GROUND FLOOR MECHANICAL VENTILATION


Supply, deliver, install, test and commission the following equipment/
items as described. Where trade names are mentioned the tenderer
must provide the same materials as other brands shall not be
accepted without a written authority to supply alternative brands by
the Mechanical Engineer.
Ductwork
A

SWG 22 Galvanized mild steel ductwork complete with bends,


transformation pieces, branch takeoffs, flanges and stiffeners all as
per the approved working drawings. The ducts shall be used in first
floor.
Extract Fan
3

Silenced extract box fan unit of duty 0.75 m /s against 150pa


External static pressure consisting of a low speed forward curved
centrifugal fan housed in galvanised and painted steel casing.The
unit shall be suitable for outdoor installation and provided with V.C.D,
cowl, and access doors. It shall be as SYSTEMAIR of U.K or
approved equivalent with approved anti vibration mountings.
Control Panel
Splash proof controlled panel manufactured from 1.2mm thick sheet
with stove enamel finish and clear perplex front cover. The panel
shall incorporate isolator contactor phase failure relay, motor starter
overload relay and overheat safety control and fuses.
Associated electrical
Associated electrical works for the above installations
Damper

Volume control damper of 250x300mm ductwork

No.

Fire damper of 250x300mm ductwork

No.

Extract Grilles
200 x 200mm register with volume control damper as manufactured
by Trox Technik or approved equivalent.

42

No.

Flexible Duct
200mm diameter flexible duct manufactured from aluminium foil
complete with connectors, stiffeners, supports, etc all as per the
120
approved working drawings. The ducts shall be used in lower ground
and ground floors.
External Louvre
All weather air extract louver complete with volume control dampers
of size 400 x 400 mm
Door Grilles
Door lourve grille to be mounted on the door. The grille to be made
of corrosion resistant material and minimm dimensions to be
400x400mm.The grille should be capable of discharging atleast
5m3/hr. It shall be as Xpelair or equal and approved.
Total Carried Forward to Collection Page
BQ 19

No.

No.

24

No.

Air Conditioning and Mechanical Ventilation

Item

Description

Qty Unit Rate (Kshs)

Extract Fans for Rooms


A

Wall mounted extract fan capable of atleast 670m /hr and having
sound pressure level of not more than 50dba at 3 meters. It shall be
complete with front cover,on/off switch,long length ladder strips
exterior productive grille, wall kit, panel fixing clips, internal lourve
grille and back drought shutter. The fan will be flush mounted into
the wall. It shall be as Xpelair GX9 or approved equivalent.
Darkroom Extract Fan
3
Dark room wall mounted extract fan capable of at least 670m /hr and
having sound pressure level less than 50dba at 3 meters. It shall be
complete with front cover, on/off switch, long length ladder strips
exterior productive grille, wall kit, panel fixing clips, internal lourve
grille, dark room cowls and back drought shutter. The fan will be
flush mounted into the wall. It shall be as Xpelair GX9 or approved
equivalent.
Radiology Extract Fan
Radiology room wall mounted extract fan capable of at least
3
670m /hr and having sound pressure level less than 50dba at 3
meters. It shall be complete with front cover, on/off switch, long
length ladder strips exterior productive grille, wall kit, panel fixing
clips, internal lourve grille, dark room cowls and back drought
shutter. The fan will be flush mounted into the wall. It shall be as
Xpelair GX9 or approved equivalent.
Split Silencer
Fan silencer constructed from rolled pre-galvanized sheet steel with
spun rings incorporating tapped insets for fixing. Absorbent material
shall be acoustic grade minimal fibre with an erosion resistant facing
the silencer to be suitable for 381mm diameter. The installed in the
supply duct and fan to be as "Woods" type B or equal and approved.
As-built Drawings Maintenance and Operation Manuals
Allow for as-built drawing, maintenance and operation manuals in
both soft and hard copies. Three copies of the as-built drawing shall
be submitted in A1 paper in a scale of 1:50
System Balancing
The systems shall be balanced such that the spaces shall be
balanced as per the designed flowrates indicated in the drawings. It
will be the onus of the tenderer to make sure that the flows are
adjusted to meet these requirements.
Duct Painting
Allow for painting (2 No coats) of the ductwork with suitable matt
paint to match the walls where the duct is exposed.