RIBRAFT
JAN 2012
TECHNICAL MANUAL
Section 1 contains information principally useful for the specifier or building designer. Section 2
is primarily aimed at the person on site installing the Firth RibRaft Floor system. While Section 3
describes the required verification checks.
This document contains design and installation information. A variation to any of the information given
requires specific engineering design and is hence beyond the scope of this document.
Firth RibRaft Floor System can be constructed for all slab-on-ground concrete floors for domestic
or residential buildings that fall within the scope of NZS 3604:2011 Timber Framed Buildings
and Clause 3 Scope of Section 1 of this Manual. The design and installation details in this
Manual shall be used to design and construct such a floor.
The Firth RibRaft Floor System is covered by the DBH Codemark. This is conditional on the
system being used as described in CertMark Australasia certification decision, which
in turn requires design in accordance with Section 1 and installation in accordance with Section 2
of this Manual and on site Verification in accordance with Section 3.
Note that a DBH Codemark means that if this manual is rigidly followed the relevant Building Control
Authority will automatically provide a building permit without the need for producer statements. To
comply with the manual does mean that Firth Concrete must be used.
CONTENTS
SECTION 1
SECTION 2
GENERAL............................................. 4
GENERAL ............................................ 15
2
2.1
2.2
2.3
2.4
2
2.1
2.2
2.3
SITE REQUIREMENTS.......................... 15
General ................................................. 15
Temporary Excavations......................... 15
Surface Water ....................................... 15
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.9.1
3.9.2
3.9.3
3.9.4
3.10
3.10.1
3.10.2
3.10.3
3.11
3.12
3.13
3.14
3.15
Concrete Installation............................. 19
Placing................................................... 19
Finishing ............................................... 19
Curing.................................................... 20
Shrinkage Control Joints....................... 20
Removal of Formwork .......................... 20
Brick Veneer........................................... 20
Landscaping/Paving.............................. 20
Ongoing Maintenance ........................... 20
3
3.1
3.2
3.3
3.4
3.5
3.6
SCOPE ................................................. 5
Structure Limitations ............................ 5
Live Loading .......................................... 6
Dead Loading ........................................ 6
Building Types ....................................... 6
Foundation Soils ................................... 6
Flow Diagrams....................................... 6
4
4.1
4.2
4.3
4.4
4.5
4.6
CONSTRUCTION DETAILS..................... 8
Pod Layout............................................. 8
Edge Beam Width and Reinforcement.. 9
Internal Ribs (non load bearing)
Width and Reinforcement ..................... 9
Internal Ribs (load bearing)
Width and Reinforcement...................... 9
Mesh Reinforcement ............................ 9
Re-entrant Corners .............................. 9
5
5.1
5.2
5.3
6
6.1
6.2
6.3
SECTION 3
1
DESIGN ............................................... 22
CONSTRUCTION .................................. 22
SECTION 1:
DESIGN INFORMATION
1
GENERAL
TECHNICAL DESCRIPTION
2.1
Overview
Pods
2.4
Concrete
Steel
SCOPE
This Clause sets out the limitations that apply to the use
of the system to ensure that specific engineering input
is not required. The concrete floor slab for buildings or
ground conditions that do not meet this scope must be
subjected to specific engineering design to comply with
the requirements of the New Zealand Building Code.
3.1
Structure Limitations
3.2
Live Loading
3.5
Building Types
Foundation Soils
3.6
Building Type
Flow Diagrams
Building
Type
Description
Ground Floor
External Walls
Single Storey
Light
Single Storey
Heavy
Two Storey
Light
Light
Two Storey
Heavy
Light
Second Storey
External Walls
No
No
Yes
No
Yes
No
No
No
Yes
Yes
Yes
No
No
Roof support
is external
and internal
load bearing
walls with
loaded
dimensions
complying
with NZS
3604:2011
No
No
Yes
Yes
Building Type C or D?
No
Yes
Yes
Yes
No
No
Timber mid-floor(s)?
Yes
Building Type A or B?
Yes
Yes
Yes
Specific
Engineering
Design
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
RIBRAFT
FLOOR SYSTEM
OK
CONSTRUCTION DETAILS
Pod Layout
Specific
Engineering
Design
For all load bearing walls and heavy internal walls, the
pods shall be cut to create a 300mm wide rib directly
under the load bearing wall, with 2-HD12 (Grade
500E) steel bars as bottom steel. Refer Figure 5(D) for
construction details under load bearing walls.
Mesh Reinforcement
/RDGEHDULQJULE
5HHQWUDQW
FRUQHUVWHHO
+'
4.6
Re-entrant Corners
% %
+'
+'
5LEVWHHO5LEVWHHO+' +'
+' +'
5LEVWHHO5LEVWHHO
ILJW\SLFDOULEUDIWSODQGZJ
' '
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
6WDUWHUEDU
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
IRUZDOO
&RQFUHWHEORFNV
6WDUWHUEDU 7LPEHU
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
VKRZQ
IRUZDOO
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
&RQFUHWHEORFNV
7LPEHU
LQGLFDWLYH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VKRZQ
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
PHVK
PHVK
PHVK
+'
+'
LQGLFDWLYH
PHVK
PHVK
+'
+'
4.2
&
ZZZILUWKFRQ]
6FDOH
0DUFK
PHVK
PHVK
),*
&
7LPEHU
+'
PHVK
5LEVWHHO
+'
/RDGEHDULQJZDOO
/RDGEHDULQJZDOO
'
7LPEHU
( (
5LEVWHHO
PHVK
PHVK
/RDGEHDULQJZDOO
5LEVWHHO
5LEVWHHO
+'
Each standard internal
'UDIW rib shall be 100mm wide and
'UDIW
5LEV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
7KHFRS\U
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
WKHSUR
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
WKHSURSHUW\RI)LUW
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
UHSURGX
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ UHSURGXFHGFRSLHG
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
GLUHFWO\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
GLUHFWO\RULQGLUHFW
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRV
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQ
'LVFODLPHU7KLVLQIRUPDWLRQ
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILF
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVK
SURGXFWV%HIRUHXVLQJD)LUWK
VXLWDEOHIRUXVHLQWKHVSHFLILF
FRQVWLWXWHVDVWDWHPHQWRIILWQ
DGYLFHVKRXOGDOZD\VEHREWD
RIWKLVLQIRUPDWLRQZLWKQRQ)
)RU7HFKQLFDO$GYLFH3K
+'
+'
PHVK
)RU7HFKQLFDO$GYLFH3K
)RU7HFKQLFDO$GYLFH3K
+'
+'
FRYHUFRYHU
W\SLFDO W\SLFDO5LEVWHHO5L
& &
PH
PHVK
+'
PHVK
7LPEHU 7LPEHU
6WDUWHUEDU
IRUZDOO
VKRZQ
LQGLFDWLYH
+'
+'
PHVK
PHVK
6WDUWHUEDU
6WDUWHUEDU
IRUZDOO IRUZDOO
VKRZQ VKRZQ
LQGLFDWLYH
LQGLFDWLYH
PHVK
PHVK
&RQFUHWHEORFNV
&RQFUHWHEORFNV
&RQFUHWHEORFNV
$ $
$OWHUQDWLYH
DUUDQJHPHQWRI
SRGV
3DUWSRG
4.4
5LEVWHHO
+'
5LEVWHHO
ILJVWDQGDUGULEUDIWFRQVWUXFWLRQGHWDLOVGZJ
ILJVWDQGDUGULEUDIWFRQVWUXFWLRQGHWDLOVGZJ
ZZZILUWKFRQ]
6FDOH
0DUFK
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
ZZZILUWKFRQ]
7KHFRS\ULJKWRIWKLVGRFXPHQWLV7KHFRS\ULJKWRIWKLVGRFXPHQWLV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
6FDOH
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
0DUFK
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRIUHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
)RU7HFKQLFDO$GYLFH3K
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
),*
),*
Figure 5 Standard
RibRaft Construction Details
RibRaft Floor System - Section 1 Design Information
LATERAL RESISTANCE
5.1
Earthquake Resistance
Sand:
Whangarei
Auckland
0.2
Tauranga
Hamilton
3
0.1
.15
2
0.
Gisborne
0.
New Plymouth
Napier
Hastings
0.4
Wanganui
0.
0.
0.4
Palmerston North
0.2
Nelson
0.3
0.
3
0.4
Kaikoura
0.5
0.2
0.4
0.3
0.4
PHVK
Christchurch
0.3
0.2
Wellington
0.4
Greymouth
Wind Resistance
Rotorua
Westport
5.2
0.13
Timaru
0.5
0.6
0.4
0.3
Dunedin
EDUULHUFXWDURXQG
VKHDUNH\SLOHV
0.2
0.1
Invercargill
PLQ
10
5RRI
7\SH
%8VSURYLGHGSHUPIRUOLYHORDGLQJRI
N3D
N3D
/LJKW
+HDY\
/LJKW
+HDY\
&
/LJKW
&
+HDY\
'
/LJKW
'
+HDY\
200km
+'SODFHG
FHQWUDOO\
%XLOGLQJ
7\SH
03D
retains shape when
moulded under hand
pressure; may stick to boots and hands;
cracks and becomes
hard, but retains shape,
PPFRYHU
when dried in direct sunlight; and when dug
5LEUDIWVKHDU
with
a spade the cut
vertical surface stands.
NH\VXSSRUW
Table 6 %UDFLQJ&DSDFLW\SURYLGHGE\)ULFWLRQDO5HVLVWDQFHSHU
6 Bracing Capacity provided by Frictional
Table
P
RIJURXQGIORRUDUHD
5.3
Shear Keys
Clad frame
timber wall
RaftMixTM
RibRaft Pod
PHVK
220
85
300
&RQWLQXRXVYDSRXU
EDUULHUFXWDURXQG
VKHDUNH\SLOHV
PLQ
+'SODFHG
FHQWUDOO\
/LJKW
+HDY\8 RibRaft
Figure
90mm thick walls
R-Values for
/LJKWfloor edge.
&on the
03D
Firth RibRaft
R Values 90mm
5RRI
7\SH
Draft 2
%8VSURYLGHGSHUPIRUOLYHORDGLQJRI
Floor Area To Perimeter Ratio m2/m
N3D
N3D
1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.50 4.00
/LJKW
$
R-value
1.39 1.51 1.63 1.74 1.85 1.96 2.07 2.18 2.28 2.48 2.68
m2 OC/W
+HDY\
$
%XLOGLQJ
7\SH
&
+HDY\
'
/LJKW
'
PPFRYHU
90mm Thick Walls On Floor Edge Table 6
For Technical Advice: Ph. 0800 800 576
PRIJURXQGIORRUDUHD
5LEUDIWVKHDU
NH\VXSSRUW
6.1
R-Values
)RU7HFKQLFDO$GYLFH3K
ILJVKHDUNH\SLOHFRQVWUXFWLRQGHWDLOVGZJ
Disclaimer7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
ZZZILUWKFRQ]
6FDOH
0DUFK
),*
1.54 1.67 1.80 1.93 2.05 2.17 2.28 2.40 2.62 2.84
11
6.2
15/20/25 series
block wall
220
85
RaftMixTM
RibRaft Pod
300
Block
R-value
m2 OC/W
15
1.46 1.59 1.71 1.84 1.96 2.07 2.19 2.30 2.41 2.63 2.84
series
20
1.52 1.66 1.79 1.92 2.04 2.17 2.29 2.40 2.52 2.75 2.93
series
25
1.57 1.72 1.85 1.99 2.12 2.24 2.37 2.49 2.61 2.85 3.08
series
of Masonry Walls
0 576
Shrinkage Control
FIG110
Services Detailing
12
Vertical Services
Horizontal Services
Nil
Slab
Nil
Notes
(1) For situations where a 100mm diameter pipe is
required to pass through the edge beam, the edge beam
shall be locally increased in width to a minimum of
500mm wide. This shall be achieved by keeping flush the
outside face of the edge beam and removing 200mm from
the pod. The width shall remain at 500mm for a distance
of 600mm beyond the service pipe. Refer to figure 12 for
details.
(2) The need for a duct 50mm larger than the service
diameter can be deleted when the pipe work does not
cross the interface between the bottom of the RibRaft
system and the ground at any point along its length. An
example would be services laid within the plane of the
pods and passing through the edge beam and discharging
to a gully trap or similar. In these cases the diameter of
the service can be increased to a maximum of 100mm
and a service duct is not required. The pipe work shall
be wrapped in denso tape where it crosses concrete
elements to prevent adhesion between the concrete and
pipe work.
(3) Where a gas pipe line runs through the RibRaft floor
system, in addition to the requirements above, the pipeline
shall enter the building through the outside face of the
perimeter foundation beam and be located in the plane of
the pods. The aim being to ensure that damage to the gas
pipe will most likely occur outside the building envelope
should movement occur between the ground and RibRaft
in a large earthquake.
(4) Larger penetrations or voids up to 450mm square
(e.g. for shower waste/traps) are permitted through the
slab provided all the conditions of this paragraph are met.
These openings shall be trimmed with 1 HD12 (Grade
500E) bar 1500mm long placed along each side of the
opening, tied to the mesh. One set of parallel bars shall be
placed on top of the mesh and the other set placed under
13
Located in
central third of beam
Disclaimer
5LEUDIW3RG
5LEUDIW3RG
+'
VWRERWWRPH[OJ
+'
VWR
ERWWRP
+'WRWRS
H[OJ
+'WRWRS
(GJHIRUPZRUN
&UDQN+'
VWRFOHDU
SHQHWUDWLRQE\PP
ZKHUHUHTXLUHG
&XWRQHEDUPD[LPXP
RQO\DVODVWUHVRUW
FHQWUHOLQHRI
SHQHWUDWLRQ
6OHHYHPPODUJHUGLDPHWHU
WKDQVHUYLFHSLSHPD[LPXP
GLDPHWHURIVOHHYHPP
/RFDOLVHGLQFUHDVHLQZLGWKDWHGJHEHDPZKHUH
YHUWLFDOVHUYLFHVXSWRPPGLDPHWHUDUHUHTXLUHG
Figure 13
Localised increase in width at edge beam where vertical services up to 100mm
diameter are required
ILJVHUYLFHVGHWDLOVGZJ
)LUWK5LE5DIW
6HUYLFHV'HWDLOV
14
)RU7HFKQLFDO$GYLFH3K
Disclaimer7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
ZZZILUWKFRQ]
6FDOH
0DUFK
),*
SECTION 2:
INSTALLATION INFORMATION
1
GENERAL
2
2.1
SITE REQUIREMENTS
General
Temporary Excavations
Surface Water
Surface water from the site shall not flow across the
slab platform. For example, on cut and fill sites the
)*/
9
9HUWLFDO'LVWDQFH
7KHUDWLR+9VKDOOQRWEHOHVVWKDQ
D
E
F
LQURFN
LQFOD\
LQRWKHUPDWHULDOV
+
+RUL]RQWDO'LVWDQFH
15
V
F DQG
OD\
12(;&$9$7,21
727$.(3/$&(,1
7+,6$5($
3.4
ILJWHPSRUDU\H[FDYDWLRQOLPLWVGZJ
E5DIW
\([FDYDWLRQ/LPLWV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
3K
'UDIW
)LUWK5LE5DIW
6LWH*UDGLQJ
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
INSTALLATION PROCEDURE
3.1
Site Preparation
ZZZILUWKFRQ]
6FDOH
0DUFK
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
)RU7HFKQLFDO$GYLFH3K
Earthworks
%XLOGLQJ)RRWSULQW
0LQLPXPPHWUH
ZZZILUWKFRQ]
6FDOH
0DUFK
16
Shear Keys
ILJSODQRIIRUPDWLRQDUHDGZJ
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
ZZZILUWKFRQ]
3.6
))/
3HULPHWHUIRUPZRUN
&*/
6DQGEOLQGLQJWR
H[WHQGPP
EH\RQGVODE
SHULPHWHU
7HPSRUDU\
IRUPZRUN
EUDFLQJ
HOHPHQWV
3.5
Sand Blinding
3.7
Edge Formwork
'UDIW
ILJIRUPZRUNGHWDLOVGZJ
The edge formwork shall be constructed
ensuring
A layer of sand shall be placed, screeded and compacted
ZZZILUWKFRQ]
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
6FDOH
)LUWK5LE5DIW
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
that
the
requirements
of
NZS
3109:1997
Concrete
over the
building platform, extending to at least
500mm
0DUFK
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
)RUPZRUN'HWDLOV
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
Construction are adhered
to. The formwork shall
beyond6DQG%OLQGLQJ'30)RUPZRUN'HWDLOV
the system perimeter refer Figure
5. The
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
)RU7HFKQLFDO$GYLFH3K
be adequately supported and braced to prevent any
maximum thickness of this blinding layer shall be
buckling or warping. If the wall is to be constructed
50mm. The surface shall be level and a minimum
in masonry veneer, formwork for a masonry veneer
of 305mm below finished floor level. A small plate
rebate should be adequately fixed to the perimeter
compactor, vibrating roller or similar, should be used
formwork.
to compact the sand blinding layer. When the building
platform is clay, it is essential that the blinding sand
is compacted onto a clay surface that has not been
Thorough cleaning of re-useable formwork and the use
softened by construction activities. If the clay has
of release agents enhances the life and performance of
been softened (i.e. has a muddy surface layer due to
formwork and maintains a quality surface finish.
construction activities), remove the softened material
),*
17
3.8
3.9
Reinforcing Steel
3DUWSRG
'HWDLOHG/D\RXWRI3RGVDQG6SDFHUV
)RU7HFKQLFDO$GYLFH3K
18
Disclaimer7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
$OWHUQDWLYH
DUUDQJHPHQWRI
SRGV
7KHFRS\ULJKWRIWKLVGRFX
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
Reinforcing steel
in the slab shall consist of Welded
WKHSURSHUW\RI)LUWKDQGVKDOOQRW
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
UHSURGXFHGFRSLHGORDQHGRUGLVS
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
GLUHFWO\RULQGLUHFWO\QRUXVHGIRU
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
Reinforcing Mesh
complying with AS/NZS 4671:2001
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKL
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRU
with a minimum weight of 2.27kg/m, a lower
characteristic stress of 500MPa, square configuration
of orthogonal bars between 150 to 300mm centres,
and ductility class L or E, hereafter referred to as 665
mesh, or mesh.
Figure 10 shows the detailed layout of the spacers and
the steel in the edge beam and the standard ribs.
ILJOD\RXWVGZJ
ZZZILUWKFRQ]
6FDOH
0DUFK
),*
5HHQWUDQW
FRUQHUVWHHO
+'
3.10
Concrete Installation
Mesh Reinforcing
'30
'30
'30
'30
'30
'30
'30
ILJ
)LUWK5LE5DIW
)LUWK5LE5DIW
)LUWK5LE5DIW
7KHFRS\ULJKWRIWKLVGRF
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
WKHSURSHUW\RI)LUWKDQGVKDOOQRW
WKHSUR
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
UHSURGXFHGFRSLHGORDQHGRUGLV
UHSURGX
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
GLUHFWO\RULQGLUHFWO\QRUXVHGIRU
GLUHFWO\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFK
SXUSRV
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULR
VSHFLILF
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
)RU7HFKQLFDO$GYLFH3K
)RU7HFKQLFDO$GYLFH3K
)RU7HFKQLFDO$GYLFH3K
6SDFHU'HWDLOV
6SDFHU'HWDLOV
3.9.4 Re-entrant Corner Steel 6SDFHU'HWDLOV
Raftmix For placement in the floor directly from
Two HD12 bars (Grade 500E), 1200mm long shall be
the concrete truck chute.
placed across the corner, tied to the top of the mesh at
Raftmix Pump For placement in the floor by
re-entrant corners at 200mm centres, with 50mm cover
concrete pump.
from the internal corner as detailed in Figure 7 (this
steel is to control cracking at this potential weak point).
Refer 2.4 of Section 1 for locations where RaftMix 25/
Raftmix 25 Pump is required.
),*
/DSDQGWLHVWHHO
7LHVWHHOKHUH
(GJHEHDP
3.10.2 Finishing
/RDGEHDULQJULE
19
3.12
Removal of Formwork
Masonry Veneer
3.10.3 Curing
Where the building is to be clad with masonry veneer,
the rebate in the edge beam shall be waterproofed with
a bituminous sealer due to the possibility of ponding
of water. Firth recommends a Flintcote or equivalent
coating on both the vertical and horizontal faces of the
rebate.
3.14
3.15
PPPHVKFKDLUV
0HVKUHLQIRUFLQJ
5LEVWHHO
(GJHEHDPWRSVWHHO
3RO\VW\UHQH3RG
'30
6DQGEOLQGLQJ
SHEAR KEYS
20
Ongoing Maintenance
)LUWK5LE5DIW
The building owner shall ensure that
the ground
6KHDU.H\3LOH&RQVWUXFWLR
surrounding the system be maintained so that the
)RU7HFKQLFDO$GYLFH3K
integrity of the system is not jeopardised.
In other
words, at no time shall the ground immediately adjacent
to the system be allowed to settle away to expose the
underside of the slab.
Landscaping/Paving
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
ZZZILUWKFRQ]
RQ'HWDLO
PHVK
&RQWLQXRXVYDSRXU
EDUULHUFXWDURXQG
VKHDUNH\SLOHV
PLQ
+'SODFHG
FHQWUDOO\
03D
PPFRYHU
5LEUDIWVKHDU
NH\VXSSRUW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
ZZZILUWKFRQ]
6FDOH
0DUFK
),*
21
SECTION 3:
VERIFICATION
1
DESIGN
CONSTRUCTION
22
)*/
9
9HUWLFDO'LVWDQFH
7KHUDWLR+9VKDOOQRWEHOHVVWKDQ
D
E
F
LQURFN
LQFOD\
LQRWKHUPDWHULDOV
+
+RUL]RQWDO'LVWDQFH
Confirmed
6ORSLQJ*URXQG6XUIDFH
foundation
Width 300mm
ILJVORSLQJJURXQGVXUIDFHGZJ
(1)
5HODWLRQVKLS2I5LEUDIW7R6ORSLQJ*URXQG6XUIDFH
)RU7HFKQLFDO$GYLFH3K
'LVFODLPHU7KLVLQIRUPDWLRQLVLQWHQGHGVROHO\DVDJXLGHIRUXVHRI)LUWK
SURGXFWV%HIRUHXVLQJD)LUWKSURGXFW\RXVKRXOGHQVXUHWKDWWKHSURGXFWLV
VXLWDEOHIRUXVHLQWKHVSHFLILFDSSOLFDWLRQ1RWKLQJLQWKLVLQIRUPDWLRQ
FRQVWLWXWHVDVWDWHPHQWRIILWQHVVIRUSDUWLFXODUSXUSRVHDSSURSULDWHH[SHUW
DGYLFHVKRXOGDOZD\VEHREWDLQHG)LUWKPDNHVQRZDUUDQW\UHJDUGLQJWKHXVH
RIWKLVLQIRUPDWLRQZLWKQRQ)LUWKSURGXFW
7KHFRS\ULJKWRIWKLVGRFXPHQWLV
WKHSURSHUW\RI)LUWKDQGVKDOOQRWEH
UHSURGXFHGFRSLHGORDQHGRUGLVSRVHGRI
GLUHFWO\RULQGLUHFWO\QRUXVHGIRUDQ\
SXUSRVHRWKHUWKDQWKDWIRUZKLFKLWLV
VSHFLILFDOO\IXUQLVKHGZLWKRXWSULRUFRQVHQW
ZZZILUWKFRQ]
6FDOH
0DUFK
),*
Width 100mm.
Reinforcement 1 x HD12.
Firth supplied spacer, max spacing of one per pod or part pod.
Width 300mm.
Reinforcement 2 x HD12 bottom.
Firth supplied spacer, max spacing of one per pod or part pod.
Pods
Mesh
40mm chairs, 1.2m max centres, min two per pod or one per part pod.
Mesh in place and 665 or equivalent area.
Mesh laps minimum of 225mm.
Reinforcement
Concrete
Service penetrations
(1) At locations of service penetrations the width of the perimeter foundation maybe locally increased.
Refer figure 12 section 1 for details.
RibRaft Floor System - Section 3 Verification
23