Escolar Documentos
Profissional Documentos
Cultura Documentos
Abstract
Reliable electrical power distribution to the
petrochemical plants becomes more and more
important. False trips could lead to equipment
damage, environmental issues, production loss, etc.
Power dips in the public grid are not rare anymore
due to the distributed generation, changes of the
grounding system in public grid, etc. A chain in the
reliable power supply to the chemical plants is the
stable operation of protective relaying. No false
tripping, fault ride through (power dip immunity) and
fast tripping when an electrical fault occurs in the
equipment are essential to reliability. Protective
relaying manufacturer are putting more and more
functions into the relaying box. The flexibility of the
relaying (multifunctional relays) leads to long setting
lists that needs to be tested, this making total scheme
testing more and more important.
This paper describes the modeling for critical
protective relaying testing (line, generator, bus,
transformer and transfer protective relaying) and the
use of Advanced Transplay. Dynamic testing has
become a standard within DOW on critical protective
relaying system and is a part of the total scheme
testing. EMTP (ATP) models are used to generate PL4,
COMTRADE files. The currents, voltages and input
changes are injected to check if the relaying is stable
or not stable. The CT Analyzer, CPC 100 data is used
to model current transformers. Generator protection
relays, transfer systems, line, bus and transformer
differentials are tested dynamically by the use of
Advanced Transplay module. The developed method
of testing is used on all critical protective relaying
applications with DOW Europe.
Figure 1:
2 EMTP Models
2.1
Current Transformers
Presentation 08.2
2.2
Voltage Transformers
2.3
Figure 3:
Figure 4:
Fault modeling
Figure 6:
Presentation 08.3
2.4
Figure 8:
Cable Modeling
A three phase simple cable with the exact PIequivalent model can be used to model the short
cables in an industrial network. For the relaying DOW
does not need the high frequency dependency model
for the cabling. The anti-aliasing filters are cutting off
the high frequencies anyhow. The modeling is not
made for electromagnetic transient study.
Test Cases
SUB 119
500m cable
Figure 9:
Fault
Plant load
Figure 7:
Presentation 08.4
Plant substation
Inc. A
Inc. B
N.C.
TIE
BUS A
N.C.
BUS B
N.O.
damping
Inertia->capacitance
V(0) -> rpm (0)
Current is torque
load model
Figure 13: UM3 EMTP Motor Model
0.9
0.8
0.7
M/Mn
0.6
T [p.u]
0.5
T[p.u] org
T org:
A0=12
A1=-35
A2=230
A3=-173
0.4
0.3
0.2
0.1
0
0
0.1
0.2
0.3
0.4
0.5
N/Nsyn
0.6
0.7
0.8
0.9
Closing coupler
CB HVP 134-1/2
Rated torque
Rated rpm
Presentation 08.5
6kV
Current measurement
Fault
0.4kV
C
Trip signal **
Trip signal **
Close signal**
SUB 134
Synchronizing unit
EMTP-program
Test universe
DOW RESTRICTED
Figure 16: Test Set-Up for Testing Main Tie Main Transfer
System
Presentation 08.6
11 1 1 13 14 15 16
1 3 4 5 6
1 3 4 5 6
= 31 3 3 33 34 35 36
41 4 4 43 44 45 46
51 5 5 53 54 55 56
[61 6 6 63 64 65 66 ]
5 Transformer Differential
Testing
2 2
2 2
(1 )
(2 )
na
(3 )
[0
(4 )
6 ]
22
1 21
+
+1
(5 )
22
2 + 21 + 1
(6 )
22 1
1
( + ) + 21
(7 )
k=na/nb
If i coil is considered in the same leg as a and b, the
faulty coil, then
1 22
= 2
1 +
22
22
(8 )
= 2
(9 )
1 + 2
1 + 2
(10)
(11)
nb
212
11 22
(12)
Presentation 08.7
5P20 600/5
20VA
S1, M1
High side 1
87T
TR 87-5
R=8 ohm
1X1
52.5kV/11 kV Uk=14%
-10*1%+20*1%
20/25MVA Dyn11
Low side 2
1000/5
5P20 2500/5
15VA
S2, M2
Low side 2
Low side 1
S2, M3
5P20 2500/5
15VA
Presentation 08.8
G6
G17
G13
G11
G12
IS-limiter
Presentation 08.9
1
= 1
()
(34)
8 Conclusions
Figure 31: Transformer Contribution
Presentation 08.10
Literature
[1] ATP rule book
[2] J.L. Blackburn; Protective relaying
[3] ETAP 11
[4] Siemens Sigra
[5] D. Dakhlan; Modeling internal faults in three
winding transformers for differential protection.
[6] M. Kezunovic; A new ATP add-on for modeling
internal faults in power transformers.
www.omicron.at | www.omicronusa.com
OMICRON