Escolar Documentos
Profissional Documentos
Cultura Documentos
College of Chemistry & Chemical Engineering, Shenzhen University, Shenzhen 518060, PR China
Ecole Centrale de Lyon 69130, France
a r t i c l e
i n f o
Article history:
Received 2 August 2007
Received in revised form 13 October 2009
Accepted 13 June 2010
Available online 13 July 2010
Keywords:
Film type cooling
Latent heat of evaporation
Energy balance
Efciency and effectiveness
a b s t r a c t
Based on heat and mass transport mechanism of lm type cooling, which was combined with an on-site
test on counter ow lm type cooling tower, a mathematical model on the evaporation and cooling efciency and effectiveness has been developed. Under typical climatic conditions, air conditioning load and
the operating condition, the mass and heat balances have been calculated for the air and the cooling
water including the volume of evaporative cooling water. Changing rule has been measured and calculated between coefcient of performance (COP) and chiller load. The inuences of air and cooling water
parameters on the evaporative cooling efciency were analyzed in cooling tower restrained by latent heat
evaporative cooling, and detailed derivation and computation revealed that both the evaporative cooling
efciency and effectiveness of cooling tower are the same characteristics parameters of the thermal performance of a cooling tower under identical assumptions.
Crown Copyright 2010 Published by Elsevier Ltd. All rights reserved.
1. Introduction
Thermal efciency is commonly used to express the cooling effect of a cooling tower, and it in fact represents water evaporative
cooling efciency [1]. Merkel developed a cooling tower model in
1925, for simplicity, several crucial suppositions have been made.
Namely:
(1) the Lewis factor of the airwater system Lef = (h/cPH hm) = 1,
(2) the outlet air of the cooling tower is water vapor saturated,
and may just be represented by the enthalpy of the air,
(3) the evaporation impact of the cooling water on the energy
balance is neglected in the cooling tower,
The effectiveness-NTU based on the same simplied assumptions as the Merkel method, NTU method is convenient and quite
accurate compared with other existing numerical methods. The
shortcoming is that it is difculty to quantify the product of the heat
transfer coefcient and the area, since the detailed information is
required on the geometry of the cooling tower, and when the operating point is changed, iterative computation is indispensible [2].
The Poppe method was proposed by Poppe and Rgener [3] to
express the Lewis factor more rigorously. The Lewis factor for
supersaturated air was derived from the empirical relationship of
the Lewis factor for unsaturated air developed by Bosnjakovic [4]
* Corresponding author. Tel.: +86 755 26538802; fax: +86 755 26536141.
E-mail address: szulyj@sohu.com (Y. Li).
0196-8904/$ - see front matter Crown Copyright 2010 Published by Elsevier Ltd. All rights reserved.
doi:10.1016/j.enconman.2010.06.036
54
Nomenclature
A
A0
COP
cPH
cPL
cpg
cpV
G
H
H
H
hm
I
Isat,wi
K
L
Lsup
NTU
P
Ps
Qc
Qe
R
ro
Tc
T
tawb
u
u
V
Greek symbols
g
thermal efciency of cooling tower
u
relative humidity
e
effectiveness of cooling tower
qa
air density, kg/m3
Du
difference of air velocity, m/s
Dt
temperature difference, C
mH
humid volume, m3/kg
Subscripts
awb
air wet-bulb temperature, C
max
maximum
min
minimum
o
standard condition
a
air
w
cooling water
in
inlet
out
outlet
2. Testing device
The system consists of two centrifugal chiller units (380RT)
mounted underground, and three cooling towers (LBC-LN-500)
mounted on the roof of a 91 m high building are parallelly connected and operated. One of the cooling towers is to the west of
the other two. The runtime of the system is from 8:00 am to
17:30 pm. Because the lling height in the cooling tower is not
high enough (only two stories, see Fig. 1), the heat and mass transfer process is only between the cooling tower and the spray tower.
55
Axial Fan V
u a taout
out
3800
500 700 480 1200
770
3300
Bank Building
4460
ta
in
tawbin in
L sup
tc
Lch
tch
tw
V
in
in
RT ,V , I ,tR22
P
tw
Cooling Pump
out
Chillers
tch
Chilling Pump
out
Model
Function
Unit
Measuring
accuracy
Germany testo
635
Digitaltemp and
hygrometer
Electric
instrument
DET06352
TES-1360
Air parameter
FLUKE316
0.3 C, 0.5% RH of
reading
0.8 C, 3% RH of
reading
1.9 5%/1.2 5%
Anemoscope
8903/06
Blower
electric
quantity
Flow speed of
air
C,
%
C,
%
A, V
m/s
Glass tube
thermometer
Mercury
Scale
division 0.1 C,
0.01 m/s
0.1 C
Air parameter
Cooling water
temp
56
Table 2
Chiller units test parameters.
Time
8:30
9:30
10:30
11:30
12:30
13:30
14:30
15:30
16:30
17:30
585.5
550
4.3
2.753
4.69
35.1
553.1
385
4.2
1.882
3.40
35.3
489.2
238
4.0
1.108
2.26
34.9
507.9
315
3.9
1.430
2.82
34.7
492.7
374
3.9
1.698
3.45
34.4
464.0
416
3.6
1.743
3.76
33.1
493.5
500
3.7
2.153
4.36
33.8
502.3
372
3.9
1.689
3.36
33.4
495.1
555
3.7
2.390
4.83
33.7
459.3
519
2.6
1.571
3.42
33.8
vH
qa
The mass rate and volume ux of the leaving humid air was calculated by the following equations respectively:
A0 ;
Gout qa;out u
A0
V out u
H 0:622
of the circulating cooling water was less than 3.9 C, and the maximum temperature difference did not exceed 4.2 C (according to
statistics data). The variation of the inlet and outlet cooling water
temperature of tw was basically the same as that of the refrigeration quantity. When the cooling range is constant the cooling
water mass ux is proportional of the air conditioning load.
u ps
p u ps
Qc P Qe
Qc
tw;in t w;out cpL
Table 3
Variation of wet-bulb temperature tawb of entering wind for cooling tower with time.
Time
8:30
9:30
10:30
11:30
12:30
13:30
14:30
15:30
16:30
17:30
27.3
26.7
27.6
27.2
27.4
27.2
27.9
28.7
27.1
27.2
27.1
28.2
26.6
28.3
26.3
27.8
26.0
27.5
27.4
27.1
57
Table 4
The measured and calculated data for air of east side cooling towers.
a
b
Time 13:30
ta (C)
u (%)
qa (kg/m3)
G (kg/s)
V (m3/h)
Entering air
Leaving aira
State conversionb
34.7
34.2
20.0
55.6
75.4
50.0
1.113
1.104
1.20
48.87
50.78
50.78
1.58 105*2
1.66 105
1.52 105
Cooling
tower
10
t w;in t w;out
t w;in t awb;in
11
Lin Lout, Gin Gout, The evaporation loss of water was not considered in Eq. (11), therefore error could be occurred in the thermal
balance calculation.
The tower effectiveness can be also determined from:
g0
Ia;out Ia;in
Isat;wi Ia;in
12
Fig. 5. Relationship between the tw,out, tawb,in, and g, in the east side towers with
time.
Table 5
The parameters of heat and mass balance.
Time 13:30 pm
ta (C)
H (kg kg1)
tw (C)
Hw (kg kg1)
G (kg s1)
L (kg s1)
I (kJ kg1)
Q (kW)
Inlet tower
Outlet tower
34.7
34.2
0.0195
0.0260
32.3
29.4
0.0229
0.0277
48.87
50.78
60.78
58.87
85.07
101.06
12,352
12,356
58
Dt m
and obtain
eg
Fig. 6. Variation of the thermal efciency g at air conditions of different inlet tower
with time.
1 eNTUR1
1 R eNTUR1
13
Starting from Eq. (13), the relationship between e and g is discussed. The e and g can be derived by the following equations:
From heat balance by the water and air
14
L cpL
Dt awb
R
G cpH
Dt w
15
NTU
t w;in t w;out
KA
L cpL
Dt m
16
1
Dtm ln
L cpL
t w;in t w;out
KA
L cpL
G cpH t w;in tawb;in
1
tw;in tw;out
L cpL
G cpH
1
tw;in tawb;in
17
The combined with that the heat balance of water and air, the
heat transfer rate as well as the log mean temperature difference,
eliminate wet-bulb temperature tawb;out of leaving air from the cooling tower and was obtain:
1
ln
L cpL
t w;in t w;out
KA
L cpL
G cpH t w;in tawb;in
1
tw;in tw;out
L cpL
G cpH
1
tw;in t awb;in
18
Take the Eqs. (11), (15), (16) and (17) substitutes into the Eq.
(18) and was obtain:
ln
1Rg
NTU1 R
1g
19
1 eNTUR1
1 e1:3191:0691
0:5577:
NTUR1
1Re
1 1:069 e1:3191:0691
Comparing formula (11) and (20), we can see that the Merkel
method and the e-NTU method gives consistent results under the
same simplied assumption. When the inlet, outlet cooling water
and the air temperature are kept constant, cpL/cpH can be regarded
as a constant, then the thermal efciency is dependent on mass rate
of the water and the air as well as the number of heat transfer units.
When the temperature of the entering and leaving cooling water
and the air web bulb is kept constant, and the number of heat transfer units is also kept constant, then the thermal efciency was controlled by ratio of the mass rate of the water and the air. The
experiment of thermal efciency with function relations of the
water and the air ratio by Fisenko et al. [17,18] through the radius
of different water drop proved that the thermal efciency of the
pack is a nonlinear monotonically decreasing function of the relation of the specic mass ow rates of the water and the air, when
the cooling water and the air temperature condition is invariable.
5. Conclusions
(1) When the temperature of the entering and leaving cooling
water and the air wet-bulb is constant, the thermal efciency of the cooling tower were controlled by the mass rate
ratio of water and air. The larger the mass rate ratio of water
and air is, the lower the thermal efciency is, that is, the
evaporation rate of the moisture is small. When the air conditioning load is increased, it is needed to increase the air
mass rate to maintain the thermal efciency constant, therefore, the blower should have the device of frequency control.
(2) The water supply is approximately 2.53.0% of the volume of
overall circulates water during test process, and should be
adjustable along with different operating mode. When the
latent heat transfer process is predominated, certain water
supply needs to be maintained. If the dry bulb temperature
of the entering air is obviously lower than the entering water
temperature, and that the relative humidity is on the higher
side, the total heat transfer will be predominated by sensible
heat transfer, and water supply can be reduced accordingly.
(3) The serious lling clogs in cooling tower could signicantly
inuence the mass ow rate of the water and the air, as well
as process of the heat and the mass transfer.
(4) After detailed derivation and the calculation, it is derived
that both the e and the g are equal to 0.5577; this indicates
that the evaporative cooling efciency and the effectiveness
of the cooling tower are the same characteristics parameters
for the thermal performance of a cooling tower.
Acknowledgements
NTUR1
1e
1 R eNTUR1
20
32:3 29:4
Dt w
tw;in tw;out
NTU
32:3 29:4
1:319;
2:198
This research has been supported by public technological project (Contract No. SY2008343).The authors would like to thank
the Bureau of science and technology and information, Shenzhen,
for their contribution in project realization. The anonymous
reviewers are also appreciated for their comments.
References
[1] Ibrahim GA, Nabhan MBW, Anabtawi MZ. An investigation into a falling lm
type cooling tower. Int J Refrig 1995;18(8):55764.
59