AGENDA
Basic Codes for Design.
General Design Consideration of IS: 456-2000.
Steps for design of a multi-storied building.
Column Design
Design of Various Structural Component
Development Length
INTRODUCTION
Analysis & design of building depends on type of building, its
complexity, number of stories etc.
Structural system is finalized after thorough Study of
architectural drawings.
Choice of an appropriate structural system is important for its
economy and safety. There are two type of building
systems:(a) Load Bearing Masonry Buildings.
(b) RCC Framed Buildings.
Structural frame is finalized & sizes of structural members
are conveyed to the concerned architect.
For internal circulation of BSNL only
INTRODUCTION
Load Bearing Masonry Buildings
Low rise buildings with small spans generally constructed as
load bearing brick walls with RCC slab & beams.
Suitable for building up to four or less stories.
Adequate for vertical loads & also serves to resists
horizontal loads like wind & earthquake by box action.
Provisions of IS: 4326 e.g. providing horizontal RCC Bands
& vertical reinforcement in brick wall etc. need to be followed
to ensure safety against earthquake
Design to be done as per BIS code IS:1905
INTRODUCTION
RCC Framed Structures
RCC frames are provided in both principal directions
and
Loads are transmitted to ground through vertical framing
system i.e Beams, Columns and Foundations.
Effective in resisting both vertical & horizontal loads.
Brick walls are non load bearing filler walls only.
Suitable for multi-storied building as it is very effective
in resisting horizontal loads due to earthquake / wind.
INTRODUCTION
RCC Framed Structures
Before starting structural design of a RCC building, the
following information/ data are required:
(i) Set of architectural drawings;
(ii) Soil Investigation report
(iii) Location of the place or city in order to decide on
wind and seismic loadings
(iv) Data for lifts, water tank capacities on top, special
roof features or loadings, etc.
BASIS OF DESIGN
Aim Of Design
To design structures with appropriate degree of safety to
Perform satisfactorily during its intended life.
Sustain all loads/ deformations of normal construction & use
Have adequate durability & resistance to fire.
Method of Design
Structure and structural elements to be normally designed by
Limit State Method.
Working Stress Method may be used where Limit State
Method can not be conveniently adopted
For internal circulation of BSNL only
LOADS
DESIGN LOAD
Design load to be taken in appropriate method of design is
Characteristic load with appropriate partial safety factors for
limit state design
Characteristic load in case of working stress method
LOAD COMBINATIONS
BASIC LOAD CASES USED FOR ANALYSIS
No. Load case
Directions
1 DL
Downwards
2 IL(Imposed/Live load) Downwards
3 EXTP (+Torsion)
+X; Clockwise torsion due to EQ
4 EXTN (-Torsion)
+X; Anti-Clockwise torsion due to EQ
5 EZTP (+Torsion)
+Z; Clockwise torsion due to EQ
6 EZTN (-Torsion)
+Z; Anti-Clockwise torsion due to EQ
LOAD COMBINATIONS
LOAD COMBINATIONS
Grade of Concrete
Minimum Grade of Concrete
Steps of Design
Steps for Design of Multi-Storeyed
RCC Framed Buildings
Step1: Study of architectural Drawings
Step2: Finalization of Structural Configuration.
Step3: Preliminary Sizes of Structural members.
Step4: Load Calculation and
Step5: Analysis for various load combinations.
Step6: Design of various structural components for
most critical load combination.
Preliminary Sizes
Finalising Preliminary Sizes
Slab: Slab thickness is decided based on span/depth ratio.
Beam: Width of beam to be at least equal to width of wall
(230 or 300 mm). Larger beam width is helpful in placement
of reinforcement in one layer & for resisting shear & torsion.
- Depth of beam generally taken as 1/12th (for Heavy Loads)
to 1/15th (for Lighter Loads) of span.
Column: Size of column depends upon axial load &
moments from both directions and is finalized after
approximate calculations.
Loads
Types of Loads
Vertical Loads
Dead Load (Self Weight) Dl As per IS-875(part-1)
Imposed Load (Live Load) LL Or IL As per IS-875 (Part-2)
Snow Load
Horizontal Loads
Earthquake Load (Seismic) EQX & EQZ (As per IS-1893)
Wind Load WL As Per IS-875 (Part-3)
Special Loads & Load Combinations
kN/m3
PLAIN CONCRETE
24
REINFORCED CONCRETE
25
BRICK MASONRY
19-20
STONE MASONRY
21-27
TIMBER
6-10
CEMENT-PLASTER
21
LIME -PLASTER
18
STEEL
kN/m2
78.5
AC SHEET -ROOFING
0.16
GI SHEET -ROOFING
0.15
MANGLORE TILES
0.65
0.16-0.23
LIVE LOAD
(kN/m2)
6.0
6.0
MDF ROOM
10.0
WEATHER MAKER
12.0
1.5
0.75
Loads
Procedure for Vertical load calculation on Columns
Step(i): Transfer slab floor load (both LL & DL) to beams
using formulae for equivalent UDL as :Equivalent UDL on short span beam = w B/4
Equivalent UDL on long span beam = w B/4 x [2-(B/L)]
where w is the total load on slab panel in KN/Sqm &
L & B respectively are long span & short spans of slab
panel.
Loads
Procedure for Vertical load calculation on Columns
Step(ii): Add weight of wall (if any), self weight of beam etc.
to obtain load on beam (in running meter). Calculate
similarly for each beam
Step(iii): Transfer loads from beams to columns.
Step(iv):Repeat Step (i) to Step (iii) for each floor.
Step(v): Add for each column for all floors to get total load on
each column at footing level for entire building.
Loads
Procedure for Horizontal (Seismic) Load Calculation
Load Calculations for Seismic Load case is carried out as
per IS:1893-2002 clause 7.5.3.
The Seismic Shear at various floor levels is calculated for
the whole Building using the values from IS 1893-2002.
Design Seismic base shear is
Vb = Ah W
Where W= Seismic weight as per clause 7.4.2 (Full dead load
+ appropriate percentage of imposed load of building as
given in Table 8)
Load Calculation
Procedure for Horizontal (Seismic) Load Calculation :
Design Imposed Load for eq. Force Calculation
Table 8 (IS 1893)
Percentage of Imposed Load to be Considered
in Seismic Weight Calculation (Clause 7.3.1 )
Imposed Uniformity
Percentage of
Distributed Floor Load
Imposed Loads
( kN/ m2 )
(1)
(2)
Upto and including 3.0
25
Above 3.0
50
For internal circulation of BSNL only
Loads
Procedure for Horizontal (Seismic) Load Calculation
Ah = Design Horizontal acceleration spectrum value (cl. 6.4.2)
= (Z/2) (I/R) (Sa/g)
Where Z = Zone factor as per table 2 of IS 1893
I= Importance factor as per table 6 of IS-1893
= 1.5 (If the bldg. is T.E. Bldg.)
R = Response reduction factor as per table 7 of IS 1893
= 3.0 for OMRF or 5.0 for SMRF
(Sa/g) = Average response acceleration coefficient based on
soil type & natural periods and damping of structure. (Refer
Fig. 2 page 16 of IS 1893)
For internal circulation of BSNL only
Load Calculation
Procedure for Horizontal (Seismic) Load Calculation :
For calculating (Sa/g) value as above we have to calculate
T i.e. Fundamental Natural Time Period (in Seconds)
(Clause 7.6 of IS Code)
T = 0.075 h0.75 (For RC Frame building)
where h = Height of building in Meter
In case of RCC building with brick in fills walls.
T = 0.09 h / d where h = height of building in meter
& d = Base dimension of the building at plinth level in
meter along the considered direction of lateral force.
Load Calculation
Procedure for Horizontal (Seismic) Load Calculation :
Distribution of base shear (Clause 7.7 of IS 1893)
Distribution of total design base shear to different floor
levels along height of building is done using formula
Fi = w i h i 2 / (i=1 to n) w i h i 2 x Vb
Where Fi = Design lateral force at floor i
Wi = Seismic weight of floor i
hi = height of floor in m from base.
n = number of storyes in the building is equal to
number of levels at which masses are located.
Vb = Total Design base shear
For internal circulation of BSNL only
ANALYSIS OF STRUCTURE
VERTICAL LOAD ANALYSIS
a) GENERAL:
It is presumed that all joints of the frame are monolithic.
To simplify analysis, three dimensional multistoried R.C.C.
framed structure is considered as combination of planer
frames in two directions.
It is assumed that each of these planer frames act
independently of other frames.
ANALYSIS OF STRUCTURE
Vertical Load Analysis
Procedure for Frame analysis for calculation of moments
in Columns & beams:
Step(i): First, the load from slab is transferred to adjoining
beams using formula given below: For computation of Bending Moments in beams, equivalent
uniformly distributed load of beam is taken as
Equivalent UDL on short beam of slab panel = w B/3.0
Equivalent UDL on long beam of slab panel = w B/6 x [ 3-(B/L)2 ]
where w is the total load on the slab panel in KN/Sqm &
L & B are long span & short spans of slab respectively.
ANALYSIS OF STRUCTURE
Vertical Load Analysis
Procedure for Frame analysis for calculation of
moments in Columns & beams:
Step(ii): Over this load, weight of wall, self weight of beam
etc. are added to get load on beam (in running metre).
Step(iii): The load (in running Metre) on each beam is
calculated as in Step (i) & Step (ii).
Step(iv): Step (i) to Step (iii) is repeated for each floor
Step(v): Then these loads are used as u.d.l on a particular
frame for analysis by moment distribution method.
ANALYSIS OF STRUCTURE
METHOD OF ANALYSIS:
Analysis of large framed structures is too Cumbersome
with classical methods of structure analysis such as
Clapeyrons theorem of three moments,
Castingilianos therefore of least work,
Poisons method of virtual work etc.
Therefore, simpler methods are mostly followed in 2-D
manual analysis of structures. These are
Hardy cross method of moment distribution.
Kanis method of iteration.
ANALYSIS OF STRUCTURE
Horizontal Load Analysis
Frame analysis for horizontal loads calculated in step 4
may be carried out by using Approximate Methods:(i) Cantilever method.
(ii) Portal method.
Approximate methods are used for preliminary designs
only.
For final design exact methods are used which are
(i) Slope deflection or matrix methods
(ii) Factor method.
Design of Columns
Design of Columns
Design of Columns
Column
A compression member, the effective length > three times
the least lateral dimension.
Short and Slender Compression Members
When both slenderness ratios lex/D and ley/b are <12
Design of Columns
Design Of Columns Important Considerations
(ii) Unsupported Length
In beam-slab construction, it is the clear distance between the floor &
under side of shallower beam framing into columns in each direction at
next higher floor level.
Design of Columns
Design Of Columns Design Approach
The design of column is complex as it is subjected to axial
loads & moments which may very independently.
Column design requires
Determination of the cross sectional dimension.
The area of longitudinal steel & its distribution.
Transverse steel.
The maximum axial load & moments acting along the length
of column are considered for design of the column section.
The transverse reinforcement is provided to impart effective
lateral support against buckling to every longitudinal bar.
Design of Columns
Design Of Columns Reinforcement Provisions as per
IS:456A. Longitudinal reinforcement
Area of longitudinal reinforcement shall be not less than
0.8% nor more than 6% of cross sectional area of the
column.
However maximum area of steel should not exceed 4% to
avoid practical difficulties in placing & compacting concrete.
In pedestals, in which the longitudinal reinf. is not taken into
account in strength calculations, nominal reinforcement
should be not be less than 0.15% of cross sectional area.
Minimum dia of longitudinal bar should be 12 mm
For internal circulation of BSNL only
Design of Columns
Design Of Columns Reinforcement Provisions as per
IS:456
A. Longitudinal reinforcement
Spacing between bars < 300mm along periphery of column
The minimum number of bars shall be four in rectangular
columns & six in circular columns.
B. Transverse reinforcement (STIRRUPS)
Diameter of lateral ties should not be less than 1/4th of dia of the
largest longitudinal bar & in no case should be less than 6 mm.
Spacing of lateral ties should not > least of the following:Least lateral dimension of the column.
16 times the smallest diameter of longitudinal bars to be tied.
300 mm.
For internal circulation of BSNL only
SLAB DESIGN
TYPES OF SLABS
Based on Ratio of long span to short span
One way slab Long span (ly)/Short span (lx ) > 2
Two way slab Long span (ly)/Short span (lx ) < 2
Based on Edge Conditions
Simply supported
Restrained Edge Conditions of supporting edge
Cantilever
For internal circulation of BSNL only
SLAB DESIGN
The design of floor slab is carried out as per
Clause 24.4 &
Clause 37.1.2 & Annexure D of IS:456-2000 .
The Bending moment coefficients are taken from
Table- 26 or
Table 27 of BIS code
depending on support conditions
Bending moment is calculated & reinforcement
steel is obtained from charts given in SP-16.
Effective span
Lesser of (i) clear
span + effective
depth of slab, &
(ii) centre to
centre of
supports
Do
Effective span
Support condition
Effective span
Cantilever span
Frames
Centre to centre
distance
SLAB DESIGN
Steps for Design of Slabs
Step 1: Selection of preliminary depth of slab
Step 2: Calculate design loads, bending moments
Step 3: Determination/checking of the effective and
total depths of slabs
Step 4: Determination of areas of steel
Step 5: Selection of diameter & spacing of
reinforcing bars
BEAM DESIGN
26.5.1.1 Tension reinforcement
a) Minimum reinforcement As = 0.85
bd
fy
where
AS =minimum area of tension reinforcement
b =breadth of beam or the breadth of the web
d =effective depth of T-beam
fy =characteristic strength of reinforcement in N/mm2 &
b) Maximum reinforcement - The maximum area of
tension reinforcement not to exceed 0.04 bD.
For internal circulation of BSNL only
BEAM DESIGN
Compression reinforcement
The maximum area of compression reinforcement
not to exceed 0.04 bD
Side face reinforcement
Where depth of web in a beam >750 mm, side face
reinf is to be provided along the two faces. The total
area of such reinf. should not < 0.1 percent of web area
and shall be
distributed equally on two faces at a spacing not >
300 mm or web thickness whichever is less.
For internal circulation of BSNL only
BEAM DESIGN
Minimum shear reinforcement (Clause 26.5.1.6)
Minimum shear reinforcement in the form of stirrups shall
be provided such that:
Asv
=
0.4
bsv
0.87fy
Maximum spacing of shear reinforcement (Clause 26.5.1.5)
The maximum spacing of shear reinforcement measured
along axis of member shall be < 0.75 d for vertical
stirrups and d for inclined stirrups at 45 degrees.
In no case shall the spacing to be >300 mm.
FOUNDATION DESIGN
Design of Foundations Important Considerations
Foundations transfer loads from the building or individual
columns to earth. Foundations must be designed to
prevent
Structural Failure
Shear failure of soil
Excessive settlement &
To minimize differential settlement
FOUNDATION DESIGN
Design of Foundations Important Considerations
To determine area required for proper transfer of total
load on the soil, the total load (the combination of dead,
live and any other load without multiplying it with any load
factor) need to be considered.
Total Load including Self Weight of footing
FOUNDATION DESIGN
Design of Foundations Important Considerations
Bending Moment (Reference Clauses- 34.2.3.1 & 34.2.3.2)
The critical section for bending Moment is considered
at the face of column, Pedestal or wall.
Shear (Reference Clause 33.2.4.1)
The critical section for one way shear is at the vertical
section located at a distance equal to the effective
depth (d) from the face of the column, pedestal or wall
of the footing in case of footings on soils.
FOUNDATION DESIGN
Design of Foundations Important Considerations
For one way action
For one way shear action, the nominal shear stress is
calculated as follows:Vu
v =
------b.d
Where
v = Shear stress, Vu = Factored vertical shear force
b = Breadth of critical section, d = Effective depth
v < c ( c = Design Shear Strength of concrete based on % of
longitudinal tensile reinforcement refer Table 61 of SP-16)
For internal circulation of BSNL only
FOUNDATION DESIGN
Design of Foundations Important Considerations
For Two Way Action (Punching shear )
Critical section for punching shear is at d/2 from the face of
column or pedastal
For two way shear action, the nominal shear stress is calculated
in accordance with clause 31.6.2 of the code as follows:Vu
v
=
---------b0.d
Where
b0
=
Periphery of the critical section
FOUNDATION DESIGN
Design of Foundations Important Considerations
Development Length (Reference Clause 34.2.4.3)
The critical section for checking the development length in a
footing shall be assumed at the same planes as those
described for bending moment in clause 34.2.3 of code and
also at all other vertical planes where abrupt changes of
section occur.
Reinforcement
Minimum % of steel in footing slab should be 0.12% &
Maximum spacing should not be more than 3 times
effective depth or 300mm which ever is less.
For internal circulation of BSNL only
DETAILING
Reinforcing steel of same type and grade shall be
used as main reinforcement in a structural member.
Simultaneous use of two different types or grades of
steel for main and secondary reinforcement is
permissible.
The calculated tension or compression in any bar at
any section shall be developed on each side of the
section by an appropriate development length or end
anchorage or by a combination thereof.
Development Length
Development Length of Bars
Ld = st /4bd,
= nominal diameter of bar, bd = design bond stress
st = stress in bar at the section considered at design load
Design bond stress in limit state method for plain bars in
tension is given in clause 26.2.1.1
For deformed bars conforming to IS 1786 these values
are to be increased by 60 %.
For bars in compression, the values of bond stress for
bars in tension is to be increased by 25 percent
Development Length