Tray-type deaerator
The typical horizontal tray-type deaerator has a vertical
domed deaerator section mounted above a horizontal
boiler feed water storage vessel. Boiler feed water
enters the vertical deaerator section above the
perforated trays and flows downward through the
perforations. Low-pressure deaerator steam enters
below the perforated trays and flows upward through
the perforations. Some designs use various types of
packed bed, rather than perforated trays, to provide
good contact and mixing between the steam and the
boiler feed water.
The steam strips the dissolved gas from the boiler feed
water and exits via the vent valve at the top of the
domed section. Should this vent valve not be opened
sufficiently the deaerator will not work properly, causing
high oxygen content in the feed water going to the
boilers. Should the boiler not have an oxygen content
Deaerator 3
Spray-type deaerator
The typical spray-type deaerator is a horizontal vessel
which has a preheating section (E) and a deaeration
section (F). The two sections are separated by a baffle
(C). Low-pressure steam enters the vessel through a
sparger in the bottom of the vessel.