General Data
Introduction
Personnel safety with miniature circuit-breakers
According to DIN VDE 0100 Part 410, in order to protect against dangerous leakage currents in the TN system, the cross-sections of the
conductor, or its distance from the protective device, must be
dimensioned such that if a fault with negligible impedance (i.e. shortcircuit) occurs at any point between a phase conductor and a PE
conductor, or a connected exposed conductive part, the device
automatically trips within the specified times of 0.4 s / 5 s.
3
4
1
2
Characteristic A
Characteristic B
Characteristic C
Characteristic D
ta 0.4 s
5 s
ta 0.4 s
5 s
ta 0.4 s
5 s
ta 0.4 s
5 s
0.3
0.5
1.0
--76.6
--76.6
----
----
76.6
46
23
153
92
46
--15.3
-92
46
1.6
2
3
47.9
38.3
25.5
47.9
38.3
25.5
----
----
14.4
11.5
7.7
28.8
23
15.4
9.6
7.6
5.1
28.8
23
15.4
4
6
8
19.1
12.7
--
19.1
12.7
--
-7.6
--
-7.6
--
5.8
3.8
2.8
11.6
7.6
5.7
3.8
2.5
1.9
11.6
7.6
5.7
10
13
16
7.6
-4.7
7.6
-4.7
4.6
-2.9
4.6
3.57
2.9
2.3
1.7
1.4
4.6
3.4
2.8
1.1
0.9
0.7
4.6
3.4
2.8
20
25
32
3.8
3.0
2.4
3.8
3.0
2.4
2.3
1.8
1.4
2.3
1.8
1.4
1.1
0.9
0.7
2.2
1.8
1.4
0.5
0.4
0.3
2.2
1.8
1.4
40
50
1.9
--
1.9
--
1.1
0.9
1.1
0.9
0.6
0.5
1.2
1.0
0.28
0.23
1.2
1.0
63
80
100
----
----
0.7
---
0.7
---
0.4
0.3
0.2
0.8
0.6
0.4
0.2
0.14
0.1
0.8
0.6
0.4
125
--
--
--
--
0.16
0.3
0.1
0.3
5SY, 5SP
5
6
7
8
9
10
11
12
13
14
15
16
17
Siemens ET B1 T 2007
3/19