Você está na página 1de 4

Configure/Setup of FT-305401 [IFC 300 Rev.

2]
(Historic) 7/10/2008 10:16:00 AM
quick setup
language
tag

English
FT305401

value p. pulse D
volume flow unit
range max C
range min C
time constant
lfc threshold
lfc hysteresis

m/h
250.00002 m/h
0.00000 m/h
3.0 s
2.0 %
1.0 %

sensor
USL
LSL
Min span
USL
LSL
Min span
USL
LSL
Min span

0.589048 Cum/s
-0.589048 Cum/s
0.011781 Cum/s
589.048 kg/s
-589.048 kg/s
11.781 kg/s
12 m/s
-12 m/s
0.24 m/s

input calibration
zero set
size
size
GK selection
GK
GKL
coil resist. Rsp
density
target conduct.
EF electr. factor
num. of electrodes
field frequency
select settling
settling time
line frequency
input filter
limitation max
limitation min
flow direction
time constant
pulse filter
pulse width
pulse limitation
noise filter
noise level
noise suppression
lfc threshold
lfc hysteresis
self test / info
empty pipe
limit empty pipe
full pipe
limit full pipe
linearity
gain
coil current
flow profile
limit flow profile

0.00230 m/s
250mm 10inch
GK and GKL
4.3962
8.8454
81.39 ohm
1.0000 kg/L
400.0000 S/cm
8.93 mm
2 electrodes
1/6*line frequency
standard
automatic

12.0000 m/s
-12.0000 m/s
normal direction
0.0 s
off
off
0.0000 m/s
0.0000 m/s

conductivity
off
off
off
on
off

7/10/2008 10:16:03 AM

Page 1 of 4

Configure/Setup of FT-305401 [IFC 300 Rev. 2]


(Historic) 7/10/2008 10:16:00 AM
self test / info
electrode noise
limit elect. noise
settling of field
liner
electr. material
IO terminals A
terminals A
measurement A
limitation max
limitation min
time constant
polarity

off
off
T
HC

off
volume flow

range max A
range min A

IO terminals B
terminals B
measurement B
limitation max
limitation min
time constant
polarity

off
flow speed

range max B
range min B

IO terminals C
terminals C
measurement C
lfc threshold
lfc hysteresis
time constant
polarity
lfc threshold
lfc hysteresis
range max C
range min C
range 100%
range 0%
ext. range max C
ext. range min C
error current

current output
volume flow
2.0 %
1.0 %
3.0 s
absolute value
2.0 %
1.0 %
250.00002 m/h
0.00000 m/h
20.0 mA
4.0 mA
20.5 mA
3.8 mA
21.5 mA
7/10/2008 10:16:03 AM

Page 2 of 4

Configure/Setup of FT-305401 [IFC 300 Rev. 2]


(Historic) 7/10/2008 10:16:00 AM
IO terminals C
error condition
special function
rc threshold
rc hysteresis
IO terminals D
terminals D
measurement D
limitation max
limitation min
time constant
polarity
lfc threshold
lfc hysteresis
range max D
range min D
pulse shape
pulse width
100% pulse rate
invert signal

error in device
off

frequency output
volume flow
120 %
-120 %
0.0 s
absolute value
2.0 %
1.0 %
250.00002 m/h
0.00000 m/h
symmetric
100.0 Hz
off

counter
funct. of counter
measurement
lfc threshold
lfc hysteresis
time constant
preset value
funct. of counter
measurement
lfc threshold
lfc hysteresis
time constant
preset value

+ counter
volume flow
0.0000 m/h
0.0000 m/h
0.0 s
0.001000 m
sum counter
volume flow
0.0000 m/h
0.0000 m/h
0.0 s
0.001000 m

device
tag
C number
language
volume flow unit
mass flow unit
flow speed unit
conductivity unit
temperature unit
volume unit
mass unit
density unit

FT305401
CG30081300
English
m/h
kg/s
m/s
S/cm
C
m
kg
kg/L

HART
manufacturer
model
dev ID
poll addr
tag
date
message
descriptor
write protect

KROHNE
IFC 300
605492
FT305401
2/28/2003
HART MESSAGE
HART DESCRIPTION
None
7/10/2008 10:16:03 AM

Page 3 of 4

Configure/Setup of FT-305401 [IFC 300 Rev. 2]


(Historic) 7/10/2008 10:16:00 AM
HART
final asmbly num
snsr s/n
universal rev
fld dev rev
software rev
hardware rev
num req preams
num resp preams
PV is
SV is
TV is
4V is
HART units
volume flow unit
mass flow unit
flow speed unit
conductivity unit
coil temp. unit
counter 1 unit
counter 2 unit
vol. flow format
mass flow format
flow speed format
conductiv. format
coil temp. format
counter 1 format
counter 2 format

66051
66051
5
2
2
1
5
volume flow
volume flow
counter 1 (C)
counter 2 (D)

Cum/s
kg/s
m/s
uS/cm
degF
Cum
Cum

7/10/2008 10:16:03 AM

Page 4 of 4