Você está na página 1de 14

Flare System: Types, Segregation, Tips, Purge System and More

Home Introduction Flare System: Types, Segregation, Tips, Purge System and

Page 1 of 14

to search type and hit enter

More

FOLLOW US ON GOOGLE+

Flare System: Types, Segregation, Tips, Purge


System and More
0

Table of contents:
1. Types of Flare
2. Segregation of Flares
3. Flare Knock-Out Drum
4. Flare KOD Liquid Removal
5. Flare KOD sizing depends on two aspects
6. Liquid Seal Drum
7. Purge reduction seals
8. Flare Purge system
9. Flare stack

1.
2.

Flaring is defined as a process of


controlled burning of exhaust gases which
generates heat and noise. Flaring is a
common practice in oil/gas exploration,
production and processing operations. A
flare system consists of a flare stack and
pipes that feed gas to the stack. The type
and amount of gas or liquids in the flare
stack governs the sizing & brightness of
the flare.

10. Flare Structure

There are many function & reason for

11. Flare Tip

flaring, few reasons for flaring are:

12. Ringlemann Chart


13. Pilot burner
14. Pilot Ignition
15. Other Accessories

3.

During well production testing after drilling


is completed
For safety and during emergencies and
maintenance
For managing gas during compression and
processing

4. Flaring at well sites to recover oil

Piping engineering
1. Types of Flare

Follow

1. Elevated Flare

+1

+ 597

2. Ground Flare
1. Enclosed Flare
2. Open Flare

SUBSCRIBE UPDATES. IT'S FREE!


Your email:
Enter email address...

Subscribe

RELATED READING
Pipe Rack Piping Study Pipe rack
piping study: My this post explains the
steps
Check List for Overall Piping Plot
Plan Project Name: Job No.: Client:
Drawing No. : Date :

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 2 of 14

Furnace & Fired Equipment: Layout


and Direct Fire Furnace and Fired
Equipment: Layout guidelines: Within
the battery limits

116
Like
Tweet

Like Page

Share

Be the first of your friends to like this

Or reach me on aj@pipingengineering.com

Popular
Elevated Flare

Recent

Comments

Nozzle Orientation Drawing


 May 15, 2015

Piping Layout Drawings Abbreviations and


Legends
 May 14, 2015

7 Excel Functions You Must


Know to Work Smarter
 May 15, 2015

Tank farm: Types, Design Considerations,


Plot Plan Arrangement, Dyke EnclosurePart 1
 May 15, 2015

Enclosed Flare

Types of Pipe Flanges Used in Piping


Systems
 May 14, 2015

Google+

Open Flare

Click to enlarge figure Typical Flare System with Elevated Flare

2. Segregation of Flares
1. Service
1. Acid gas flare

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 3 of 14

2. Cold dry flare


3. Warm wet flare
2. Pressure
1. Atmospheric
2. Low pressure
3. High pressure

3. Flare Knock-Out Drum


1. Objective
1. Separate bulk liquid from gas
2. Limit liquid droplet size entrained with gas to the flare
3. Provide adequate residence time for liquid
2. Sizing basis
1. Based on API 521
2. Separation of liquid droplet size of 300-600 microns considering the design case
for the flare
3. 20-30 minutes of liquid hold-up time based on a relief case that results in
maximum liquid
4. No internals to facilitate separation
5. Many orientations / options possible, horizontal KODs most preferred

Flare KO Drum elevation


3. Flare Knock-Out Drum Elevation
1. KO drum elevation decides pipe rack elevation based on 1:500 slope of main flare
header

Flare KO Drum elevation


2. KO drum elevation determined by pump NPSH requirement
3. To reduce pipe rack elevation options are
4. Reduce KOD elevation (option 1)
1. Use vertical can pump

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 4 of 14

2. Locate pump within pit


3. Locate KO drum within pit
5. Use intermediate KO drums (option 2)

>Flare KO Drum elevation arrangement (Option 1)

Flare KO Drum elevation arrangement (Option 2)

4. Flare KOD Liquid Removal


Remove liquid from flare KOD after relief to avoid overfill during future relief event
1. Options
1. Draining to evaporation pond or closed drain drums
2. Liquid removal by flare KOD pumps
3. Heater to be installed in KOD where freezing, pour point issues exist
4. Rate of liquid removal to consider frequency and amount of liquid release
5. High level in flare KOD to be considered for plant shutdown
2. Sizing of Flare KOD

Flare KO Drum
1. LLLL shall be sufficiently high to avoid any sludge deposition impacting LT nozzle
(150 mm in above figure not correct, consider 300 mm minimum for services
which are not clean).
2. LLLL shall be minimum 700-300 in case flare drum electrical heaters need to be
installed.
3. LLLL Level at which pump trips.
4. LLL Level at which both pumps stops
5. HLL Level at which first pump starts
6. HHLL Level at which second pump starts
7. HHHLL Level at which entire plant goes into pressurized trip.

5. Flare KOD sizing depends on two aspects


Liquid Hold up requirement during a major liquid or two phase release.
Sufficient distance shall be available between inlet device bottom and HHHLL. It is
possible to have manually initiated depressurization even after HHHLLL. Any
possible liquid shall be accommodated above HHHLL.

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 5 of 14

Distance between HLL and HHHLL shall be designed to accommodate maximum


liquid release scenario(?). Some standards this distance is between HHLL and
HHHLL.
Residence time required for drop of liquid particles of 300-600 micron size.
Liquid particles separate
When the residence time of the vapor or gas is equal to or greater then the time
required to travel the available vertical height at the dropout velocity of the liquid
particles and
When the gas velocity is sufficiently low to permit the liquid dropout to fall. This
vertical height is usually taken as the distance from the maximum liquid level.

6. Liquid Seal Drum


1. Objective
1. Prevent flashback from flare tip back to flare headers
2. Avoid air ingress into flare system during sudden temperature changes leading to
condensation and maintain positive system pressure
2. Use
1. Used in flare gas recovery systems
2. Staged flaring between enclosed flare and full size emergency flare
3. Design specifications
1. Water as liquid sealing fluid not recommended for extremely cold releases; waterglycol mixtures of sufficient concentration used instead

Liquid Seal Drum

7. Purge reduction seals


1. Objective
1. Prevent air infiltration into flare system at low flow rates
2. Reduce amount of continuous purge gas injection into flare stack
2. Design options
1. Buoyancy seal (molecular / density seal)
2. Velocity seal (fluidic seal)

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 6 of 14

Purge Reduction Seal

8. Flare Purge system


1. Objective
1. Prevent air infiltration into flare system at low flow rates
2. Prevent vacuum formation in flare headers and system following steaming or
large relief event
2. Design specification
1. Continuous purge rate with velocity in stack
1. 1-5 fps : without molecular seal
2. 01 : with molecular seal
3. 02-0.04: with velocity seal
2. Approximate purge flow rate can be calculated using section 7.3.3.3 of API 521.

Purge Reduction Seal

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 7 of 14

Flare P&ID

9. Flare stack
1. Objective
1. Combustion of relief gases at elevation to minimize radiation exposure to
personnel/ equipment/ structure
2. Ensure adequate dispersion of un-burnt hydrocarbons and toxic components

Flare protection
2. Design considerations
1. Radiation: Limit radiation, either continuous and peak, on off-site properties and
persons, equipment, buildings and personnel on the installation. Applicable to
impacted area, restricted area and equipment lay-out.
2. Flammable gas: Avoid ignition of a flammable gas cloud released from a cold vent
or in case of flare flame out.
3. Toxic hazards: (Mainly for H2S and SO2, but not limited to) limit the risk of a toxic
gas cloud to reach off-site population, provide means of alarm and adequate
protection to personnel present in the restricted area.
4. Noise: Limit both continuous and peak noise
5. Stack height is determined by HSE group based on permissible radiation level as
per project philosophy or API 521.

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 8 of 14

6. Taller stack will result in smaller sterile zone.


7. Locate process plant upwind of flare.

10. Flare Structure


Self supported flare stack
Guy wired supported flare stack
Derrick supported flare stack
More than one flare may be supported on the same structure

Flare Stack Support

11. Flare Tip


Produce desired destruction/combustion efficiency of maximum specified relief gas
Establish and maintain proper ignition
Pilot gas /Pilot burners/ Ignition system
Ensure stable combustion
Windshield
Retention rings
Result in smokeless operation at normal continuous flows or at100% flows
Steam
Air (high pressure or low pressure)
High pressure water
No external medium, maintain high pressure at tip by staging

Flare Tip

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 9 of 14

Flare Tip

Flare Tip: Velocity Seal (top view)

Based on velocity of gas exit from tip, flare tips are considered as sonic and subsonic
(pipe flare) type. This is the term used by process designer for high pressure flares
and low pressure flares.
General stack pressure drops are as given below.
Sonic flare 2 to 4 bar
Subsonic flare 0.2-0.5 bar
Open Pipe flare tips: These are used for combustion of gases that do not produce
smoke, gases with a low heating value, or for installations where smokeless
combustion of heavy hydrocarbons is not required. These flare tips are one of the
lower capital cost options for safe disposal of waste gases. In general these kind of
flares have tips with very low pressure drop.
Open pipe flare tips with steam injection: Steam injection is provided reduce the
smoke formation.
Open pipe flare tip with high pressure gas injection: This will increase the
turbulence at flare tip and reduce the smoke formation. Fuel gas can be generally
used as assist gas. Fuel gas injection can be either continuous or initiated
manually based on monitoring of flare tip.

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 10 of 14

Air assisted flare tip: When smokeless flaring is desired and neither steam nor assist
gas is available, blowers can be used to inject combustion air directly into the waste
gas stream as it exits the flare tip. Combustion efficiency of flared gas is increased by
installing air blower which will reduce smoke formation.
Multiple nozzle type flares: They are used where high flare gas pressures are
available (1 barg and up) and where it is preferred to have some smokeless burning
capability and also lower radiation levels. These kinds of flares are used for HP flare
application. They have good combustion efficiency and less chances of smoke
formation.
Coanda flare tip: The Coanda effect is a gas-adhesion principle that dramatically
enhances the combustion process, resulting in maximum destruction of waste
gases. Coanda Effect occurs when gas is passed over and adheres to a carefully
profiled, curved surface, creating a near vacuum that pulls in substantial amounts of
air. The air turbulently mixes with the gas flow, resulting in high-efficiency
combustion.

Open Pipe Flare

Multi Nozzle Flare

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 11 of 14

Coanda Flare

12. Ringlemann Chart


A series of charts, numbered 0 to 5, that simulate various smoke densities by
presenting different percentages of black.
Ringelmann No. 0 is clear smoke
Ringelmann No. 5 is 100 percent black.
Ringelmann No. 1 is equivalent to 20 percent black

Ringleman Chart

13. Pilot Burner


1. Objective
1. Provide flame for reliable ignition of main flare gas at all times
2. Design specifications
1. Pilot system to comply with API 537
Minimum number of pilots

Flare burner outer diameter, DN

1 (2 for toxic gas)

Up to 200

>200 to 600

>600 to 1050

>1050 to 1500

To be agreed with purchaser

>1500

2. Pilots designed to remain lit and capable of being relit at wind speeds up to 160
km/h under dry conditions

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 12 of 14

Pilot gas line

14. Pilot Ignition


1. High Energy Ignition (HEI)
1. Electrode capable of high energy or high voltage discharge near pilot tip
2. Does not require propagation of a flame front as in FFG system
3. Does not require compressed air, self aspirating pilots
4. Simple and easy to use and automate, require little training or maintenance. Reignition takes few seconds
5. Shutdown of flare system required for maintenance
6. Back up FFG ignition (when using HEI) may be considered for
1. Very tall flares that are difficult to access
2. Flare systems that can be off line only once in more than 3-5 years
3. Offshore platforms in corrosive and salt environments

Electrical Ignition Panel


2. Flame Front Generator (FFG)
1. Ignition line from panel to flare pilot filled with flammable fuel gas- air mixture
and spark introduced. Mixtures ignited and flame front travels through piping to
ignite pilot at flare tip
2. FFG panel located at grade
3. Panel operated manually or automated to reignite of pilot flame out detection.
Re-ignition can take several minutes
4. Moisture accumulation can lead to corrosion, flame extinguishment Ignition lines
to be heat traced

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 13 of 14

FFG Panel

FFG System

15. Other Accessories


Flow measurement
Monitoring relief devices leaks during normal operation
Assess flaring of gases due to pressure control operations
Note relief flows for assessing flare system adequacy checks and potential for
flare gas recovery
Non-intrusive ultrasonic flow meters with wide range and no pressure drop is
preferred
Smokeless flaring : medium control
Proper steam or air control is required
By measuring gas being flared and adjusting steam rate / blower capacity
Detection smoke using infra-red analyzers
Aircraft Warning Lights
Required when flare heights exceed 61m or when site is close to airport
Type and number based on regulations
Related Posts:

Pipe Rack Piping Study Pipe rack piping study: My this post explains the steps
Check List for Overall Piping Plot Plan Project Name: Job No.: Client: Drawing No. :
Date :
Furnace & Fired Equipment: Layout and Direct Fire Furnace and Fired Equipment:
Layout guidelines: Within the battery limits
Guidelines for Acoustic Induced Vibration (AIV), Flow Introduction The scope of this
topic is to define the
Winterization: Protection Against Low Ambient Temperature Table of contents: 1.
PURPOSE 2. SCOPE 3. DESCRIPTION 3.1

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Flare System: Types, Segregation, Tips, Purge System and More

Page 14 of 14

MORE READ
Different Steam Trap

Piping Stress Critical

Piping Stress Critical

Arrangements on

Linelist: Format and

Lines: Procedure

Steam Headers in

Use, Responsibilities

Defining the Basis For

Piping System

and Method of

Piping Critical Line List

February 8, 2016

Operation

March 16, 2016

May 15, 2015

LEAVE A REPLY
Your email address will not be published. Required fields are marked *

Name *

Email *

Check here to Subscribe to notifications for new

posts
Post Comment

Confirm you are NOT a spammer

copyright Piping-engineering 2016 All Rights Reserved. Privacy Policy | About Us

http://www.piping-engineering.com/flare-system-types-segregation-tips-purge-system-a...

7/8/2016

Você também pode gostar