ASHRAE Class 1 Standard

Class 1: Typically a data center with tightly


controlled environmental parameters and
mission critical operations
R
Recommended
d dT
Temperature:
t
18 27oC
Recommended Humidity: 60%RH
Max rate of change: 5oC/h
Max dew point: 15oC
Measure at 1.5m above the floor (TIA-942)

Cold/Hot Aisle Arrangement

Room measured point

Measured point:
1.5m above floor
<= 27oC, 60%RH

~29OC 45%RH

CITEC

Equipment

DOWNFLOW

Rack

UNIT

~22
22OC 70%RH