Escolar Documentos
Profissional Documentos
Cultura Documentos
DESCRIPTION
Hosereelsystemisintendedfortheoccupanttouseduringtheearlystagesofafireandcomprises
hose reel pumps, fire water storage tank, hose reel, pipe work and valves. A typical hose reel
installationisshowninFigure7.1.
7.2
DESIGN REQUIREMENTS
M.S.1489Part1:HydrantSystems,HoseReelsandFoamInlets;
M.S.1447:Hosereelswithsemirigidhose;
M.S.1488:Semirigidhosesforfirstaidfixedinstallations.
Wherethetotalnumberofhosereelsinthebuildingdoesnotexceedfour(4),thestandbypumpset
maybeelectricallydrivenandneednotbeprovidewithemergencypower.
Thehosereelpumpsetsshouldbeprotectedfromtheweatherandawayfromlocationslikelytobe
flooded. Pump rooms may be located anywhere in the building or on the roof but should be
ventilatedbynaturalormechanicalmeansandprovidedwiththenecessarysignage.
7.2.4 Hose Reel Tanks
Thefirewaterstoragetankshouldbesizedbasedon2275litresforthefirsthosereeland
1137.5litresforeveryadditionalhosereeluptoamaximum9,100litresforeachsystem.
Thetankmaybeofpressedsteel,fibreglassreinforcedpolyester(FRP)orconcrete.Pressedsteel
tankswhereusedshouldbehotdippedgalvanizedandcoatedinternallywithbituminouspaintfor
corrosionprotection.Thetankshouldbecompartmentedandwaterlevelindicatorshouldbe
providedtoshowtheamountofwateravailable.Theexternalsurfaceofthetankshouldbepainted
redorwherethisisnotdesirable,aredbandofminimum200mmshouldbepaintedtoindicatethat
thisisafiretank.
Thehosereeltankshouldberefilledautomaticallyfromawatersupplypipeofminimum50mm
diametertoprovideaminimumflowrateof150l/min.
Althoughhosereeltanksareusuallyseparatedfromdomesticwaterstoragetanks,thetwocanbe
combined.Insuchcases,thetankcapacityshouldbethesumtotalofthewaterstorageforboth
domesticaswellasforhosereelsandthetapoffpointforthedomesticusemustbetheabovethe
tapofpointforthehosereelsystemsuchthattheminimumfirereserveforhosereelisalways
maintained.
7.2.5 Pump Starter Panels and Controls
PumpstarterpanelshouldbecompletewithindicatorlightsasshownintheFigure7.2.Ventilation
slotsshouldbeprovidedwithinsectscreentoprevententryofvermin.
Hosereelpumpsshallstartautomaticallyuponactuationofthepressureswitches.Usuallytwo
pressureswitchesareprovidedwiththefollowingsuggestedsettings:
Startingandstoppingthedutypumpsetat80%and100%ofsystempressurerespectively;
and
Startingandstoppingthestandbypumpsetat60%and100%ofsystempressure
respectively.
Fordieselpumpsets,theseshouldbecapableofautomaticstartingbutshouldonlybestopped
manually.
7.2.6 Gravity Feed Hose Reel System
Wherethetankislocatedontherooforupperfloorsandthestaticpressureisadequatetoachieve
therequirepressure,thehosereelsmaybefeddirectlyfromthehosereeltank.Ifpumpsare
requiredfortheupperfloors,abypasspipeisusuallyprovided.Whereexcessivepressureis
encountered,pressurereducingvalvesshouldbeinstalledwithamanualbypassincasethepressure
reducingvalvefails.
7.3
DESIGN CHECKLIST
a.
n.
Designflowrateateachhosereelshallbe30l/minbasedonthetopmostfournumbersof
hosereelsinusesimultaneously.
Minimumdesignstaticpressureatentryofeachhosereel:__________bar.
Hosereeltype:__________.
Hoselength:__________meters.
Watersource:
Pumpsuctiontank.
Gravitytank.
Firewatermain.
Others:__________
Watertankcapacity:__________litres.
*(2,275litresforthefirsthosereel,eachadditionalhosereelrequireextra1,137.5litresup
to9,100litres).
Pressurereducingvalveset:
Yes.Pressurereducingrange:__________barto__________bar.
No.
Hosereelspacing:__________m.
Totalnumberofhosereel:__________nos.
Nozzlesareadjustableandspraytype.Size:__________mmnomdiameter.
Risersize(minimumnominalsize50mm):__________mm.
Pipematerial:__________.
Hosereelpump:
Ratedflowrate:__________litres/minat__________metrehead.
Pipenominalsize:Suction:__________mm;Delivery:__________mm.
7.4
7.4.1
a.
b.
7.4.2
a.
b.
c.
d.
e.
f.
b.
c.