection system)
Each compressor operates in the following order of priority.
In the case of multi-outdoor-unit system, each compressor operates in any of Pattern 1
through Pattern 3 according to the rotation of outdoor units.
Pattern 1
Pattern 2
Pattern 3
REYQ14P, 16P
No. 2 No. 1
No. 2 No. 1
STD1
INV2
INV
INV1
REYQ22P, 24P
REYQ18P, 20P
No. 1
No. 2 No. 3
No. 1 No. 3
No. 2 No. 4
No. 2
No. 1 No. 3
No. 2 No. 4
No. 1 No. 3
INV
INV
INV
INV
STD1
STD1
STD1
REYQ30P, 32P
REYQ26P, 28P
No. 1 No. 3
No. 2 No. 4
INV
STD1
INV
INV
STD1 STD2
STD1 STD2
INV
STD1 STD2
REYQ34P, 36P
No. 1
No. 2
No. 4
No. 3
No. 1
No. 4
No. 2
No. 3
No. 5
INV
Function
INV
STD1
INV
STD1 STD2
101
Basic Control
Si37-701
REYQ38P, 40P
No. 1 No. 4
No. 2 No. 5
No. 3 No. 6
No. 1 No. 4
No. 2 No. 5
No. 3 No. 6
INV
INV
STD1
STD1
INV
STD1 STD2
REYQ42P, 44P
No. 1 No. 4
No. 3 No. 6
No. 2 No. 5
INV
INV
INV
STD1
STD1 STD2
STD1 STD2
REYQ46P, 48P
INV
INV
INV
STD1 STD2
STD1 STD2
STD1 STD2
*
In the case of combination of 3 outdoor units, the above diagram shows master unit, slave unit 1, and slave unit 2
from left to right.
Compressors may operate in any pattern other than those mentioned above according to the operating status.
102
Function
Si37-701
Basic Control
Compressor Step Control (Multi outdoor unit connection is available on the standard connection system)
Compressor operations vary with the following steps according to information in "2.2 Compressor PI Control".
Furthermore, the operating priority of compressors is subject to information in " Operating Priority and Rotation of
Compressors".
Single unit installation
REYQ8PY1, 10PY1, 12PY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
INV
52Hz
56Hz
62Hz
68Hz
74Hz
80Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
132Hz
144Hz
158Hz
166Hz
176Hz
188Hz
202Hz
210Hz
52Hz
62Hz
68Hz
74Hz
80Hz
88Hz
96Hz
104Hz
116Hz
124Hz
132Hz
144Hz
158Hz
176Hz
188Hz
202Hz
210Hz
STD1
Initial step
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
REYQ14PY1, 16PY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
INV1
52Hz
56Hz
62Hz
66Hz
70Hz
74Hz
80Hz
88Hz
92Hz
96Hz
104Hz
110Hz
116Hz
124Hz
132Hz
144Hz
158Hz
166Hz
176Hz
188Hz
202Hz
210Hz
218Hz
232Hz
248Hz
266Hz
INV2
52Hz
56Hz
62Hz
66Hz
70Hz
74Hz
80Hz
88Hz
92Hz
96Hz
104Hz
110Hz
116Hz
124Hz
132Hz
144Hz
158Hz
166Hz
176Hz
188Hz
202Hz
210Hz
218Hz
232Hz
248Hz
266Hz
Initial step
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
STD2 : Standard compressor 2
2. Depending on the operating conditions of compressors, the compressors may run in patterns
other than those aforementioned.
Function
103
Basic Control
Si37-701
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
104
Function
Si37-701
Basic Control
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
105
Basic Control
Si37-701
STD
Initial step
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
ON3
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
STD
Initial step
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
STD
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
ON4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
106
Function
Si37-701
Basic Control
STD
Initial step
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON4
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
STD
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
ON5
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
STD
Initial step
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON4
ON5
ON5
ON5
ON5
ON5
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
STD
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON1
ON2
ON2
ON2
ON2
ON2
ON3
ON3
ON3
ON3
ON3
ON4
ON4
ON4
ON4
ON4
ON5
ON5
ON5
ON5
ON5
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
ON6
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
107
Basic Control
2.3
Si37-701
2.4
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
Fan revolutions (rpm)
STEP No.
0
1
2
3
4
5
6
7
8
9
Single type
8HP
10HP
12HP
14HP
16HP
0
0
0
0
0
285/255 285/255 285/255 285/255 285/255
315/285 315/285 315/285 360/315 360/315
360/330 360/330 360/330 395/365 395/365
430/400 430/400 430/400 480/440 480/440
590/560 590/560 590/560 560/530 560/530
690/660 690/660 690/660 760/730 760/730
820/790 820/790 820/790 960/930 960/930
920/890 920/890 951/931 1125/1095 1155/1125
920/890 920/890 1020/990 1125/1095 1200/1170
Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2
M8
0
350
370
400
450
540
610
680
710
796
M10
0
350
370
400
450
560
680
710
750
821
Multiple type
M12
M14
M16
0
0/0
0/0
350
230/0
230/0
370
380/0
380/0
400
290/260 290/260
450
375/345 375/345
560
570/540 570/540
680
720/690 720/690
710
910/880 910/880
775
1091/1061 1091/1061
870
1136/1106 1136/1106
Fan1/Fan2 Fan1/Fan2
* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
108
Function
Si37-701
2.5
Basic Control
Pc>3.28MPa
PI control
Fan step 8
PI control
Pc>3.18MPa
Fan step 7
Pc>3.08MPa
PI control
Lapse of 20 sec.
PI control
Hold
the
current
-1 step on
+1 step on
step on outdoor
outdoor unit fan
outdoor
unit fan
unit fan
PI control
Function
Lapse of 20 sec.
109
Basic Control
2.6
Si37-701
Note:
Unit 1
Condenser
Condenser
Condenser
Condenser
Not in use
Evaporator
Evaporator
Unit 2
Condenser
Condenser
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
Unit 3
Condenser
Evaporator
Not in use
Evaporator
Not in use
Not in use
Evaporator
*
GR is a numeric value representing the current balance state
that is calculated from the target condensing temperature,
target evaporating temperature, current condensing
temperature, and current evaporating temperature.
The mode for an single type and a multi type with two units connected is Unit 1 Mode and Unit 2
Mode. Unit 1 Mode, Unit 2 Mode and Unit 3 Mode are available only for three unit connected
multi type.
[Independent system]
Outdoor unit
Outdoor unit
Condenser Condenser
Evaporator
GR > 25
GR < -20
GR > 15
Outdoor unit
condensing temperature,
target evaporating
Outdoor unit
GR > 25
Evaporator Condenser
GR < -10
temperature, current
Evaporator Evaporator
condensing temperature,
and current evaporating
temperature.
Outdoor unit
2
A2
GR < -10
Outdoor unit
2
B1
3
A3
GR < -20
Outdoor unit
2
GR > 15
A4
GR > 25
110
Evaporator
B2
GR < -20
GR < -10
Outdoor unit
2
GR > 15
GR > 25
Evaporator Evaporator
GR < -10
Outdoor unit
1
GR > 15
Condenser Condenser
Outdoor unit
1
B3
GR < -10
Outdoor unit
1
Function
Si37-701
Special Control
3. Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
Symbol
Compressor 1
Compressor 2
Elect.
symbol
Control
before
startup
Startup control
STEP1
M1C
Compressor 3
M2C
0 Hz
52 Hz+OFF+OFF
52Hz+OFF+OFF+2STEP /
20 sec.
(Until it reaches
Pc-Pe>0.39 MPa)
STEP4
Ta<20C: OFF
Ta20C: STEP4
M3C
M1F
STEP2
M2F
Electronic expansion
valve (Main)
EVM
Y1E
Y3E
0 pls
1375 pls
1375 pls
Electronic expansion
valve (Supercooling)
EVT
Y2E
Y5E
0 pls
0 pls
0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ
Y4E
80 pls
80 pls
80 pls
20SA
Y2S
Y9S
OFF
OFF
OFF
20SB
Y8S
ON
ON
ON
SVE
Y5S
Y10S
OFF
ON
ON
SVP
Y4S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
liquid pipe )
SVL
Y3S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
gas vent pipe)
SVG
Y1S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
exhaust pipe)
SVO
Y7S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT
Y6S
OFF
OFF
OFF
A lapse
of 60
sec.
A lapse of 15 sec.
OR
Ending conditions
Function
A lapse of 90 sec.
Pc - Pe>0.39 MPa
111
Special Control
Si37-701
Symbol
Compressor 1
Compressor 2
Elect.
symbol
Control
before
startup
Startup control
STEP1
M1C
M2C
Compressor 3
M3C
M1F
STEP2
0 Hz
52 Hz+OFF+OFF
52Hz+OFF+OFF+2STEP /
20 sec.
(Until it reaches
Pc-Pe>0.39 MPa)
STEP4
20SA=ON: STEP7
20SA=OFF
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
20SA=ON: STEP7
20SA=OFF
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
M2F
Electronic expansion
valve (Main)
EVM
Y1E
Y3E
0 pls
20SA=ON: SH Control
20SA=OFF: 1375 pls
20SA=ON: SH Control
20SA=OFF: 1375 pls
Electronic expansion
valve (Supercooling)
EVT
Y2E
Y5E
0 pls
0 pls
0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ
Y4E
80 pls
80 pls
80 pls
20SA
Y2S
Y9S
When
outdoor
heat
exchanger
is
evaporator
: ON
When
outdoor
heat
exchanger
is
condenser
: OFF
20SB
Y8S
OFF
OFF
OFF
SVE
Y5S
Y10S
OFF
OFF
OFF
SVP
Y4S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
liquid pipe )
SVL
Y3S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
gas vent pipe)
SVG
Y1S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
exhaust pipe)
SVO
Y7S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT
Y6S
OFF
OFF
OFF
A lapse
of 60
sec.
A lapse of 15 sec.
OR
Ending conditions
112
A lapse of 90 sec.
Pc - Pe>0.39 MPa
Function
Si37-701
3.2
Special Control
For startup, oil return operation, or setup after defrosting, start up multiple compressors at a high speed according to the
conditions of indoor units with thermostat ON, thus maximizing the equipment capacity.
INV
STD
25
20
Pc
9
15
Pressure
8
7
10
Number of
compressors
6
5
Pe
5
4
3
Time
[Control]
1. Start multiple INV compressors in the system at one time.
2. Start multiple STD compressors in the system at intervals of 15 seconds.
Function
113
Special Control
3.3
Si37-701
This function is used to recover refrigerant oil that flows out from the compressor to the system side by conducting oil
return operation in order to prevent the compressor from running out of refrigerant oil.
Symbol
Compressor 1
Compressor 2
M1C
Compressor 3
Outdoor unit fan 1
Outdoor unit fan 2
Elect. symbol
M2C
M3C
M1F
M2F
52Hz+ON+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used
before oil return operation)
52Hz+ON+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used
before oil return operation)
20SA
Y2S
Y9S
OFF
OFF
20SB
Y8S
ON
ON
Electronic expansion
valve (main)
EVM
Y1E
Y3E
1375pls
1375pls
Electronic expansion
valve (subcooling)
EVT
Y2E
Y5E
SH control
SH control
Electronic expansion
valve (refilling refrigerant) EVJ
Y4E
80pls
80pls
SVE
Y5S
Y10S
ON
ON
SVP
Y4S
OFF
OFF
SVL
Y3S
0pls
0pls
SVG
Y1S
0pls
0pls
Y7S
0pls
0pls
Y6S
0pls
0pls
End conditions
or
or
114
Function
Si37-701
Special Control
Thermo ON unit
Fan
Motorized valve
OFF
Thermo ON unit
192pls
Elect. symbol
Y4E
600pls
Y5E
760pls
Y2E
480pls
Y3E
480pls
Y1E
0pls
Function
115
Special Control
Si37-701
Symbol
Compressor 1
Compressor 2
Elect. symbol
M1C
Compressor 3
M2C
M3C
M1F
M2F
EVT
Y1E
Y3E
Y2E
Y5E
PI control
EVJ
Y4E
80pls
20SA
Y2S
Y9S
Four way valve (for high- and lowpressure gas pipe selection)
20SB
Y8S
OFF
SVE
OFF
SVP
Y5S
Y10S
Y4S
0pls
SVL
Y3S
0pls
SVG
Y1S
0pls
SVO
Y7S
0pls
SVT
Y6S
0pls
EVM
End conditions
or
Pe_min<0.22MPa
After a lapse of 9 min.
116
Function
Si37-701
Fan
Motorized valve
Fan
Motorized valve
Special Control
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Function
Y1E
117
Special Control
3.4
Si37-701
Defrost Operation
[Start conditions]
Referring to the following conditions, start defrost operation.
When there is a decrease in the coefficient of heat transfer of outdoor unit heat exchanger
When there is a drop in the temperature of outdoor unit heat exchanger outlet (Tb)
&
When the low pressure stays low for a certain amount of time (2 hours minimum)
Furthermore, the thermal conductivity of outdoor unit heat exchanger is calculated by Tc, Te, and compressor loads.
Defrosting outdoor unit actuator
Elect.
Symbol symbol
Compressor 1
M1C
Defrost operation
Compressor 3
M3C
REYQ81012P: 232Hz+ON
REYQ1416P: 232Hz+232Hz
REMQ8P: 210Hz
REMQ1012P: 210Hz+ON
REMQ1416P: 202Hz+ON+ON
M1F
OFF
OFF
Pcmax<2.36MPa
Pcmax>2.45MPa
Pcmax<2.36MPa Pcmax>2.45MPa
Compressor 2
M2C
FANSTEP4
FANSTEP4
M2F
Pcmax>3.04MPa
Pcmax<2.95MPa Pcmax>3.04MPa
Pcmax<2.95MPa
FANSTEP6
FANSTEP6
20SA
Y2S
Y9S
OFF
OFF
20SB
Y8S
Holds
Holds
EVM
1375pls
0pls
EVT
Y1E
Y3E
Y2E
Y5E
SH control
0pls
EVJ
Y4E
80pls
80pls
SVE
ON
OFF
SVP
Y5S
Y10S
Y4S
OFF
OFF
SVL
Y3S
0pls
0pls
SVG
Y1S
0pls
0pls
SVO
Y7S
0pls
0pls
SVT
Y6S
0pls
0pls
or
or
30 sec.
Pc_max>3.04MPa
or
118
Function
Si37-701
Special Control
Symbol
Compressor 1
Compressor 2
Compressor 3
Elect.
symbol
Defrost operation
M1C
REYQ81012P: 232Hz+ON
REYQ1416P: 232Hz+232Hz
REMQ8P: 210Hz
REMQ1012P: 210Hz+ON
REMQ1416P: 210Hz+ON+ON
M2C
M3C
Fan control
Fan control
20SA
M1F
M2F
Y2S
Y9S
ON
ON
20SB
Y8S
Holds
Holds
EVM
PI control
PI control
EVT
Y1E
Y3E
Y2E
Y5E
SH control
0pls
EVJ
Y4E
80pls
80pls
SVE
OFF
OFF
SVP
Y5S
Y10S
Y4S
OFF
OFF
SVL
Y3S
0pls
0pls
SVG
Y1S
0pls
0pls
SVO
Y7S
0pls
0pls
SVT
Y6S
0pls
0pls
Fan
Motorized valve
Defrost operation
Motorized valve
Defrost operation
Remote controller setting
OFF
Remote controller setting
Normal opening degree
0pls
0pls
Thermo ON unit
Unit not in operation
Thermo OFF unit
Thermo ON unit
Unit not in operation
Thermo OFF unit
REYQ
OFF
OFF
OFF
0pls
0pls
0pls
REMQ
LL
LL
LL
224pls
0pls
224pls
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Defrost operation
0pls
760pls
0pls
480pls
0pls
Elect. symbol
Y4E
Y5E
Y2E
Y3E
Y1E
Defrost operation
760pls
0pls
60pls
0pls (REYQ8~16P) 60pls (REMQ8~16P)
0pls (PI control for cool/heat concurrent operation)
Function
119
Special Control
3.5
Si37-701
Symbol
Compressor 1
Compressor 2
M1C
Compressor 3
Outdoor unit fan 1
Elect.
symbol
M2C
124 Hz+OFF+OFF
OFF
Fan control
Fan control
M3C
M1F
M2F
EVM
Y1E
Y3E
1375 pls
1375 pls
EVT
Y2E
Y5E
0 pls
0 pls
EVJ
Y4E
80 pls
80 pls
20SA
Y2S
Y9S
OFF
OFF
20SB
Y8S
ON
ON
SVE
Y5S
Y10S
ON
ON
SVP
Y4S
OFF
OFF
SVL
Y3S
OFF
OFF
SVG
Y1S
OFF
OFF
SVO
Y7S
OFF
OFF
SVT
Y6S
OFF
OFF
Ending conditions
or
5 min.
Pe_min<0.49 MPa
Pc_max<2.94 MPa
Master unit Tdi>110C
Master unit Tp>125C
* Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
120
Function
Si37-701
Special Control
Symbol
Compressor 1
Compressor 2
M1C
Compressor 3
Outdoor unit fan 1
Elect.
symbol
M2C
124 Hz+OFF+OFF
OFF
Fan control
Fan control
M3C
M1F
M2F
EVM
Y1E
Y3E
EVT
Y2E
Y5E
0 pls
0 pls
EVJ
Y4E
80 pls
80 pls
20SA
Y2S
Y9S
20SB
Y8S
OFF
OFF
SVE
Y5S
Y10S
OFF
OFF
SVP
Y4S
OFF
OFF
SVL
Y3S
OFF
OFF
SVG
Y1S
OFF
OFF
SVO
Y7S
OFF
OFF
SVT
Y6S
OFF
OFF
Ending conditions
or
3 min.
Pe_min<0.25 MPa
Pc_max<3.13 MPa
Master unit Tdi>110C
Master unit Tp>140C
* Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
Function
121
Special Control
3.6
Si37-701
Standby
Elect.
symbol
Compressor1
Compressor2
Actuator
Operation
REYQ8~16P
REMQ8P
REMQ1012P
REMQ1416P
M1C
OFF
OFF
OFF
OFF
M2C
OFF
OFF
OFF
Compressor3
M3C
OFF
MF1
Ta>30C: STEP4
Ta30C: OFF
Ta>30C: STEP4
Ta30C: OFF
Ta>30C: STEP4
Ta30C: OFF
Ta>30C: STEP4
Ta30C: OFF
MF2
Ta>30C: STEP4
Ta30C: OFF
Ta>30C: STEP4
Ta30C: OFF
EVM
Y1E
Y3E
0 pls
EVT
Y2E
Y5E
0 pls
EVJ
Y4E
80 pls
20SA
Y2S
Y9S
Holds
20SB
Y8S
Holds
SVE
Y5S
Y10S
OFF
SVP
Y4S
OFF
SVL
Y3S
OFF
SVG
Y1S
OFF
SVO
Y7S
OFF
SVT
Y6S
OFF
Ending conditions
2 min.
122
Discharge pipe
temperature > 75C
Crankcase heater
ON
Function
Si37-701
3.7
Special Control
Stopping Operation
Elect.
symbol
Compressor1
Compressor2
Compressor3
Actuator
Operation
REYQ8~16P
REMQ8P
REMQ1012P
REMQ1416P
M1C
OFF
OFF
OFF
OFF
M2C
OFF
OFF
OFF
M3C
OFF
M1F
OFF
OFF
OFF
OFF
M2F
OFF
OFF
EVM
Y1E
Y3E
0 pls
EVT
Y2E
Y5E
0 pls
EVJ
Y4E
80 pls
20SA
Y2S
Y9S
Holds
20SB
Y8S
Holds
SVE
Y5S
Y10S
OFF
SVP
Y4S
OFF
SVL
Y3S
OFF
SVG
Y1S
OFF
SVO
Y7S
OFF
SVT
Y6S
OFF
Ending conditions
Judgment Criteria
Malfunction Code
0.07MPa
E4
4.0MPa
E3
135C
F3
U1
L8
93C
L4
Function
123
Protection Control
Si37-701
4. Protection Control
4.1
When high
pressure is limited
Pc_max
>3.47MPa
Pc_max
>3.55MPa
Upper limit
compressor step:
2-step down
After 10 sec.
Pc_max
<3.24MPa
Upper limit
compressor step:
1-step up
Pc_max
>3.64MPa
High pressure
standby
124
Function
Si37-701
Protection Control
Pc_max>3.31MPa
Pc_max<2.94MPa
When high
pressure is limited
Compressor step:
7 STEP down
Pc_max
>3.42MPa
&
After 10 sec.
Pc_max>3.31MPa
Pc_max>3.64MPa
High pressure
standby
Function
125
Protection Control
4.2
Si37-701
Because of common low pressure, the following control is performed in the system.
Pe_min indicates the minimum value within the system.
Normal Operation
Pe_min<0.34MPa
Pe_min>0.39MPa
Single type:
8~12HP: 52Hz+OFF
14~16HP: 52Hz+52Hz (upper limit)
Multi type:
52Hz+OFF+OFF (upper limit)
Pe_min<0.07MPa
Low pressure
standby
126
Function
Si37-701
Protection Control
Pe_min
<0.17MPa
&
Pe_min>0.23MPa
Upper limit compressor step=max (Max. step)
Compressor step:
2-step down
After 10 sec.
Pe_min
>0.27MPa
Pe_min
<0.17MPa
Pe_min
<0.13MPa
Current
step maintained
After 15 sec.
Pe_min
>0.20MPa
Upper limit compressor step:
2-step up
After 15 sec.
After 10 sec.
Pe_min<0.07MPa
Low pressure
standby
Function
127
Protection Control
4.3
Si37-701
The following control is performed for each compressor of single unit as well as multi units.
[INV compressor]
Normal operation
or
HTdi>115C
Tp>135C
&
or
HTdi<100C
Tp<110C
INV upper limit step=max (Max. step)
HTdi>115C
Tp>135C
&
HTdi<110C
Tp<125C
Frequency agreement
HTdi>130C
or
or
HTdi>135C
HTdi>120C continues for 10 minutes or more.
Discharge pipe
temperature
standby
[STD compressor]
HTds : Value of STD compressor discharge
pipe temperature ( Tds) compensated
with outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.
or
Applicable STD
compressor stops.
After 10 min.
128
Function
Si37-701
4.4
Protection Control
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
Perform the following control of integrated as well as multi units for each INV compressor.
Normal operation
&
10 seconds
Current status
maintained
Inverter current value
<14.7A
continues for 20 seconds
INV Comp. upper limit
step: 1-step up
Function
129
Protection Control
Si37-701
Perform the following control of integrated as well as multi units for each INV compressor.
Normal operation
Tfin>84C
&
Tfin<81C
INV upper limit frequency=max (210Hz)
Tfin>93C
130
Function
Si37-701
4.5
Protection Control
Demand to operate.
Function
131
Other Control
Si37-701
5. Other Control
5.1
Backup Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor
unit from operating, and then conduct emergency operation only with operational compressors
or outdoor units.
"Emergency operation with remote controller reset" and "Emergency operation with outdoor unit
PC board setting" are available
operation with (2) Emergency operation with
Operating method (1) Emergency
remote controller reset
outdoor unit PC board setting
(Auto backup operation)
(Manual backup operation)
Backup operation by the
REYQ8 ~ 16PY1
compressor
Backup
operation
by
the
Backup
operation by the
REYQ18 ~ 48PY1
indoor unit
outdoor unit
Applicable model
5.2
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using Demand 1 Setting or Demand 2 Setting.
To operate the unit with this mode, additional setting of Continuous Demand Setting or
external input by external control adapter is required.
Set item
Demand 1
Demand 2
5.3
Condition
Mode 1
Mode 2
Mode 3
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
132
Function
Si37-701
Start
(Option)
Turn ON
power supply
Aux. electric
52H
heater
: OFF
Humidifier Mu : OFF
Initialize electronic
expansion valve 20E
Detect louver lock
LED in remote
controller turns ON
Cyclic operation with
RUN/STOP pushbutton
Run or Stop?
Swing flap
Stop
No
Frost
prevention condition?
Yes
Yes
No
Run
Is the
safety device
activated?
No
Is the RUN
indicating lamp
blinking?
Microcomputer dry
ON/OFF
OFF
Yes
Fan: MF
Operating with set air flow rate
(Option)
Blast
*2
*4
Fan MF : Stop
Is
Restart prevention
operation in progress?
(5 min.)
No
Is
frost prevention
operation in progress?
Electronic
expansion valve 20E : Closed
Temp. control
Heating Operation
Blasting Operation
Drain
pump kit
Aux. electric
heater
(Option)
Is
test run
in progress?
(Option)
*3
No
Louver MA : Stop
Cooling or
Heating?
Heating
Cooling Operation
Cooling
ON
No
Blast or Temp.
control?
No
MP : OFF
*5
52H : OFF
Humidifier Mu : OFF
(Option)
Thermostat-ONoperation signal to
outdoor unit: Output
20E : Closed
Thermostat-ONoperation signal to
outdoor unit: Output
(Option)
*6
*1. If any malfunction occurs, the relevant malfunction code will be displayed according to the malfunction
code display of the remote controller.
*2. When the aux. electric heater turns ON, the fan will stop after it conducts residual operation for 1 min.
*3. When the drain pump kit turns ON, the drain pump kit will stop after it conducts residual operation for a
period of 5 min.
*4. If the evaporator inlet temperature is kept at not more than -5C for a period of cumulative 10 min. or
not more than -1C for a cumulative period of 40 min., frost prevention operation will be conducted. If
the evaporator inlet temperature is kept at not less than 7C for a consecutive period of 10 min., the
frost prevention operation will be reset.
*5. Thermostat status
Set temperature
OFF
ON
MP : ON
*6. The FXCQ, FXFQ, FXKQ, and FXSQ series have the drain pump kit as standard equipment.
Function
133
Si37-701
Heating Operation
(option)
Microcomputer
dry display
*7
Drain
pump kit
MP : OFF
*8
Thermostat status
OFF
Fan MF : Operating
in L mode after it stops for 6 min.
ON
Fan MF :
Operating in L mode
Electronic
expansion valve 20E :
Superheated degree control
No
Swing flap?
Electronic 20E :
expansion valve
Closed
*12
(Option)
*12
Yes
Swing flap
Is
defrost operation in Yes
progress?
No
*13
Is hot
Yes
starting in progress?
No
DEFROST/HOT START
indicating lamp: ON
DEFROST/HOT START
indicating lamp: OFF
Restart
prevention operating
in progress?
(4 min.)
Yes
No
Is test run
in progress?
(1)
*14
Thermostat status
(3)
(2)
(Option)
*9
Aux.
electric heater 52H
Blasting Operation
Aux.
electric heater 52H
: OFF
Humidifier Mu : OFF
(Option)
Drain
pump kit
MP : OFF
Aux.
electric heater
52H : OFF
*15
Yes
Swing flap
52H : ON
Humidifier Mu : ON
Is
outlet air temperature
drop protection in
progress?
Fan MF :
LL operation
No
Fan MF :
Operating with set air flow rate
Electronic 20E :
expansion valve
Closed
Aux.
electric heater 52H
: OFF
Humidifier Mu : OFF
Yes
Fan MF :
Operating in L mode
Fan MF :
Stop
No
*10
*11
Fan MF:
Operating with set air flow rate
Electronic 20E :
expansion valve
Closed
A
*9. Blasting operation
By setting the remote controller to BLAST, the
fan will operate with thermostat OFF in set
temperature control operation mode.
*10. Set wind direction
According to blasting instruction from the
remote controller, the wind direction is set to
100% horizontal while in heating operation.
*11. Fan
According to blasting instruction from the
remote controller, the fan is put into operation in
LL mode while in heating operation.
134
(Option)
Aux.
electric heater
: OFF
Humidifier Mu : ON
Humidifier Mu : OFF
Swing flap
(Option)
(Option)
Electronic
expansion valve 20E :
Open
(2)
b
-4
(1)
-2
Set temp.
Suction air temp.
Function
Si37-701
6.2
Thermostat Control
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
And, assuming suction temperature has changed from 30C to 18C (F A):
Body thermostat sensor is used for temperatures from 30C to 25C (F D).
Remote controller thermostat sensor is used for temperatures from 25C to 21C (D B).
Body thermostat sensor is used for temperatures from 21C to 18C (B A).
Function
135
Heating
Si37-701
When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesnt become cold by widening the range in which thermostat sensor in remote
controller can be used so that suction temperature is higher than the preset temperature.
Ex: When heating Assuming the preset temperature in the figure above is 24C, and
the suction temperature has changed from 18C to 28C (A D):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18C to 25C (A C).
Remote controller thermostat sensor is used for temperatures from 25C to 28C (C D).
And, assuming suction temperature has changed from 28C to 18C (D A):
Remote controller thermostat sensor is used for temperatures from 28C to 23C (D B).
Body thermostat sensor is used for temperatures from 23C to 18C (B A).
136
Function
Si37-701
Cooling operation:
Heating operation:
While in a single remote controller group control, the body thermostat is only used for this
control.
Furthermore, while in heating operation, cassette-mounted indoor units conduct the thermostat
control by a value compensated by -2C for the value detected with the body thermostat.
(Through field settings, the thermostat differential setting can be changed from 1C to 0.5C.
For details on the changing procedure, refer to information on page onward.)
In dry operation
Thermostat OFF
In dry operation
Thermostat OFF
Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of six
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor temperature while in thermostat OFF mode.)
Function
137
6.3
Si37-701
6.3.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
1. The objective of residual operation is to completely drain any moisture adhering to the fin of
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.3.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF :
138
Function
Si37-701
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
Note:
Function
If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. AF is then displayed as operation continues.
139
6.4
Si37-701
Freeze Prevention
Freeze
Prevention by Off
Cycle (Indoor
Unit)
When the temperature detected by liquid pipe temperature thermistor (R2T) of the indoor unit
heat exchanger drops too low, the unit enters freeze prevention operation in accordance with
the following conditions, and is also set in accordance with the conditions given below.
When freeze prevention is activated, the electronic expansion valve is closed, the drain pump
turns ON and the fan tap is fixed to L air flow. When the following conditions for stopping are
satisfied, it returns.
Conditions for starting freeze prevention: Temperature is -1C or less for total of 40 min., or
temperature is -5C or less for total of 10 min.
Conditions for stopping freeze prevention: Temperature is +7C or more for 10 min.
continuously
10 min.
+7C
0C
5C
Freeze prevention operation
Forced OFF by thermostat
(VG005)
10 min.
OR
10 min.
+7C
0C
1C
Freeze prevention operation
Forced OFF by thermostat
t1
t2
t3
t4
t >40min.
0C
OR
10 min.
+7C
+1C
Freeze prevention operation
Forced OFF by thermostat
t1
140
t2
t3
t4
t >15min.
Function
Si37-701
6.5
Set temperature
OFF
2C
2C
OFF
60C
Condensing pressure
equivalent saturated
temperature
OFF
Function
141
6.6
Si37-701
FXFQ
FXAQ
OFF
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Swing
OFF
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Swing
LL
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
LL
Hot start from thermostat Swing
OFF mode (for prevention
of cold air)
Wind direction set LL
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
OFF
Horizontal
Horizontal
Totally closed
Horizontal
Horizontal
Totally closed
Swing
Swing
Swing
Set
Set
Set
Swing
Swing
Swing
Swing
Set
Set
Set
Swing
Swing
Swing
Set
Set
Set
Swing
Horizontal
Horizontal
Totally closed
Set
Horizontal
Totally closed
Swing
Swing
Swing
Swing
Set
Set
Set
Swing
Flap
FXCQ
FXHQ
FXKQ
Defrosting operation
Swing
Stop
Thermostat ON in dry
operation using micro
computer
Thermostat OFF in dry
operation using micro
computer
Thermostat OFF in
Cooling cooling
Swing
L*1
OFF or L
Wind direction set
Swing
Set
OFF
Stop
Micro computer control
(including cooling
operation)
142
Function
Si37-701
6.7
Function
143
6.8
Si37-701
Fan
H/L remote
controller setting
LL
Louver
OFF
Remote controller
setting
Normal control
Po (Horizontal)
144
Function
Si37-701
6.9
P0
P1
P2
P3
P4
Standard Setting
position
P0
P0
P1
P1
P3
P4
P4
P4'
P0
P1
P2
P2
P0'
P1'
P2'
P2
Draft
prevention
position
P0
P4
P3'
P3
P4
P0''
P1''
P2''
P4'' P3''
Prohibited
P0'
P1'
P2'
P3'
P4'
Prohibited
Function
P0''
P1''
P2''
P3''
P4''
(VL012)
145
Si37-701
146
Function
Si37-701
Part 5
Test Operation
1. Test Operation ....................................................................................148
1.1 Installation Process ..............................................................................148
1.2 Procedure and Outline .........................................................................149
1.3 Operation when Power is Turned On ...................................................168
Test Operation
147
Test Operation
Si37-701
1. Test Operation
1.1
Installation Process
Below Figure shows the installation process. Install in the order of the steps shown.
3. Selection of Location
7. Field Wiring
6. Refrigerant Piping
9. Pipe Insulation
148
Test Operation
Si37-701
1.2
Test Operation
Have the airtight test and the vacuum drying been conducted
according to the procedure in the Installation Manual?
Calculate a necessary additional refrigerant charging amount according to the procedure for
calculation shown below.
Procedure for calculating additional refrigerant charging amount (Unit: 0.1 kg)
R
Total length of
22.2-mm
0.37
liquid pipe)
Total length of
19.1-mm
0.26
liquid pipe)
Total length of
15.9-mm
0.18
liquid pipe)
Total length of
12.7-mm
0.12
liquid pipe)
1.02
Total length
of 9.5-mm
liquid pipe)
Test Operation
0.059
Total length
of 6.4-mm 0.022
liquid pipe)
149
Test Operation
Si37-701
Correction
amount
3.6 kg
1.0kg
1.5kg
2.0kg
+
2.5kg
Model REYQ32-40PY1
Model REYQ42PY1
Model REYQ44-46PY1
Model REYQ48PY1
Correction amount
Ratio of total capacity of the
connected indoor units to the
rated capacity of the outdoor Model
Model
unit (A)
REYQ18 REYQ34 32PY1
48PY1
3.0kg
3.5kg
4.0kg
4.5kg
100%<A120%
120%<A130%
0.5kg
0.5kg
1.0kg
If there is a refrigerant shortage, charge a liquid refrigerant through the stop valve service
port with the stop valves of liquid and those of gas closes after the completion of vacuum
drying.
If the refrigerant charging is still insufficient, "turn ON the power supply" following the
information on the next page.
Has the additional refrigerant charging amount been
recorded on the "Precautions for servicing" label?
150
Equalizing pipe
stop valve
Open
Open
Open
Test Operation
Si37-701
Test Operation
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
(*) The master unit is the outdoor unit to which the transmission wiring for
the indoor units is conncted.
The other outdoor units are slave units.
Make field settings with outdoor
unit PC board.
Test Operation
151
Test Operation
Si37-701
Nitrogen
Gauge manifold
Charge hose
Outdoor unit
Valve B
Measuring
device
Valve C
Vacuum pump
: Field piping
: Gas flow
To BS
(or indoor) unit
Valve A
: Shutoff valve
: Service port )
REYQ18~48PY1
Equalizer pipe shutoff valve
HP/LP gas pipe shutoff valve
Suction gas pipe shutoff valve
Measuring
device
Nitrogen
Gauge manifold
R-410A tank
(with siphon)
Outdoor
unit
Outdoor
unit
Outdoor
unit
Vacuum pump
: Field piping
: Gas flow
Valve C
To BS
(or indoor) unit
: Shutoff valve
: Service port )
Note:
The airtightness test and vacuum drying should be done using the service
ports of equalizer pipe, HP/LP gas pipe, suction gas pipe and liquid pipe
shutoff valve.
See the [R-410A] Label attached to the front plate of the outdoor unit for
details on the location of the service port (see figure at right)
See [Shutoff valve operation procedure] in 1.2.5.1 Before Working
for details on handling the shutoff valve.
[R-410A] Label
The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains the refrigerant, so use caution when attaching the charge
hose.
152
Test Operation
Si37-701
Test Operation
Drying.
Always insulate the liquid piping, the HP/LP gas piping, the gas piping, the equalizer pipe
Test Operation
(between the outdoor units for the outdoor multi system) and these pipe connections.
Failing to insulate the pipes may cause leaking or burns.
Especially, be sure to insulate the HP/LP gas piping as withstanding as the suction pipe
because the suction gas follows in the HP/LP gas piping when the system is whole cooling
mode.
And be sure to use the insulation which can withstand such temperatures of 120C or more
for the HP/LP gas piping, the equalizer pipe and the gas piping because the HP/LP gas
follows in these pipings.
Reinforce the insulation on the refrigerant piping according to the installation environment.
Condensation might form on the surface of the insulation. Refer to the below.
Ambient temperature : 30C, humidity : 75% to 80% RH : min. thickness : 15mm.
If the ambient temperature exceeds 30C and the humidity 80% RH, then the min.
thickness is 20mm.
See the Engineering data book for detail.
If there is a possibility that condensation on the shutoff valve might drip down into the indoor
unit through gaps in the insulation and piping because the outdoor unit is located higher than
the indoor unit, etc., this must be prevented by caulking the connections, etc. (Refer to next
figure)
The piping lead-out hole lid should be attached after opening a knock hole. (Refer to next
figure)
If small animals and the like might enter the unit through the piping lead-out hole, close the
hole with blocking material (procured on site) after completion of 1.2.5 Additional
Refrigerant Charge and Check Operation. (Refer to next figure)
153
Test Operation
Si37-701
Caulking, etc.
Insulation material
Block
Note:
After knocking out the holes, we recommend you remove burrs in the knock holes (See
above figure) and paint the edges and areas around the edges using the repair paint.
1.2.5.1
Before Working
[About the refrigerant cylinder]
Check whether the cylinder has a siphon pipe before charging and place the cylinder so that the
refrigerant is charged in liquid form. (See the figure below.)
With siphon pipe
Stand the cylinder upright and charge.
(The siphon pipe goes all the way inside,
so the cylinder does not need be put
upside-down charge in liquid form.)
Other tanks
Stand the cylinder upside-down and charge.
Note:
Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an
improper material, it may cause an explosion or accident.
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition
to change, which may prevent normal operation.
154
Test Operation
Si37-701
Test Operation
10HP type
12HP type
14HP type
16HP type
9.5
Liquid pipe shutoff valve
The 12HP type corresponds to the 12.7diameter onsite piping using the accessory
pipe.
12.7
25.4
The 8HP type corresponds to the 19.1-diameter onsite piping using the
accessory pipe.
Suction gas shutoff valve The 10HP type corresponds to the 22.2-diameter onsite piping using the
accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
19.1
HP/LP gas shutoff valve
The 8HP type corresponds to the 15.9-diameter onsite piping using the
accessory pipe.
The 1416 HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
REYQ18~48PY1
8HP type
10HP type
12HP type
14HP type
16HP type
9.5
Liquid pipe shutoff valve
The 12HP type corresponds to the 12.7diameter onsite piping using the accessory
pipe.
12.7
25.4
The 8 10HP type corresponds to the 22.2-diameter onsite piping using
Suction gas shutoff valve the accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
19.1
HP/LP gas shutoff valve
Equalizer pipe shutoff
valve
Test Operation
155
Test Operation
Si37-701
Service port
Cap
Seal section
Hex holes
Shaft (valve body)
fig 34
[To open]
1. Remove the cap and turn the shaft counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
[To close]
1. Remove the cap and turn the shaft clockwise with the hexagon wrench (JISB4648).
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
<Tightening torque>
Shutoff valve
size
9.5
5.4 - 6.6
12.7
8.1 - 9.9
Hexagonal wrench
4 mm
27.0 - 33.0
Hexagonal wrench
8 mm
19.1
25.4
156
Service port
13.5 - 16.5
18.0 - 22.0
11.5 - 13.9
22.5 - 27.5
Test Operation
Si37-701
Test Operation
1. Press the MODE button (BS1) once at Setting Mode 1 (H1P: off) and set
H H H H H H H
1 2 3 4 5 6 7
P P P P P P P
5333333
5334333
5333434
3. Press the RETURN button (BS3) and read the number of units from the
5353553
32 0 + 16 1 + 8 0 + 4 1 + 2 1 + 1 0 = 22 units
Note: 000000 indicates 64 units.
4. Press the MODE button (BS1) once. This returns to Setting Mode 1
3343333
Note:
Press the MODE button (BS1) if you get confused while operating.
This returns to Setting Mode 1 (H1P: OFF, default).
Test Operation
157
Test Operation
1.2.5.2
Si37-701
Inspection door
EL. COMPO. BOX lid
LED
(H1~8P)
Inspection door
Push button(BS1~5)
Use an insulated rod to operate the push buttons via the EL. COMPO. BOXs inspection door.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
Caution
Make sure to use the protect tool (protective groves and goggles) when charging the
refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable
working.
After the outdoor unit stops operating, the fan may keep rotation for a while.
Note:
If operation is performed within 12 minutes after the BS, indoor and outdoor units are turned
on, H2P will be lit on and the compressor will not operate.
Check the LED display indicate as shown [Display of normal system] in chapter 1.2.5.2.1.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operating. This is not a malfunction.
The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the units internal piping is already charged with
refrigerant, so be careful when connecting the charge hose.
After adding the refrigerant, make sure to close the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.
See [Shutoff valve operation procedure] in chapter 1.2.5.1 for details on how to handle
shutoff valves.
When done or when pausing the refrigerant charging operation, close the valve of the
refrigerant tank immediately.
The refrigerant charge port of this product have electric expansion valve.
The valve will be closed at end of refrigerant charging. However the valve will be opened on
operation after refrigerant charging (check operation, normal operation, etc.).
If the tank is left with the valve open, the amount of refrigerant which is properly charged
may be off the point.
Make sure to perform the check operation after installation. Otherwise, the malfunction code
U3 will be displayed and normal operation cannot be performed.
And the failure of Check of miswiring may also cause abnormal operation. Performance
may drop due to the failure of Judgment of piping length.
Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.
The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is completed. (See
chapter 1.2.6)
The check operation cannot be performed in recovery or other service modes.
158
Test Operation
Si37-701
Test Operation
Measuring device
Outdoor
unit
Valve C
R-410A tank (with siphon)
: Field pipings
: Refrigerant flow
Valve A
To BS,
indoor unit
: Shutoff valve
: Service port )
REYQ18~48PY1
Equalizer pipe shutoff valve
HP/LP gas pipe shutoff valve
Charge hose
Suction gas
shutoff valve
Liquid pipe
shutoff valve
Outdoor
unit A
Outdoor
unit B
Outdoor
unit C
Refrigerant
charge port
Measuring device
R-410A tank (with siphon)
: Field pipings
: Refrigerant flow
Valve A
Valve B
Valve C
To BS,
indoor unit
: Shutoff valve
( : Service port )
4. If the additional charging amount was charged fully, close the valve B and go to step 7.
If the additional charging amount was not charged fully, close the valve B and go to step 5.
5. Perform the refrigerant charging operation following [Refrigerant charging operation
procedure] as shown below, and charge the remaining refrigerant of the additional charging
amount. For performing the refrigerant charging operation the push button on the PC-board
(A1P) of outdoor unit (In case of multi system, master unit) are use. (See the figure on the
previous page) In addition, the refrigerant are charged from the refrigerant charge port via
the valve A.
(See the next figure)
For operating the push button and opening and closing the valve, follow the work procedure.
Test Operation
159
Test Operation
Si37-701
Note:
The refrigerant will be charged about 30kg in one hour at outdoor temp. 30C DB (12kg at
0CDB).
If you need to speedup in case of multi system, connect the refrigerant tanks to each outdoor
unit as shown in the next figure.
REYQ8~16PY1
Charge hose
Refrigerant charge port
HP/LP gas pipe shutoff valve
Suction gas shutoff valve
Liquid pipe shutoff valve
Valve B
Measuring device
Outdoor
unit
Valve C
R-410A tank (with siphon)
Valve A
: Field pipings
: Refrigerant flow when charging
: Shutoff valve
: Service port )
REYQ18~48PY1
Suction pipe
shutoff valve
Liquid pipe
shutoff valve
Outdoor
unit A
Refrigerant
charge port
Measuring device
Valve A
Valve B
R-410A tank (with siphon)
: Field pipings
: Refrigerant flow when charging
160
Valve C
To BS,
indoor unit
: Shutoff valve
( : Service port )
Valve A
Test Operation
Si37-701
Test Operation
C/H SELECTOR
L.N.O.P DEMA-ND MULTI
IND MASTER SLAVE
H3P
4
H4P
7
H5P
7
H6P
7
H7P
7
H8P
7
Master unit
Sub unit 1
Sub unit 2
(*) How to distinguish the master unit, sub unit 1, and sub unit 2 in the multi system.
Method 1 : By the H8P (MULTI) LED display
4 (ON) : Master unit 5 (Blinking) : Sub unit 1 7 (OFF) : Sub unit 2
Method 2 : By the transmission wiring to indoor unit
Transmission wiring is connected : Master unit
Transmission wiring is not connected : Sub unit 1 or Sub unit 2
(3) Charge the remained refrigerant by additional refrigerant charging operation of service
mode.
About the method of additional refrigerant charging operation, refer to the [Service
Precaution] labe (lower) attached on the EL. COMPO. BOX lid of the outdoor unit.
EL. COMPO.BOX lid
Inspection door
[Service Precaution] label (upper)
[Service Precaution] label (lower)
(4) Close the valve A if the additional charging amount of refrigerant was charged, and push
the RETURN button (BS3) once.
Test Operation
161
Test Operation
Si37-701
6. After completing the additional refrigerant charging, record the charging amount on the
accessory REQUEST FOR THE INDICATON label (Installation records) and adhere it to
the back side of the front panel. Also, record the factory charged refrigerant amount,
additional refrigerant amount in the field and total refrigerant amount of the system to
ADDITIONAL REF. CHARGE label and adhere in the proximity of the refrigerant charge
port. About ADDITIONAL REF. CHARGE label.
Otherwise, malfunction code U3 will be displayed in the remote controller and nomal
operation can not be carried out.
Check of shutoff valve opening
Check of miswiring
Judgment of piping length
Check of refrigerant overcharge
Note:
Check operation can not carried out at outdoor temp. less than -5C.
Perform the check operation at day or time that outdoor temp. is -5C or more.
[Check Operation Procedure]
1. Close the EL. COMPO. BOX lid and all front panels except as the side of the EL. COMPO.
BOX and turn on the power to the outdoor unit and all connected BS, indoor units. (Be sure
to turn the power on at least 6 hours before operation in order to have power running to the
crank case heater.)
2. Make the onsite settings as needed using the push button (BS1-BS5) on the outdoor unit
PC-board (A1P) with the power on. (See 1.2.6 Onsite Settings)
3. Perform the check operation following the Check Operation Method of the [Service
Precautions] label (lower) on the EL. COMPO. BOX lid. The system operation for about
40~60 minutes and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after the system stop, check
operation is completed. Normal operation will be possible after 5 minutes. If the malfunction
code is displayed in the remote controller, correct the malfunction following [Remote
controller displays malfunction code] and perform the check operation again.
Note:
For interrupting the check operation, push RETURN button (BS3).
Check operation method
[Note] Make sure to open the equalizer (only for Multi system), suction pipe, dual pressure gas
pipe and liquid pipe shutoff valves completely.
In the check operation, the following works will be automatically performed.
Check of miswiring / Check of shutoff valve opening / Check of refrigerant overcharge /
Judgment of piping length
Make sure to carry out the check operation after the first installation.
Otherwise, the malfunction code "U3" will be displayed in the remote controller and normal
operation cannot be carried out.
When the check operation is finished normally, normal operation can be carried out after 5
minutes.
For Multi system, check the setting and result on the master unit. (See Caution for Multi
connecting system )
The abnormality of each indoor unit can not be checked. After the check operation is finished,
check the indoor units individually by normal operation using the remote controller.
[Operation procedure]
To protect the compressor, make sure to turn on the power supply for 6 hours before stating
operation.
(After turning on the power supply, the unit can not start the operation until the H2P LED
goes off. (maximum 12 minutes))
162
Test Operation
Si37-701
Test Operation
Test Operation
163
Test Operation
Si37-701
Installation error
Remedial action
The shutoff valve of the outdoor unit is Open the shutoff valve.
left closed.
U1
The phases of the power to the outdoor Exchange two of the three phases (L1,
unit is reversed.
L2, L3) to make a proper connection.
U1
U4
LC
UF
Refrigerant overcharge.
Insufficient refrigerant.
E3
F6
UF
E4
F3
U7, U4
UF, UH
UA
REYQ18~48PY1
Malfunction code
E3, E4, F3, F6
UF
U1
U1, U4, LC
UF
E3, F6, UF
E4, F3
Installation error
Remedial action
The shutoff valve of the outdoor unit is Open the shutoff valve.
left closed.
The phases of the power to the outdoor Exchange two of the three phases (L1,
unit is reversed.
L2, L3) to make a proper connection.
No power is supplied to an outdoor, BS Make sure the power source wire is
or indoor unit (including phase
properly connected to the outdoor, BS or
interruption).
indoor unit and revise if necessary.
There is conflict on the connection of
transmission wiring in the system.
Refrigerant overcharge.
Insufficient refrigerant.
Note:
If any malfunction codes other than the above are displayed, check the service manual for how
to respond.
164
Test Operation
Si37-701
Test Operation
Warning
Test Operation
165
Test Operation
Si37-701
1.2.7.2
Test Run
After check operation is completed, operate the unit normally and check the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corresponding outdoor unit is also
operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller to see if they operate
properly.
NOTE:
Heating is not possible if the outdoor temperature is 24C or higher. Refer to the Operation
manual.
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote controller is pushed.
When the system operation is stopped by the remote controller, the outdoor units may
continue operating for further 5 minutes at maximum.
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.
If the check operation was not performed at first installation, the malfunction code U3 will be
displayed in the remote controller. Perform the check operation following 1.2.5.2.2
Procedure of check operation.
166
Test Operation
Si37-701
1.2.7.3
Test Operation
Test Operation
167
Test Operation
1.3
Si37-701
Indoor unit
Indoor unit
1.3.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PC Board has been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Indoor unit
Service cover
[Service Precautions] label
Switch box cover
Switch box
(the upper right)
Caution When the 400 volt power supply is applyed to "N" phase by mistake,
replace Inverter PC board (A2P) and control transformer (T1R, T2R) in
switch box together.
(V0847)
168
Test Operation
Si37-701
HAP
(3) Mode setting switch
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
1 2 3 4 1 2 3 4
DS1
DS2
F1 F2 F1 F2 Q1 Q2
Indoor
Outdoor
Outdoor
Outdoor
Multi outdoor
(V3054)
Test Operation
169
Field Setting
Si37-701
3. Field Setting
3.1
MODE NO.
SECOND
CODE NO.
FIRST
CODE NO.
FIELD
SET
MODE
UNIT NO.
SETTING
.
1 7
TEST
(V0292)
170
Test Operation
Si37-701
Field Setting
Test Operation
171
Field Setting
Si37-701
172
Test Operation
Si37-701
Field Setting
12(22)
13(23)
15(25)
Super
long life
filter
Light
02
04
Details
No
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
(1)
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
(2)
(3)
Remote
controller + Body
thermostat
Only body
thermostat
Only remote
controller
thermostat
Display
No display
Indoor unit
turned ON by
thermostat
Forced OFF
01:0
Not equipped
Equipped
LL
(4)
Operation
output
Malfunction
output
(5)
ON/OFF control
External
protection
device input
(6)
1C
0.5C
(7)
LL
(8)
02:1
03:2
04:3
05:4
06:5
07:6
08:7
F (4 directions)
T (3 directions)
W (2
directions)
(9)
(10)
(11)
(12)
Equipped
Not equipped
Draft prevention
Standard
Ceiling
Soiling
prevention
(13)
(14)
Standard
High static
pressure
(15)
Not equipped
Equipped
Not equipped
Equipped
(16)
(17)
Not equipped
Equipped
(18)
Not equipped
Equipped
(19)
Notes :
Test Operation
03
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. 88 may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to Equipped, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
173
Field Setting
Si37-701
Double
flow
Corner
type
Slim
Ceiling
mounted
duct type
Ceiling
Concealed
(Duct)
Type (Aus.
exclusive
use)
Ceiling
mounted
built-in
type
Ceiling
Ceiling
mounted suspended
duct type type
Wall
mounted
type
Floor
standing
type
Concealed
Floor
standing
type
FXFQ
FXZQ
FXCQ
FXKQ
FXDQ
FDYQ
FXSQ
FXMQ
FXHQ
FXAQ
FXLQ
FXNQ
Filter sign
Remote
controller
thermostat
sensor
Set fan
speed when
thermostat
OFF
Air flow
adjustment
Ceiling
height
Air flow
direction
Air flow
direction
adjustment
(Down flow
operation)
Air flow
direction
adjustment
range
{1
Discharge
air temp.
(Cooling)
Discharge
air temp.
(Heating)
174
Test Operation
Si37-701
Field Setting
Standard
Long Life
200 hrs.
100 hrs.
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
10 (20)
Setting
Long-Life Filter
Ultra-Long-Life Filter (1)
10 (20)
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote
controller thermistor.
10 (20)
12 (22)
03
04
Test Operation
Remarks
Indoor unit thermostat ON/OFF signal is
provided.
Output linked with "Start/Stop" of remote
controller is provided.
In case of "Malfunction Display" appears
on the remote controller, output is
provided.
175
Field Setting
Si37-701
Setting Table
Mode No.
Setting
Switch No.
Setting
Position No.
01
12 (22)
02
03
12(22)
Differential value
1C
0.5C
12 (22)
Contents
LL air flow
Preset air flow
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
176
Test Operation
Si37-701
Field Setting
12 (22)
Contents
LL air flow
Preset air flow
Setting Switch
No.
13(23)
Setting Position
Setting
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
0
02
High Ceiling (H) Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
0
02
High Ceiling (H) Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
13 (23)
Second Code
No.
01
02
03
Setting
F : 4-direction air flow
T : 3-direction air flow
W : 2-direction air flow
Test Operation
Mode No.
13 (23)
Setting
Down-flow operation: Yes
Down-flow operation: No
177
Field Setting
Si37-701
Setting Table
Mode No.
13 (23)
02
03
Setting
Upward (Draft
prevention)
Standard
Downward (Ceiling
soiling prevention)
Some indoor unit models are not equipped with draft prevention (upward) function.
13 (23)
15 (25)
Setting
Setting of humidifier
15 (25)
2
02
178
Contents
Without direct duct
connection
With direct duct
connection equipped
with fan
Test Operation
Si37-701
Field Setting
15 (25)
3
02
Contents
Individual operation of
humidifier
Interlocked operation
between humidifier and
drain pump
Test Operation
Mode No.
15 (25)
Contents
Individual operation of
ventilation
179
Field Setting
Si37-701
In order to conduct the central remote control using the central remote controller and the unified
ON/OFF controller, Group No. settings should be made by group using the operating remote
controller.
Make Group No. settings for central remote control using the operating remote controller.
1. While in normal mode, press and hold the
switch for a period of four seconds or
more to set the system to Field Setting Mode.
2. Select the MODE No. 00 with the
button.
3. Use the
button to select the group No. for each group.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Press
to set the selected group No.
5. Press
to return to the NORMAL MODE.
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For wireless remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
BRC7C Type
BRC7E Type
BRC4C Type
180
button (advance/backward).
4. Enter the selected group numbers by pushing
button.
5. Push
button and return to the normal mode.
Test Operation
Si37-701
Field Setting
Indoor/Outdoor Outdoor/Outdoor
Centoral Remote
Controller
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
F1 F2
F1 F2 P1 P2
RC
1-00
F1 F2 P1 P2
F1 F2
F1 F2 P1 P2
Main RC
F1 F2 P1 P2
No Remote Controller
1-03
Caution
RC Sub
1-01
F1 F2
F1 F2 P1 P2
RC
1-02
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
RC
1-04
(V0917)
When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
181
Field Setting
How to Select
Operation Mode
Example
ON by remote
controller
(Unified ON by
central remote
controller)
Rejection
Si37-701
Whether operation by remote controller will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
OFF by remote
controller
(Unified OFF by
central remote
controller)
OFF by
remote
controller
Rejection
Rejection
Temperature
control by
remote controller
Operation mode
setting by
remote controller
Acceptance
Acceptance
Control
mode is "1."
(VL069)
Unified operation,
individual operation
by central remote
controller, or
operation controlled
by timer
Unified OFF,
individual stop by
central remote
controller, or timer
stop
OFF
Temperature
Operation Control mode
control
mode setting
Rejection
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Acceptance
(Example)
Rejection (Example)
Rejection
Rejection (Example)
Acceptance
Rejection
Centralized
Acceptance
Acceptance
Acceptance
Rejection
Individual
Acceptance
Acceptance
Timer operation
possible by
remote controller
Acceptance
(During timer at ON
position only)
Acceptance
(During timer at ON
position only)
Rejection
Acceptance
Acceptance
Rejection
10
Acceptance
(Example)
1(Example)
Rejection
11
Acceptance
Rejection
12
Acceptance
Rejection
13
Acceptance
Rejection
14
Acceptance
Rejection
15
Acceptance
Rejection
16
Acceptance
Rejection
7 1
17
Acceptance
Rejection
18
Acceptance
Rejection
19
Do not select timer operation possible by remote controller if not using a remote controller.
Operation by timer is impossible in this case.
1. Factory setting
182
Test Operation
Si37-701
3.2
Field Setting
Function setting
Setting of low
noise
operation (*1)
Setting of
demand
operation (*1)
Setting of
AirNet
address
Setting of
high static
pressure
A. Use external input to step down the upper Use the "External control adaptor for
outdoor unit".
limit of the fan (factory set to Step 8),
Set to "External control adaptor for
providing low noise level.
outdoor unit" with No. 12 of "Setting mode
(1) Mode 1: Step 5 or lower
2" and select the mode with No. 25.
(2) Mode 2: Step 4 or lower
If necessary, set the "Capacity priority
(3) Mode 3: Step 3 or lower
setting" to ON with No. 29.
B. The low noise operation aforementioned
Make this setting while in "Setting mode
is enabled in nighttime automatic low
2".
noise operation mode.
Select a mode with No. 22 of "Setting
Start time: Possible to select in the range
mode 2".
of 20:00 to 24:00 hours.
Select the start time with No. 26 and the
End time: Possible to select in the range
end time with No. 27.
of 06:00 to 08:00 hours.
If necessary, set the "Capacity priority
(Use the said time as a guide since the
setting" to ON with No. 29.
start time and the end time are estimated
according to outdoor temperatures.)
Used to place limits on the compressor For setting with the use of "external
control adapter":
operating frequency to control the upper
Set the system to "External control
limit of power consumption.
adaptor for outdoor unit" with No. 12 of
(1) Mode 1 of Demand 1: 60% or less of
Setting mode 2" and select the mode with
rating
No. 30.
(2) Mode 2 of Demand 1: 70% or less of
rating
For setting only in "Setting mode 2":
(3) Mode 3 of Demand 1: 80% or less of
Set the system to Normal demand mode
rating
with No. 32 of "Setting mode 2" and select
(4) Demand 2: 40% or less of rating
the mode with No. 30.
Used to make address setting with AirNet Set the AirNet to an intended address
using binary numbers with No. 13 of
connected.
"Setting mode 2".
Make this setting to operate a system with
diffuser duct while in high static pressure
mode. (Use this setting mode when
shields are installed on upper floors or
Set No. 18 of "Setting mode 2" to ON.
balconies.)
* In order to mount the diffuser duct,
remove the cover from the outdoor unit
fan.
Make this setting to prevent a rise in room
temperature due to minute heating
capacity generated by heating thermostat Set the Setting item No. 41 of Setting
OFF unit or non-heating-operation unit
mode 2 to heating thermostat OFF unit or
while in heating operation.
non-heating-operation unit.
(Overseas unit: Default set to ON)
Prevention of
minute
heating
operation by
heating
thermostat
OFF unit or
non-heatingoperation unit
Setting of BS Make this setting to shorten the BS CoolHeat selection control time.
Set the Setting item No. 42 of Setting
Cool-Heat
mode 2 to ON.
selection
control time
Test Operation
Reference
page
199
199
201
201
194
194
195
195
183
Field Setting
Setting item
Service setting
Si37-701
Indoor unit
fan forced H
operation
Indoor unit
forced
operation
Change of
targeted
evaporating
temperature
(in cooling)
Change of
targeted
condensing
temperature
(in heating)
Setting of
defrost
selection
Setting of
sequential
startup
Used to operate the indoor unit in forced Set No. 6 of "Setting mode 2" to indoor
unit forced operation mode.
operation mode.
In cooling operation, used to change the Select high side or low side with No. 8 of
targeted evaporating temperature for
"Setting mode 2".
compressor capacity control.
In heating operation, used to change the Select high side or low side with No. 9 of
targeted condensing temperature for
"Setting mode 2".
compressor capacity control.
Used to change a temperature at which
the defrost operation is initiated, thus
making the initiation easy or hard.
Reference
page
194
194
194
194
194
194
207, 208
194
194
Set No. 21 of "Setting mode 2" to ON.
194
Set No. 21 of "Setting mode 2" to ON.
195
Set No. 24 of "Setting mode 2" to ON.
195
Set No. 28 of "Setting mode 2" to ON.
185
For setting items of (*1), refer to detailed information provided on page 192 onward.
184
Test Operation
Si37-701
Field Setting
ON
ON
OFF
OFF
1 2 3 4
DS1
1 2 3 4
DS2
Caution
DIP switch Setting after changing the main PC board(A1P) to spare parts PC board
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main PC board(A1P) to spare parts PC board, please carry out the
following setting.
Initial conditions of dip switches
ON
OFF
ON
OFF
1 2 3 4
DS1
1 2 3 4
DS2
ON
Contents
200V class (220V)
DS2-3
DS2-4
Test Operation
Multiple
Single use
use Single
(sab)
use (Main)
DS1-4 DS1-3
DS2-1 DS1-4
Domestic
Japan
Overseas
General
OFF
OFF
ON
OFF
ON
OFF
Europe
REYQ10P
OFF
ON
OFF
OFF
REY(M)Q12P
ON
OFF
ON
REY(M)Q14P
OFF
ON
ON
REY(M)Q16P
ON
ON
ON
REYQ12P
OFF
ON
OFF
OFF
REYQ14P
ON
OFF
OFF
ON
REYQ16P
ON
OFF
ON
OFF
For detail of the setting procedure, refer to information on the following pages.
While the PC board assembly is replaced, the "U3" malfunction (Test run not carried out yet)
code is displayed. In this case, carry out the test run again.
If the "PJ", "UA", or "U7" malfunction code is displayed, recheck for DIP switch settings.
After the completion of rechecking for the settings, turn ON the power supply again.
185
Field Setting
Si37-701
A1P
LED
EB****
Factory Set (
DS1 DS2
ON
OFF
1
Allocation
Setting method (
Application model
HEAT RECOVERY(8HP)
REYQ8PY1
2 3
DS1
DS1
2 3
DS2
DS2
ON
HEAT RECOVERY(10HP)
ON
REYQ10PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
General
overseas
HEAT RECOVERY(12HP)
ON
REYQ12PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(14HP)
ON
REYQ14PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(16HP)
ON
REYQ16PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(8HP)
REYQ8PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
HEAT RECOVERY(10HP)
ON
REYQ10PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
For Europe
HEAT RECOVERY(12HP)
ON
REYQ12PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(14HP)
ON
REYQ14PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(16HP)
ON
REYQ16PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
1 2 3 4
186
1 2 3 4
Test Operation
Si37-701
Field Setting
Single Use
A3P
LED
EB****
Factory Set (
DS1 DS2
ON
OFF
1
Allocation
Setting method (
Application model
HEAT RECOVERY(8HP)
REYQ8PY1
2 3
DS1
DS1
2 3
DS2
DS2
ON
HEAT RECOVERY(10HP)
ON
REYQ10PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
General
overseas
HEAT RECOVERY(12HP)
ON
REYQ12PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(14HP)
ON
REYQ14PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(16HP)
ON
REYQ16PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(8HP)
REYQ8PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
HEAT RECOVERY(10HP)
ON
REYQ10PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
For Europe
HEAT RECOVERY(12HP)
ON
REYQ12PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(14HP)
ON
REYQ14PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(16HP)
ON
REYQ16PY1B
1 2 3 4
DS1
1 2 3 4
DS2
OFF
1 2 3 4
Test Operation
1 2 3 4
187
Field Setting
Si37-701
Multiple Type
Allocation
Application model
HEAT RECOVERY(8HP)
REMQ8PY1
Setting method (
DS1
ON
HEAT RECOVERY(10HP)
ON
REMQ10PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
General
overseas
HEAT RECOVERY(12HP)
ON
REMQ12PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(14HP)
ON
REMQ14PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(16HP)
ON
REMQ16PY1
1 2 3 4
DS1
1 2 3 4
DS2
OFF
HEAT RECOVERY(8HP)
REMQ8PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
HEAT RECOVERY(10HP)
REMQ10PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
For Europe
HEAT RECOVERY(12HP)
REMQ12PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
HEAT RECOVERY(14HP)
REMQ14PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
HEAT RECOVERY(16HP)
REMQ16PY1B
1 2 3 4
DS1
1 2 3 4
DS2
ON
OFF
1 2 3 4
188
1 2 3 4
Test Operation
Si37-701
Field Setting
Single-outdoor-unit
system
Outdoormulti
system
Master
Slave 1
Slave 2
MODE
H1P
TEST
H2P
7
7
7
7
7
7
7
7
COOL/HEAT select
Multi;
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
IND
H3P
H7P
H8P
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
(Factory setting)
Pushbutton switches
BS1
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
REWIRING
Used for
onsite setting
Used to change
the setting mode
Setting mode 2
(Normal)
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 1
Push the BS1(MODE button) one time. MODE
MODE
On
H1P
Off
H1P
H1P
(V2761)
Test Operation
189
Field Setting
Si37-701
Setting mode 1
(Initial condition)
Setting mode 2
Monitor mode
Press BS3
(RETURN button).
Setting condition
selection (SET button)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS1
(MODE button).
Press BS1
(MODE button).
(V2762)
190
Test Operation
Si37-701
Field Setting
a. Setting mode 1
This mode is used to set and check the following items.
Check items The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Low noise operating conditions (In normal operation / In low noise operation)
(3) Demand operating conditions (In normal operation / In demand operation)
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
MODE TEST
H1P
H2P
COOL/HEAT select
Low
Demand
IND MASTER SLAVE noise
H7P
H6P
H3P
H4P
H5P
7
Current operating conditions
7Normal 8Abnormal
9In preparation or in
check operation
Test Operation
191
Field Setting
Si37-701
No.
b. Setting mode 2
Push and hold the MODE (BS1)
button for 5 seconds and set to
Setting mode 2.
Digital pressure
gauge kit display
Cool/heat unified
address
Low noise/demand
address
Test operation
settings
6
8
9
10
12
13
18
20
21
22
24
Push the RETURN (BS3) button and
set to the initial status of Setting
mode 2.
29
Capacity
precedence setting
30
Demand setting 1
32
Normal demand
setting
27
(V2764)
28
192
Setting of external
low noise level
Night-time low
noise operation
start setting
Night-time low
noise operation end
setting
Power transistor
check mode
Check after
disconnection of
compressor wires
25
26
Description
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
11
Setting item
Test Operation
Si37-701
Field Setting
No.
38
39
40
41
42
51
Setting item
Emergency
operation
(Setting for the unit
1 operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the unit
2 operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the unit
3 operation
prohibition in multioutdoor-unit
system)
Description
The numbers in the "No." column represent the number of times to press
the SET (BS2) button.
Test Operation
193
Field Setting
Si37-701
Setting item
Digital pressure
gauge kit display
MODE
H1P
TEST
H2P
IND
H3P
C/H selection
Master Slave
H4P
H5P
Low
noise
H6P
Demand
H7P
Address
Binary number
(4 digits)
~
15
Cool / Heat
Unified address
Address
Binary number
(6 digits)
Low noise/demand
address
Address
Binary number
(6 digits)
Test operation
8788888
8777778
8777787
8777778
8777787
8777778
8777787
8777877
8777787
8777778
8777877
8777787
8777778
8777877
8777787
8777778
8777778
8777787
8777778
8777787
Test operation: ON
Test operation: OFF
Normal operation
Indoor forced fan H
Normal operation
Indoor forced operation
High
Te setting
Tc setting
changeover
10 Defrost
setting
Sequential operation
11 setting
low noise/
12 External
demand setting
13 Airnet address
8
8
7
7
7
7
8
8
7
8
8
7
8
7
OFF
ON
Address
Binary number
(6 digits)
Additional refrigerant
20 charging operation
setting
Refrigerant
21 recovery/vacuuming
mode setting
8888888
8777778
8777787
194
8777777
8777778
~
63
18 High static pressure
setting
8788888
8777777
8777778
~
31
3
8778888
8777777
8777778
~
31
Factory set
8777777
8777778
8777778
8777787
8777778
8777787
8777777
8777778
8777787
8777788
Test Operation
Si37-701
Field Setting
Setting item
ENECUT test
24 operation (Domestic
Japan only)
MODE
H1P
TEST
H2P
IND
H3P
C/H selection
Master
Slave
H4P
H5P
Low
noise
H6P
Demand
H7P
About 7:00
About 8:00 (factory setting)
transistor
28 Power
check mode
Capacity
29 precedence setting
OFF
ON
OFF
ON
60 % demand
30 Demand setting 1
70 % demand
80 % demand
Normal demand
32 setting
Emergency
operation
(Master unit with
38 multi-outdoor-unit
system is inhibited to
operate.)
Emergency
operation
unit 1 with
39 (Slave
multi-outdoor-unit
system is inhibited to
operate.)
Emergency
operation
40 (Slave unit 2 with
multi-outdoor-unit
system is inhibited to
operate.)
Prevention of minute
heating operation by
41 heating thermostat
OFF unit or nonheating-operation
unit
OFF
ON
OFF
8777787
OFF
8777778
8777787
OFF
8777778
8777787
OFF
8777777
8777778
8777787
8777788
8777777
8777778
8777787
8777788
8777777
8777778
8777787
Non-heating-operation unit
Heating thermostat OFF unit
Non-heating-operation + Thermostat OFF unit
6 min.
4 min.
8 min.
11 min.
Automatic judgment
Master-slave set-up
51 for multi outdoor
units
Factory set
8777778
8777787
8777778
8777787
8777877
8777778
8777787
8777877
8777778
8777787
8777877
8777778
8777787
8777778
8777787
8777778
8777787
8777877
8777778
8777787
8777778
Master
Slave 1
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
Test Operation
195
Field Setting
Si37-701
c. Monitor mode
No.
Setting item
196
H1P
H2P
H3P
H4P
H5P
H6P
H7P
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
7
7
8
8
7
7
8
7
8
7
Various settings
Not used
Airnet address
9
9
9
9
9
9 7 7 7 8 7 8
9 7 7 7 8 8 7
9 7 7 7 8 8 8
9 7 7 8 7 7 7
9 7 7 8 7 7 8
10
11
LED display
Data display
Lower 4 digits
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
9 7 7 8 7 8 7
9 7 7 8 7 8 8
12
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
9 7 7 8 8 8 7
Malfunction
code table
15
Contents of malfunction
(1 cycle before)
9 7 7 8 8 8 8
Refer page
226.
16
(2 cycle before)
20
21
22
9
9
9
9
25
9 7 8 8 7 7 8
Contents of malfunction
7
7
7
7
8
8
8
8
7
7
7
7
7
8
8
8
7
7
7
8
Lower 6 digits
7
7
8
7
Lower 6 digits
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of indoor units connected
Used to make setting of the number of indoor units connected to an out door
unit.
*2: Number of outdoor units connected
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*3: Number of outdoor units connected
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of indoor units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
Test Operation
Si37-701
Field Setting
ON
OFF
Short
Medium
Long
Te setting
H
M
L
Tc setting
H
M
L
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
9 797997
16
32
4
8
1
2
977 7979
64 16
No.12 128 32
977 7997
4
No.13
1
2
See the preceding page for a list of data, etc. for No. 0 - 25.
Test Operation
197
Field Setting
Si37-701
2
SS1
SS2
When using cool/heat selector, connect to the terminal A, B and C on the EC of the electric
parts box.
EXAMPLE OF TRANSMISSION LINE CONNECTION
Example of connecting transmission wiring.
Connect the transmission wirings as shown in the Fig. 1.
In case of the indoor unit connect as the cool-only unit, it wire
he terminal F1 F2 of the last BS unit.
OUT/D.BS
F1 F2
IN/D
F1 F2
OUT/D.BS
Final BS unit
F1
F1 F2
F1 F2
OUT/D.BS
COOL/HEAT
selector
B
C
F1 F2
F1
F2
IN/D
F1 F2
OUT/D.BS
Final BS unit
COOL/HEAT
selector
Fig. 1
198
Cooling only
BS unit B
BS unit A
F1 F2
F2
IN/D
Final unit
F1 F2
REMOTE
CONTROLLER
A
B
1st unit
REMOTE
CONTROLLER
REMOTE
CONTROLLER
F1 F2 F1 F2
IN/D
OUT/D.BS
F1 F2
Branch wiring
Outside unit
F1 F2
A
B
C
F1 F2
F1 F2
COOL/HEAT
selector
Indoor unit for cooling
Test Operation
Si37-701
Field Setting
Content
Set the outdoor unit fan to Step 5 or lower.
Set the outdoor unit fan to Step 4 or lower.
Set the outdoor unit fan to Step 3 or lower.
A. When the low noise operation is carried out by external instructions (with the use
of the external control adapter for outdoor unit)
1. Connect the external adapter of the outdoor unit, and then connect the external input wiring
to the low-noise operation input terminal on the terminal block (X1M). (Refer to the figure
shown below.)
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., Level 1", "Level 2",
or "Level 3") for set item No. 25 (Setting of external low noise level).
4. If necessary, while in "Setting mode 2", set the setting condition for the set item No. 29
(Setting of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the low
noise operation command will be ignored to put the system into normal operation mode.)
B. When the low noise operation is carried out automatically at night (The external
control adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Level 1", "Level 2", or "Level 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
If carrying out demand or low-noise input, connect the adaptor's
terminals as shown below.
F1
F2
N
P
X1M
1 2 3 C Low
Demand noise
Outside
wiring
indicated by
dotted line.
Test Operation
199
Field Setting
Si37-701
Rated operation
sound
Operation sound of
level 1
Approx. 55 db (target)
Operation sound of
level 2
Approx. 50 db (target)
Operation sound of
level 3
Approx. 45 db (target)
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
200
Test Operation
Si37-701
Field Setting
Condition
Level 1
Demand 1
Level 2
Level 3
Demand 2
Demand 3
Setting procedure
Description
Operate with power
of approx. 60% or
less of the rating.
Operate with power
of approx. 70% or
less of the rating.
Operate with power
of approx. 80% or
less of the rating.
Operate with power
of approx. 40% or
less of the rating.
External control
adapter
A. When the demand operation is carried out by external instructions (with the use of the
external control adapter for outdoor unit).
1. Connect the external adapter of the outdoor unit, and then connect the external input wiring
to the low-noise operation input terminal on the terminal block (X1M). (Refer to the figure
shown below.)
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the Normal demand operation is carried out. (Use of the external control
adapter for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
If carrying out demand or low-noise input, connect the adaptor's
terminals as shown below.
F1
F2
N
P
X1M
1 2 3 C Low
Demand noise
Outside
wiring
indicated by
dotted line.
Test Operation
201
Field Setting
Si37-701
The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power consumption"
has been set at
factory.)
(V3081)
(V3082)
Power consumption
202
Test Operation
Si37-701
Field Setting
H1P lights.
During the setting mode 1 is displayed, In low noise operation and In demand control are
displayed.
2. Setting mode 2 (H1P on)
c In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. Setting
you want.
e Push the BS3 (RETURN button) one time, and the present setting content is displayed.
Push the BS2 (SET button) several times and match the LED display with the setting
Test Operation
203
Field Setting
Si37-701
{: ON
d
c
Setting
No.
Setting
contents
22
External
low noise /
Demand
setting
Night-time
low noise
setting
Setting
contents
YES
OFF
(Factory
setting)
{
{
{
{
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
9
9
z
9
z
9
9
{
{
z
z
z
z
z
z
9
z
z
z
z
9
{
{
{
z
z
z
z
z
z
z
z
z
9
z
z
z
z
9
z
9
z
AM 8:00
(Factory
setting)
Low noise
precedence
(Factory
setting)
Capacity
precedence
60 % of
rated power
consumption
70 % of
rated power
consumption
(Factory
setting)
80 % of
rated power
consumption
OFF
(Factory
setting)
ON
Mode 2
Mode 3
External
low noise
setting
Mode 1
Mode 2
(Factory
setting)
Mode 3
26
Night-time
low noise
start setting
PM 8:00
PM 10:00
(Factory
setting)
PM 0:00
27
29
30
32
Night-time
low noise
end setting
AM 6:00
AM 7:00
Capacity
precedence
setting
Demand
setting 1
Normal
demand
setting
204
NO
(Factory
setting)
Mode 1
25
9: Blink
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
z: OFF
Test Operation
Si37-701
Field Setting
Test Operation
205
Field Setting
Si37-701
Unit stopping
3:OFF 9:BLINK)
3383333
Press the TEST button for 5 seconds.
Step 1
Pressure equalizing
3933338
10 sec to 10 minutes
Step 2
Step 3
3933383
20 sec to 2 minutes
Stop valve close check
Step4~8
Step 9
Judgement function
3938338
5 minutes
Step 10
3938383
5 minutes
Completion
206
Test Operation
Si37-701
Field Setting
compressor
Backup
operation
by
the
Backup
operation by the
REYQ18 to 48PY1
indoor unit
outdoor unit
Applicable model
H1P-----------H7P
8111111
8811881
8111119(Factory setting)
(4) Press the OPERATE button (BS2) once. 8111191
(5) Press the CHECK button (BS3) twice.
8111111
(6) Press the PAGE button (BS1) once.
1181111
Test Operation
207
Field Setting
Si37-701
H1P-----------H7P
8111111
8811888
8111119(Factory setting)
8111111
1181111
<REYQ18 to 48PY1>
Make disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
*It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
LED display (8: ON, 1: OFF, 9: Blink)
H1P-----------H7P H8P
Outdoor unit 1: 1181111 8
Outdoor unit 2: 1111111 9
Outdoor unit 3: 1111111 1(Factory setting)
H1P-----------H7P
8111111
8811881
8111119(Factory setting)
8111111
1181111
H1P-----------H7P
8111111
8811888
8111119(Factory setting)
(4) Press the OPERATE button (BS2) once. 8111191
(5) Press the CHECK button (BS3) twice.
8111111
(6) Press the PAGE button (BS1) once.
1181111
H1P-----------H7P
8111111
8818111
8111119(Factory setting)
208
8111111
1181111
Test Operation
Si37-701
Part 6
Troubleshooting
1. Symptom-based Troubleshooting .......................................................212
2. Troubleshooting by Remote Controller ...............................................215
2.1
2.2
2.3
2.4
2.5
2.6
2.7
Troubleshooting
Si37-701
Troubleshooting
Si37-701
Troubleshooting
211
Symptom-based Troubleshooting
Si37-701
1. Symptom-based Troubleshooting
1
Symptom
The system does not start operation at all.
Supposed Cause
Blowout of fuse(s)
Cutout of breaker(s)
Countermeasure
Turn Off the power supply and
then replace the fuse(s).
If the knob of any breaker is in
its OFF position, turn ON the
power supply.
If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Power failure
212
Troubleshooting
Si37-701
Symptom-based Troubleshooting
Symptom
The system
This symptom occurs
conducts fan
immediately after turning ON
operation but not the power supply.
cooling or
heating
operation.
The airflow rate Even pressing the AIRFLOW
is not
RATE SET button makes no
reproduced
changes in the airflow rate.
according to the
setting.
The airflow
direction is not
reproduced
according to the
setting.
10 A white mist
comes out from
the system.
11 The system
produces
sounds.
<Outdoor unit>
Pitch of operating sounds
changes.
Troubleshooting
Supposed Cause
The system is in preparation
mode of operation.
Countermeasure
Wait for a period of approximately
10 minutes.
Normal operation.
Normal operation.
213
Symptom-based Troubleshooting
Symptom
12 Dust comes out Dust comes out from the
from the system. system when it restarts after
the stop for an extended period
of time.
13 Odors come out In operation
from the system.
14 Outdoor unit fan
does not rotate.
In operation
Supposed Cause
Countermeasure
Dust, which has deposited on the Normal operation.
inside of indoor unit, is blown out
from the system.
Odors of room, cigarettes or else
adsorbed to the inside of indoor
unit are blown out.
The reason is that fan revolutions
are controlled to put the operation
to the optimum state.
The reason is that the system is
checking to be sure the remote
controller is normal.
It stops in order to prevent oil or
refrigerant from dwelling.
214
Si37-701
Normal operation.
This code is displayed for a period
of approximately one minute at
maximum.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
Normal operation.
Normal operation.
Troubleshooting
Si37-701
Local
setting
mode
Service
mode
Normal
mode
Press Inspection/Test Operation button once.
Or after 30 minutes
Test
operation
mode
Troubleshooting
(V0815)
215
2.2
Si37-701
Explanation
If operation stops due to malfunction, the remote controllers operation LED blinks, and
malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when the inspection mode is entered.) The malfunction code enables you to tell what
kind of malfunction caused operation to stop. See page 224 for malfunction code and
malfunction contents.
Operation LED
ON/OFF button
Inspection display
Malfunction code
Inspection/Test button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or
more will clear the failure history indication shown above. In this case, on the codes display,
the malfunction code will blink twice and then change to 00 (=Normal), the Unit No. will
change to 0, and the operation mode will automatically switch from check mode to normal
mode (displaying the set temperature).
216
Troubleshooting
Si37-701
2.3
In the Case of
BRC7C Type
BRC7E Type
BRC4C Type
If equipment stops due to a malfunction, the operation indicating LED on the light reception
section flashes.
The malfunction code can be determined by following the procedure described below. (The
malfunction code is displayed when an operation error has occurred. In normal condition, the
malfunction code of the last problem is displayed.)
1. Press the INSPECTION/TEST button to select Inspection.
The equipment enters the inspection mode. The Unit indication lights and the Unit No.
display shows flashing 0 indication.
2. Set the Unit No.
Press the UP or DOWN button and change the Unit No. display until the buzzer (*1) is
generated from the indoor unit.
*1 Number of beeps
3 short beeps : Conduct all of the following operations.
1 short beep : Conduct steps 3 and 4.
Continue the operation in step 4 until a buzzer remains ON. The continuous buzzer indicates
that the malfunction code is confirmed.
Continuous beep : No abnormality.
3. Press the MODE selector button.
The left 0 (upper digit) indication of the malfunction code flashes.
4. Malfunction code upper digit diagnosis
Press the UP or DOWN button and change the malfunction code upper digit until the
malfunction code matching buzzer (*2) is generated.
The upper digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
*2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Malfunction code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
Troubleshooting
217
Si37-701
The lower digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
218
Troubleshooting
Si37-701
Troubleshooting
219
2.4
Si37-701
Inspection Mode
Operating the INSPECTION/TEST button on the remote controller will make it possible to
check the malfunction codes, indoor unit model codes, and outdoor unit model codes while in
inspection mode.
0
Unit
L0
Malfunction code
Inspection
Malfunction code blinks when a malfunction occurs.
Inspection/test
operation
0
Unit
L0
Malfunction code
Inspection
Inspection mode
Inspection/test
operation
Display
Example model
FXCQ25
028
FXFQ63
071
System classification
VRV system
Display
071
FCJ
Indoor unit model code display
VRV system
VRV system
VRV system
Display
AA1
Outdoor unit model code display
Inspection/test
operation
Test operation
Test operation mode
Wall mounted
FXAQ
Double flow
FXCQ
Corner
FXKQ
Multi flow
FXFQ
Ceiling suspended
FXHQ
Built-in
FXSQ
Floor standing
FXLQ
FXMQ
FXNQ
FXZQ
FXDQ
Display
Inspection/test
operation
Model
Type
Model
AA1
RSXYP
AA3
RXYP
A92
RSEYP
AA5
RSXYP-L
AAA
VRV II
RXYQ-M
AAC
VRV II M/C
RXYQ-MA
RXYQ-P
RXQ-P
AAE
VRV III
A9E
REYQ-P
(V2775)
220
Troubleshooting
Si37-701
2.5
Service Mode
Operation
Method
Troubleshooting
221
Mode
No
40
Function
Malfunction
hysteresis display
Si37-701
Unit 1
Malfunction code
2-U4
40
Malfunction code
Hystory No: 1 - 9
1: Latest
(VE007)
41
Display of sensor
and address data
Sensor type
1 1
41
27
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
Temperature C
Address display
Unit No.
Address type
1 8
41
Address
(VE008)
43
Forced fan ON
Unit 1
43
(VE009)
44
Individual setting
Unit 1
Code
44
1 3
Fan speed 1: Low
3: High
(VE010)
45
1
Code
0 2
45
46
47
222
This function is not used by VRV Ill R-410A Heat Recovery 50Hz.
Troubleshooting
Si37-701
2.6
Normal
operation
mode
Test run
mode
Press the RUN/STOP button after the completion of test run mode setting, and a test run
starts.
(The remote controller will display "TEST RUN" on it.)
2.7
ON/OFF button
Inspection display
Malfunction code
(VL050)
Troubleshooting
223
Indoor Unit
Outdoor Unit
224
Si37-701
Unit No.
9
9
9
9
9
9
AF
AH
AJ
C4
8
8
9
9
7
7
9
9
9
9
9
9
C5
C9
CJ
E1
E3
E4
E5
E6
E7
E9
8
9
9
9
9
9
9
9
8
9
9
9
9
9
9
9
8
9
9
9
9
9
9
9
F3
F6
F9
H7
H9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
J2
J3
9
9
9
9
9
9
J4
J5
J6
J7
J8
J9
9
9
9
9
9
9
JA
JC
L1
L4
L5
L8
L9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
8: ON
Malfunction contents
7: OFF
9: Blink
Page
Referred
230
231
232
234
235
237
239
241
242
243
244
245
246
247
248
250
252
254
255
258
260
262
265
267
268
269
265
271
272
273
274
275
276
278
280
281
283
285
287
Troubleshooting
Si37-701
8: ON
Malfunction Operation Inspection
code
lamp
display
Outdoor Unit
LA
9
9
Unit No.
Malfunction contents
Central
Remote
Controller
and
Schedule
Timer
M8
8 or 7
MA
8 or 7
Heat
Reclaim
Ventilation
MC
64
65
8 or 7
8
8
9
7
7
9
9
9
6A
6A
6F
6H
94
8
9
8
8
9
7
9
7
7
9
9
9
9
9
9
System
LC
P1
P4
9
9
9
9
9
9
PJ
U0
U1
U2
U3
U4
8
9
9
9
9
7
9
9
9
9
9
9
9
9
9
U5
U5
U7
U8
9
9
9
9
9
7
U9
UA
UC
UE
8
9
8
9
8
9
UF
UH
M1
8 or 7
7: OFF
9: Blink
Page
Referred
290
293
294
296
297
299
300
303
304
307
307
308
314
315
316
319
320
323
324
326
327
328
330
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting
225
Si37-701
<Monitor mode>
PC board malfunction
Malfunctions
Detail
description
on next
page.
PC board malfunction
Faulty PC board
Abnormal discharge pressure
HPS activated
Abnormal suction pressure
Pe malfunction
Compressor lock
INV compressor lock detected
OC activation
STD1 compressor lock detected
STD2 compressor lock detected
Overload, overcurrent and abnormal
Instantaneous overcurrent of 1DC fan
lock of outdoor unit fan motor
motor
1DC fan motor lock detected
Instantaneous overcurrent of 2DC fan
motor
2DC fan motor lock detected
Electronic expansion valve
EV4M (main)
malfunction
EV3J (refrigerant charging)
EV2T (subcool heat exchanger)
Positioning signal malfunction of
1DC fan motor positioning signal
outdoor unit fan motor
malfunction
2DC fan motor positioning signal
malfunction
Abnormal outdoor temperature
Ta sensor malfunction (short-circuited
or open)
Abnormal discharge pipe temperature Td malfunction
Abnormal heat exchanger
Refrigerant overcharged
temperature
BS unit electronic expansion valve
BS EVH disconnected (Y4E)
malfunction
BS EVL disconnected (Y5E)
BS EVHS disconnected (Y2E)
BS EVLS disconnected (Y3E)
BS EVSC disconnected (Y4C)
Current sensor malfunction
CT1 sensor malfunction (STD
compressor 1)
CT2 sensor malfunction (STD
compressor 2)
CT sensor malfunction (system)
Discharge pipe temperature sensor
Tdi sensor malfunction (R31T)
malfunction
Tds1 sensor malfunction (shortcircuited) (R32T)
Tds2 sensor malfunction (shortcircuited) (R33T)
Heat exchanger gas temperature
Tg sensor malfunction (R2T, R11T)
sensor malfunction
Suction pipe temperature sensor
TsA sensor malfunction (shortmalfunction
circuited) (R8T, R10T)
Heat exchanger temperature sensor
Tb sensor malfunction (R4T, R12T)
malfunction
Liquid pipe temperature sensor
Tsc sensor malfunction (R6T, R14T)
malfunction
TL sensor malfunction (R9T)
Heat exchanger liquid pipe
Tf sensor malfunction (R7T, R15T)
temperature sensor malfunction
Subcool heat exchanger temperature Tsh sensor malfunction (R5T, R13T)
sensor malfunction
Discharge pressure sensor
Pc sensor malfunction (S1NPH)
malfunction
Suction pressure sensor malfunction Pe sensor malfunction (S1NPL)
Malfunction
code
Remote
controller
E1
E3
E4
E5
E6
E7
E9
H7
H9
F3
F6
F9
J2
J3
J4
J5
J6
J7
J8
J9
JA
JC
8 : ON
9 : Blink
1 : OFF
226
Troubleshooting
Si37-701
8: ON
7: OFF
9:Blink
Malfunction Confirmation of malfunction 1 (Check 1) Confirmation of malfunction 2 (Check 2) Confirmation of malfunction 3 (Check 3) Confirmation of malfunction 4 (Check 4)
code
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
E1
9
7 7 9 9 9
7 7 7 9 9
7 7 7 7 9
7 7 9 9
E3
E4
E5
E6
9
9
9
9
9
7
7
7
7
7
7
7
9
9
9
7
9
7
7
9
9
9
7
9
7
E7
E9
9
9
9
7
7
7
7
9
7
9
9
9
9
7
7
J3
J4
J5
J6
J7
J8
J9
JA
JC
(L2)
L4
L5
L5
L8
9
9
7
7
H7
H9
F3
F6
J2
L1
9
9
7
7
9
9
7
9
9
7
L9
LC
9
Display of contents of
malfunction (first digit)
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
7
7
7
7
9
7
9
7
7
7
7
7
7
7
9
9
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
9
7
7
7
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
9
9
9
7
7
7
9
9
9
7
7
7
Display of contents of
malfunction (second digit)
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
9
7
7
7
7
7
7
7
7
7
7
9
7
7
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
7
9
7
7
7
7
9
7
9
7
9
7
9
7
7
7
7
7
7
7
7
9
7
9
7
7
9
7
7
7
7
7
7
7
7
7
9
9
7
7
7
7
7
7
7
7
7
9
7
9
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
7
7
7
7
7
7
7
9
7
9
7
7
7
7
7
7
7
9
7
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
7
9
7
9
7
9
Display 1 of
malfunction in detail
1
1
Display 2 of
malfunction in detail
1
Troubleshooting
7
7
9
9
7
9
7
9
Master
Slave1
Slave2
System
227
Si37-701
<Monitor mode>
Malfunctions
Description of malfunction
Faulty IPM
Current sensor failure confirmation 1
Current sensor failure confirmation 2
IGBT malfunction
Overheat of INV radiation fin
temperature
Instantaneous overcurrent of INV
IGBT malfunction
Electronic thermal 1
Electronic thermal 2
Loss of synchronization
Speed degradation after startup
Thunder detected
Stall prevention (increased current)
Stall prevention (startup failure)
Abnormal starting waveform
Loss of synchronization
INV transmission data malfunction
INV transmission malfunction
Unbalanced INV power supply voltage
Electronic thermal
Detail
description
on next
page.
Malfunction
code
Remote
controller
L1
L4
L5
L8
L9
LC
P1
P4
PJ
Out-of-gas alarm
Reversed phase malfunction
Reversed phase malfunction (ON)
Insufficient INV voltage
INV open phase (single phase)
Abnormal charge of capacitor of INV
main circuit
Test run not carried out yet
IN-OUT transmission malfunction
System malfunction
Malfunction caused when mounting
the external control adapter
Alarm given when mounting the
external control adapter
Malfunction caused between the
master and the slave 1
Malfunction caused between the
master and the slave 2
Multi REYP models connected
Faulty address setting of slaves 1 and 2
4 or more outdoor units connected in
the same system
Erroneous address of slaves 1 and 2
Other system or other unit in the same
system
Excess indoor units connected
Erroneous refrigerant used for indoor
unit
Faulty combination of outdoor units
Faulty independent installation
Faulty connection of former BS unit
Faulty connection between outdoor
and BS unit
Faulty connection between BS units
Wrong number of indoor units
connected to BS unit
Wrong wiring (auto address error)
Multi level converter malfunction
Multi level converter alarm
Multi level converter data malfunction
Multi level converter transmission
malfunction
U0
U1
U2
U3
U4
U7
U9
UA
UH
UJ
UF
8 : ON
9 : Blink
1 : OFF
228
Troubleshooting
Si37-701
8: ON
7: OFF
9:Blink
Malfunction Confirmation of malfunction 1 (Check 1) Confirmation of malfunction 2 (Check 2) Confirmation of malfunction 3 (Check 3) Confirmation of malfunction 4 (Check 4)
code
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1
9
9 7 7 7 9
7 7 7 9 9
7 7 7 7 9
7 7
P3
P4
PJ
U2
9
9
9
7
7
7
7
7
7
7
7
9
7
9
7
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
9
9
7
7
9
7
7
7
7
7
9
7
7
7
7
9
9
9
9
9
9
9
9
9
U3
U4
U7
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
9
9
7
7
7
7
7
7
9
7
9
7
9
9
7
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
7
9
9
9
9
9
7
7
9
9
7
7
9
7
9
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
7
7
7
7
9
9
9
9
9
9
9
9
9
9
9
7
7
9
7
7
9
9
7
7
7
7
7
9
7
7
9
7
9
7
7
9
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
U0
U1
U7
U9
UA
9
9
9
9
7
9
9
7
9
9
UA
UH
UJ
UJ
UF
Display of contents of
malfunction (first digit)
Display of contents of
malfunction (second digit)
Display 1 of
malfunction in detail
Display 2 of
malfunction in detail
1
Troubleshooting
7
7
9
9
7
9
7
9
Master
Slave1
Slave2
System
229
Si37-701
Remote
Controller
Display
A0
Applicable
Models
Method of
Malfunction
Detection
Detect open or short circuit between external input terminals in indoor unit.
Malfunction
Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Troubleshooting
Caution
External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
block.
YES
NO
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO
YES
230
Troubleshooting
Si37-701
3.2
Remote
Controller
Display
A1
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
NO
YES
Troubleshooting
231
3.3
Si37-701
Remote
Controller
Display
A3
Applicable
Models
FXCQ, FXFQ, FXSQ, FXKQ, FXDQ, FXMQ, FXHQ (Option), FXMQ200,250M (Option), FXAQ
(Option), FXMQ-MF (Option)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
232
Troubleshooting
Si37-701
Troubleshooting
Caution
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
The float
switch is connected to
X8A of the indoor unit
PC board.
NO
YES
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
A short
circuit connector is
connected to
X8A.
NO
Connect either a short circuit
connector or float switch and
turn on again.
YES
YES
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
NO
Defect of indoor unit PC board.
YES
NO
Water builds up
in the drain pan.
NO
YES
YES
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoorunit PC
board.
NO
Replace float switch.
Modify the float switch's
connection and turn on again.
NO
Connect the drain pump and
turn on again.
YES
The drain
pump works when
the power supply is reset
for the indoor
unit.
YES
Check the drain piping for
clogging or upward slope, etc.
NO
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5minutes of resetting
the power
supply).
YES
NO
Replace indoor unit PC board.
Troubleshooting
233
3.4
Si37-701
Remote
Controller
Display
A6
Applicable
Models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns cant be detected even when output voltage to the fan is maximum
Supposed
Causes
Troubleshooting
Caution
Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit PC
board?
NO
YES
Wiring
between the
indoor unit PC board and
fan motor is
disconnected.
YES
NO
Does the fan motor run?
NO
YES
234
Troubleshooting
Si37-701
3.5
Remote
Controller
Display
A7
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Error code is displayed but the system operates continuously.
Supposed
Causes
Troubleshooting
235
Si37-701
Troubleshooting
Caution
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
Indoor unit
is a model equipped
with a swing flap
function
NO
YES
The swing
motor works when
the power supply is turned
off and then back
on.
YES
NO
The connector
is connected to X9A of
the indoor unit PC
board.
NO
Connect the connector to X9A
and turn on again.
YES
The limit switch
functions normally.
NO
YES
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PC board is 220 ~ 240
VAC (60 Hz) / 220 VAC
(50 Hz) when turned on
again (within 30
seconds of
turning on
again).
The connecting
cable is short-circuited
or disconnected.
YES
NO
NO
YES
The connecting cable
has no continuity.
YES
NO
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
YES
NO
236
Troubleshooting
Si37-701
3.6
Remote
Controller
Display
A9
Applicable
Models
FXFQ25~125M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Either of the following conditions is seen/caused/ occurs while the unit stops operation.
z Temperature of suction air (R1T) temperature of liquid pipe of heat exchanger (R2T)>8C.
z Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Supposed
Causes
Troubleshooting
237
Si37-701
Troubleshooting
Caution
NO
YES
Electronic
expansion valve is
connected to X7A of
indoor unit PC
board.
NO
YES
Coil
check (1) of
electronic expansion valve
drive indicates
normal.
NO
YES
Relay
cables short circuit or
disconnected.
YES
NO
When restarting the operation after
shutting the power supply off does
not work, replace indoor unit PC
board.
1: How to check the coil of electronic expansion valve drive
Remove the connector for electronic expansion valve (X7A) from PC board. Measure the resistance
value between pins and check the continuity to judge the condition.
1) White
White (1)
Red (5)
2) Yellow
1
3
3) Orange
Orange (3)
4) Blue
2
6) Brown
238
Troubleshooting
Si37-701
A9
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Supposed
Causes
Troubleshooting
239
Si37-701
Troubleshooting
Caution
Electronic
expansion valve
is connected to X7A of
indoor unit PC
board.
NO
YES
Coil check
(1) of electronic
expansion valve drive
indicates
normal.
NO
YES
Relay
cables short circuit or
disconnected.
YES
NO
When restarting the operation
after shutting the power supply off
does not work, replace indoor unit
PC board.
1: How to check the coil of electronic expansion valve drive
Remove the connector for electronic expansion valve (X7A) from PC board. Measure the resistance
value between pins and check the continuity to judge the condition.
1) White
White (1)
Red (5)
2) Yellow
1
3
3) Orange
Orange (3)
4) Blue
2
6) Brown
240
Troubleshooting
Si37-701
3.7
Remote
Controller
Display
AF
Applicable
Models
Method of
Malfunction
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.
Malfunction
Decision
Conditions
Supposed
Causes
When the float switch changes from ON to OFF while the compressor is in non-operation.
Error code is displayed but the system operates continuously.
Troubleshooting
Caution
Field drain
piping has a defect such as
upward sloping.
YES
NO
A humidifier
unit (optional accessory)
is installed on the
indoor unit.
YES
NO
Defect of indoor unit PC board.
(V2782)
Troubleshooting
241
3.8
Si37-701
Remote
controller display
AJ
Applicable
Models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
When the capacity code is not contained in the PC boards memory, and the capacity setting
adaptor is not connected.
Supposed
Causes
Troubleshooting
Caution
The indoor
unit PC board was replaced
with a replacement
PC board.
NO
Replace the indoor unit PC board.
YES
Was the
capacity setting
adapter mounted when
replacing the
PC board?
NO
YES
242
Troubleshooting
Si37-701
3.9
Remote
Controller
Display
C4
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
YES
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 k to 90 k
YES
NO
Troubleshooting
243
Si37-701
C5
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
YES
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 k to 90 k
YES
NO
244
Troubleshooting
Si37-701
C9
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
NO
YES
5 k to 90 k
YES
NO
Troubleshooting
245
Si37-701
CJ
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the remote controller air temperature thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Troubleshooting
Caution
YES
NO
Note:
Press the Operate/ Stop button for 4 seconds and more while the malfunction code is
displayed in the inspection mode.
Refer to Thermistor Resistance / Temperature Characteristics table on P405.
246
Troubleshooting
Si37-701
E1
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Abnormality is detected under the communication conditions in the hardware section between
the indoor unit and outdoor unit.
Malfunction
Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal.
Supposed
Causes
Troubleshooting
Caution
Return to normal?
YES
NO
Check
if inside / outside
relay wires of outdoor
main PC board is
disconnected.
YES
NO
Troubleshooting
247
Si37-701
E3
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure:
2.85MPa
Supposed
Causes
248
Troubleshooting
Si37-701
Troubleshooting
Caution
Are the
three points above
OK?
NO
YES
Mount a pressure gauge on the high-pressure
service port.
Reset the operation using the remote controller,
and then restart the operation.
YES
Is the HPS
operating value normal
(i.e., 4.0MPa)?
YES
NO
Are the
characteristics of the high
pressure sensor normal?
(See 1.)
NO
NO
YES
Service Checker
Connect the service checker to compare the high pressure value and the
actual measurement value by pressure sensor (Refer to 1) by using the
service checker.
Check if the
high pressure value and
the actual measurement value by
pressure sensor are
the same.
NO
YES
The high pressure sensor is normal, and the pressure detected with the PC board is also normal.
The high pressure has really become high.
Referring to information on P340, remove the causes by
CHECK 5 which the high pressure has become high.
1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on P407.)
2: Make measurement of voltage of the pressure sensor.
+5V
Red
(3)
Black
(2)
Micro controller
A/D input
(1)
High
pressure
sensor
White
Make measurement of DC
voltage between these wires.
Troubleshooting
249
Si37-701
E4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under compressor operation.
Operating pressure:0.07MPa
Supposed
Causes
250
Troubleshooting
Si37-701
Troubleshooting
Caution
NO
Is the stop
valve open?
YES
Mount a pressure gauge on the low-pressure
service port.
Reset the operation using the remote controller,
and then restart the operation.
Are the
characteristics of the
low pressure sensor
normal?
(See 1.)
NO
YES
Service Checker
Connect the service checker to compare the low pressure
value and the actual measurement value by pressure sensor
(Refer to 1) by using the service checker.
Check if the
low pressure value and
the actual measurement value
by pressure sensor are
the same.
NO
YES
The low pressure sensor is normal, and the pressure
detected with the PC board is also normal.
The low pressure has really become low.
1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the
connector, and then convert it to pressure according to information on P407.)
2: Make measurement of voltage of the pressure sensor.
+5V
Connector for low pressure sensor
(Blue)
Micro controller
A/D input
(4)
Red
(3)
Black
(2)
White
Low
pressure
sensor
(1)
Troubleshooting
251
Si37-701
E5
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phasecurrent waveform.
Malfunction
Decision
Conditions
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Supposed
Causes
252
Troubleshooting
Si37-701
Troubleshooting
Caution
NO
Local factor
Open the stop valve.
YES
Check if
the relay wires to the
compressor are
correct.
NO
YES
Check if the
connection of UVW
phase order is
correct.
NO
YES
Power OFF
Check if
the wiring is the
same as in the electric
wiring diagram.
YES
The insulation
resistance of the compressor
is low (not more than
100k).
NO
Check if the wiring has
any error in mistake for
inverter compressor.
YES
V
Ensure correct connection.
NO
The compressor
coil has disconnection
of wires.
YES
NO
Restart and
check the operation.
Check if the condition
occurs again.
NO
YES
Check if
the start mode is in
the high differential pressure
(not less than
0.5 MPa).
YES
NO
Power ON
Check
if the inverter
output voltage between 3
phases is within
5V.
NO
YES
Troubleshooting
253
Si37-701
E6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
400 V unit : 15.0 A
Supposed
Causes
Troubleshooting
Caution
NO
YES
NO
Is the power
supply voltage
normal?
YES
Is the
magnetic switch
(K2M, K3M) normal?
(1)
YES
NO
NO
Check the wiring from power supply ~ current sensor (A6P, A7P) ~
MgS (K2M, K3M) ~ compressor
Is
above wiring
correct?
NO
Correct wiring.
YES
Is
current sensor
correct? 1
YES
NO
Note:
254
1 One of the possible factors may be chattering due to rough MgS contact.
2 Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0A during STD compressor stop.
Troubleshooting
Si37-701
E7
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect a malfunction based on the current value in the INVERTER PC board (as for motor 2,
current value in the fan PC board).
Detect a malfunction for the fan motor circuit based on the number of rotation detected by hole
IC during the fan motor operation.
Malfunction
Decision
Conditions
Overcurrent is detected for INVERTER PC board (A2P) or fan INVERTER PC board (A5P)
Troubleshooting
255
Si37-701
Troubleshooting
Caution
Check if
any foreign substances
around the fan.
YES
NO
Check the connection status of the connectors
Fan motor 1: relay connector or X1A, X2A of compressor
inverter PC board.
Fan motor 2: relay connector or X1A, X2A of fan inverter
PC board.
Check
if any connector is
disconnected.
YES
NO
Check the color of relay connectors
Fan motor 1: Both power supply wire and signal wire are
all white.
Fan motor 2: Both power supply wire and signal wire are
red in the PC board side and white in the motor side.
Relay
connectors have
any connection
error.
NO
YES
256
12HP
5HP
8HP
18HP
Troubleshooting
Si37-701
Troubleshooting
Continued from the previous page.
No continuity
of fuse (FIU) on the fan
inverter PC board.
YES
NO
Unable to
rotate the fan manually
with ease when removing
the connector of the
fan motor.
YES
NO
Resistance
value between the power
supply wire terminal of fan motor
and the motor frame (metal) is
1M and below.
YES
NO
Check 1 (Referring to the information on P337)
Check fan motor connector (power supply wire)
The resistance
value between UVW phases
of fan motor is out of balance, or
short circuit between
UVW phases.
YES
NO
Check 2 (Referring to the information on P337)
Check fan motor connector (signal wire)
The signal
wire short circuits
between Vcc and GND
and between UVW
and GND.
YES
NO
Put the power supply ON to check the following
LED lamps.
1) HAP lamp on the compressor PC board (A2P)
2) HAP lamp on the fan inverter PC board (A5P)
HAP lamp
for the A5P does not
blink on the condition that
HAP lamp for A2P
is blinking.
YES
NO
Replace fan motor 2.
Troubleshooting
257
Si37-701
E9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
258
Troubleshooting
Si37-701
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Return to normal?
NO
Check the electronic expansion valve corresponding to the malfunction code E9 in the monitor
mode.
(Refer to P218~219 for how to check.)
When Check 4 shows as follows:
Electronic expansion valve for main use (Y1E, Y3E for Single, Y1E for Multi)
When Check 4 shows as follows:
Electronic expansion valve for refrigerant charge (Y4E for Single, Y2E for Multi)
When Check 4 shows as follows:
Electronic expansion valve for subcooling (Y2E, Y5E for Single, Y3E for Multi)
Explanation of
Master unit
Slave unit 1
Slave unit 2
System
The connector
of outdoor unit PC board
(A1P) for electronic expansion
valve is connected.
NO
YES
The coil
resistance of electronic
expansion valve isnormal.
(Refer to 1)
YES
NO
Make measurement of resistance between the connector pins, and then make sure the resistance
falls in the range of 40 to 50.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
(V3067)
Troubleshooting
259
Si37-701
F3
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level (135 C and above)
When the discharge pipe temperature rises suddenly (120 C and above for10 successive
minutes)
Supposed
Causes
260
Troubleshooting
Si37-701
Troubleshooting
Caution
Check if
discharge pipe
thermister property is
normal.
(1)
NO
YES
Service Checker
Connect the service checker to compare the
temperature of discharge pipe by using service
checker with actual measurement value of discharge
pipe thermister (Refer to 1).
Check if
temperature of
discharge pipe by using
service checker is the same with
actual measurement value
of discharge pipe
thermister.
NO
Troubleshooting
261
Si37-701
F6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Excessive charging of refrigerant is detected by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run.
Malfunction
Decision
Conditions
When the amount of refrigerant, which is calculated by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run, exceeds the
standard.
Supposed
Causes
Refrigerant overcharge
Misalignment of the outside air thermistor
Misalignment of the heat exchanging deicer thermistor
Misalignment of the liquid pipe thermistor
Troubleshooting
Caution
Are the
above thermistor
installed on pipes
correctly?
NO
YES
Remove the outside air thermistor,
heat exchanging deicer thermister
and the liquid pipe thermistor from
the outdoor PC board and measure
resistance with a tester.
Is the
characteristic of the
above thermistor
normal?
YES
NO
Replace thermistor.
Refrigerant overcharged.
(V2797)
262
Troubleshooting
Si37-701
Troubleshooting
263
264
Si37-701
Troubleshooting
Si37-701
H7
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
265
Si37-701
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Master unit
Slave unit 1
Slave unit 2
System
NO
NO
YES
Check the connector
of the fan motor (1).
Check if the
resistance of the fan
motor lead wire between Vcc and
UVW and between GND and
UVW are balanced.
YES
1. Check procedure for fan motor connector
(1) Power OFF the fan motor.
(2) Remove the connector (X2A or X4A) on the PC board to
measure the following resistance value.
Judgment criteria: resistance value between each phase is
within 20%
Connector
for signal wires (X2A or X4A)
X2A
5 Gray
GND
4 Pink
Vcc
3 Orange
2 Blue
1 Yellow
Measure the
resistance
between VccUVW and
GND-UVW.
(V2799)
266
Troubleshooting
Si37-701
H9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Troubleshooting
Caution
Connector is
connected to X18A of
outdoor PC board
(A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(1.8k to
800k)
YES
NO
Troubleshooting
267
Si37-701
J2
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Troubleshooting
Caution
Master unit
Slave unit 1
Slave unit 2
System
Is the
connector for
current sensor
connected to X25A, X26A
on outdoor unit
PC board
(A1P)?
NO
YES
Are the
current sensors inversely
connected to two STD
compressors?
YES
NO
Applicable
compressor coil wire is
broken.
NO
Is the
current sensor
mounted on the T-phase
(A6P) and R-phase
(A8P) wire?
YES
YES
NO
Replace compressor.
268
Troubleshooting
Si37-701
J3
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R31T, R32T, R33T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Defect of thermistor connection
Troubleshooting
Caution
Connector
is connected to X29A
of outdoor unit
PC board
(A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R31, 32T or R33T from the
outdoor unit PC board.
(2.5k to
1.3k)
YES
NO
The alarm indicator is displayed when the fan is being used also.
Refer to Thermistor Resistance / Temperature Characteristics table on P405.
Troubleshooting
269
Si37-701
J4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Connector is
connected to X30A of
outdoor PC board
(A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R2T or R11T) from the
outdoor unit PC
board. (1.8k
to 800k)
YES
NO
270
Troubleshooting
Si37-701
J5
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the suction pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed
Causes
Troubleshooting
Caution
Connector
is connected to
X30A, of outdoor unit
PC board.
(A1P)
NO
YES
Resistance
is normal when
measured after disconnecting the thermistor
(R8T or R10T) from the
outdoor unit PC
board. (1.8k to
800k)
YES
NO
Troubleshooting
271
Si37-701
J6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Troubleshooting
Caution
Connector
is connected to X30A
of outdoor unit PC
board (A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
R4T or R12T from the
indoor unit PC
board. (1.8k
to 800k)
YES
272
Troubleshooting
Si37-701
J7
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Is
the connector
for liquid pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
NO
YES
Is the
resistance
measured after
removing the thermistor
(R6T) (R9T) or (R14T) from
outdoor unit PC board
normal? (1.8k
to 800k)
YES
NO
Troubleshooting
273
Si37-701
J8
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Is
the connector
for liquid pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
NO
YES
Is the
resistance
measured after
removing the thermistor
(R7T or R15T) from outdoor
unit PC board normal?
(1.8k to
800k)
YES
NO
274
Troubleshooting
Si37-701
J9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Supposed
Causes
Troubleshooting
Caution
Is
the connector
for subcooling heat
exchanger gas pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
NO
YES
Is the
resistance
measured after
removing the thermistor
(R5T or R13T) from outdoor
unit PC board normal?
(1.8k to
800k)
YES
NO
Troubleshooting
275
Si37-701
JA
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
NO
YES
If the
PCB pressure
detection normal?
(Make a comparison between the
checker pressure data and the
voltage characteristics
(2).)
NO
YES
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of the high
pressure sensor
normal?
NO
YES
S1NPH
(V2806)
276
Troubleshooting
Si37-701
Troubleshooting
277
Si37-701
JC
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
NO
YES
If the
PC board pressure
detection normal?
(Make a comparison between the
checker pressure data and the
voltage characteristics
(1).)
NO
YES
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of the low
pressure sensor
normal?
YES
NO
278
Troubleshooting
Si37-701
Troubleshooting
279
Si37-701
L1
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected based on the current value during waveform output before starting
compressor.
Malfunction is detected based on the value from current sensor during synchronous operation
when starting the unit.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Check if
the unit recovers to
normal operation.
YES
NO
Check 4
Check if the power
transistor is
normal.
NO
YES
Check if
insulation resistance of
the compressor is 100k
and above.
NO
YES
Replace the inverter PC board
(A2P).
Check 4
Check if the power
transistor of the fan
driver is normal.
NO
Replace the compressor inverter
PC board (A2P) and fan inverter
PC board (A5P).
YES
280
Troubleshooting
Si37-701
L4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 93C.
Supposed
Causes
Troubleshooting
Caution
Power OFF
Fin temperature
of the compressor
inverter is high.
YES
NO
Remove and insert the fin
thermistor connector "X111A".
Power ON
Turn ON
the power supply,
YES
and then check whether or
not the malfunction
recurs.
NO
Troubleshooting
End of measures
It is supposed that
radiation fin
temperature has risen
due to on-site causes.
Conduct the checks
shown below.
Radiation fin for
stains
Airflow for interference
Fan propeller for
damage
Whether or not
outdoor temperature
is too high
281
Si37-701
282
Troubleshooting
Si37-701
L5
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
283
Troubleshooting
Si37-701
Compressor inspection
Caution
NO
YES
Check if
the compressor lead
wires are normal.
NO
YES
Check if the
wiring and connection to
the compressor
are normal.
NO
YES
Power OFF
Insulation
resistance of the compressor
is 100 k or
below.
YES
Replace inverter
compressor.
NO
Compressor
coils are disconnected.
YES
Replace inverter
compressor.
NO
Check 4
Check if the power transistor
is normal.
NO
YES
NO
YES
Power OFF
and the Power
ON again
Continue operation.
Momentary power failure
is possible.
Failure
occurs again after restarting
the unit.
Failure
occurs again after restarting
the unit.
NO
Continue operation.
YES
Replace inverter
compressor.
284
Troubleshooting
Si37-701
L8
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Faulty compressor
285
Troubleshooting
Si37-701
Caution
Check if the
stop valve is open.
NO
YES
Check if the
compressor lead wires are
normal.
Check if the
wiring and connection to
the compressor are
normal.
NO
NO
Replace compressor
lead wires.
Power OFF
Insulation
resistance of the compressor
is 100 k or
below.
Check 4
Check if the power transistor
is normal.
YES
YES
NO
YES
Connect the compressor lead
wires then restart the operation.
Malfunction code
L8 is displayed again.
NO
Continue operation.
YES
Check if the
pressure difference between high
pressure and low pressure before
restarting is 0.2MPa
or below.
YES
NO
286
Defective pressure
equalizing in the
refrigerant circuit.
Inspection of the
compressor.
Troubleshooting
Si37-701
L9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
287
Si37-701
Troubleshooting
Caution
Check if it
is the first time to start
after installation.
NO
YES
Check if a
right amount of refrigerant
is charged.
NO
YES
Check if the
stop valve is open.
NO
YES
Refrigerant
is sleeping. ( The unit is out
of power supply for more than
6 hours.)
YES
NO
Check if the
insulation resistance of the
compressor is more
than 100k.
NO
YES
Check if the
compressor lead wires are
disconnected.
YES
NO
Correct the wiring then supply
power to restart.
288
Troubleshooting
Si37-701
Troubleshooting
Continued from the previous page.
(Start failure due to aged operation.)
Refrigerant
is sleeping. ( The unit is out
of power supply for more
than 6 hours.)
NO
YES
Check if the
insulation resistance of the
compressor is 100k
or over.
NO
YES
Broken inside
the compressor
YES
NO
Check 4
Check if the power
transistor is
normal.
NO
YES
Recheck the compressor/
refrigerant circuit.
Troubleshooting
289
Si37-701
LC
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Check the communication state between inverter PC board and control PC board by microcomputer.
Malfunction
Decision
Conditions
Supposed
Causes
290
Malfunction of connection between the inverter PC board and outdoor control PC board
Defect of outdoor control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
Faulty fan inverter
Incorrect type of fan inverter
Faulty compressor
Faulty fan motor
Troubleshooting
Si37-701
Troubleshooting
Caution
NO
YES
Power ON
Check
whether or not
the power supply voltage
between L2 and N falls in
the range of 220 to
240VAC?
NO
On-site cause.
Correct the wiring.
YES
Is the type
(PC No.) of the fan
inverter correct?
NO
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
NO
Power OFF
The insulation
resistance is low (i.e., not
more than
100k.)
YES
FAN1
PC0511-1
PC0511-1
PC0511-3
PC0511-3
PC0511-1
FAN2
PC0511-4
PC0511-4
PC0511-2
Replace the
compressor.
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
NO
The insulation
resistance is low (i.e., not
more than
1M.)
YES
NO
<REYQ8/10/12P>
<REYQ14/16P>
<Multi>
Troubleshooting
291
Si37-701
Troubleshooting
A
Power OFF
YES
F400U of the
A3P has been
molten.
NO
NO
NO
YES
NO
The LC malfunction recurs.
YES
NO
End of measures:
The malfunction may
temporarily result from
on-site causes.
Causes:
Instantaneous power
failure (open phase),
noises, or else.
F400U
292
Troubleshooting
Si37-701
P1
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
minutes.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PC board
Defect of K2 relay in inverter PC board
Improper main circuit wiring
Troubleshooting
Caution
Imbalance
in supplied voltage is
in excess of 14 V
(Y1). 1
YES
Open phase?
NO
NO
Is
the voltage
imbalance applied to the
inverter in excess of
14 V (Y1)?
2
YES
No abnormalities are
observed in the power
supply, but the imbalance
in voltage recurs.
YES
Open phase
Normalize field cause.
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2 contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Explanation for users In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave Be sure to explain to the user that
there is a "power supply imbalance"
it up to him to improve the imbalance.
for which DAIKIN is not responsible.
(V2816)
Troubleshooting
293
Si37-701
P4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
Troubleshooting
Caution
Power OFF
YES
Replace the
compressor.
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The insulation
resistance is low (i.e., not more than
1M.)
YES
NO
Remove and insert the fin
thermistor connector [X111A].
Power ON
Turn ON the
power supply, and then check
whether or not the malfunction
recurs.
YES
NO
End
294
Troubleshooting
Si37-701
Troubleshooting
295
Si37-701
PJ
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
The faulty (or no) field setting after replacing main PC board or faulty PC board combination is
detected through communications with the inverter.
Malfunction
Decision
Conditions
Whether or not the field setting or the type of the PC board is correct through the communication
date is judged.
Supposed
Causes
Troubleshooting
Caution
Has the PC
board been replaced?
NO
YES
When replacing
the PC board, were field
setting properly
made?
NO
YES
Is the type of
PC board correct?
YES
NO
296
Troubleshooting
Si37-701
U0
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect gas shortage based on the temperature difference between low pressure or suction pipe
and heat exchanger.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
297
Si37-701
Troubleshooting
Caution
In cooling mode
Set up a pressure gauge at the service port on the low
pressure side.
Reset the operation using the remote controller then restart.
Check if the
low pressure is 0.1MPa
or below. (1)
NO
Check if the
property of low pressure
sensor is normal.
(2)
YES
NO
YES
Replace the main PC board
(A1P).
Remove the factor of
decreasing low pressure by
referring to Check 6 .
1
Check if the
temperature difference between
the suction pipe and the heat exchanger
is 20 C and over.
NO
Check if the
property of suction pipe thermister
(A7T) and heat exchanger thermister
(R4T) are normal.
(*3)
NO
YES
3: Compare the thermister resistance value with the value on the surface
thermometer.
298
Troubleshooting
Si37-701
U1
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
YES
NO
Operation
is normal if one
place of power supply
line phase is
replaced.
NO
YES
Reverse phase
Counter measure of the problem is
completed by phase replacement.
Replace outdoor unit PC board
(A1P).
(V2820)
Troubleshooting
299
Si37-701
U2
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
current-limiting voltage does not reach 200V or more or exceeds 740V.
Supposed
Causes
300
Troubleshooting
Si37-701
Troubleshooting
Caution
On-site causes.
Make proper wire connections
without open phase, erroneous
connections, or erroneous order of
phases.
YES
Power ON
Power OFF
NO
Unbalanced
power supply? (Not more
NO
than 2%: Phase voltage of not
more than approx.
5V)
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
NO
The
YES
insulation resistance is
low (i.e., not more than
100k.)
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
NO
The
YES
insulation resistance is
low (i.e., not more than
1M.)
NO
On-site causes
Correct the unbalanced loads to
eliminate the unbalanced state.
Unbalanced voltage will cause
extremely unbalanced current,
thus impairing the service life of or
resulting in the malfunction of the
equipment.
Has the
power transistor got
faulty?
YES
NO
YES
Troubleshooting
301
Si37-701
Troubleshooting
A
Power OFF
<Multi>
Check for connector connections: Remove
and insert the connectors shown below.
Furthermore, check the connectors for
terminal conditions and continuity.
X1M power receiving terminal X400A A3P
A3P X401A X10A A4P
A1P X28A X6A A4P
A4P X61A X402A A3P
A4P X1A X403A A3P
A4P P1,P2 Reactor terminal L1R
A4P P3,N3 P1,N1 A5P
A5P P2,N2 P1,N1 A7P
Has the
inverter PC board caused
damage?
YES
Single : A5P, A8P
Multi : A4P
Replace the inverter PC board.
If the PC board replaced is badly
damaged, the compressor is
likely to get faulty. To make sure,
recheck the compressor.
NO
Has the
fan driver caused
damage?
<Single>
Check for connector connections: Remove
and insert the connectors shown below.
Furthermore, check the connectors for
terminal conditions and continuity.
X1M power receiving terminal X400A A3P
A4P or A7P X401A X10A A5P or A8P
A1P or A3P X28A X6A A5P or A8P
A5P or A8P X61A X402A A4P or A7P
A5P or A8P X1A X403A A4P or A7P
A5P or A8P P1,P2 Reactor terminal L1R
A5P or A8P P3,N3 P1,N1 A5P
A6P P2,N2 P1,N1 A7P
YES
NO
YES
NO
Power ON
Stop (standby)
when the compressor
starts up.
YES
NO
The U2
malfunction recurs.
YES
NO
End of measures:
The malfunction may temporarily
result from on-site causes.
Causes: Instantaneous power
failure (open phase), noises, or
else.
302
Troubleshooting
Si37-701
U3
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Troubleshooting
Caution
Has the
check operation
performed on Outdoor
unit PC board?
YES
NO
Troubleshooting
303
Si37-701
U4
Applicable
Models
Method of
Malfunction
Detection
Check if the transmission between indoor unit and outdoor unit is correctly executed using
microcomputer.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
304
or wrong wiring
Outdoor unit power supply is OFF
System address doesnt match
Defect of indoor unit PC board
Defect of outdoor unit PC board
Troubleshooting
Si37-701
Troubleshooting
Caution
In Check 4,
LED lamp indicates
as follows:
NO
YES
Check if
indoor unit PC board or
outdoor unit PC board has been replaced.
Or check if indoor/ outdoor, outdoor/
outdoor connecting wires
are normal.
YES
NO
Check if all
the indoor remote controllers
within the same refrigerant
circuit display
U4.
NO
YES
Check if the
indoor/ outdoor, outdoor/
outdoor connecting wires
are normal.
YES
NO
NO
Lights do not
go out for 12 minutes
or more.
NO
The fuse on
the outdoor unit PC
board is blown.
NO
YES
YES
Press the rewiring button on the
main PC board of the outdoor unit.
Keep pressing for 5 seconds or
more.
NO
Check if
the indoor/ outdoor,
outdoor/ outdoor connecting
wires are normal.
YES
YES
Check if
the LED in preparation
mode (H2P) on the outdoor
unit PC board
blink.
YES
Check if the
NO
voltage between RS
terminals on the outdoor unit
PC board is 200V.
NO
YES
Check if
the operation is normal
with 1 circuit after outdoor/ outdoor
connecting wires are
removed.
YES
Troubleshooting
NO
305
Si37-701
Troubleshooting
Caution
NO
Continue operation.
YES
NO
YES
The indoor units PC board
indicating U9 are normal.
Check the indoor units in the other
circuits to diagnose failure
according to the corresponding
malfunction codes.
306
Troubleshooting
Si37-701
U5
Applicable
Models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Using
2-remote controllers
control.
YES
NO
All indoor
PC board microcomputer
monitors blink.
YES
NO
NO
YES
Operation
returns to normal when
the power is turned off
momentarily.
YES
Normal
SS1 of
both remote controllers
is set to "MAIN."
YES
NO
NO
Replace the indoor unit PC
board.
Normal
NO
YES
Normal
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
(V2823)
Troubleshooting
307
Si37-701
U7
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error in connecting wires between outdoor unit and outdoor unit outside control
adapter
Connection error in connecting wires across outdoor units
Setting error in switching cooling/ heating
Integrated address setting error for cooling/ heating
308
Troubleshooting
Si37-701
Troubleshooting
Caution
Check 3
Check 4
Go on to the Diagnosis Flow 1
Check 3
Check 4
Go on to the Diagnosis Flow 2
Check 3
Check 4
Go on to the Diagnosis Flow 3
Check 3
Check 4
Go on to the Diagnosis Flow 4
Check 3
Check 4
Go on to the Diagnosis Flow 5
Check 3
Check 4
Go on to the Diagnosis Flow 6
Check 3
Check 4
Go on to the Diagnosis Flow 7
Check 3
Check 4
Go on to the Diagnosis Flow 8
Troubleshooting
309
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 1
Check 4
Check if
any disconnection or
connection error is detected in
connecting wires with
outside control
adapter.
NO
YES
Check if
the normal condition
monitor LED for the outdoor
unit PC board
blinks.
NO
YES
Check if power
is supplied to the
outdoor units.
NO
Supply power to the outdoor
unit.
YES
Replace the outdoor unit main
PC board.
Check if
the normal condition monitor
LED for the outside control
adapter blinks.
YES
NO
Check if
the power supply
wire for the outside control
adapter is connected to
5V supply
line.
NO
YES
Replace the PC board of the
outside control adapter.
Replace the outdoor unit main
PC board.
310
Troubleshooting
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 2
Check 4
Switch cooling/heating in
a lump.
NO
YES
Setting of
cooling/heating switch
for the outside control
adapter is Master
in a lump.
YES
NO
Setting of
cooling/heating switch
for the outside control adapter
is Slave in a lump.
NO
YES
Check if
the normal condition
NO
monitor LED for the outdoor
unit main PC board
blinks.
YES
Check if the
NO
outdoor unit is powered on.
YES
Replace the main PC board of
the outdoor unit.
Check if
the normal condition
NO
monitor LED for the outside
control adapter
blinks.
YES
Set the
cooling/heating switch
of the outside control adapter to
individual. Then check if the
failure occurs again.
Check if
the power supply
wire for the outside control
adapter is connected
to 5V supply
line.
NO
YES
NO
YES
Replace the main PC board of
the outdoor unit.
Troubleshooting
311
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 3
Check 4
Check
the connection status
of connecting wires of Multi Slave 1
with outdoor multi. Check if the wiring
is not disconnected or is about to
be disconnected.
NO
YES
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Check 3
Diagnosis Flow 4
Check 4
Check the
connection status
of connecting wires of Multi
Slave 2 with outdoor multi. Check if the wiring
is not disconnected or is about
to be disconnected.
NO
YES
Correct the connecting wires of
the outdoor multi and then reset
the power supply.
Check 3
Diagnosis Flow 5
Check 4
Check
if the outdoor unit is
REYQ8~16PY1.
NO
YES
Remove the connecting wires of
the outdoor multi and then reset
the power supply.
312
Troubleshooting
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 6
Check 4
Check
the connection
status of one of the connecting
wires of Outdoor Multi. Check
if the wiring is broken or
disconnected.
NO
YES
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Check 3
Diagnosis Flow 7
Check 4
In the
connection status
of theoutdoor multi, check if
more than 4 outdoor units
are connected.
NO
YES
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Check 3
Diagnosis Flow 8
Check 4
Check the
connection status of the
connecting wires of outdoor multi. Check
if the wiring has any connection error
or broken, or is about to be
disconnected.
NO
YES
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Troubleshooting
313
Si37-701
U8
Applicable
Models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Using 2-remote
controllers control.
NO
YES
SS1
of both remote controllers is
set to "SUB."
YES
SS1
of remote controller PC boards
is set to "MAIN."
NO
YES
NO
314
Troubleshooting
Si37-701
U9
Applicable
Models
Method of
Malfunction
Detection
Detect malfunction signal for the other indoor units within the circuit by outdoor unit PC board.
Malfunction
Decision
Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Troubleshooting
Caution
NO
Continue operation.
YES
"U9"
has been displayed for 2
minutes or more.
YES
Troubleshooting
NO
315
Si37-701
UA
Applicable
Models
Method of
Malfunction
Detection
A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units is out of the allowable range.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Check 3
Check 4
Go on to the Diagnosis Flow 1
Check 3
Check 4
Go on to the Diagnosis Flow 2
Check 3
Check 4
Go on to the Diagnosis Flow 3
Check 3
Check 4
Go on to the Diagnosis Flow 4
316
Troubleshooting
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 1
Check 4
The number
of indoor units connected
to the same refrigerant circurt system
should not be more than
64 units.
YES
NO
The number of indoor units
exceeds the standard. Check the
connection to correct.
Check 3
Diagnosis Flow 2
Check 4
YES
NO
Match the refrigerant types of the
outdoor unit and the indoor unit.
Troubleshooting
317
Si37-701
Troubleshooting
Caution
Check 3
Diagnosis Flow 3
Check 4
NO
YES
Check
if the outdoor
unit PC board is replaced
with PC board for
spare parts.
NO
YES
Check
if the unit is not
connected to outdoor
units of different
models.
NO
YES
Check the model of the outdoor
unit.
Check if
the spare parts PC board
setting is correct.
NO
YES
Replace the spare parts PC board.
Check 3
Diagnosis Flow 4
Check 4
318
Troubleshooting
Si37-701
UC
Applicable
Models
Method of
Malfunction
Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Troubleshooting
319
Si37-701
UE
Applicable
Models
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
320
unit
Connector for setting master controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting
Si37-701
Troubleshooting
Caution
Check
the indoor
unit for which
UE is displayed.
Is the the transmission
malfunction (UE)
caused on
all indoor
units?
YES
Continued to A
(on the following
page)
NO
Is the
power supply of
the indoor unit, on which
the UE occurred,
turned ON?
NO
YES
Has
the setting of
central control group No.
been made with the
indoor unit on which
the UE
occurred?
NO
YES
YES
NO
For VRV
systems, can the
setting of central controlgroup
No. be made in one and
the same refrigerant
system?
YES
Was
the central
control group No.
for indoor unit
changed?
Can
the setting of
central control group
No be made?
NO
YES
NO
Troubleshooting
321
Si37-701
Troubleshooting
A
Check the
transmission
wiring between central
equipment for any broken
wire. For details, refer to
information in the Procedure
for checking broken
wires section.
(Refer P.332)
Abnormal
Normal
Check the
transmission
wiring with the master
unit central equipment for
any broken wire. For details,
refer to information in the
Procedure for checking
broken wires
section.
(Refer P.332)
Abnormal
Normal
Has the
master unit central
setting connector been
connected?
NO
YES
Disconnect the transmission
wiring of the master unit
central equipment, and then
check the voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multiple meter.
Is the
voltage between
the terminals F1 (+)
and F2 (-) in the range of
15.2 to 17.6
VDC?
YES
NO
322
Troubleshooting
Si37-701
UF
Applicable
Models
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
Supposed
Causes
outdoor units
Failure to execute check operation
Defect of indoor unit PC board
Stop valve is left in closed
Troubleshooting
Caution
NO
YES
Is the
check operation
carried out?
NO
YES
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES
Is indoor
-outdoor and outdooroutdoor unit transmission
wiring normal?
YES
Replace indoor unit PC board.
NO
NO
Note:
Troubleshooting
Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
323
Si37-701
UH
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
outdoor units
Defect of indoor unit PC board
Defect of outdoor unit main PC board (A1P or A3P)
324
Troubleshooting
Si37-701
Troubleshooting
Caution
Is
electricity
being introduce for
the first time after
YES
installation or after an indoor
or outdoor unit PC
board has been
replaced?
NO
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
NO
Normal
YES
NO
YES
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?
NO
Normal
YES
Disconnect
the outdoor-outdoor
unit transmission
wiring to create the onesystem status, and then
check whether or not
the system is
normal.
YES
NO
Does
a UH malfunction occur
for all indoor units in
the system?
YES
NO
(V2831)
Troubleshooting
325
Si37-701
M1 PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
With M1 displayed
Without M1 displayed
326
Troubleshooting
Si37-701
4.2
Remote
Controller
Display
M8
Applicable
Models
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data. (The system will be
automatically reset.)
Malfunction
Decision
Conditions
When no master controller is present at the time of the startup of slave controller.
When the centralized controller, which was connected once, shows no response.
Supposed
Causes
Troubleshooting
Caution
Were
any changes
made to the number
of units of central
equipment? (The central
equipment was connected once,
and then disconnected, or
additional central
equipment was
installed.)
YES
NO
NO
Have power
supplies to every central
equipment been
turned ON?
YES
Is the display of LCD OK?
Nothing is
displayed on the LCD by operating
Ve-Up controller.
(1)
NO
NO
YES
Abnormal
YES
Troubleshooting
327
4.3
Si37-701
Remote
Controller
Display
MA
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
When the remote control adapter is present.
Supposed
Causes
328
Troubleshooting
Si37-701
Troubleshooting
Caution
Has the
remote control adapter
(KRP2A series) been
connected?
YES
NO
Has the
schedule timer been
connected?
YES
Has
the Interface for
BaCnet been
connected?
NO
YES
NO
Has the
DMF-IF been
connected?
YES
NO
Has the parallel
interface been
connected?
YES
NO
NO
Are there
two or more units
of central equipment
with master unit setting
connectors (CN1/X1A)
connected?
YES
Has the
Independent/
YES
Combined use
connector(CN1/X1A) of the
schedule timer been
connected?
NO
Reset the
power supplies of every
central equipment.
Troubleshooting
329
4.4
Si37-701
Remote
Controller
Display
MC
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Two or more units of central remote controllers and Intelligent Touch Controllers are
Supposed
Causes
connected, and all of them are set to master unit central setting or slave unit central setting.
Two units of schedule timers are connected.
Troubleshooting
Caution
Did the
malfunction
occur while in the first test
run using the intelligent
Touch controller?
NO
YES
Is the
Master/Slave setting of the
central equipment
correct?
NO
Is the Master/
Slave setting of the
central equipment
correct?
Be sure to
refer to the
Master/
Slave
setting
table.
Check 9 Correct the setting of the
combination of master and
1
slave units, and then reset
the power supplies of every
central equipment.
YES
YES
NO
Was the
central equipment
connected once, and then
disconnected, or was additional
central equipment
installed?
YES
Reset the power supplies of
every central equipment.
NO
Turn ON the power supply of
the central equipment with
"MC" displayed once again.
If the intelligent Touch
controller is used, correct the
setting of the combination of
master and slave units again
while in DIII-NET test run
mode, referring to the
Master/Slave setting table.
(Refer P183.)
With "MC"
displayed
Is the "MC"
displayed again?
Without "MC"
displayed
Reset the power supplies of
every central equipment.
330
Troubleshooting
Si37-701
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
331
Si37-701
Troubleshooting
Caution
Is a
malfunction
code displayed on the
remote controller?
YES
NO
Has a
once connected
indoor unit been removed
or its address
changed?
YES
NO
Is the
power supply for
the indoor unit displaying
a malfunction
turned
on?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Is
transmission
with all indoor units
malfunctioning?
NO
YES
YES
NO
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Is
the group
No. of malfunctioning
indoor units
set?
YES
NO
NO
Is the
master
controller's connector for
setting master controller
disconnected.
YES
NO
Replace the central PC board.
(V2841)
332
Troubleshooting
Si37-701
5.2
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the centralized controller, which was connected once, shows no response.
The control ranges are overlapped.
When multiple master central controller are present.
When the schedule timer is set to individual use mode, other central controller is present.
When the wiring adaptor for electrical appendices is present.
Supposed
Causes
Troubleshooting
333
Si37-701
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Has a once
connected optional
controller for centralized
control been disconnected
or its address
changed?
YES
NO
Is the
power supply
turned on for all
optional controllers for
centralized
control?
YES
Is the
reset switch
of all optional controllers
for centralized
control set to
"normal"?
NO
NO
YES
Is
transmission wiring
disconnected or wired
incorrectly?
YES
NO
Is
a central remote
controller or schedule timer
connected?
YES
NO
Are
two or more unified
ON / OFF controllers
connected?
NO
Is the
central remote
controller or schedule
timer displaying a
malfunction?
334
NO
YES
Is the setting
of the unified
ON / OFF controller's
switch for setting
each address
duplicated?
YES
2A
YES
NO
(V2842)
Troubleshooting
Si37-701
2A
Is the
wiring adaptor for
electrical appendices
connected?
YES
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
NO
Is a schedule timer
connected?
YES
NO
Is a parallel interface
connected?
YES
NO
Is the
schedule timer's
individual/combined
connector
connected?
NO
Are
there two or
more optional
controllers for centralized
control connected with the
connector for setting
master
controller?
YES
NO
Reset the power supply
for all optional controllers
for centralized control
simultaneously.
If the malfunction is still not cleared:
YES
(V2843)
Troubleshooting
335
5.3
Si37-701
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Central control address (group No.) is not set for indoor unit.
Improper control range setting switch
Improper wiring of transmission wiring
Troubleshooting
Caution
Is the central
control address (group No.) NO
set for the
indoor unit?
YES
Is the control
range setting switch
set correctly?
NO
YES
Is
the transmission
wiring disconnected or
wired incorrectly?
YES
NO
Replace the unified ON/OFF
controller.
(V2844)
336
Troubleshooting
Si37-701
[CHECK 1]
[CHECK 2]
Troubleshooting
Red
White
Black
5 Gray
GND
4 Pink
Vcc
3 Orange
2 Blue
1 Yellow
337
Si37-701
Defective solenoid
valve coil
Defective solenoid
valve body
Faulty
discharge
pipe
temperature
control
Faulty
subcooling
motorized
valve control
(EV2)
Subcooling
motor
operated
valve failure
Control
failure
(2)
Temperature
increase of
discharge
pipe
Superheat due to
defective compressor
Indoor unit
motorized
valve failure
Faulty control
Faulty control
Refrigerant gas
shortage
Large resistance
of piping
Superheat due to
shaft damage
Faulty
superheated
degree
control.
[In heading
mode]When
outdoor unit
electronic
expansion valve
becomes too
narrow (4)
Defective valve
body
Defective low
pressure sensor
Defective subcool
heat exchange
outlet thermister
Defective control
PC board
Faulty of 4 way
switch valve
operation
Compressor
overheat
Bend/collapse
1: Refer to Low pressure protective control (P126) for hot gas bypass control.
2: Refer to P108 for subcooling electronic expansion valve control.
3: Superheating temperature control in cooling mode is conducted by indoor unit electronic expansion valve. (Refer to P143)
4: Superheating temperature control in heating mode is conducted by outdoor unit electronic expansion valve (EVM).
(Refer to P108).
5: Judgment criteria of superheat operation:
Suction gas superheating temperature: 10 degrees and over. Discharge gas superheating temperature: 45 degrees
and over, except for immediately after starting and drooping control, etc..
(Use the above stated values as a guide. Depending on the other conditions, the unit may be normal despite the values
within the above scope.)
338
Troubleshooting
Si37-701
[Preparation]
Tester
Point of Measurement
+
P2
U
P2
V
P2
W
U
P2
V
P2
W
P2
N3
U
N3
V
N3
W
U
N3
V
N3
W
N3
Judgment Criteria
Remarks
No.
1
2
3
4
5
6
7
8
9
10
11
12
2 ~ 15k
2 ~ 15k
Point of Measurement
+
P2
U
P2
V
P2
W
U
P2
V
P2
W
P2
N3
U
N3
V
N3
W
U
N3
V
N3
W
N3
Judgment Criteria
Remarks
0.3 ~ 0.7V
J1
J2
J3
P1
DM
P3
P1
N3 U V
P2 P3
IGBT
X10A K2
L1
L2
L3
J1
J2
J3
N3
W
X11A
(V2895)
Troubleshooting
339
Si37-701
Local
pressure
rise
[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Rise in high
pressure
Faulty high
pressure
control
High pipe
resistance
Clogging of foreign
particles
Faulty outdoor
Faulty valve coil
unit motorized
valve
Faulty valve body
A temperature difference in excess of 10C
between the inlet and the outlet is deemed to be abnormal.
Faulty high pressure sensor
Faulty
control
Faulty control PC board
Faulty valve coil
Faulty indoor
unit motorized
valve
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *2.)
[In cooling]
High suction
air
temperature
of the
condenser
Faulty
control
Short circuit
High suction
air temperature
of indoor unit
Short circuit
[In heating]
Degradation
in condensing
capacity
Dirty condenser
Decreased
fan airflow
rate
Decreased
fan
output
High air
passage
resistance
Excessive refrigerant charging
Improper model selection [In heating]
Faulty fan
motor
Faulty control
PC board
(Including
capacity setting)
Dirty filter
Obstacle
Refer to P262.
Is the indoor unit too small compared to
the large-sized outdoor unit?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EVM) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for subcooled degree control.
(For details, refer to Electronic Expansion Valve Control on P143.)
SDK04009
340
Troubleshooting
Si37-701
Abnormally low
low-pressure
(Low evaporating
temperature)
Faulty
compressor
capacity
control
Faulty low
pressure
protection
control
Faulty indoor
unit electronic
expansion valve
Low suction
air temperature
of the
evaporator
Faulty
control
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(See *4.)
[In cooling]
Faulty
control
Short circuit
[In heating]
High pipe
resistance
Degradation
in condensing
capacity
Refer to P297.
Moisture choke
Dirty
evaporator
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Dirty filter
Obstacle
*1: For details of the compressor capacity control while in cooling, refer to Compressor PI Control on P100.
*2: The low pressure protection control includes low pressure protection control and hot gas bypass control. For details, refer to P126.
*3: In cooling, the indoor unit electronic expansion valve is used for superheated degree control. (For details, refer to P143.)
*4: In heating, the outdoor unit electronic expansion valve (EVM) is used for superheated degree control of outdoor unit heat exchanger.
(For details, refer to P108.)
Troubleshooting
SDK04009
341
Si37-701
Short-circuit
between the
outdoor-outdoor
unit terminal
parts.
Indoor-outdoor Unit
Transmission Wiring
Short-circuit between
the indoor-outdoor unit
terminal parts.
Outdoor-outdoor Unit
Transmission Wiring
342
Troubleshooting
Si37-701
Unified
ON/OFF Schedule
timer
controller
1 to 2
units
(*1)
1 unit
(*1)
1 to 8
units
1 to 2
units
1 to 4
units
1 to 16
units
(*1)
1 unit
1 unit
Central
remote
controller
Provided
Not provided
Unified
ON/OFF
controller
Schedule
timer
(*1)
1 unit
1 to 16
units
1 unit
1 unit
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Not provided
Not provided
Only a
single unit:
"Provided",
Others: "Not
provided"
Not provided
Provided
(*1) The intelligent Touch controller and the schedule timer are not available for combined use.
(*2) The intelligent Touch controller, central remote controller, and the unified ON/OFF controller have been set to "Provided with the master
unit central setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit central setting
connector" at the factory, which is attached to the casing of the main unit.
Troubleshooting
343
Si37-701
#1
Slave
#2
#3
#1
Pattern
#4
#2
1-00~4-15
Master/
Slave
#3
5-00~8-15
Master/
Slave
#4
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
CRC
Master
CRC
Master
CRC
Slave
CRC
Slave
CRC
Master
CRC
Slave
Intelligent
Touch
controller
Master
Intelligent
Touch
controller
Slave
CRC
Master
Intelligent
Touch
controller
Slave
Intelligent
Touch
controller
Master
CRC
Slave
CRC
Master
Intelligent
Touch
controller
Master
344
Troubleshooting
Si37-701
Overcharge of refrigerant
[Cooling]
Indoor unit
motorized valve
opens too
much. (*1)
Faulty indoor
unit motorized
valve
Faulty control
Faulty control
of superheated
degree
[Heating]
Outdoor unit
motorized valve
opens too
much. (*2)
Faulty outdoor
unit motorized
valve
Wet operation
Faulty control
Dirty evaporator
Degraded
evaporation
capacity
Reduced
fan output
Reduced
air quantity
(including faulty
capacity setting)
Increased
resistance
in air
passage
Dirty filter
Obstacles
*1: "Superheated degree control" in cooling operation is exercised with the indoor unit motorized valve. (Refer to
information on P143.)
*2: "Superheated degree control" in heating operation is exercised with the outdoor unit motorized valve (EV1).
(Refer to information on P108.)
*3: Guideline of superheated degree to judge as wet operation
Suction gas superheated degree: Not more than 3C; Discharge gas superheated degree: Not more than
15C, except immediately after compressor starts up or is running under drooping control.
(Use the values shown above as a guideline. Even if the superheated degree falls in the range, the compressor
may be normal depending on other conditions.)
Troubleshooting
345
Si37-701
Frequency comes to
the minimum level.
Supercooled degree
becomes higher.
(Liquid connection
pipe temperature
lowers.)
High pressure
(LP is maintained
at a constant level.)
Low pressure
LP rises due to
reduced compressor
output.
Frequency
To maintain LP, frequency
increases under the capacity
control.
The outdoor unit motorized valve is
closed due to the overload control.
Heating
Frequency comes to
the minimum level.
(HP is maintained
at a constant level.)
High pressure
Low pressure
LP rises due to
reduced frequency.
LP drops due to closed
outdoor unit motorized
valve.
Hot gas bypass is activated
for LP protection, i.e.,
hunting at LP.
Frequency
To maintain HP, frequency reduces
under the capacity control.
(Degree of overcharge)
Proper quantity
346
Troubleshooting
Si37-701
High pressure
HP drops with decrease
in compressor capacity.
(LP is maintained
at a constant level.)
Low pressure
LP rises as the opening
degree of the indoor unit
motorized valve becomes
larger. Frequency slightly
increases under the
capacity control.
Frequency
To maintain LP,
frequency drops
due to the
capacity control.
Heating
The opening degree of the outdoor unit motorized valve becomes larger.
The outdoor unit motorized valve fully opens and frequency increases.
Discharge pipe or LP drooping control
High pressure
(HP is maintained
at a constant level.)
Frequency comes to
the minimum level.
Low pressure
Frequency
To maintain LP, frequency
drops due to the capacity
control.
Frequency drops
due to the drooping
control.
Troubleshooting
347
Si37-701
348
In case of construction during rainy reason, if dew condensation occurs in the piping due
to extended construction period, or rainwater or else may enter the piping during
construction work:
Troubleshooting
Si37-701
Compressor current
Code
Name
Major cause
L5
Instantaneous overcurrent of
inverter compressor
Liquid sealing
Faulty compressor
Faulty inverter PC board
L8
Overcurrent of inverter
compressor (Electronic thermal)
L1
No output is given.
L9
E5
Faulty compressor
L4
Malfunction of fan
Running in overload for an
extended period of time
Faulty inverter PC board
U2
P1
LC
PJ
PC board mismatching
P4
Troubleshooting
PC board of different
specification mounted
349
Si37-701
LC
L5
Heavy-current
part (Power
transmission etc.)
U2
P1
L1
P4
L4
Compressor
Weak-current Inverter
PC board
part
Power supply
(3 phase, 400VAC)
L8
PJ
E5
PCB mismatching
When incorrect inverter
PC board is connected
Radiator fin temperature rise
When the radiator fin
temperature reached
93C or more
Faulty fin thermistor
When the fin thermistor resistor detects
an open circuit (-30C or less) or a short
circuit (120C or more)
L9
Current
Faulty inverter
When the heavy current part of
inverter gets faulty (gives no output)
Instantaneous
overcurrent
L5
32.3A
Compressor overcurrent
(Electronic thermal 2)
19.0A
16.1A
L8
Compressor overcurrent
(Electronic thermal 1)
L8
5 consecutive sec.
260 consecutive sec.
Max. control
Time
350
Troubleshooting
Si37-701
Part 7
Appendix
1. Piping Diagrams..................................................................................352
1.1 Outdoor Unit .........................................................................................352
1.2 Indoor Unit............................................................................................357
1.3 BS Unit .................................................................................................360
6.
7.
8.
9.
Appendix
351
Piping Diagrams
Si37-701
1. Piping Diagrams
1.1
Outdoor Unit
S2NPL
3D058154A
S1NPH
352
Appendix
Si37-701
Piping Diagrams
S2NPL
3D058153A
REYQ14P / 16PY1
S1NPH
Appendix
353
Piping Diagrams
Si37-701
REMQ8PY1
3D057743
354
Appendix
Si37-701
Piping Diagrams
REMQ10PY1, 12PY1
3D057742
Appendix
355
Piping Diagrams
Si37-701
REMQ14PY1, 16PY1
3D057741
356
Appendix
Si37-701
1.2
Piping Diagrams
Indoor Unit
Heat exchanger
(4)
Fan
(2)
(3)
Liquid piping connection port
(Flare connection)
Filter
(1)
Electronic
Filter
expansion valve
DU220-602J
Code
Appendix
Name
Code
(1)
Y1E
(2)
R1T
(3)
Liquid pipe
R2T
(4)
Gas pipe
R3T
Capacity
GAS
20 / 25 / 32 / 40 / 50M(A)
63 / 80 / 100 / 125M(A)
200M(A)
250M(A)
12.7
15.9
19.1
22.2
Main function
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
Used for thermostat control.
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
Used for gas superheated degree control while in
cooling operation.
(mm)
Liquid
6.4
9.5
9.5
9.5
357
Piping Diagrams
Si37-701
FXZQ
358
Gas
12.7
(mm)
Liquid
6.4
Appendix
Si37-701
Piping Diagrams
FXDQ
4D043864H
Appendix
Gas
(mm)
Liquid
12.7
6.4
15.9
9.5
359
Piping Diagrams
Si37-701
FXDYQ
Gas pipe
connection port
Heat exchanger
Fan
Liquid pipe
connection port
Filter
Filter
Electronic
expansion valve
4PDA0350
1.3
360
Gas
15.9
19.1
22.2
(mm)
Liquid
9.5
9.5
9.5
BS Unit
Appendix
Si37-701
Outdoor Unit
3D056775D
REYQ8 / 10 / 12PY1
Appendix
361
Si37-701
3D056774C
REYQ14 / 16PY1
362
Appendix
Si37-701
3D055307E
REMQ8PY1
Appendix
363
Si37-701
3D055308E
REMQ10 / 12PY1
364
Appendix
Si37-701
3D055309E
REMQ14P / 16PY1
Appendix
365
2.2
Si37-701
Field Wiring
3D057764
366
Appendix
Si37-701
3D057762
Appendix
367
Si37-701
3D057763
368
Appendix
Si37-701
2.3
Indoor Unit
3D039556A
Appendix
369
Si37-701
3D039557A
370
Appendix
Si37-701
3D039600A
Appendix
371
Si37-701
3D038359
372
Appendix
Si37-701
3D039564C
Appendix
373
Si37-701
3D045500C
374
Appendix
Si37-701
3D049604A
Appendix
375
HAP
M1F
R1T
R2T
R3T
T1R
X1M
X2M
X3M
X18A
Y1E
A1P
C1R
F1U
F2U
Std
GRN/YLW
K3R
6
K2R
6
X3M
1~
F1U
M1F
RED
7
6
C1R
(see table)
High
K1R
RED
OGR
C1R
12F
11F
20F
YLW
VOITEL
WTH
WTH
GYR
GYR
BNR
BNR
BLU
BLU
FU (3AG Type)
5A Slow Blow
6.3A Slow Blow
8A Slow Blow
OGR
376
OGR
MODEL
80
100 & 125
145
NOTES
1.
T1R
BLUE
X7A
M
t
X12A
R2T
R1T
X13A
Y1E
HAP
RYF1
RYF2
RYF3
X8A
FC
X4A
FH
FLL
FL
X30A
X11A X18A
R3T
BLK
PINK
PINK
WHITE
YELLOW
ORANGE
BLUE
BLACK
K1R
BRN
T2
T1
F2
F1
P2
P1
X2M
1
0
K2R
K2R
T1R
X1M
F1U
K1R
C1R
X3M
K3R
SWITCH BOX
X2M
A1P
K3R
3PDA0313
4. GROUNDTHESHIELD OFTHE
REMOTECONTROLLERCORDTO
THE INDOOR UNIT.
WIRED REMOTE
CONTROLLER
(OPTIONALACCESSORY)
1
See Note 4
R1T
P2
P1
INPUTFROM OUTSIDE
NOTE-3
TRANSMISSION WIRING CENTRAL
REMOTECONTROLLER
GRY
: TERMINAL
3. INCASE USINGCENTRAL REMOTE
2. SYMBOLSSHOW ASFOLLOWS
: CONNECTOR
CONTROLLER,CONNECT ITTOTHE
BLK : BLACK
BLU: BLUE
: FIELD WIRING
UNIT IN ACCORDANCEWITHTHE
ORG: ORANGE
RED: RED
: PLUG ANDSOCKET
ATTACHED INSTALLATIONMANUAL.
GRN: GREEN
WHT: WHITE
: JUMPERCONNECTOR
GRY: GREY
YLW: YELLOW
: WIRECLAMP
BRN: BROWM
X3A
L F2U
RED
L NE
POWER SUPPLY
220~240V 50Hz
X1M
Appendix
Si37-701
Appendix
377
Si37-701
3D039561B
378
Appendix
Si37-701
3D039620B
Appendix
379
Si37-701
3D039621B
FXMQ200MA / 250MAVE
380
Appendix
Si37-701
3D039801D
Appendix
381
Si37-701
3D034206D
382
Appendix
Si37-701
3D039826D
Appendix
383
BS Unit
3D055928C
2.4
Si37-701
384
Appendix
Si37-701
Outdoor Unit
3.1.1 REYQ8PY1~12PY1
Item
Name
Inverter
Compressor
STD 1
STD 2
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
Symbol
M1C
JT170G-KYE@T
Y1E
Y2E
EV
Temperature
protection
Others
Appendix
15.0A
M3C
M1F
Pressure
protection
3.0A
(for General
overseas : 1.14A)
Fully closed: 0pls Fully open: 1375pls
Fully closed: 0pls Fully open: 480pls
0~480pls
3.0A
+0
For M1C
S1PH
High pressure
For M2C
switch
S2PH
For M3C
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Inverter fin temperature
protection
(Radiator fin thermistor)
Fuse
REYQ12PY1
14.7A
M2C
OC protection
device
Fan motor
REYQ8PY1
Model
REYQ10PY1
JT1GCVDKYR@SA
+0
ON: 3.00.15MPa
ON: 3.00.15MPa
S3PH
SENPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
F1U
F2U
F1U
250V AC 5A Class B
385
Si37-701
3.1.2 REYQ14PY1~16PY1
Item
Name
Type
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC
protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Electronic expansion valve (Refrigerant charge)
Inverter
Pressure
protection
Temperature
protection
Others
386
Symbol
Model
REYQ14PY1
REYQ16PY1
JT1GCVDKYR@SA
M1C
14.7A
JT170G-KYE@T
M2C
15.0A
JT170G-KYE@T
M3C
15.0A
M1F, M2F
1.2A
Y1E
Y2E
EV
For M1C
S1PH
S2PH
For M3C
S3PH
+0
OFF: 4.0 0.12 MPa
SENPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
F1U
F2U
F1U
250V AC 5A Class B
Fuse
+0
ON: 3.00.15MPa
ON: 3.00.15MPa
ON: 3.00.15MPa
Appendix
Si37-701
3.1.3 REMQ8PY1
Item
Name
Type
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC
protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Refrigerant charge)
Electronic expansion valve (Subcool)
Inverter
Pressure
protection
Temperature
protection
Others
Appendix
Model
REMQ8PY1
JT1GCVDKYR@SA
Symbol
M1C
14.7A
M2C
M3C
M1F
3.0A
Y1E
Y2E
Y3E
For M1C
S1PH
S2PH
For M3C
S3PH
SENPL
OFF : 0.07MPa
R3T
OFF : 135C
R1T
OFF : 93C
For main PC
board
F1U
F2U
F1U
250V AC 5A Class B
Fuse
+0
ON : 3.00.15MPa
387
Si37-701
3.1.4 REMQ10PY1~12PY1
Item
Name
Type
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC
protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Refrigerant charge)
Electronic expansion valve (Subcool)
Inverter
Pressure
protection
Temperature
protection
Others
388
Symbol
Model
REMQ10PY1
REMQ12PY1
JT1GCVDKYR@SA
M1C
14.7A
JT170G-KYE@T
M2C
15.0A
M3C
M1F
3.0A
Y1E
Y2E
Y3E
For M1C
S1PH
S2PH
For M3C
S3PH
SENPL
OFF : 0.07MPa
R3T
OFF : 135C
R1T
OFF : 93C
For main PC
board
F1U
F2U
F1U
250V AC 5A Class B
Fuse
+0
ON : 3.00.15MPa
+0
ON : 3.00.15MPa
Appendix
Si37-701
3.1.5 REMQ14PY1~16PY1
Item
Name
Type
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC
protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Refrigerant charge)
Electronic expansion valve (Subcool)
Inverter
Pressure
protection
Temperature
protection
Others
Appendix
Symbol
Model
REMQ14PY1
REMQ16PY1
JT1GCVDKYR@SA
M1C
14.7A
JT170G-KYE@T
M2C
15.0A
JT170G-KYE@T
M3C
15.0A
M1F, M2F
1.2A
Y1E
Y2E
Y3E
For M1C
S1PH
S2PH
For M3C
S3PH
Fuse
+0
+0
+0
ON : 3.00.15MPa
ON : 3.00.15MPa
ON : 3.00.15MPa
SENPL
OFF : 0.07MPa
R3T
OFF : 135C
R1T
OFF : 93C
For main PC
board
F1U
F2U
F1U
250V AC 5A Class B
389
3.2
Si37-701
Indoor Side
Remote
Controller
Symbol
FXFQ25
MVE
FXFQ32
MVE
FXFQ40
MVE
FXFQ50
MVE
Wired Remote
Controller
FXFQ80
MVE
BRC1C62
Option
Wireless Remote
Controller
Fan Motor
FXFQ63
MVE
BRC7E61W
M1F
DC380V 30W 8P
DC 380V 120W 8P
Drain Pump
M1P
Swing Motor
M1S
MP35HCA[3P007482-1]
Stepping Motor DC16V
R1T
R3T
ST8605-5 8 L1000
20k (25C)
R2T
ST8602A-5 6 L1000
20k (25C)
Motors
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Thermal Fuse
TFu
Transformer
T1R
Model
Parts Name
Remote
Controller
Symbol
FXCQ
20MVE
FXCQ
25MVE
FXCQ
32MVE
FXCQ
40MVE
FXCQ
50MVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC7C62
FXCQ
63MVE
FXCQ
80MVE
FXCQ Remark
125MVE
Option
AC 220~240V 50Hz
Fan Motor
M1F
110W
115W
Thermal Fuse 152C
Motors
120W
130W
Drain Pump
M1P
Swing Motor
M1S
MT8-L[3PA07509-1]
AC200~240V
R1T
ST8601-6 4 L1250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-6 8 L1250
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-5 6 L1000
20k (25C)
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Others
390
150W
185W
87C : ON
Appendix
Si37-701
Model
Parts Name
Remote
Controller
Symbol
Wired Remote
Controller
FXZQ
20MVE
FXZQ
25MVE
FXZQ
32MVE
FXZQ
40MVE
FXZQ
50MVE
Remark
BRC1C61
Option
Wireless Remote
Controller
BRC7E530W
AC 220~240V 50Hz
Fan Motor
M1F
155W 4P
Thermal Fuse 135C
C1
4.0 F 400VAC
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
Swing Motor
M1S
MP35HCA [3P080801-1]
AC200~240V
R1T
ST8601A-1 4 L250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-3 8 L630
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-3 6 L630
20k (25C)
Float Switch
S1L
FS-0211
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Motors
Others
Appendix
391
Si37-701
Model
Parts Name
Remote
Controller
Symbol
FXKQ
25MAVE
FXKQ
32MAVE
FXKQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C61
Remark
FXKQ
63MAVE
Option
AC 220~240V 50Hz
Fan Motor
M1F
115W 4P
120W 4P
M1P
AC 220-240V (50Hz)
PLD-12200DM
Thermal Fuse 145C
Swing Motor
M1S
MP35HCA [3P080801-1]
AC200~240V
R1T
ST8601-13 4 L630
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-7 8 L1600
20k (25C)
R2T
ST8602A-7 6 L1600
20k (25C)
Thermistor (Heat
Exchanger)
Others
145W 4P
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
105C :
Model
Parts Name
Remote
Controller
Symbol
FXDQ
FXDQ
FXDQ
FXDQ
20N(A)VE(T), 25N(A)VE(T), 32N(A)VE(T),
40N(A)VE(T)
PVE(T)
PVE(T)
PVE(T)
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
FXDQ
50N(A)VE(T)
Remark
FXDQ
63N(A)VE(T)
Option
AC 220~240V 50Hz
Fan Motor
M1F
162W
1130W
Thermal protector
130C: OFF, 83C: ON
Motors
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
R1T
ST8601-1 4 L=250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-4 8 L=800
20k (25C)
R2T
ST8602A-4 6 L=800
20k (25C)
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211E
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
392
Appendix
Si37-701
Parts Name
Remote
Controller
Symbol
Model
Remark
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
20MVE 25MVE 32MVE 40MVE 50MVE 63MVE 80MVE 100MVE 125MVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
Option
AC 220~240V 50Hz
Fan Motor
M1F
Motors
150W
165W
185W
1125
W
Thermal protector
135C : OFF 87C : ON
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
R1T
ST8601-4 4 L800
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-7 8 L1600
20k (25C)
R2T
ST8602A-6 6 L1250
20k (25C)
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Parts Name
Remote
Controller
Symbol
1225W
Model
FXMQ
FXMQ
FXMQ
FXMQ
FXMQ
FXMQ
FXMQ
FXMQ Remark
40MAVE 50MAVE 63MAVE 80MAVE 100MAVE 125MAVE 200MAVE 250MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
Option
AC 220~240V 50Hz
Fan Motor
M1F
Motors
1100W
1160W
1270W
1430W
1380W2
87C : ON
10 F
400V
8 F
400V
10 F
400V
12 F
400V
C1R
R1T
ST8601A-5 4 L1000
20k (25C)
ST8601A-13
4 L630
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605A-4 8 L800
20k (25C)
ST8605A-5
8 L1000
R2T
ST8602A-4 6 L800
20k (25C)
ST8602A-6
6 L1250
Thermistor (Heat
Exchanger)
Others
Appendix
Float switch
S1L
Fuse
F1U
Transformer
T1R
5 F-400V
FS-0211
250V 5A 5.2
250V 10A
TR22H21R8
393
Si37-701
Model
Parts Name
Remote
Controller
Symbol
FXHQ
32MAVE
FXHQ
63MAVE
Wired Remote
Controller
FXHQ
100MAVE
BRC1C62
Wireless Controller
Remark
Option
BRC7E63W
AC 220~240V/220V 50Hz/60Hz
Fan Motor
M1F
163W
1130W
Motors
Capacitor for Fan Motor
C1R
80C : ON
3.0F-400V
9.0F-400V
Swing Motor
M1S
MT8-L[3P058751-1]
AC200~240V
R1T
ST8601A-1 4 L250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-6 8 L = 1250
20k (25C)
ST8605-6 8 L = 1250
20k (25C)
R2T
ST8602A-6 6 L = 1250
20k (25C)
ST8602A-6 6 L = 1250
20k (25C)
Thermistor (Heat
Exchanger)
Others
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Model
Parts Name
Remote
Controller
Symbol
FXAQ
20MAVE
FXAQ
25MAVE
FXAQ
32MAVE
FXAQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC7E618
FXAQ
50MAVE
FXAQ
63MAVE
Remark
Option
AC 220~240V 50Hz
Fan Motor
M1F
Motors
140W
143W
MSFBC20C21 [3SB40550-1]
AC200~240V
Swing Motor
M1S
R1T
ST8601-2 4 L400
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-2 8 L400
20k (25C)
R2T
ST8602-2 6 L400
20k (25C)
394
80C : ON
Float Switch
S1L
OPTION
Fuse
F1U
250V 5A 5.2
Appendix
Si37-701
Model
Parts Name
Remote
Controller
Symbol
FXLQ
20MAVE
FXLQ
25MAVE
FXLQ
32MAVE
FXLQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
FXLQ
50MAVE
FXLQ
63MAVE
Remark
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
115W
125W
Thermal protector 135C : OFF
C1R
1.0F-400V
0.5F-400V
1.0F-400V
R1T
ST8601-6 4 L1250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-9 8 L2500
20k (25C)
R2T
ST8602A-9 6 L2500
20k (25C)
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
Others
135W
120C : ON
1.5F-400V
2.0F-400V
FXNQ
50MAVE
FXNQ
63MAVE
Model
Parts Name
Remote
Controller
Symbol
FXNQ
20MAVE
FXNQ
25MAVE
FXNQ
32MAVE
FXNQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
Remark
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
115W
125W
Thermal protector 135C : OFF
C1R
1.0F-400V
0.5F-400V
1.0F-400V
R1T
ST8601-6 4 L1250
20k (25C)
(for Heat
Thermistors Thermistor
Exchanger High Temp.)
R3T
ST8605-9 8 L2500
20k (25C)
R2T
ST8602A-9 6 L2500
20k (25C)
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
Others
Appendix
135W
120C : ON
1.5F-400V
2.0F-400V
395
Option List
Si37-701
4. Option List
4.1
Type
Item
H/R
Wireless
FXCQ-M
FXFQ-M
BRC7C62
BRC7E61W
FXZQ-M8 FXKQ-MA
BRC7E530W7
BRC4C61
FXDQ-P
FXDQ-NA
BRC4C62
FXSQ-M
BRC4C62
BRC4C62
BRC7E63W
BRC7E618
BRC4C62
Remote controller
BRC2C51
BRC3A61
KRP1B61
KRP1B59
KRP1B57
KRP1B61
KRP1B56
KRP1B61
KRP1C3
KRP1B61
6-1
KRP2A61
KRP2A62
KRP2A62
KRP2A61
KRP2A53
KRP2A61
KRP2A62
KRP2A61
KRP2A61
6-2
KRP4A51
KRP4A53
KRP4A53
KRP4A51
KRP4A54
KRP4A51
KRP4A52
KRP4A51
KRP4A51
Remote sensor
KRCS01-1
KRCS01-1
BRC1C62
Wired
BRC1D61
Note 2,3
KRP1B96
Note 2,3
KRP1D98
DTA104A61
Note 4,6
KRP1B101
DTA104A62
BRC2C51
BRC3A61
KRCS01-1
DTA104A61
Note 4,6
KRP1B101
Note 5
KRP4A91
DTA104A53
DTA104A61
Note 3
KRP1C93
DTA104A62
Note 2,3
KRP4A93
DTA104A61 DTA104A61
Note:
1. Installation box is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
Various PC Boards
No.
Part name
Model No.
KRP1B56
KRP1B57
KRP1B59
KRP1B61
KRP1C3
DTA109A51
Function
PC board when equipped with auxiliary electric heater in the indoor unit.
Up to 1,024 units can be centrally controlled in 64 different groups.
Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of
branches: 16) apply to each adaptor.
System Configuration
No.
1
1-1
2
Part name
KJB311A
2-2
KJB212A
Schedule timer
DTA102A52
For UAT(Y)-K(A),FD-K
DTA107A55
7-1
Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
system.
Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
KEK26-1
DST301BA61
Function
DCS301BA61
2-1
DTA103A51
Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
(128 units). Can turn units ON/OFF twice per day.
Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
-NET
DTA109A51
Expander Adaptor
Mounting plate
KRP4A92
Note:
1. Installation box for
396
Model No.
DCS302CA61
Wiring restrictions (max. lengh : 1,000m, total wiring lengh : 2,000m, max. number of branches : 16)
apply to each adaptor.
Fixing plate for DTA109A51
Appendix
Si37-701
Option List
Part name
1-1
1-2
intelligent Touch
Controller
Model No.
Basic
Option
DCS601A52
Software
P. P. D.
DCS002C51
Web
DCS004A51
Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
1-3
1-4
KJB411A
128 units
Basic
Number of
Hardware units to be
connected
2-2
Function
DCS601C51
Software
2-3
DAM602B52
256 units
DAM602B51
512 units
DAM602B51x2
768 units
DAM602B51x3
1024 units
DAM602B51x4
P.P.D.
DAM002A51
Web
DAM004A51
Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
Eco
DAM003A51
DAM101A51
2-5
Di unit
DEC101A51
2-6
Dio unit
DEC102A51
DMS502B51
Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through BACnet communication.
DAM411B51
Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
independently.
Optional Di board
DAM412B51
Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
independently.
DMS504B51
Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through LONWORKS communication.
Parallel interface
Basic unit
DPF201A51
Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
4 units.
Temperature
measurement units
DPF201A52
Temperature
setting units
DPF201A53
DCS302A52
Interface between the central monitoring board and central control units.
3
3-1
3-2
4
Communication line
2-4
6
7
8
Contact/analog
signal
Notes:
1. BACnet is a registered trademark of American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE).
Appendix
397
Option List
4.2
Si37-701
REYQ8 ~ 16PY1(E)
Series
Models
REYQ10PY1
REYQ12PY1
REYQ14PY1
REYQ16PY1
REYQ8PY1E
Distributive
Piping
Optional accessories
REYQ10PY1E
REYQ12PY1E
REYQ14PY1E
REYQ16PY1E
Refnet header
Model
KHRP25M33H
(Max. 8 branch)
KHRP25M33H, KHRP25M72H
(Max. 8 branch) (Max. 8 branch)
Refnet joint
Model
KHRP25A22T, KHRP25A33T
KHRP25A22T, KHRP25A33T
(KHRP25A72T+KHRP25M72TP)
Model
KWC25C450
KWC25C450E
KWC25C450
KWC25C450E
Model
BHGP26A1
BHGP26A1E
BHGP26A1
BHGP26A1E
C : 3D057610A
REYQ18 ~ 32PY1(E)
Series
Models
REYQ20PY1
REYQ22PY1
REYQ24PY1
REYQ18PY1E
Distributive
Piping
Optional accessories
REYQ20PY1E
REYQ22PY1E
REYQ24PY1E
Refnet header
Model
KHRP25M33H, KHRP25M72H
(Max. 8 branch) (Max. 8 branch)
Refnet joint
Model
KHRP25A22T, KHRP25A33T
(KHRP25A72T+KHRP25M72TP)
Model
Model
KWC26C2802
KWC26C280E2
BHFP26P90
KWC26C2802
KWC26C280E2
Model
BHGP26A1
BHGP26A1E
BHGP26A1
BHGP26A1E
REYQ26PY1
REYQ28PY1
REYQ26PY1E
REYQ28PY1E
REYQ30PY1
REYQ32PY1
REYQ30PY1E
REYQ32PY1E
Series
Models
Distributive
Piping
Optional accessories
Refnet header
Model
Refnet joint
Model
Model
Model
Model
BHFP26P90
KWC26C280
KWC26C450
BHGP26A1
KWC26C280E
KWC26C450E
KWC26C4502
KWC26C450E2
BHGP26A1E
BHGP26A1
BHGP26A1E
C : 3D057611C
REYQ34 ~ 48PY1(E)
Series
Models
Distributive
Piping
Optional accessories
REYQ34PY1E
REYQ36PY1E
REYQ38PY1E
REYQ40PY1E
Refnet header
Model
Refnet joint
Model
Model
Model
Model
BHFP26P136
KWC26C2802
KWC26C450
BHGP26A1
KWC26C280E2
KWC26C450E
REYQ42PY1E
REYQ44PY1E
REYQ46PY1
REYQ48PY1
BHGP26A1E
Series
KWC26C280
KWC26C4502
BHGP26A1
Models
Optional accessories
Distributive
Piping
REYQ42PY1
REYQ44PY1
Refnet header
Model
Refnet joint
Model
REYQ46PY1E
REYQ48PY1E
Model
Model
KWC26C280E
KWC26C450E2
KWC26C4503
BHFP26P136
KWC26C4503
Model
BHGP26A1E
BHGP26A1
BHGP26A1E
C : 3D057612C
Appendix
Si37-701
5m or less
than 5m
Maximum length from a connection
kit. 10m or less from first branch.
(Equivalent Piping Length 13m)
Connection
Kit B
Connection
Kit A
Since there is a possibility that oil may be collected on a stop machine side, install piping
between outdoor units to go to level or go up to an outdoor unit, and to make a slope.
(V3036)
Less than 2m
(V3037)
Vertical
Projection
200mm or
more
Less than 2m
2m or more
Vertical
Projection
Less than 2m
Appendix
Vertical
Projection
Less than 2m
(V3038)
399
5.2
Si37-701
Wrong
Good
Good
Vertical
Projection
(V3040)
Outdoor Unit - Multi Connection Piping Kit Actual piping length 10m or less, equivalent length 13m or less
piping length 165m or less, equivalent length 190m or
Max.allowable Multi Connection Piping Kit - Indoor Unit Actual
less, the total extension 1000m or less
Piping Length
Actual piping length 40m or less
REFNET Joint - Indoor Unit
(Refer to Page 403 Note 2 in case of up to 90m)
Outdoor Unit - Outdoor Unit
5m or less
Allowable
Outdoor Unit is above
50m or less 90m or less
Level
Outdoor Unit - Indoor Unit
Outdoor Unit is below
90m
Difference
Indoor Unit - Indoor Unit
15m or less
400
Appendix
Si37-701
Example of connection
(Connection of 8 indoor units)
Outdoor unit
REFNET joint (A~G)
REFNET header
f
i
B1
F
g
j
2
n
p
B3 B4
B2
m
o
4
c
r
s
d
B3
h
f
1
p
B
o
k
5
d
f
b
B1 B2 B3
e
c
g
8
7
B1 ~ B4 : BS Unit
1~6
: Indoor unit (Cool/Heat selection possible)
7, 8
: Indoor unit (Cooling only)
B1 ~ B5
: BS Unit
1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible)
5, 6
: Indoor unit (Cooling only)
Outdoor unit
H3
h
B4
j
B5
k
B6
m
6
7
8
B1 ~ B4 : BS Unit
1~6
: Indoor unit (Cool/Heat selection possible)
7, 8
: Indoor unit (Cooling only)
Outdoor unit
REFNET joint (A~G)
(*1) "
r
u
t
REFNET joint (A~G)
c
f
i
m
2
o
4
q
5
b
c
B1
B1 ~ B4 : BS Unit
1~6
: Indoor unit (Cool/Heat selection possible)
7, 8
: Indoor unit (Cooling only)
B3
h
f
1
B2
2
B5 n
B4
j
4
k
5
t
REFNET header
p
B
o
d
6
H2
F
g
r
u
REFNET header
d
f
b
B1 B2 B3
e
c
g
8
7
h
B4
j
B5
k
i
4
B6
m
6
7
H2
Multi
outdoor
system
REYQ
18~48
H1
H1
H1
B2
B5 n
i
B4
j
4
e
B1
q
5
H1
H2
H3
H2
Liquid pipe
Single
outdoor
system
REYQ
8~16
H2
BS
Unit
REFNET header
a
H1
Gas pipe
H3
Liquid pipe
Outdoor unit
H2
Outdoor unit
Indoor unit
side
(2 pipes)
H1
Outdoor unit
side
(3 pipes)
B1 ~ B5
: BS Unit
1 ~ 4 , 7 , 8 : Indoor unit (Cool/Heat selection possible)
5, 6
: Indoor unit (Cooling only)
B1 ~ B4 : BS Unit
1~6
: Indoor unit (Cool/Heat selection possible)
7, 8
: Indoor unit (Cooling only)
Actual pipe
length
Between outdoor unit (*2)
Equivalent
Maximum and indoor unit
length
allowable
Total extention length
length
Between first outdoor unit multi
Actual and
connection piping kit and outdoor unit Equivalent
(in case of multi system)
pipe length
Pipe length between outdoor unit (*2) and indoor unit 165m
Example 6 : a + b + 165m, 8 : a + m + n + p 165m Example 8 : a + o 165m
Example 8 : a + b + c + d + e + s 165m
Equvalent pipe length between outdoor unit (*2) and indoor unit 190m (Note 1)
(Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100, 160 to be 4m, that of BSVQ250 to be 6m for calculation purposes)
Total piping length from outdoor unit (*2) to all indoor unit 1000m
Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit 10m
Outdoor unit
r 10m
Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit 13m
Difference in height between outdoor unit and indoor unit (H1) 50m (Max 40m if the outdoor unit is below)
s
r
Difference in height between adjacent indoor units (H2) 15m
u
Difference in height between adjacent outdoor units (H3) 5m
Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit 40m (Note 2)
Example 8 : b + c + d + e + s 40m
Example 6 : b + 40m, 8: m + n + p 40m
Example 8 : o 40m
Appendix
Difference in height
Difference in height
Difference in height
Actual pipe
length
401
Si37-701
Equalizer pipe
(part D)
Piping between outdoor unit
multi connection piping kit
and outdoor unit (part C)
Piping between outdoor unit multi
connection piping kits (part B)
Piping between outdoor unit and
refrigerant branch kit (part A)
x
<
640
15.9
34.9
38~48HP type
640 x < 920
34.9
28.6
19.1
920 x
41.3
Piping between outdoor unit multi connection piping kit and outdoor unit (part C)
Choose from the following table in accordance with the capacity type of
Piping between refrigerant branch kit, BS unit and indoor unit
the outdoor unit connected.
(unit : mm)
(unit : mm)
Match to the size of the connection piping on the indoor unit.
Piping size (O. D.)
Outdoor unit
Piping
size
(O.
D.)
HP/LP gas pipe
Liquid pipe
capacity type Suction gas pipe
Indoor unit capacity type
gas pipe
Liquid pipe
22.2
9.5 0.8
8,10HP type
19.1
12.7
6.4
20
25
32
40
50
type
12HP type
12.7
28.6
15.9
63
80
100
125
type
22.2
14,16HP type
19.1
9.5
200 type
250 type
22.2
Equalizer pipe (part D) (outdoor multi system only)
Piping size (O. D.)
Temper grade and wall thickness for pipes
(Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)
Copper tube O. D.
Temper grade
Wall thickness
(Min. requirement)
402
6.4
9.5 12.7 15.9 19.1 22.2 25.4 28.6 31.8 34.9 38.1 41.3
O type
1/2H type
0.80
0.80
0.80
0.99
0.80
0.80
0.88
0.99
1.10
1.21
1.32
(unit : mm)
19.1
1.43
Appendix
Si37-701
R=
Total length(m)
of liquid piping
size at 22.2
Additional refrigerant to
be charged : R(kg)
R should be rounded
off in units of 0.1 kg.
Total length(m)
of liquid piping
size at 19.1)
0.37
Total length(m)
of liquid piping
size at 15.9)
Total length(m)
of liquid piping
size at 9.5
0.18
Total length(m)
of liquid piping
size at 12.7
0.059
Total length(m)
of liquid piping
size at 6.4
0.26
1.02
0.12
0.022
REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT
MODEL NAME
INDOOR
REYQ18
REYQ34
CONNECTION
~
~
CAPACITY
32PY1 48PY1
0.5kg
0.5kg
1.0kg
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : REYQ34PY1
Total capacity of indoor unit : 116%
a : 19.1 30m
b : 19.1 20m
c : 9.5 10m
d : 9.5 10m
e : 9.5 10m
f : 9.5 10m
g : 9.5 10m
h : 9.5 10m
i : 9.5 10m
j : 9.5 10m
k : 9.5 20m
l : 9.5 20m
m : 9.5 20m
n : 9.5 10m
o : 6.4 10m
p : 6.4 10m
r : 12.7 3m
s : 9.5 3m
t : 9.5 3m
u : 15.9 1m
a, b
= 27.148
u
27.1kg
c~n, s, t
o, p
REYQ34PY1 116%
System
REYQ8 ~ 10PY1
REYQ12 ~ 16PY1
REYQ18 ~ 24PY1
REYQ26 ~ 48PY1
Liquid pipe
9.5 12.7
12.7 15.9
15.9 19.1
19.1 22.2
It is necessary to increase the main pipes of outdoor unit and first refrigerant branch kit
(liquid side) by one size, if the difference in height between outdoor unit and indoor unit is
over than 50m.
1.Outdoor unit
2.Main pipes
3.Increase only liquid pipe size
4.First refrigerant branch kit
5.BS unit
6.Indoor unit
3
Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied. (In case of "Branch with REFNET joint")
Required Conditions
Example Drawings
8 b + c + d + e + f + g + p 90 m
increase the pipe size of b, c, d, e, f, g
a+b2+c2+d2+e2+f2+g2
+ h + i + j + k + l + m + n + p 1000 m
h, i, j....... p 40 m
15.9 19.1
19.1 22.2
22.2 25.4*
28.6 31.8*
Outdoor unit
a
b
A
h
1
j
2
e
D
l
4
m
5
H1
f
E
k
3
34.9 38.1*
n
6
Indoor units ( 1 - 8 )
7
8
*If available on the site, use this size. Otherwise it can not be increased.
Appendix
403
Si37-701
404
Appendix
Si37-701
TC
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
Appendix
0.0
88.0
79.1
71.1
64.1
57.8
52.3
47.3
42.9
38.9
35.3
32.1
29.2
26.6
24.3
22.2
20.3
18.5
17.0
15.6
14.2
13.1
12.0
11.1
10.3
9.5
8.8
8.2
7.6
7.0
6.7
6.0
5.5
5.2
4.79
4.46
4.15
3.87
3.61
3.37
3.15
2.94
2.75
2.51
2.41
2.26
2.12
1.99
1.87
1.76
1.65
1.55
1.46
1.38
R1T
R2T
R3T
R1T
R2T
R4T
R5T
R6T
TC
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
0.0
197.81
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
111.99
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
65.84
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
39.96
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
25.01
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
16.10
0.5
192.08
181.16
170.94
161.36
152.38
143.96
136.05
128.63
121.66
115.12
108.96
103.18
97.73
92.61
87.79
83.25
78.97
74.94
71.14
67.56
64.17
60.96
57.94
55.08
52.38
49.83
47.42
45.14
42.98
40.94
39.01
37.18
35.45
33.81
32.25
30.77
29.37
28.05
26.78
25.59
24.45
23.37
22.35
21.37
20.45
19.56
18.73
17.93
17.17
16.45
15.76
TC
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
0.0
16.10
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
10.63
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
7.18
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
4.96
4.79
4.62
4.46
4.30
4.16
4.01
3.88
3.75
3.62
3.50
3.38
3.27
3.16
3.06
2.96
2.86
2.77
2.68
2.60
2.51
(k)
0.5
15.76
15.10
14.48
13.88
13.31
12.77
12.25
11.76
11.29
10.84
10.41
10.00
9.61
9.24
8.88
8.54
8.21
7.90
7.60
7.31
7.04
6.78
6.53
6.53
6.53
6.53
6.06
5.84
5.43
5.05
4.87
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
3.44
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
2.47
405
Si37-701
Outdoor Unit
Thermistors for
Discharge Pipe
(R3T, R3133T)
TC
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
406
0.0
640.44
609.31
579.96
552.00
525.63
500.66
477.01
454.60
433.37
413.24
394.16
376.05
358.88
342.58
327.10
312.41
298.45
285.18
272.58
260.60
249.00
238.36
228.05
218.24
208.90
200.00
191.53
183.46
175.77
168.44
161.45
154.79
148.43
142.37
136.59
131.06
125.79
120.76
115.95
111.35
106.96
102.76
98.75
94.92
91.25
87.74
84.38
81.16
78.09
75.14
72.32
0.5
624.65
594.43
565.78
538.63
512.97
488.67
465.65
443.84
423.17
403.57
384.98
367.35
350.62
334.74
319.66
305.33
291.73
278.80
266.51
254.72
243.61
233.14
223.08
213.51
204.39
195.71
187.44
179.57
172.06
164.90
158.08
151.57
145.37
139.44
133.79
128.39
123.24
118.32
113.62
109.13
104.84
100.73
96.81
93.06
89.47
86.04
82.75
79.61
76.60
73.71
70.96
TC
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
0.0
72.32
69.64
67.06
64.60
62.24
59.97
57.80
55.72
53.72
51.98
49.96
48.19
46.49
44.86
43.30
41.79
40.35
38.96
37.63
36.34
35.11
33.92
32.78
31.69
30.63
29.61
28.64
27.69
26.79
25.91
25.07
24.26
23.48
22.73
22.01
21.31
20.63
19.98
19.36
18.75
18.17
17.61
17.07
16.54
16.04
15.55
15.08
14.62
14.18
13.76
13.35
0.5
70.96
68.34
65.82
63.41
61.09
58.87
56.75
54.70
52.84
50.96
49.06
47.33
45.67
44.07
42.54
41.06
39.65
38.29
36.98
35.72
34.51
33.35
32.23
31.15
30.12
29.12
28.16
27.24
26.35
25.49
24.66
23.87
23.10
22.36
21.65
20.97
20.31
19.67
19.05
18.46
17.89
17.34
16.80
16.29
15.79
15.31
14.85
14.40
13.97
13.55
13.15
TC
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
0.0
13.35
12.95
12.57
12.20
11.84
11.49
11.15
10.83
10.52
10.21
9.92
9.64
9.36
9.10
8.84
8.59
8.35
8.12
7.89
7.68
7.47
7.26
7.06
6.87
6.69
6.51
6.33
6.16
6.00
5.84
5.69
5.54
5.39
5.25
5.12
4.98
4.86
4.73
4.61
4.49
4.38
4.27
4.16
4.06
3.96
3.86
3.76
3.67
3.58
3.49
3.41
(k))
0.5
13.15
12.76
12.38
12.01
11.66
11.32
10.99
10.67
10.36
10.06
9.78
9.50
9.23
8.97
8.71
8.47
8.23
8.01
7.78
7.57
7.36
7.16
6.97
6.78
6.59
6.42
6.25
6.08
5.92
5.76
5.61
5.46
5.32
5.18
5.05
4.92
4.79
4.67
4.55
4.44
4.32
4.22
4.11
4.01
3.91
3.81
3.72
3.62
3.54
3.45
3.37
Appendix
Si37-701
Pressure Sensor
8. Pressure Sensor
Detected Pressure
PH = 1.38V-0.69
PL = 0.57V-0.28
PH : High pressure (MPa)
PL : Low pressure (MPa)
V : Voltage (V)
Appendix
407
Si37-701
J1
J2
J3
P1
P3
N3 U
Electronic circuit
DM
P1
P2 P3
IGBT
X10A K2
J1
L1
J2
L2
L3
J3
N3
W
X11A
(V2895)
According to the checking aforementioned, it is probed that the malfunction results from the
faulty inverter.The following section describes supposed causes of the faulty inverter.
1 Faulty compressor (ground leakage)
1 Faulty fan motor (ground leakage)
1 Entry of conductive foreign particles
1 Abnormal voltage (e.g. overvoltage, surge (thunder), or unbalanced voltage)
In order to replace the faulty inverter, be sure to check for the points aforementioned.
408
Appendix
Si37-701
Measuring
point
+
P3
U
2
3
4
5
6
7
8
9
10
11
12
P3
P3
U
V
W
N3
N3
N3
U
V
W
No.
V
W
P3
P3
P3
U
V
W
N3
N3
N3
Criterion
Remark
2 to 15k
Not less
than
15k
(including)
It may take
time to
determine the
resistance due
to capacitor
charge or else.
2 to 15k
Measuring
point
+
P1
J1
2
3
4
5
6
7
8
9
10
11
12
P1
P1
J1
J2
J3
N3
N3
N3
J1
J2
J3
No.
Appendix
J2
J3
P1
P1
P1
J1
J2
J3
N3
N3
N3
Criterion
Remark
2 to 15k
Not less
than
15k
(including)
2 to 15k
It may take
time to
determine the
resistance due
to capacitor
charge or else.
Measuring
point
+
-
1
2
3
4
P3
P3
P3
U
U
V
W
P3
5
6
7
8
9
10
11
12
V
W
N3
N3
N3
U
V
W
P3
P3
U
V
W
N3
N3
N3
Criterion
Remark
Not less
than
1.2V
(including)
0.3 to 0.7V
Not less
than
1.2V
(including)
Measuring
point
+
-
1
2
3
4
P1
P1
P1
J1
J1
J2
J3
P1
5
6
7
8
9
10
11
12
J2
J3
N3
N3
N3
J1
J2
J3
P1
P1
J1
J2
J3
N3
N3
N3
Criterion
Remark
Not less
than
1.2V
(including)
0.3 to 0.7V
Not less
than
1.2V
(including)
409
Si37-701
410
Appendix
Si37-701
Part 8
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................412
1.1 Outline ..................................................................................................412
1.2 Refrigerant Cylinders............................................................................414
1.3 Service Tools........................................................................................415
411
Si37-701
Outline
Refrigerant name
Composing
substances
Design pressure
Refrigerant oil
Ozone destruction
factor (ODP)
Combustibility
Toxicity
HCFC units
R-22
Single-component
refrigerant
2.75MPa (gauge pressure)
= 28.0 kgf/cm2
0.05
None
None
None
None
None
None
boiling points.
2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar
boiling points.
3. The design pressure is different at each product. Please refer to the installation manual for
each product.
(Reference) 1 MPa
412
Si37-701
Steam pressure
(kPa)
Liquid
Vapor
Density
(kg/m3 )
Liquid
Vapor
Specific enthalpy
(kJ/kg)
Liquid
Vapor
Specific entropy
(kJ/KgK)
Liquid
Vapor
413
1.2
Si37-701
Refrigerant Cylinders
Cylinder specifications
Siphon tube
Cylinder
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
414
Si37-701
1.3
Service Tools
R-410A is used under higher working pressure, compared to previous refrigerants
(R-22,R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to
Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other
problems. Therefore, gauge manifolds and charge hoses that are used with a previous
refrigerant (R-22,R-407C) can not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
Tool compatibility
Tool
Compatibility
HFC
HCFC
R-410A
R-407C
R-22
Gauge manifold
Charge hose
Charging cylinder
Gas detector
Vacuum pump
(pump with reverse flow
preventive function)
Weighting instrument
Charge mouthpiece
{
{
{
Pipe expander
Pipe bender
Refrigerant recovery
device
Refrigerant piping
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
Copper tube material and thickness
Pipe size
6.4
9.5
12.7
15.9
19.1
22.2
25.4
28.6
31.8
38.1
44.5
Material
O
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-up
R-407C
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.2
1.4
1.6
Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-up11
R-410A
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.1
1.4
1.6
* O: Soft (Annealed)
H: Hard (Drawn)
415
Si37-701
1. Flaring tool
Flare gauge
Specifications
2 Dimension A
Unit:mm
Nominal size
A +00.4
Tube O.D.
Do
Class-2 (R-410A)
Class-1 (Conventional)
1/4
6.35
9.1
9.0
3/8
9.52
13.2
13.0
1/2
12.70
16.6
16.2
5/8
15.88
19.7
19.4
3/4
19.05
24.0
23.3
Differences
2 Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
416
Si37-701
2. Torque wrench
Specifications
2 Dimension B
Nominal size
1/2
5/8
Unit:mm
Class-1
24
27
Class-2
26
29
Previous
24
27
Dimension B
Specifications
2 Discharge speed
50 l/min (50Hz)
60 l/min (60Hz)
2 Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adapter
Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
417
Si37-701
4. Leak tester
Specifications
2 Hydrogen detecting type, etc.
2 Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2 Offers high rust resistance and stability over long period of time.
Differences
2 Can be used for R-410A and R-22 units.
Specifications
2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
2 1/4" 5/16" (2min 2.5min)
2 No oil is used in pressure test of gauges.
For prevention of contamination
418
Si37-701
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2 Change in pressure
2 Change in service port diameter
Specifications
2 Working pressure 5.08 MPa (51.8 kg/cm2)
2 Rupture pressure 25.4 MPa (259 kg/cm2)
2 Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
2 Pressure proof hose
2 Change in service port diameter
2 Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
419
Si37-701
Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = 2g
TA101B (for 20-kg cylinder) = 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
10.Charge mouthpiece
Specifications
2 For R-410A, 1/4" 5/16" (2min 2.5min)
2 Material is changed from CR to H-NBR.
Differences
2 Change of thread specification on hose connection side (For the R-410A use)
2 Change of sealer material for the HFCs use.
420
Si37-701
Index
A
A0 .........................................................................230
A1 .........................................................................231
A3 .........................................................................232
A6 .........................................................................234
A7 .........................................................................235
A9 .................................................................237, 239
Abnormal Discharge Pipe Temperature ...............260
Abnormal Outdoor Fan Motor Signal ...................265
About Refrigerant R-410A ....................................412
Actuation of High Pressure Switch .......................248
Actuation of Low Pressure Sensor .......................250
Address Duplication of Centralized Controller .....319
Address Duplication, Improper Setting .................330
AF .........................................................................241
AJ .........................................................................242
Applicable range of Field setting ..........................174
Auto Restart after Power Failure Reset ...............176
B
Backup Operation ................................................132
Basic Control ..........................................................99
C
C4 .........................................................................243
C5 .........................................................................244
C9 .........................................................................245
Centralized Control Group No. Setting .................180
Check Operation not Executed ............................303
CJ .........................................................................246
Compressor PI Control .........................................100
Contents of Control Modes ..................................181
Current Sensor Malfunction .................................268
D
Defective Inverter PC Board ................................280
Defrost Operation .................................................118
Demand Operation ...............................................132
Detailed Explanation of Setting Modes ................175
Discharge Pipe Protection Control .......................128
Display Under Centralized Control Blinks
(Repeats Double Blink) .................................336
Display Under Centralized Control Blinks
(Repeats Single Blink) ..................................333
Drain Level above Limit ........................................241
Drain Pump Control ..............................................138
E
E1
E3
E4
E5
E6
E7
E9
.........................................................................247
.........................................................................248
.........................................................................250
.........................................................................252
.........................................................................254
.........................................................................255
.........................................................................258
Index
F
F3 ........................................................................ 260
F6 ........................................................................ 262
Fan Motor (M1F) Lock, Overload ........................ 234
Faulty Field Setting after Replacing Main PC Board
or Faulty Combination of PC Board ............. 296
Field Setting ........................................................ 170
Field Setting from Outdoor Unit ........................... 183
List of Field Setting Items ............................. 183
Setting by push button switches ................... 189
Field Setting from Remote Controller .................. 170
Filter Sign Setting ................................................ 175
Freeze Prevention ............................................... 140
Functional Parts Layout ........................................ 62
REMQ10P, 12P .............................................. 65
REMQ14P, 16P .............................................. 66
REYQ14P, 16P ............................................... 63
REYQ8P, 10P, 12P ........................................ 62
G
Gas Shortage Alert .............................................. 297
H
H7 ........................................................................ 265
H9 ........................................................................ 267
Heating Operation Prohibition ............................. 132
High Pressure Protection Control ........................ 124
I
Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller ............. 316
Improper Combination of Optional Controllers for
Centralized Control ...................................... 328
Inverter Compressor Motor Lock ......................... 252
Inverter Compressor Starting Failure .................. 287
Inverter Over-Ripple Protection ........................... 293
Inverter Protection Control .................................. 129
J
J2
J3
J4
J5
J6
J7
J9
JA
JC
........................................................................ 268
........................................................................ 269
........................................................................ 270
........................................................................ 271
........................................................................ 272
........................................................................ 273
........................................................................ 275
........................................................................ 276
........................................................................ 278
Si37-701
L
L1 .........................................................................280
L4 .........................................................................281
L5 .........................................................................283
L8 .........................................................................285
L9 .........................................................................287
LC .........................................................................290
List of Electrical and Functional Parts ..................385
Indoor Unit .....................................................390
Outdoor Unit ..................................................385
Louver Control for Preventing Ceiling Dirt ............145
Low Pressure Protection Control .........................126
M
M1 ........................................................................326
M8 ........................................................................327
MA ........................................................................328
Malfunction code indication by outdoor unit
PC board .......................................................226
Malfunction of Capacity Determination
Device ...........................................................242
Malfunction of Discharge Pipe Thermistor
(R31, 32T, 33T) .............................................269
Malfunction of Drain Level Control System
(S1L) .............................................................232
Malfunction of Electronic Expansion
Valve Coil ......................................................239
Malfunction of High Pressure Sensor ...................276
Malfunction of Inverter Radiating Fin Temperature
Rise ...............................................................281
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor ..................................................294
Malfunction of Liquid Pipe Thermistor 1
(R6T) (R9T) or (R14T) ..................................273
Malfunction of Liquid Pipe Thermistor 2
(R7T or R15T) ...............................................274
Malfunction of Low Pressure Sensor ...................278
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E~Y5E) ..........................................258
Malfunction of Outdoor Unit Fan Motor ................255
Malfunction of Subcooling Heat Exchanger Gas Pipe
Thermistor (R5T or R13T) .............................275
Malfunction of Swing Flap Motor (M1S) ...............235
Malfunction of System, Refrigerant System Address
Undefined ......................................................324
Malfunction of Temperature Sensor for Heat
Exchanger Gas (R2T or R11T) .....................270
Malfunction of Thermistor (R1T) for Suction Air ...245
Malfunction of Thermistor (R2T) for
Heat Exchanger ............................................243
Malfunction of Thermistor (R3T) for
Gas Pipes .....................................................244
Malfunction of Thermistor (R4T or R12T) for Outdoor
Unit Heat Exchanger .....................................272
Malfunction of Thermistor (R8T or R10T) for
Suction Pipe ..................................................271
Malfunction of Thermostat Sensor in Remote
Controller ......................................................246
Malfunction of Transmission between Centralized
Controller and Indoor Unit .............................320
ii
O
Oil Return Operation ........................................... 114
Operation Lamp Blinks ........................................ 331
Operation Mode .................................................... 98
Operation When Power is Turned On ................. 168
Option List ........................................................... 396
Other Control ....................................................... 132
Outdoor Unit Fan Control in Cooling Operation .. 109
Outdoor Unit PC Board Layout ........................... 169
Outdoor Unit Thermistors for Discharge Pipe ..... 406
P
P1 ........................................................................ 293
P4 ........................................................................ 294
PC Board Defect ................................. 231, 247, 326
Piping Installation Point ....................................... 399
The Example of a Wrong Pattern ................. 400
PJ ........................................................................ 296
Power Supply Insufficient or
Instantaneous Failure ................................... 300
Precautions for New Refrigerant (R-410A) .......... 412
Pressure Sensor ................................................. 407
Procedure and Outline ........................................ 149
Protection Control ............................................... 124
Pump-down Residual Operation ......................... 120
R
Refrigerant Circuit ................................................. 50
REYQ14P, 16P ............................................... 52
REYQ8P, 10P, 12P ........................................ 50
Refrigerant Cylinders .......................................... 414
Refrigerant Flow for Each Operation Mode ........... 67
REYQ14P, 16P ............................................... 75
REYQ8P, 10P, 12P ........................................ 67
Refrigerant Overcharged ..................................... 262
Restart Standby .................................................. 122
Reverse Phase, Open Phase .............................. 299
S
Service Tools ...................................................... 415
Setting by pushbutton switches ........................... 189
Setting Contents and Code No. .......................... 173
Index
Si37-701
T
Test Operation .....................................................148
Procedure and Outline ...................................149
The Example of a Wrong Pattern .........................400
Thermistor Resistance /
Temperature Characteristics .........................405
Thermostat Sensor in Remote Controller .............135
Transmission Failure (Across Outdoor Units) ......308
Troubleshooting
(OP: Central Remote Controller) ...................326
Troubleshooting
(OP: Unified ON/OFF Controller) ..................331
U
U0 .........................................................................297
U1 .........................................................................299
U2 .........................................................................300
U3 .........................................................................303
U4 .........................................................................304
U5 .........................................................................307
U7 .........................................................................308
U8 .........................................................................314
U9 .........................................................................315
UA ........................................................................316
UC ........................................................................319
UE ........................................................................320
UF ........................................................................323
UH ........................................................................324
Index
iii
Si37-701
iv
Index
Si37-701
C
Centralized Control Group No. Setting .................180
BRC1C Type .................................................180
BRC4C Type .................................................180
BRC7C Type .................................................180
BRC7E Type ..................................................180
Group No. Setting Example ...........................181
Check 2 ................................................................337
Check Operation not Executed ............................303
Contents of Control Modes ..................................181
How to Select Operation Mode ......................182
Current Sensor Malfunction .................................268
D
Defective Inverter PC Board ................................280
Display Under Centralized Control Blinks
(Repeats Double Blink) .................................336
Display Under Centralized Control Blinks
(Repeats Single Blink) ..................................333
Display of sensor and address data .....................222
Drain Level above Limit .......................................241
Drain Pump Control .............................................138
When the Float Switch is Tripped and AF is
Displayed on the Remote
Controller ..........................................139
When the Float Switch is Tripped During Heating
Operation ..........................................139
When the Float Switch is Tripped while the
Cooling Thermostat is OFF ...............138
When the Float Switch is Tripped While the
Cooling Thermostat is ON ................138
E
Electronic Expansion Valve Malfunction / Dust
Clogging ........................................................237
Error of External Protection Device ......................230
Example of Connection (R-410A Type) ...............401
F
Fan Motor (M1F) Lock, Overload .........................234
Faulty Field Setting after Replacing Main PC Board or
Faulty Combination of PC Board ..................296
Field Setting from Outdoor Unit ...........................183
Mode changing procedure .................... 189, 190
Setting by dip switches ..................................185
Freeze Prevention ................................................140
Functional Parts Layout .........................................62
Drawings & Flow Charts
I
Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller ............ 316
Improper Combination of Optional Controllers for
Centralized Control ...................................... 328
Inspection Mode .................................................. 220
Inverter Compressor Motor Lock ......................... 252
Inverter Compressor Starting Failure .................. 287
Inverter Over-Ripple Protection ........................... 293
L
Louver Control for Preventing Ceiling Dirt ........... 145
M
Malfunction of Capacity Determination Device ... 242
Malfunction of Discharge Pipe Thermistor
(R31, 32T, 33T) ............................................ 269
Malfunction of Drain Level Control System
(S1L) ............................................................ 232
Malfunction of Electronic Expansion
Valve Coil ..................................................... 239
Malfunction of High Pressure Sensor .................. 276
Malfunction of Inverter Radiating Fin Temperature
Rise .............................................................. 281
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor ................................................. 294
Malfunction of Liquid Pipe Thermistor 1
(R6T) (R9T) or (R14T) ................................. 273
Malfunction of Liquid Pipe Thermistor 2
(R7T or R15T) .............................................. 274
Malfunction of Low Pressure Sensor .................. 278
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E~ Y5E) ........................................ 258
Malfunction of Outdoor Unit Fan Motor ............... 255
Malfunction of Subcooling Heat Exchanger Gas Pipe
Thermistor (R5T or R13T) ............................ 275
Malfunction of Swing Flap Motor (M1S) .............. 235
Malfunction of System, Refrigerant System Address
Undefined ..................................................... 324
Malfunction of Temperature Sensor for Heat
Exchanger Gas (R2T or R11T) .................... 270
Malfunction of Thermistor (R1T) for
Outdoor Air ................................................... 267
Malfunction of Thermistor (R1T) for
Suction Air .................................................... 245
Malfunction of Thermistor (R2T) for
Heat Exchanger ........................................... 243
Malfunction of Thermistor (R3T) for Gas Pipes ... 244
Malfunction of Thermistor (R4T or R12T) for
Outdoor Unit Heat Exchanger ...................... 272
Malfunction of Thermistor (R8T or R10T) for
Suction Pipe ................................................. 271
v
Si37-701
O
Operation Lamp Blinks .........................................331
Outdoor Unit PC Board Layout ............................169
T
Test Operation .................................................... 148
Thermostat Sensor in Remote Controller ............ 135
Cooling .......................................................... 135
Heating ......................................................... 136
Torque wrench .................................................... 417
Transmission Failure (Across Outdoor Units) ..... 308
Troubleshooting
(OP: Central Remote Controller) .................. 326
Troubleshooting
(OP: Unified ON/OFF Controller) ................. 331
Troubleshooting by Remote Controller ............... 215
W
Weigher for refrigerant charge ............................ 420
Wired Remote Controller ..................................... 170
Wireless Remote Controller - Indoor Unit ........... 171
BRC4C type .................................................. 171
BRC7C type .................................................. 171
BRC7E type .................................................. 171
Wiring Diagrams for Reference ........................... 361
Field Wiring ................................................... 366
Indoor Unit .................................................... 369
Outdoor Unit ................................................. 361
P
PC Board Defect ................................. 231, 247, 326
Piping Diagrams ...................................................352
Indoor Unit .....................................................357
Outdoor Unit ..................................................352
Piping Installation Point ........................................399
The Example of A Wrong Pattern ..................400
Power Supply Insufficient or
Instantaneous Failure ...................................300
Pressure Sensor ..................................................407
R
Refrigerant Flow for Each Operation Mode ............67
Refrigerant Overcharged .....................................262
Remote Controller Self-Diagnosis Function .........223
Remote Controller Service Mode .........................221
REMQ10P, 12P .....................................................65
REMQ14P, 16P .....................................................66
Reverse Phase, Open Phase ..............................299
REYQ14P, 16P ......................................................63
REYQ8P, 10P, 12P ................................................62
S
Self-diagnosis by Wired Remote Controller .........216
Self-diagnosis by Wireless Remote Controller .....217
Setting of Low Noise Operation and Demand
Operation ......................................................199
Image of operation in the case of A ...... 200, 202
Image of operation in the case of
A and B .................................... 200, 202
Image of operation in the case of B ...... 200, 202
Simplified Remote Controller ...............................172
BRC2A51, BRC2C51 ....................................172
STD Compressor Motor Overcurrent/Lock ...........254
System is not Set yet ...........................................323