Outdoor Units
JOSI-DAX012-N11
JOAU-DLY012-H11
JOSI-DAX018-N11
JOAU-DLY018-H11
JOSI-DBC012-N11
JOSI-DCD012-N11
JOSI-DBC018-N11
JOSI-DCD018-N11
JOSI-DBF018-N11
JOSI-DBC024-N11
JOSI-DCD024-N11
JOSI-DBF024-N11
JOAU-DLY024-H11
JOSI-DBC030-N11
JOSI-DCD030-N11
JOSI-DBF030-N11
JOAU-DLY030-H11
JOSI-DBC036-N11
JOSI-DCD036-N11
JOSI-DBF036-N11
JOSI-DBC048-N11
JOSI-DCD048-N11
JOSI-DBF048-N11
REFRIGERANT
REFRIGERANT
JOAU-DLY036-H13
JOAU-DLY048-H13
JOAU-DLY060-H13
JOSI-DCD060-N11
R410A
JOAU-DLY036-H11
HEATPUMP
March 2016
Contents
The specifications, designs, and information in this book are subject to change without notice for
product improvement.
Contents
General Information
Part 1
General Information
1. Model Lists ..................................................................................2
2. External Appearance .................................................................3
2.1 Indoor Units .................................................................................................. 3
2.2 Outdoor Units................................................................................................ 4
General Information
Model Lists
1. Model Lists
1.1 Indoor Units
R410A (capacity multiplied by 1000Btu/h)
Type
Function
Duct
Ceiling-floor
12
18
24
30
36
48
Ceiling-floor(Wine Cellar)
Cooling
Four-way cassette(compact)
Console
60
Compressor type
Compressor Brand
JOAU-DLY012-H11
Rotary
GMCC
JOSI-DBC012-N11
JOSI-DCD012-N11
JOSI-DAX012-N11
JOAU-DLY018-H11
Rotary
GMCC
JOAU-DLY024-H11
Twin-rotary
GMCC
JOAU-DLY030-H11
Twin-rotary
GMCC
JOAU-DLY036-H11
Twin-rotary
Mitsubishi
JOAU-DLY036-H13
Twin-rotary
Mitsubishi
JOAU-DLY048-H13
Twin-rotary
Mitsubishi
JOAU-DLY060-H13
Twin-rotary
Mitsubishi
JOSI-DBC018-N11
JOSI-DCD018-N11
JOSI-DBF018-N11
JOSI-DAX018-N11
JOSI-DBC024-N11
JOSI-DCD024-N11
JOSI-DBF024-N11
JOSI-DCD030-N11
JOSI-DBC030-N11
JOSI-DBF030-N11
JOSI-DBC036-N11
JOSI-DCD036-N11
JOSI-DBF036-N11
JOSI-DCD048-N11
JOSI-DBF048-N11
JOSI-DBC048-N11
JOSI-DCD060-N11
General Information
External Appearance
2. External Appearance
2.1 Indoor Units
Super slim cassette
Compact Four-way cassette
Ceiling-Floor
Console
Duct(12000-48000Btu/h)
Duct(60000Btu/h)
General Information
External Appearance
General Information
Product specification
3. Product specification
Model Indoor Unit
JOSI-DBC012-N11
JOAU-DLY012-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
3.5
3.5
Pdesign
kW
3.5
3.5
W/W
5.6
3.8
A+
SEER/EER /SCOP/COP
(2)
Average
kWh
219
1289
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
V/Ph/Hz
H/M/L
RPM
700/580/500
700/580/500
H/M/L
m3/hr
650/530/450
650/530/450
Min-Max
Pa
H/M/L
dB(A)
55
H/M/L
dB(A)
42/38/34
l/hr
1.5
Moisture removal
INDOOR
16
Centrifugal fan x1
mm
OD25
WxHxD
mm
570x260x570
kg
16
LxWxH
mm
655x655x290
kg
19
WxHxD
mm
647x50x647
kg
2.5
LxWxH
mm
715x715x123
kg
4.5
units
7levels
Refrigerant control
Capillary +EXV
Rotary DC Inverter
Axial x 1
Fan speeds
H/L
RPM
850
Air flow
H/L
m3/hr
2200
H/L
dB(A)
62
220-240V/Single/50Hz
(5)
Dimensions
H/L
dB(A)
52
WxHxD
mm
760x590x285
kg
35.4
LxWxH
mm
887x355x645
Weight
Package dimensions
Packaged weight
Stacking height
kg
37.9
units
4 levels
Refrigerant type
R410A
General Information
kg(5m)
1.1
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
3/8"(9.52)
Max.tubing length
m.
Max.20
Max.height difference
m.
Max.10
Remote control
Product specification
JOSI-DAX012-N11
JOAU-DLY012-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
3.5
3.6
Pdesign
kW
3.5
3.5
W/W
6.1
3.8
SEER /SCOP
(2)
Average
A++
kWh
201
1290
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
16
Centrifugal fan x1
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
810/780/680/530
700/640/560/440
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
58
H/M/L
dB(A)
44 / 40 /36
l/hr
1.5
mm
OD16
mm
700x600x210
kg
15
mm
810x305x710
kg
20
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
8 levels
Capillary +EXV
Rotary DC Inverter
OUTDOOR
700/640/560/440
Moisture removal
Dimensions
Axial x 1
Fan speeds
H/L
RPM
850
Air flow
H/L
m3/hr
2200
H/L
dB(A)
62
H/L
dB(A)
52
WxHxD
mm
760x590x285
kg
35.4
mm
887x355x645
kg
37.9
units
4 levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.1
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
3/8"(9.52)
Max.tubing length
m.
Max.20
Max.height difference
m.
Max.10
810/780/680/530
Remote control
General Information
Product specification
JOSI-DCD012-N11
JOAU-DLY012-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
3.5
3.8
Pdesign
kW
3.5
3.4
W/W
5.1
3.8
kWh
240.1960784
1252.631579
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER/EER /SCOP/COP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
16
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1200/1070/900
1200/1070/900
560/440/410
560/440/410
H/M/L
m3/hr
Min-Max
Pa
25(0~40)
H/M/L
dB(A)
58
H/M/L
dB(A)
41/39/36
Moisture removal
l/hr
1.5
mm
OD25
mm
700x210x635
kg
18
mm
915x655x290
kg
22.8
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Rotary DC Inverter
OUTDOOR
Average
Axial x 1
Fan speeds
H/L
RPM
850
Air flow
H/L
m3/hr
2200
H/L
dB(A)
62
H/L
dB(A)
52
WxHxD
mm
760x590x285
kg
35.4
mm
887x355x645
kg
37.9
units
4 levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.1
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
3/8"(9.52)
Max.tubing length
m.
Max.20
Max.height difference
m.
Max.10
General Information
Product specification
JOSI-DBC018-N11
JOAU-DLY018-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
5.3
Pdesign
kW
5.3
W/W
5.6
3.8
A+
kWh
313
1953
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER/EER /SCOP/COP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+16
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
820/670/500
800/650/500
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
60
H/M/L
dB(A)
48/40/33
800/650/500
l/hr
2.0
mm
OD25
mm
570x260x570
kg
16.5
mm
655x655x290
kg
19
mm
647x50x647
kg
2.5
mm
715x715x123
kg
4.5
Dimensions
WxHxD
Weight
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Rotary DC Inverter
OUTDOOR
820/670/500
Moisture removal
Package dimensions
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
2500
H/L
dB(A)
65
H/L
dB(A)
55
WxHxD
mm
845x700x320
kg
46
mm
965x395x755
kg
50
units
3levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.8
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
1/2"(12.7)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.20
Average
Remote control
General Information
Product specification
JOSI-DAX018-N11
JOAU-DLY018-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
4.7
Pdesign
kW
4.7
W/W
5.6
3.8
A+
kWh
294
1842
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER /SCOP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+16
Centrifugal fan x1
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
900/850/780/700
740/700/640/560
900/850/780/700
H/M/L
m3/hr
Min-Max
Pa
740/700/640/560
H/M/L
dB(A)
60
H/M/L
dB(A)
45/ 42 /39
Moisture removal
l/hr
2.0
mm
OD16
mm
700x600x210
kg
15
mm
810x305x710
kg
20
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
8 levels
Capillary +EXV
Rotary DC Inverter
OUTDOOR
Average
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
2500
H/L
dB(A)
65
H/L
dB(A)
55
WxHxD
mm
845x700x320
kg
46
mm
965x395x755
kg
50
units
3levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.8
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
1/2"(12.7)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.20
General Information
Remote control
Product specification
JOSI-DBF018-N11
JOAU-DLY018-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
5.3
5.9
Pdesign
kW
5.3
5.3
W/W
6.1
3.8
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
304
1953
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+16
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
950/850/750
900/750/600
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
60
H/M/L
dB(A)
44/41/38
l/hr
2.0
mm
OD25
mm
1068x235x675
kg
25
mm
1145x755x313
kg
31.5
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Rotary DC Inverter
OUTDOOR
900/750/600
Moisture removal
Dimensions
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
2500
H/L
dB(A)
65
H/L
dB(A)
55
WxHxD
mm
845x700x320
kg
46
mm
965x395x755
kg
50
units
3levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.8
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
1/2"(12.7)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.20
10
950/850/750
Remote control
General Information
Product specification
JOSI-DCD018-N11
JOAU-DLY018-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
5.3
5.6
Pdesign
kW
5.3
5.1
W/W
6.4
3.8
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
290
1879
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+16
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1030/880/800
1030/880/800
1250/950/800
1250/950/800
H/M/L
m3/hr
Min-Max
Pa
25(0-60)
H/M/L
dB(A)
58
H/M/L
dB(A)
45/43/39
Moisture removal
l/hr
2.0
mm
OD25
mm
920x270x635
kg
28
mm
1135x655x350
kg
31.5
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Compressor type. model
Rotary DC Inverter
OUTDOOR
6levels
Capillary +EXV
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
2500
H/L
dB(A)
65
H/L
dB(A)
55
WxHxD
mm
845x700x320
kg
46
mm
965x395x755
kg
50
units
3levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
1.8
gr / 1m
15
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
1/2"(12.7)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.20
General Information
11
Product specification
JOSI-DBC024-N11
JOAU-DLY024-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
7.2
Pdesign
kW
7.2
7.8
W/W
6.1
3.9
Average
A++
kWh
413
2800
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+20
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
700/600/450
1780/1560/1360
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
62
H/M/L
dB(A)
47 / 45 /42
l/hr
2.5
mm
OD32
mm
840x245x840
kg
24
mm
900x900x265
kg
28
mm
950x55x950
kg
mm
1035x1035x90
kg
Dimensions
WxHxD
Weight
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
1780/1560/1360
Moisture removal
Package dimensions
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
3500
H/L
dB(A)
69
H/L
dB(A)
57
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.2
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
12
700/600/450
Remote control
General Information
Product specification
JOSI-DBF024-N11
JOAU-DLY024-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
7.2
7.8
Pdesign
kW
7.2
7.8
W/W
6.4
3.9
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
394
2800
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+20
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1200/1080/890
1400/1250/1100
H/M/L
m3/hr
Min-Max
Pa
1400/1250/1100
H/M/L
dB(A)
63
H/M/L
dB(A)
52/50/46
Moisture removal
l/hr
2.3
mm
OD25
mm
1068x235x675
kg
25
mm
1145x755x313
kg
30
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
1200/1080/890
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
3500
H/L
dB(A)
69
H/L
dB(A)
57
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.2
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
General Information
Remote control
13
Product specification
JOSI-DCD024-N11
JOAU-DLY024-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
7.8
Pdesign
kW
7.8
W/W
6.6
3.8
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
371
2874
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+20
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1030/880/800
1030/880/800
1250/950/800
1250/950/800
H/M/L
m3/hr
Min-Max
Pa
25(0-80)
H/M/L
dB(A)
63
H/M/L
dB(A)
46/43/39
Moisture removal
l/hr
2.3
mm
OD25
mm
920x270x635
kg
28
mm
1135x655x350
kg
31.5
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Compressor type. model
Twin-rotary DC Inverter
OUTDOOR
Axial x 1
Fan speeds
H/L
RPM
800
Air flow
H/L
m3/hr
3500
H/L
dB(A)
69
H/L
dB(A)
57
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.2
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
14
6levels
Capillary +EXV
General Information
Product specification
JOSI-DBC030-N11
JOAU-DLY030-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
8.5
8.6
Pdesign
kW
8.5
8.1
W/W
6.4
3.9
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
465
2908
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
720/630/560
1850/1600/1400
H/M/L
m3/hr
Min-Max
Pa
1850/1600/1400
H/M/L
dB(A)
62
H/M/L
dB(A)
50 / 47 / 44
Moisture removal
l/hr
3.0
mm
OD32
mm
840x245x840
kg
26.5
mm
900x900x265
kg
30.5
mm
950x55x950
kg
mm
1035x1035x90
kg
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
720/630/560
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
3800
H/L
dB(A)
70
H/L
dB(A)
58
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.45
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
General Information
Remote control
15
Product specification
JOSI-DBF030-N11
JOAU-DLY030-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
8.5
Pdesign
kW
8.5
8.5
W/W
6.4
3.9
Average
A++
kWh
465
3051
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x3
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1300/1150/1000
1850/1650/1450
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
64
H/M/L
dB(A)
53/50/46
l/hr
2.5
mm
OD25
mm
1285x235x675
kg
30
mm
1360x755x313
kg
35
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
1850/1650/1450
Moisture removal
Dimensions
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
3800
H/L
dB(A)
70
H/L
dB(A)
58
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.45
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
16
1300/1150/1000
Remote control
General Information
Product specification
JOSI-DCD030-N11
JOAU-DLY030-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
8.3
9.2
Pdesign
kW
8.3
8.5
W/W
6.3
3.8
SEER/EER /SCOP/COP
(2)
Average
A++
kWh
461
3132
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1150/1000/860
1150/1000/860
1990/1580/1140
1990/1580/1140
H/M/L
m3/hr
Min-Max
Pa
37(0~80)
H/M/L
dB(A)
65
H/M/L
dB(A)
48/44/40
Moisture removal
l/hr
2.5
mm
OD25
mm
1140x270x775
kg
35
mm
1355x795x350
kg
42
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Compressor type. model
Twin-rotary DC Inverter
OUTDOOR
6levels
Capillary +EXV
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
3800
H/L
dB(A)
70
H/L
dB(A)
58
WxHxD
mm
900x860x315
kg
59
mm
1043x395x915
kg
63
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.45
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
50
Max.height difference
m.
25
General Information
17
Product specification
JOSI-DBC036-N11
JOAU-DLY036-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
10
10.5
Pdesign
kW
10
10
W/W
5.4
3.8
kWh
648
3684
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER/EER /SCOP/COP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
720/630/560
1850/1600/1400
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
63
H/M/L
dB(A)
51/49/46
1850/1600/1400
l/hr
3.8
mm
OD32
mm
840x245x840
kg
26.5
mm
900x900x265
kg
30.5
mm
950x55x950
kg
mm
1035x1035x90
kg
Dimensions
WxHxD
Weight
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
720/630/560
Moisture removal
Package dimensions
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
73
mm
1120x435x1100
kg
83
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.75
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
18
Average
Remote control
General Information
Product specification
JOSI-DBF036-N11
JOAU-DLY036-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
10.5
11
Pdesign
kW
10.5
10.2
W/W
3.8
A+
kWh
613
3758
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x4
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1200/1050/850
1200/1050/850
2200/1850/1500
H/M/L
m3/hr
Min-Max
Pa
2200/1850/1500
H/M/L
dB(A)
65
H/M/L
dB(A)
52 / 49 /43
Moisture removal
l/hr
3.5
mm
OD25
mm
1650x235x675
kg
40
mm
1725x755x313
kg
46
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
Average
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
73
mm
1120x435x1100
kg
83
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.75
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
General Information
Remote control
19
Product specification
JOSI-DCD036-N11
JOAU-DLY036-H11
Flared
Heating
Units
Cooling
Capacity (1)
kW
10
11
Pdesign
kW
10
10.2
W/W
5.3
3.8
kWh
660
3758
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
220-240V/Single/50Hz
10+30
Centrifugal fan x3
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
960/880/800
960/880/800
1740/1560/1180
1740/1560/1180
H/M/L
m3/hr
Min-Max
Pa
37(0~80)
H/M/L
dB(A)
62
H/M/L
dB(A)
42/39/36
Moisture removal
l/hr
3.5
mm
OD25
mm
1200x300x865
kg
44
mm
1385x920x373
kg
52.5
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Twin-rotary DC Inverter
OUTDOOR
6levels
Capillary +EXV
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
73
mm
1120x435x1100
kg
83
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
2.75
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
20
Average
General Information
Product specification
JOSI-DBC036-N11
JOAU-DLY036-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
10
10.5
Pdesign
kW
10
10
W/W
5.4
3.8
kWh
648
3684
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER/EER /SCOP/COP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+20
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
720/630/560
720/630/560
1850/1600/1400
H/M/L
m3/hr
Min-Max
Pa
1850/1600/1400
H/M/L
dB(A)
63
H/M/L
dB(A)
51/49/46
Moisture removal
l/hr
3.8
mm
OD32
mm
840x245x840
kg
26.5
mm
900x900x265
kg
30.5
mm
950x55x950
kg
mm
1035x1035x90
kg
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
Average
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
77
mm
1120x435x1100
kg
88
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
General Information
Remote control
21
Product specification
JOSI-DBF036-N11
JOAU-DLY036-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
10.2
11
Pdesign
kW
10.2
10
W/W
5.7
3.8
A+
kWh
626
3684
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
SEER/EER /SCOP/COP
(2)
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+20
Centrifugal fan x4
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1200/1050/850
2200/1850/1500
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
65
H/M/L
dB(A)
52 / 49 /43
2200/1850/1500
l/hr
3.5
mm
OD25
mm
1650x235x675
kg
40
mm
1725x755x313
kg
46
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
1200/1050/850
Moisture removal
Dimensions
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
77
mm
1120x435x1100
kg
88
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
22
Average
Remote control
General Information
Product specification
JOSI-DCD036-N11
JOAU-DLY036-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
10.2
11
Pdesign
kW
10.2
10.2
W/W
5.1
3.8
kWh
700
3758
Tbiv
oC
N/A
-7
Tol
oC
N/A
-15
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+20
Centrifugal fan x3
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
960/880/800
960/880/800
1740/1560/1180
1740/1560/1180
H/M/L
m3/hr
Min-Max
Pa
37(0~80)
H/M/L
dB(A)
62
H/M/L
dB(A)
42/39/36
Moisture removal
l/hr
3.5
mm
OD25
mm
1200x300x865
kg
44
mm
1385x920x373
kg
52.5
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
Average
Axial x 1
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
60
WxHxD
mm
990x965x345
kg
77
mm
1120x435x1100
kg
88
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
General Information
23
Product specification
JOSI-DBC048-N11
JOAU-DLY048-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
12.5
13
Pdesign
kW
W/W
3.21
3.61
SEER/EER /SCOP/COP
(2)
Average
kWh
Tbiv
oC
Tol
oC
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+25
Centrifugal fan x1
Fan speeds
Air flow
(3)
INDOOR
(5)
H/M/L
RPM
770/610/540
2200/1800/1600
H/M/L
m3/hr
Min-Max
Pa
H/M/L
dB(A)
64
H/M/L
dB(A)
54/50/47
l/hr
4.5
mm
OD32
mm
840x245x840
kg
29
mm
900x900x292
kg
33
mm
950x55x950
kg
mm
1035x1035x90
kg
Dimensions
WxHxD
Weight
LxWxH
Packaged weight
Frame outline dimensions
WxHxD
Frame Weight
Frame package dimensions
LxWxH
units
Refrigerant control
7levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
2200/1800/1600
Moisture removal
Package dimensions
Axial x 2
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
61
WxHxD
mm
938x1369x392
kg
102.5
mm
1095x495x1505
kg
116
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
4.35
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
24
770/610/540
Remote control
General Information
Product specification
JOSI-DBF048-N11
JOAU-DLY048-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
14
14.6
Pdesign
kW
W/W
3.21
3.61
SEER/EER /SCOP/COP
(2)
Average
kWh
Tbiv
oC
Tol
oC
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+25
Centrifugal fan x4
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1320/1200/1120
2300/1900/1700
H/M/L
m3/hr
Min-Max
Pa
2300/1900/1700
H/M/L
dB(A)
68
H/M/L
dB(A)
57/54/51
Moisture removal
l/hr
4.5
mm
OD25
mm
1650x235x675
kg
40
mm
1725x755x313
kg
46
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
6levels
Capillary +EXV
Twin-rotary DC Inverter
OUTDOOR
1320/1200/1120
Axial x 2
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
61
WxHxD
mm
938x1369x392
kg
102.5
mm
1095x495x1505
kg
116
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
4.35
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
General Information
Remote control
25
Product specification
JOSI-DCD048-N11
JOAU-DLY048-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
14
17
Pdesign
kW
W/W
3.21
3.72
SEER/EER /SCOP/COP
(2)
Average
kWh
Tbiv
oC
Tol
oC
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+25
Centrifugal fan x3
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1120/1100/1020
1120/1100/1020
2410/1640/1300
2410/1640/1300
H/M/L
m3/hr
Min-Max
Pa
50(0~100)
H/M/L
dB(A)
62
H/M/L
dB(A)
42/39/36
Moisture removal
l/hr
4.5
mm
OD25
mm
1200x300x865
kg
44
mm
1385x920x373
kg
53
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Compressor type. model
Twin-rotary DC Inverter
OUTDOOR
Axial x 2
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7200
H/L
dB(A)
70
H/L
dB(A)
61
WxHxD
mm
938x1369x392
kg
102.5
mm
1095x495x1505
kg
116
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
4.35
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
65
Max.height difference
m.
30
26
6levels
Capillary +EXV
General Information
Product specification
JOSI-DCD060-N11
JOAU-DLY060-H13
Flared
Heating
Units
Cooling
Capacity (1)
kW
16
19.5
Pdesign
kW
W/W
3.22
3.62
SEER/EER /SCOP/COP
(2)
Average
kWh
Tbiv
oC
Tol
oC
Power supply
Circuit breaker rating
V/Ph/Hz
380-420V/Three-phase/50Hz
10+25
Centrifugal fan x2
Fan speeds
Air flow
(3)
(5)
H/M/L
RPM
1070/920/820
1070/920/820
3010/2410/1940
3010/2410/1940
H/M/L
m3/hr
Min-Max
Pa
50(0~200)
H/M/L
dB(A)
67
H/M/L
dB(A)
57/54/51
Moisture removal
l/hr
5.0
mm
0D25
mm
1400x440x858
kg
75
mm
1590x895x470
kg
83
Dimensions
WxHxD
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
units
Refrigerant control
Compressor type. model
Twin-rotary DC Inverter
OUTDOOR
6levels
Capillary +EXV
Axial x 2
Fan speeds
H/L
RPM
860
Air flow
H/L
m3/hr
7500
H/L
dB(A)
70
H/L
dB(A)
61
WxHxD
mm
938x1369x392
kg
102.5
mm
1095x495x1505
kg
116
units
2levels
Dimensions
Weight
Package dimensions
LxWxH
Packaged weight
Stacking height
Refrigerant type
R410A
kg(5m)
4.8
gr / 1m
30
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
3/4"(19)
Max.tubing length
m.
65
Max.height difference
m.
30
General Information
27
Features
4. Features
4.1. To meet Europe A level, actual EER/COP of new product with BLDC motors of indoor & outdoor unit and
DC compressor will be higher than 3.4.
4.2. Low ambient kit is standard for outdoor units
4.3. Network control function is standard for the indoor units.
4.4. Standard auto restart function and follow me function.
4.5. Slim cassette with standard remote controller, wire controller and CCM for optional. Med Duct and
HESP duct with standard wired controller, remote controller and CCM for optional.
4.6. Standard anti-cold air function.
4.7. Standard auto defrosting function.
4.8. Standard self-diagnose function.
4.9. Standard timer function and sleep mode function controlled by controller.
28
General Information
Indoor Units
Part 2
Indoor Units
Super Slim Cassette Type ..................................................30
Duct Type .............................................................................50
Ceiling & Floor Type ...........................................................89
Four-way Cassette Type (Compact) ................................108
Console Type .....................................................................121
Indoor Units
29
Indoor Units
30
Indoor Units
Features
1. Features
1.1 Fresh air intake function
Fresh air fulfills air quality more healthy and comfortable.
Ventilation motor is optional to increase the effect of fresh air.
New air-intake
1.2
Ionizer generator
connector
Ventilation motor
connector
Indoor Units
31
Features
1.3
1.4
Built-in draining pump
Due to the improvement of structure, more convenient to repair or replace the draining pump.
Draining Pump
32
Built-in draining pump to make sure condensed water drain out reliably.
Indoor Units
Features
1.5
Terminals for alarm lamp and long-distance on-off controller connection are
standard
Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human
control.
Alarm lamp
Long-distance on-off controller
1.6
Twins Combination(24~30K)
The units can be installed as Twin systems: one outdoor unit can connect with two indoor units. The
indoor units can be combined in any of the different available ratings.
Indoor Units
33
Dimensions
2. Dimensions
34
Model
JOSI-DBC024-N11
245
>275
JOSI-DBC030-N11
245
>275
JOSI-DBC036-N11
245
>275
JOSI-DBC048-N11
287
>317
Indoor Units
Service Space
>1000mm
3. Service Space
>1000m m
>1000m m
>1000mm
Chart 3
Indoor Units
35
Wiring Diagrams
4. Wiring Diagrams
JOSI-DBC024-N11
36
JOSI-DBC030-N11
JOSI-DBC036-N11
JOSI-DBC048-N11
Indoor Units
Electric Characteristics
5. Electric Characteristics
Indoor Unit
Model
JOSI-DBC024-N11
JOSI-DBC030-N11
JOSI-DBC036-N11
JOSI-DBC048-N11
Hz
50
50
50
50
Voltage
220-240
220-240
220-240
220-240
Min
198
198
198
198
Max
254
254
254
254
Power
Supply
MFA
10
10
10
10
Notes:
MFA: Max. Fuse Amps. (A)
Indoor Units
37
Sound Levels
6. Sound Levels
1.4m
Microphone
38
Model
JOSI-DBC024-N11
JOSI-DBC030-N11
JOSI-DBC036-N11
JOSI-DBC048-N11
62
47
45
42
62
50
47
44
63
51
49
46
64
54
50
47
Indoor Units
Accessories
7. Accessories
Name
Shape
Quantity
Installation Fittings
Drain joint
Seal ring
Owner's manual
Installation manual
Expansible hook
Installation hook
Orifice
Drainpipe Fittings
Others
Installation accessory
(The product you have
might not be provided the
following accessories
Indoor Units
39
24000
30000
36000
36000
48000
Phase
Frequency and
Voltage
Indoor
Power
Unit
Wiring(mm2)
Power
Circuit
Breaker/
Fuse (A)
Phase
Frequency and
Voltage
Outdoor
Power
Unit
Wiring(mm2)
Power
Circuit
Breaker/
Fuse (A)
Indoor/Outdoor Connecting
Wiring(Weak Electric Signal)
(mm2)
Indoor/Outdoor Connecting
Wiring(Strong Electric Signal)
(mm2)
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
31.0
31.0
31.0
31.0
31.0
15/10
15/10
15/10
15/10
15/10
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
1-phase
220-240V,
50Hz
3-phase
380-415V,
50Hz
3-phase
380-415V,
50Hz
32.5
32.5
34.0
52.5
52.5
30/20
40/30
40/30
30/20
30/25
30. 5
30. 5
30. 5
30. 5
30. 5
40
Indoor Units
Field Wiring
9. Field Wiring
Indoor Units
41
42
Indoor Units
Indoor Units
Quantity
1
2
1
1
4
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
43
44
Indoor Units
Indoor Units
BOM Code
2011099A2561
202400100007
203342890005
P0000449603
P0000449698
P0000449689
201109901903
P0000449696
P0000449731
201142790001
202242790002
201242890006
201542890054
201642890046
201600320003
201642890048
201600320001
202301300804
202440500004
202242790001
201242790007
P0001115013
201242790004
201242590012
201242790009
P0001115013
201242790003
201242790011
201142790002
202400300529
201100100846
201142790004
203342590050
201242590004
201142590002
201342591519
202301450125
202301450116
202440120100
202301000950
201242590023
17317000A15640
202301310095
201242990003
202400600203
202742000002
202856001093
202742590002
201142500032
Part Name
Panel assembly
Louver motor
Display box assembly
Panel assembly
Cover assembly of installation plate
Air inlet grille assembly
Air filter
Transmission framework
Louver
Cover
Foam tray assembly for condenser water
Evaporator fixing hanger
Evaporator assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Base foam assembly
Board assembly III
Hook
Board assembly I
Chassis assembly
Board assembly II
Hook
Board assembly
Evaporator fixing board
Pipe fixing board assembly
Asynchronous motor
Fan assembly
Ventilation assembly
Electronic control box assembly
Electronic control box
Insulation plate
Main control board assembly
Wire joint
Wire joint
Ambient temperature sensor assembly
Reactance
Cover of electronic control box I
Remote controller
Water level sensor assembly
Water Pump installation bracket assembly
Drain pump
Pump rubber washer
Drain pipe
Drain pipe
Water pipe
Quantity
1
2
1
1
4
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
45
46
Indoor Units
BOM Code
2011099A2561
202400100007
203342890005
P0000449603
P0000449698
P0000449689
201109901903
P0000449696
P0000449731
201142790001
202242790002
201242890006
201542890054
201642890046
201600320003
201642890048
201600320001
202301300804
202440500004
202242790001
201242790007
P0001115013
201242790004
201242590012
201242790009
P0001115013
201242790003
201242790011
201142790002
202400300529
201100100846
201142790004
203342590050
201242590004
201142590002
201342591519
202301450125
202301450116
202440120100
202301000950
201242590023
17317000A15640
202301310095
201242990003
202400600203
202742000002
202856001093
202742590002
201142500032
Indoor Units
Part Name
Panel assembly
Louver motor
Display box assembly
Panel assembly
Cover assembly of installation plate
Air inlet grille assembly
Air filter
Transmission framework
Louver
Cover
Foam tray assembly for condenser water
Evaporator fixing hanger
Evaporator assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Base foam assembly
Board assembly III
Hook
Board assembly I
Chassis assembly
Board assembly II
Hook
Board assembly
Evaporator fixing board
Pipe fixing board assembly
Asynchronous motor
Fan assembly
Ventilation assembly
Electronic control box assembly
Electronic control box
Insulation plate
Main control board assembly
Wire joint
Wire joint
Ambient temperature sensor assembly
Reactance
Cover of electronic control box I
Remote controller
Water level sensor assembly
Water Pump installation bracket assembly
Drain pump
Pump rubber washer
Drain pipe
Drain pipe
Water pipe
Quantity
1
2
1
1
4
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
47
48
Indoor Units
Indoor Units
BOM Code
2011099A2561
202400100007
203342890005
P0000449603
P0000449698
P0000449689
201109901903
P0000449696
P0000449731
201142790001
202242790002
201242990039
201542990025
201642990044
201600320003
201642990006
201600320001
202301300804
202440500004
202242990004
201242990035
P0001115013
201242990034
201242590012
201242990037
P0001115013
201242990036
201242790011
201142790002
202400300529
201100100846
201142990003
203342590050
201242590004
201142590002
201342591519
202301450125
202301450116
202440120100
202301000950
201242590023
17317000A15640
202301310095
201242990003
202400600203
202742000002
202856001093
202742590002
201142500032
Part Name
Panel assembly
Louver motor
Display box assembly
Panel assembly
Cover assembly of installation plate
Air inlet grille assembly
Air filter
Transmission framework
Louver
Cover
Foam tray assembly for condenser water
Evaporator fixing hanger
Evaporator assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Base foam assembly
Board assembly III
Hook
Board assembly I
Chassis assembly
Board assembly II
Hook
Board assembly
Evaporator fixing board
Pipe fixing board assembly
Asynchronous motor
Fan assembly
Ventilation assembly
Electronic control box assembly
Electronic control box
Insulation plate
Main control board assembly
Wire joint
Wire joint
Ambient temperature sensor assembly
Reactance
Cover of electronic control box I
Remote controller
Water level sensor assembly
Water Pump installation bracket assembly
Drain pump
Pump rubber washer
Drain pipe
Drain pipe
Water pipe
Quantity
1
2
1
1
4
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
49
Duct Type
Duct Type
1. Features ...........................................................................51
2. Dimensions......................................................................55
3. Service Space ..................................................................57
4. Wiring Diagrams .............................................................59
5. Static Pressure ................................................................63
6. Electric Characteristics ..................................................69
7. Sound Levels...................................................................70
8. Accessories .....................................................................71
9. The Specification of Power ............................................72
10. Field Wiring ...................................................................73
11. Exploded View and Spare Part list ..............................75
50
Indoor Units
Features
1. Features
JOSI-DCD012-N11,JOSI-DCD018-N11,JOSI-DCD024-N11,
JOSI-DCD048-N11
JOSI-DCD030-N11,
JOSI-DCD036-N11,
Front Board, Canvas Air Passage, Filter, Panel, for easy installation
Front Board
Filter
Panel
1.2 Easy Installation: Two air inlet styles (Bottom side or Rear side)
Air inlet from rear is standard for all capacity; air inlet from bottom is optional.
The size of air inlet frame from rear and bottom is same, its very easy to move the cover from bottom to
rear side, or from rear to the bottom, in order to matching the installation condition.
Indoor Units
51
Features
Motor
Blower Housing
Ventilated Panel
Reserved remote on-off ports and central control ports, can connect the cable of an on-off controller or a
central controller to realize remote on-off control function or group control function.
Built-in drain pump can lift the water to 750mm upmost. Its convenient to install drainage piping under
most space condition.
52
Indoor Units
750mm upmost
Features
The units can be installed as Twin systems: one outdoor unit can connect with two indoor units. The
indoor units can be combined in any of the different available ratings.
Indoor Units
53
Features
JOSI-DCD060-N11
The air outlet flange is isolated from either top panel or base panel, which makes the maintenance
much easier when connecting duct.
Different solutions for any shape room by using kinds of air distribution ducts.
L-shaped
area
54
Y-shaped
area
Indoor Units
Dimensions
2. Dimensions
JOSI-DCD012-N11,JOSI-DCD018-N11,JOSI-DCD024-N11,JOSI-DCD030-N11,JOSI-DCD036-N11,
JOSI-DCD048-N11
D
C
F
A
Model
Outline dimension(mm)
Size of outline
dimension mounted
plug
L
M
JOSI-DCD012-N11
700
210
635
570
65
493
35
119
595
200
80
740
350
JOSI-DCD018-N11
920
270
635
570
65
713
35
179
815
260
20
960
350
JOSI-DCD024-N11
920
270
635
570
65
713
35
179
815
260
20
960
350
JOSI-DCD030-N11
1140
270
775
710
65
933
35
179
1035
260
20
1180
490
JOSI-DCD036-N11
1140
270
775
710
65
933
35
179
1035
260
20
1180
490
JOSI-DCD048-N11
1200
300
865
800
80
968
40
204
1094
288
45
1240
500
Indoor Units
55
56
44
duct flange)
20
385(air inlet
2-3.2
280
280
5
duct flange)
385(air outlet
10 10
1436(suspension position)
1000
500
500
1000
1400
Dimensions
JOSI-DCD060-N11
700(suspension position)
770
440
44
20
Indoor Units
Service Space
3. Service Space
JOSI-DCD012-N11,JOSI-DCD018-N11,JOSI-DCD024-N11,JOSI-DCD030-N11,JOSI-DCD036-N11,
JOSI-DCD048-N11
Ensure enough space required for installation and maintenance.
All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following:
Indoor Units
57
Service Space
JOSI-DCD060-N11
Ensure enough space required for installation and maintenance.
500mm or more
600mm or more
Indoor unit
58
Indoor Units
Wiring Diagrams
4. Wiring Diagrams
JOSI-DCD012-N11
JOSI-DCD018-N11
Indoor Units
59
Wiring Diagrams
JOSI-DCD024-N11
60
JOSI-DCD030-N11
JOSI-DCD036-N11
JOSI-DCD048-N11
JOSI-DCD060-N11
Indoor Units
Wiring Diagrams
JOSI-DCD018-N11
JOSI-DCD024-N11
Indoor Units
JOSI-DCD030-N11
JOSI-DCD036-N11
61
Wiring Diagrams
JOSI-DCD048-N11
62
JOSI-DCD060-N11
Indoor Units
Static Pressure
5. Static Pressure
JOSI-DCD012-N11
DCD012
Indoor Units
63
Static Pressure
JOSI-DCD018-N11 / JOSI-DCD024-N11
ESP selection
Switch ENC2 setting
ESP Setting-0 (0-25Pa)
DCD 18 & 24
Fan speed
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
L0
M0
H0
L1
M1
H1
L2
M2
H2
L3
M3
H3
L4
M4
H4
RPM
800
880
1030
830
900
1050
930
1000
1150
1150
1220
1350
1150
1220
1350
DCD018 / DCD024
DCD018 / DCD024
DCD018 / DCD024
64
Indoor Units
Static Pressure
JOSI-DCD030-N11
ESP selection
Switch ENC2 setting
ESP Setting-0 (0-25Pa)
DCD 030
Fan speed
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
L0
M0
H0
L1
M1
H1
L2
M2
H2
L3
M3
H3
L4
M4
H4
RPM
800
950
1100
860
1000
1150
920
1050
1180
950
1070
1200
950
1070
1200
DCD030
DCD030
Indoor Units
65
Static Pressure
JOSI-DCD036-N11
ESP selection
Switch ENC2 setting
ESP Setting-0 (0-25Pa)
DCD 036
Fan speed
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
L0
M0
H0
L1
M1
H1
L2
M2
H2
L3
M3
H3
L4
M4
H4
RPM
720
800
900
800
880
960
860
950
1030
970
1040
1110
1020
1100
1200
DCD036
DCD036
DCD036
66
Indoor Units
Static Pressure
JOSI-DCD048-N11
ESP selection
Switch ENC2 setting
Fan speed
DCD 048
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
FANL
FANM
FANHH
L0
M0
H0
L1
M1
H1
L2
M2
H2
L3
M3
H3
L4
M4
H4
RPM
750
880
1000
830
950
1070
900
990
1120
1020
1100
1200
1020
1100
1200
DCD048
DCD048
DCD048
Indoor Units
67
Static Pressure
JOSI-DCD060-N11
DCD060
DCD060
68
Indoor Units
Electric Characteristics
6. Electric Characteristics
Model
Indoor Units
Indoor Unit
Power Supply
Hz
Voltage
Min.
Max.
MFA
JOSI-DCD012-N11
50
220-240
198
254
JOSI-DCD018-N11
50
220-240
198
254
10
JOSI-DCD024-N11
50
220-240
198
254
10
JOSI-DCD030-N11
50
220-240
198
254
10
JOSI-DCD036-N11
50
220-240
198
254
10
JOSI-DCD048-N11
50
220-240
198
254
10
JOSI-DCD060-N11
Note:
MFA: Max. Fuse Amps. (A)
50
220-240
198
254
10
69
Sound Levels
7. Sound Levels
Concealed Duct Type
Discharge
Suction
Duct
Duct
1.4m
Microphone
70
Model
Sound Power
dB(A)
JOSI-DCD012-N11
57
41
39
36
JOSI-DCD018-N11
58
45
43
39
JOSI-DCD024-N11
63
46
43
39
JOSI-DCD030-N11
65
48
44
40
JOSI-DCD036-N11
62
42
39
36
JOSI-DCD048-N11
62
42
39
36
JOSI-DCD060-N11
67
57
54
51
Indoor Units
Accessories
8. Accessories
JOSI-DCD012-N11,JOSI-DCD018-N11,JOSI-DCD024-N11,JOSI-DCD030-N11,JOSI-DCD036-N11,
JOSI-DCD048-N11
Name
Shape
Quantity
Binding tape
Seal sponge
Drain joint
Seal ring
Wired controller
Owners manual
Installation manual
Drainpipe Fittings
(for cooling & heating)
Others
JOSI-DCD060-N11
Name
Shape
Quantity
Drain joint
Seal ring
Wired controller
Owners manual
Installation manual
Drainpipe Fittings
(for cooling & heating)
Others
Indoor Units
71
72
18000
24000
30000
36000
36000
1-phase
1-phase
1-phase
1-phase
1-phase
48000-600
00
1-phase
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
31.0
31.0
31.0
31.0
31.0
31.0
15/10
15/10
15/10
15/10
15/10
15/10
1-phase
1-phase
1-phase
1-phase
1-phase
3-phase
3-phase
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
380-415V,
50Hz
380-415V,
50Hz
31.5
32.5
32.5
32.5
34.0
52.5
52.5
20/16
20/16
30/20
40/30
40/30
30/20
30/25
30. 5
30. 5
30. 5
30. 5
30. 5
30. 5
12000
41.0
Indoor Units
Field Wiring
JOSI-DCD018-N11
Indoor Units
73
74
Indoor Units
Indoor Units
75
Quantity
1
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
76
Indoor Units
Indoor Units
77
78
BOM Code
201270390381
201170590004
201100100807
201170590003
201280200005
201270290101
201280200006
202400300070
201270290100
201270390312
201270390384
201270890021
201570290053
202440500004
201670290116
201600320002
201670290118
201600320000
201270390313
202301300804
202270290004
201270390383
201270890021
17223000A02258
201270590384
202301450042
202301310072
17123000A00882
202301000950
201270590100
201270290082
2033702A0077
201370290012
17317100A07945
201270390314
201270390385
201270290078
201270390379
203319900796
201270590340
201319903060
202301900138
Part Name
Chassis assembly
Up volute shell
Centrifugal fan
Below volute shell
Fan motor axes clamp (left)
Fan motor fixing board
Fan motor axes clamp (right)
Asynchronous motor
Supporter of fan motor
Middle beam assembly
Left clapboard assembly
Hook
Evaporator assembly
Pipe temperature sensor assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Evaporator right support board assembly
Pipe temperature sensor assembly
Water collector
Right clapboard assembly
Hook
Electronic control box assembly
Electronic control box
Wire joint
Ambient temperature sensor assembly
Main control board assembly
Reactor
Cover of electronic control box
Pipe clamp board assembly
Display box assembly
Display board assembly
Wired controller
Rear beam
Rear cover assembly
Top cover assembly
Fan motor fixing base
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Quantity
1
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
79
80
BOM Code
201270390381
201170590004
201100100807
201170590003
201280200005
201270290101
201280200006
202400300070
201270290100
201270390312
201270390384
201270890021
201570390029
202440500004
201670390138
201600320003
201670390130
201600320001
201270390313
202301300804
202270290004
201270390383
201270890021
17223000A02258
201270590384
202301450042
202301310072
17123000A00882
202301000950
201270590100
201270290082
2033702A0077
201370290012
17317100A07945
201270390314
201270390315
201270290078
201270390379
203319900796
201270590340
201319903060
202301900138
202400600005
201270290085
202301310051
201270390316
201170290011
Part Name
Chassis assembly
Up volute shell
Centrifugal fan
Below volute shell
Fan motor axes clamp (left)
Fan motor fixing board
Fan motor axes clamp (right)
Asynchronous motor
Supporter of fan motor
Middle beam assembly
Left clapboard assembly
Hook
Evaporator assembly
Pipe temperature sensor assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Evaporator right support board assembly
Pipe temperature sensor assembly
Water collector
Right clapboard assembly
Hook
Electronic control box assembly
Electronic control box
Wire joint
Ambient temperature sensor assembly
Main control board assembly
Reactor
Cover of electronic control box
Pipe clamp board assembly
Display box assembly
Display board assembly
Wired controller
Rear beam
Rear cover assembly
Top cover assembly
Fan motor fixing base
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Drain pump
Holder of drain pump
Liquid level sensor assembly
Flange
Air filter
Quantity
1
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
81
BOM Code
201270590299
201170590004
201100100807
201170590003
201280200005
201270290101
201280200006
202400300510
201270290100
201270590298
201270590302
201270890021
201570590113
202301300804
202440500004
201670590265
201600320003
201670590266
201600320001
201270590181
202270590004
201270590301
201270890021
17223000A02258
201270590384
202301450042
202301310072
17123000A00882
202301000950
201270590100
201270290082
2033702A0077
201370290012
17317100A07945
201270590183
201270590184
201270590272
201270590176
203319900794
201270590340
201319903054
202301900138
202400600005
201270290085
202301310051
201270590185
201170590006
Part Name
Chassis assembly
Up volute shell
Centrifugal fan
Below volute shell
Fan motor axes clamp (left)
Fan motor fixing board
Fan motor axes clamp (right)
Asynchronous motor
Supporter of fan motor
Middle beam assembly
Left clapboard assembly
Hook
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Output pipe assembly
Copper nut
Input pipe assembly
Copper nut
Evaporator right support board assembly
Water collector
Right clapboard assembly
Hook
Electronic control box assembly
Electronic control box
Wire joint
Ambient temperature sensor assembly
Main control board assembly
Reactor
Cover of electronic control box
Pipe clamp board assembly
Display box assembly
Display board assembly
Wired controller
Rear beam
Rear cover assembly
Top cover assembly
Right clapboard strengthen board
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Drain pump
Holder of drain pump
Liquid level sensor assembly
Flange
Air filter
Quantity
1
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
83
84
BOM Code
201270790180
201170590004
201100100807
201170590003
201286000008
201286000053
202400300055
201270790176
201286000007
201286000052
202501180006
202970790001
201287000011
202732400001
201270790183
201270890021
201270790178
201570790050
202301300804
202440500004
201670790142
201600320001
201670790225
201600320003
202270990001
201270790134
201270790182
201270890021
17223000A02258
201270590384
202301450042
17123000A00882
202301310072
202301000950
201270590100
17317100A07945
2033702A0077
201370290012
201270290082
201270790042
201270790179
201270790136
201270790135
201270790177
202400600005
201270290085
202301310051
201270790137
201170790007
Part Name
Chassis assembly
Up volute shell
Centrifugal fan
Below volute shell
Fan motor top fixing clamp (right)
Fan motor below fixing clamp (right)
Asynchronous motor
Fan motor fixing board
Fan motor top fixing clamp (left)
Fan motor below fixing clamp (left)
Connecting shaft
Coupling
Bearing Fixing board
Bearing base
Left clapboard assembly
Hook
Middle beam assembly
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Input pipe assembly
Copper nut
Output pipe assembly
Copper nut
Water collector
Evaporator right support board assembly
Right clapboard assembly
Hook
Electronic control box assembly
Electronic control box
Wire joint
Main control board assembly
Ambient temperature sensor assembly
Reactor
Cover of electronic control box
Wired controller
Display box assembly
Display board assembly
Pipe clamp board assembly
Right clapboard strengthen board
Rear beam assembly
Rear cover assembly
Top cover assembly
Supporter assembly of fan motor
Drain pump
Holder of drain pump
Liquid level sensor assembly
Flange
Air filter
Quantity
1
3
3
3
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
85
86
BOM Code
201270790180
201170590004
201100100807
201170590003
201286000008
201286000053
202400300055
201270790176
201286000007
201286000052
202501180006
202970790001
201287000011
202732400001
201270790183
201270890021
201270790178
201570790050
202301300804
202440500004
201670790142
201600320001
201670790225
201600320003
202270990001
201270790134
201270790182
201270890021
17223000A02256
201270590384
202301450042
17123000A00881
202301310072
201270590100
17317100A07945
2033702A0077
201370290012
201270290082
201270790042
201270790179
201270790136
201270790135
201270790177
202400600005
201270290085
202301310051
201270790137
201170790007
Part Name
Chassis assembly
Up volute shell
Centrifugal fan
Below volute shell
Fan motor top fixing clamp (right)
Fan motor below fixing clamp (right)
Asynchronous motor
Fan motor fixing board
Fan motor top fixing clamp (left)
Fan motor below fixing clamp (left)
Connecting shaft
Coupling
Bearing Fixing board
Bearing base
Left clapboard assembly
Hook
Middle beam assembly
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Input pipe assembly
Copper nut
Output pipe assembly
Copper nut
Water collector
Evaporator right support board assembly
Right clapboard assembly
Hook
Electronic control box assembly
Electronic control box
Wire joint
Main control board assembly
Ambient temperature sensor assembly
Cover of electronic control box
Wired controller
Display box assembly
Display board assembly
Pipe clamp board assembly
Right clapboard strengthen board
Rear beam assembly
Rear cover assembly
Top cover assembly
Supporter assembly of fan motor
Drain pump
Holder of drain pump
Liquid level sensor assembly
Flange
Air filter
Quantity
1
3
3
3
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
87
88
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
Indoor Units
Indoor Units
89
Features
1. Features
1.1. New design, more modern and elegant appearance.
1.4. Three level fan speed, more humanism design, meets different air-supply requirement.
1.5. New foam drain pan with plastic-spraying inner surface
90
Indoor Units
Dimensions
2. Dimensions
Indoor Units
Model
JOSI-DBF018-N11
1068
675
235
983
220
JOSI-DBF024-N11
1068
675
235
983
220
JOSI-DBF030-N11
1285
675
235
1200
220
JOSI-DBF036-N11
1285
675
235
1200
220
JOSI-DBF048-N11
1650
675
235
1565
220
91
Service Space
3. Service Space
92
Indoor Units
Wiring Diagrams
4. Wiring Diagrams
JOSI-DBF018-N11
JOSI-DBF024-N11
Indoor Units
JOSI-DBF030-N11
JOSI-DBF036-N11
JOSI-DBF048-N11
93
Wiring Diagrams
JOSI-DBF018-N11
JOSI-DBF024-N11
94
JOSI-DBF030-N11
JOSI-DBF036-N11
JOSI-DBF048-N11
Indoor Units
Electric Characteristics
5. Electric Characteristics
Indoor Units
Model
Power Supply
Hz
Voltage
Min.
Max.
MFA
50
220-240
198
254
10
50
220-240
198
254
10
50
220-240
198
254
10
JOSI-DBF036-N11
50
220-240
198
254
10
JOSI-DBF048-N11
50
220-240
198
254
10
JOSI-DBF018-N11
JOSI-FWDB018-N11
JOSI-DBF024-N11
JOSI-FWDB024-N11
JOSI-DBF030-N11
Note:
MFA: Max. Fuse Amps. (A)
6. Sound Levels
Microphone
1m
1m
Air outlet side
1.5m
1m
Microphone
Ceiling
Floor
Noise level dB(A)
Model
Sound Power
dB (A)
JOSI-DBF018-N11
60
44
41
38
JOSI-DBF024-N11
63
52
50
46
JOSI-DBF030-N11
64
53
50
46
JOSI-DBF036-N11
65
52
49
43
JOSI-DBF048-N11
68
57
54
51
Indoor Units
95
Accessories
7. Accessories
Name
Others
Shape
Quantity
1. Remote controller
5. Owner's manual
6. Installation manual
18000
24000
30000
36000
36000
48000
Phase
Frequency
and
Indoor
Voltage
Unit
Power
Power
Wiring(mm2)
Circuit
Breaker/
Fuse (A)
Phase
Frequency
and
Outdoor
Voltage
Unit
Power
Power
Wiring(mm2)
Circuit
Breaker/
Fuse (A)
Indoor/Outdoor Connecting
Wiring(Weak
Electric
Signal) (mm2)
Indoor/Outdoor Connecting
Wiring(Strong
Electric
Signal)
(mm2)
1-phase
1-phase
1-phase
1-phase
1-phase
1-phase
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
31.0
31.0
31.0
31.0
31.0
31.0
15/10
15/10
15/10
15/10
15/10
15/10
1-phase
1-phase
1-phase
1-phase
3-phase
3-phase
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
220-240V,
50Hz
380-415V,
50Hz
380-415V,
50Hz
32.5
32.5
32.5
34.0
52.5
52.5
20/16
30/20
40/30
40/30
30/20
30/25
30.5
30.5
30.5
30.5
30.5
30.5
96
Indoor Units
9. Field Wiring
JOSI-DBF018-N11
JOSI-DBF024-N11
Indoor Units
JOSI-DBF030-N11
JOSI-DBF036-N11
JOSI-DBF048-N11
97
98
Indoor Units
BOM Code
1
1.1
1.2
2
3
4
5
5.1
5.1
5.2
5.2.1
5.3
5.4
5.5
6
6.1
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
25.1
25.2
25.3
25.3
25.5
25.7
26
28
28.1
28.2
28.3
201144290054
201144790024
201144790023
2012442A0012
2013447A0064
2011447A0009
201544190036
202301300804
202301300111
201644190055
201600320000
201644190053
201544290182
201600320002
202244290014
202400200100
201244790047
201144790018
201132590888
202400200162
201144690032
201144690083
202400300447
201280200006
201280200005
201252490002
201144690033
201144790017
201244790033
201144290056
201244290053
201244790034
201144790019
201244490048
203344290030
201244790050
201344290050
202301450042
202301450125
202301310072
202301000950
17317000A15640
203319900795
201270590340
201319903056
202301900138
Indoor Units
Part
Name
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
1
1
1
1
2
1
2
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
99
100
Indoor Units
Indoor Units
BOM Code
201144290054
201144790024
201144790023
2012442A0012
2013447A0064
2011447A0009
201544290181
202301300804
202301300111
201644290197
201600320001
201644290196
201544290182
201600320003
202244290014
202400200100
201244790047
201144790018
201132590888
202400200162
201144690032
201144690083
202400300447
201280200006
201280200005
201252490002
201144690033
201144790017
201244790033
201144290056
201244290053
201244790034
201144790019
201244490048
203344290030
201244790050
201344290050
202301450042
202301450125
202301310072
202301000950
17317000A15640
203319900795
201270590340
201319903056
202301900138
Part Name
Air inlet grille assembly I
Air filter I
Air filter II
Top cover assembly
Display board assembly
Display installation box
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Input pipe assembly
Copper nut
Output pipe assembly
Evaporator
Copper nut
Water collector
Louver motor (vertical)
Pipe clamp board
Supporter of louver
Insulated axis
Louver motor
Volute shell (above)
Centrifugal fan
Asynchronous motor
Fan motor axes clamp (right)
Fan motor axes clamp (left)
Fan motor fixing board
Volute shell (below)
Right cover
Right hook
Louver
Chassis assembly
Left hook
Left cover
Cover of electronic control box
Electronic control box assembly
Electronic control box
Main control board assembly
Wire joint
Wire joint
Ambient temperature sensor assembly
Reactance
Remote controller
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
1
1
1
1
2
1
2
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
101
102
Indoor Units
No.
1
1.1
2
3
4
5
5.1
5.1
5.2
5.2.1
5.3
5.4
5.5
6
6.1
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
28.1
28.3
28.4
28.4
28.5
28.7
29
30
32
32.1
32.2
32.3
201144790015
201144790024
2012444A0012
2013447A0064
2011447A0009
201544490266
202301300804
202301300111
201644690252
201600320001
201644490324
201544690174
201600320003
202244490015
202400200100
202970790001
201132590888
201252490002
201144690032
201287000011
202732400001
202501180103
202400300512
201280200006
201280200005
201144690083
201144690033
201144790017
201244790033
201144790018
201144490040
202400200162
201244490052
201244790034
201144790019
201244490048
203344290030
201244790050
201344290050
202301450042
202301450125
202301310072
202301000950
201244790047
17317000A15640
203319900796
201270590340
201319903060
202301900138
Indoor Units
Part
Name
Quantity
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
1
1
1
3
3
1
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
103
104
Indoor Units
BOM Code
201144790014
201144790023
201144790015
201144790024
2012447A0016
2011447A0009
2013447A0064
201544790144
202301300804
202301300111
201644790189
201600320001
201644790192
201544790139
201600320003
202244790001
202400200100
201132590888
201144690032
201252490002
201144690083
201280200006
201280200005
202400300070
201144690033
201144790017
201244790033
201144790018
201144790006
202400200162
201244790034
201144790019
17317000A15640
201244490048
203344490068
201244790050
202301450116
202301450125
201344490054
202301310072
202301000950
201244790047
201244690053
203319900796
201270590340
201319903060
202301900138
Indoor Units
Part Name
Air inlet grille assembly II
Air filter I
Air inlet grille assembly I
Air filter II
Top cover assembly
Display installation box
Display board assembly
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Input pipe assembly
Copper nut
Output pipe assembly
Evaporator
Copper nut
Water collector
Louver motor
Insulated axis
Volute shell (above)
Fan motor fixing board
Centrifugal fan
Fan motor axes clamp (right)
Fan motor axes clamp (left)
Asynchronous motor
Volute shell (below)
Right cover
Right hook
Supporter of louver
Louver
Louver motor
Left hook
Left cover
Remote controller
Cover of electronic control box
Electronic control box assembly
Electronic control box
Wire joint
Wire joint
Main control board assembly
Ambient temperature sensor assembly
Reactor
Pipe clamp board
Chassis assembly
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Quantity
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
4
2
4
2
2
2
4
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
105
106
Indoor Units
BOM Code
201144790014
201144790023
201144790015
201144790024
2012447A0016
2011447A0009
2013447A0064
201544790144
202301300804
202301300111
201644790189
201600320001
201644790192
201544790139
201600320003
202244790001
202400200100
201132590888
201144690032
201252490002
201144690083
201280200006
201280200005
202400300070
201144690033
201144790017
201244790033
201144790018
201144790006
202400200162
201244790034
201144790019
17317000A15640
201244490048
203344490068
201244790050
202301450116
202301450125
201344490054
202301310072
202301000950
201244790047
201244690053
203319900796
201270590340
201319903060
202301900138
Indoor Units
Part Name
Air inlet grille assembly II
Air filter I
Air inlet grille assembly I
Air filter II
Top cover assembly
Display installation box
Display board assembly
Evaporator assembly
Pipe temperature sensor assembly
Pipe temperature sensor assembly
Input pipe assembly
Copper nut
Output pipe assembly
Evaporator
Copper nut
Water collector
Louver motor
Insulated axis
Volute shell (above)
Fan motor fixing board
Centrifugal fan
Fan motor axes clamp (right)
Fan motor axes clamp (left)
Asynchronous motor
Volute shell (below)
Right cover
Right hook
Supporter of louver
Louver
Louver motor
Left hook
Left cover
Remote controller
Cover of electronic control box
Electronic control box assembly
Electronic control box
Wire joint
Wire joint
Main control board assembly
Ambient temperature sensor assembly
Reactor
Pipe clamp board
Chassis assembly
Electronic control box assembly
Electronic control box
Inverter control board assembly
Radiator
Quantity
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
4
2
4
2
2
2
4
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
107
108
Indoor Units
Features
1. Features
1.1 New panel
The body size is 570260570mm, its just smaller than the ceiling board, so its very easy for
installation and will not damage the decoration. The panel size is 64750647mm.
The hooks are designed in the four corners of the body, which can save installation space.
The E-box is simply and safely built inside the indoor unit. Its convenient for installation and
maintenance. Can check the control part easily, you only need to open the air return grille.
Indoor Units
109
Dimensions
2. Dimensions
110
Indoor Units
Service Space
3. Service Space
Indoor Units
111
Wiring Diagrams
4. Wiring Diagrams
JOSI-DBC012-N11
S2
S1(1-2)
0-F
0-F
0-F
0-F
OFF-OFF
ON-OFF
OFF-ON
ON-ON
Address
(Central control)
0-15(Default=0)
16-31
32-47
48-63
SW1-1
OFF
ON
OFF
ON
SW1-2
OFF
OFF
ON
ON
SW6-1
SW6-2
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Temp. Compensation
(Heating)
6(Default)
4
2
Reserved
SW3
OFF
ON
Auto Restart
With Auto Restart (Default)
W/O Auto Restart
SW2
OFF
ON
Alarm
Output
RCW8(Optional)
M
5
RCW6
(Optional)
Y/G
Fresh Air
Remote
Control
JR6
10
ALARM
P5
CN15
CN8
INDOOR UNIT
MAINBOARD
CN13
CN3
CN5
CH
JR6
CN33
CN1
Y/G
To Central
Control
TO OUTDOOR UNIT
JOSI-DBC018-N11
Alarm
Output
RCW8
(Optional)
Remote
Control
JR6
10
ALARM
CN15
CN8
INDOOR UNIT
MAINBOARD
CN13
CN3
CN5
CH
JR6
CN33
CN1
5
Y/G
To Central
Control
POWER
TO OUTDOOR UNIT
112
Indoor Units
Temperature
Indoor Units
113
Electric Characteristics
6. Electric Characteristics
Indoor Units
Model
Power Supply
Hz
Voltage
Min.
Max.
MFA
JOSI-DBC012-N11
50
220-240
198
254
JOSI-DBC018-N11
50
220-240
198
254
10
Note :
MFA: Max. Fuse Amps. (A)
7. Sound Levels
1.4m
Microphone
114
Model
JOSI-DBC012-N11
55
42
38
34
JOSI-DBC018-N11
60
48
40
30
Indoor Units
Accessories
8. Accessories
Name
Shape
Quantity
Installation Fittings
Drain joint
Seal ring
Owner's manual
Installation manual
Expansible hook
Installation hook
Orifice
Drainpipe Fittings
Others
Installation accessory
(The product you have
might not be provided the
following accessories
JOSI-DBC012-N11
Phase
Indoor Unit
Power
1-phase
220-240V, 50Hz
Wiring(mm2)
31.0
15/10
Phase
Outdoor Unit
Power
1-phase
1-phase
220-240V, 50Hz
220-240V, 50Hz
31.5
32.5
20/16
20/16
(mm2)
Indoor Units
JOSI-DBC018-N11
30. 5
41.0
115
Field Wiring
JOSI-DBC018-N11
116
Indoor Units
Indoor Units
117
118
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Indoor Units
119
120
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Indoor Units
Console Type
Console Type
1. Features ...............................................................................................123
2. Dimensions .........................................................................................125
3. Service Space......................................................................................126
4. Wiring Diagrams .................................................................................127
5. Air Velocity and Temperature Distributions(Reference Data) ........128
6. Electric Characteristics ......................................................................129
7. Sound Levels ......................................................................................130
8. Accessories .........................................................................................131
9. The Specification of Power ................................................................131
10. Field Wiring .......................................................................................132
11. Exploded View and Spare Part list ..................................................133
Console Type
121
Features
1. Features
1.1. Modern and elegant appearance
The simple and stylish designs can nicely harmonies with your living space.
Quick Cooling
Air outlet from top and bottom to make quick cooling ------When the A/C is just switched on, or room
temp. is still high, cold air will be blown out from top and bottom air outlet to cool down the room quickly
Air outlet from top to maintain room temp. ----When the room has been cooled down, or the A/C has
been opened over 1 hour, cold air only from the top outlet to keep constant room temp
Heating mode
Anti-cold air ------When the AC is just turn on, temperature of evaporator is very low, in this case, in
order to prevent cold air direct blowing, only the upper louver is opened in a high position, the lower
louver closed.
Console Type
123
Features
Advanced centrifugal fan technology makes a fast airflow and reduces the indoor noise lower to 28dB.
124
Console Type
Dimensions
2. Dimensions
JOSI-DAX012-N11JOSI-DAX018-N11
Console Type
125
Service Space
3. Service Space
126
Console Type
Wiring Diagrams
4. Wiring Diagrams
JOSI-DAX012-N11
JOSI-DAX018-N11
Console Type
127
Airflow velocity
Temperature
128
Console Type
Electric Characteristics
6. Electric Characteristics
Model
Console Type
Indoor Units
Power Supply
Hz
Voltage
Min.
Max.
MFA
JOSI-DAX012-N11
50
220-240
198
254
JOSI-DAX018-N11
Note:
MFA: Max. Fuse Amps. (A)
50
220-240
198
254
10
129
Sound Levels
7. Sound Levels
1m
Microphone
1.5m
130
Model
Noise Power
dB(A)
JOSI-DAX012-N11
58
44
40
36
JOSI-DAX018-N11
60
45
42
39
Console Type
Accessories
8. Accessories
Name
Installation fittings
Shape
Hook
Remote controller
Frame
Mounting screw(ST2.910-C-H)
Others
Quantity
2
1
1
/
/
JOSI-DAX012-N11
Phase
Indoor Unit
Power
1-phase
220-240V, 50Hz
Power Wiring(mm2)
31.0
15/10
Phase
Outdoor Unit
Power
Wiring(mm2)
1-phase
1-phase
220-240V, 50Hz
220-240V, 50Hz
31.5
32.5
20/16
30/20
(mm2)
Console Type
JOSI-DAX018-N11
(mm2)
30. 2
41.0
131
Field Wiring
JOSI-DAX018-N11
132
Console Type
Console Type
133
134
BOM Code
2011440A0001
201144090002
201144090022
201544090014
202301310085
201144090030
201144090016
201244090009
201131410703
201132200713
17222600A00055
201144090009
201144090010
201244090003
202301310072
202301400072
201244090002
201144090008
201344090004
17122700A00866
201244090004
201344090029
201144090044
202400200052
P0000281380
201144090042
202400200053
201244090008
P0000283050
201144090011
201244290015
17317000A15640
201144090005
201244090001
201100100020
202400300014
201244090005
Part Name
Panel assembly
Air filter
Panel frame assembly
Evaporator assembly
Pipe temperature sensor assembly
Ventilation assembly
Chassis assembly
Hang board assembly
Anti-bacterial filter
Bracket of air filter
Electronic control box assembly
Installation plate of electric parts I
Electrical control box
Fixing board of electronic control box II
Ambient temperature sensor assembly
Wire joint
Electronic control box seal plate
Installation plate of electric parts
Display board assembly
Main control board assembly
Fixing board of electronic control box I
Auxiliary electric heater control board
Water collector
Louver motor
Underside louver
Air outlet assembly
Louver motor
Rear net
Up louver
Pipe clamp
Installation clamp
Remote controller
Insulation washer
Cover of electronic control box
Centrifugal fan
Fan motor
Supporter assembly of fan motor
Quantity
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
Console Type
Console Type
135
136
BOM Code
2011440A0001
201144090002
201144090022
201544190012
202301310085
201144090030
201144090016
201244090009
201131410703
201132200713
203344190019
201144090009
201144090010
201244090003
202301310072
202301450125
201244090002
201144090008
201344090004
201344190028
201244190000
202301300077
203310900018
201344090029
201144090044
202400200052
P0000281380
201144090042
202400200053
201244090008
P0000283050
201144090011
201244290015
17317000A15640
201144090005
201244090001
201100100020
202400300014
201244090005
Part Name
Panel assembly
Air filter
Panel frame assembly
Evaporator assembly
Pipe temperature sensor assembly
Ventilation assembly
Chassis assembly
Hang board assembly
Anti-bacterial filter
Bracket of air filter
Electronic control box assembly
Installation plate of electric parts I
Electrical control box
Fixing board of electronic control box II
Ambient temperature sensor assembly
Wire joint
Electronic control box seal plate
Installation plate of electric parts
Display board assembly
Main control board assembly
Fixing board of electronic control box I
Pipe temperature sensor assembly
Network module assembly
Auxiliary electric heater control board
Water collector
Louver motor
Underside louver
Air outlet assembly
Louver motor
Rear net
Up louver
Pipe clamp
Installation clamp
Remote controller
Insulation washer
Cover of electronic control box
Centrifugal fan
Fan motor
Supporter assembly of fan motor
Quantity
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
Console Type
Outdoor Units
Part 3
Outdoor Units
1. Dimensions ....................................................................138
2. Service Space.................................................................140
3. Piping Diagrams ............................................................141
4. Wiring Diagrams ............................................................142
5. Electric Characteristics .................................................146
6. Operation Limits ............................................................147
7. Sound Levels .................................................................148
8. Exploded View and Spare Part list ...............................149
Outdoor Units
137
Dimensions
1. Dimensions
Model
Unitmm
A
JOAU-DLY012-H11
760
530
290
315
270
285
590
JOAU-DLY018-H11
845
560
335
360
312
320
700
JOAU-DLY024-H11
900
590
333
355
302
315
860
JOAU-DLY030-H11
900
590
333
355
302
315
860
JOAU-DLY036-H11
990
624
366
396
340
345
965
JOAU-DLY036-H13
990
624
366
396
340
345
965
138
Outdoor Units
Dimensions
Model
Unitmm
A
JOAU-DLY048-H13
938
633.5
404
448
370
392
1369
JOAU-DLY060-H13
938
633.5
404
448
370
392
1369
Outdoor Units
139
Service Space
2. Service Space
(Wall or obstacle)
Air inlet
More than 30cm
Air inlet
Maintain channel
More than 60cm
Air outlet
140
Outdoor Units
Piping Diagrams
3. Piping Diagrams
JOAU-DLY012-H11
JOAU-DLY018-H11
JOAU-DLY024-H11
INDOOR
JOAU-DLY030-H11
OUTDOOR
Electronic
expansion valve
CAPILIARY TUBE
LIQUID SIDE
2-WAY VALVE
T3 Condenser
temp. sensor
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
T4 Ambient
temp. sensor
T1 Room temp.
sensor
T2 Evaporator
temp. sensor
middle
T2B Evaporator
temp. sensor
outlet
GAS SIDE
4-WAY VALVE
3-WAY VALVE
Accumulator
Low pressure
switch
High pressure
switch
T5 Discharge
temp. sensor
COOLING
Compressor
HEATING
JOAU-DLY036-H11
JOAU-DLY036-H13
JOAU-DLY048-H13
INDOOR
JOAU-DLY060-H13
OUTDOOR
CAPILIARY TUBE
LIQUID SIDE
Electronic
expansion valve
2-WAY VALVE
T3 Condenser
temp. sensor
HEAT
EXCHANGE
(EVAPORATOR)
T2 Evaporator
temp. sensor
middle
T2B Evaporator
temp. sensor
outlet
HEAT
EXCHANGE
(CONDENSER)
T4 Ambient
temp. sensor
T1 Room temp.
sensor
GAS SIDE
4-WAY VALVE
3-WAY VALVE
Accumulator
Compressor
Low pressure
switch
COOLING
Oil return Capillary
Outdoor Units
HEATING
141
Wiring Diagrams
4. Wiring Diagrams
JOAU-DLY012-H11
142
Outdoor Units
Wiring Diagrams
JOAU-DLY018-H11
JOAU-DLY024-H11
JOAU-DLY030-H11
JOAU-DLY036-H11
Outdoor Units
143
Wiring Diagrams
JOAU-DLY036-H13
JOAU-DLY048-H13
144
Outdoor Units
Wiring Diagrams
JOAU-DLY060-H13
Outdoor Units
145
Electric Characteristics
5. Electric Characteristics
Model
Outdoor Unit
Power Supply
Hz
Voltage
Min.
Max.
MFA
JOAU-DLY012-H11
50
220-240V
198V
254V
16
JOAU-DLY018-H11
50
220-240V
198V
254V
16
JOAU-DLY024-H11
50
220-240V
198V
254V
20
JOAU-DLY030-H11
50
220-240V
198V
254V
30
JOAU-DLY036-H11
50
220-240V
198V
254V
30
JOAU-DLY036-H13
50
380-415V
342V
440V
20
JOAU-DLY048-H13
50
380-415V
342V
440V
25
50
380-415V
342V
440V
25
JOAU-DLY060-H13
Note:
MFA: Max. Fuse Amps. (A)
146
Outdoor Units
Operation Limits
6. Operation Limits
Temperature
Mode
Room temperature
Cooling operation
Heating operation
17
30
050
Outdoor temperature
-1550
(For the models with
low temperature
cooling system)
-1524
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features may come
into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the
surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum
angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
Outdoor Units
147
Sound Levels
7. Sound Levels
Outdoor Unit
Microphone
1.0m
Note: H= 0.5 height of outdoor unit
148
Model
JOAU-DLY012-H11
62
52
JOAU-DLY018-H11
65
55
JOAU-DLY024-H11
69
57
JOAU-DLY030-H11
70
58
JOAU-DLY036-H11
70
60
JOAU-DLY036-H13
70
60
JOAU-DLY048-H13
70
61
JOAU-DLY060-H13
70
61
Outdoor Units
Outdoor Units
149
No.
Bom Code
Part
202301310063
2011374G0003
Rear Net
201537390033
Condenser Assembly
202440500004
Temperature Sensor
201237200299
201237590105
Chassis Assembly
201237500263
201137900008
201137400000
Water receiver
10
2011374A0004
12
201237400407
Front Panel
13
201100390002
14
202400300060
Brushless DC Motor
15
201237390026
16
201237500241
Separator Assembly
16.3
202301000867
Reactor
17
201237400400
18
201237900028
19
203337590112
19.1
201237300162
19.2
201337590086
19.3
201137300162
19.4
202301990015
Radiator
19.5
201237300318
20
203337790146
20.1
202301400223
Wire holder
20.2
201237590046
21
2016373A0211
21.1
201600720095
21.2
201600600521
4-way Valve
22
201637391551
22.1
201600740523
Liquid valve
23
201400620600
25
202301310068
28
201600320001
Brass Nut
28
201600320000
Brass Nut
150
Name
Quantity
Outdoor Units
Outdoor Units
151
152
BOM Code
202301310075
2011481G0001
201537990084
201637991011
201537990003
201637991010
202440500004
201237300316
201257090054
201237890121
201137900007
201137390017
201248100389
201248100390
2011379A0005
2011374A0005
201100300553
202400300535
201257090067
201248100384
201257190097
201248100367
201257190118
2033752A0057
201157190011
2013752A0014
201375290027
201157190010
202301901173
203375290076
201257190117
202301450042
202301450121
201675290610
201600700078
201601300554
needs to be updated
201600720194
201600690011
201601010017
201400603269
202448200000
201248090001
202301000903
201600320002
201600320000
202402220154
Part Name
Ambient temperature sensor assembly
Rear net
Condenser assembly
Input pipe assembly
Condenser assembly
Fluted pipe assembly
Pipe temperature sensor assembly
Valve plate
Chassis assembly
Rear right clapboard assembly
Big handle
Water collector
Front right clapboard assembly
Front panel
Air outlet grille
Round sticker of air outlet grille
Axial flow fan
Asynchronous motor
Supporter assembly of fan motor
Rear supporter
Top cover assembly
Left supporter
Partition board assembly
Electronic control box assembly
Cover of electronic control box
Main control board assembly
Inverter control board assembly
Installation board for E-parts
Radiator
Terminal board assembly
Installation plate of electric parts
Wire joint
Wire joint
Liquid valve assembly
Liquid valve
Electronic expansion valve assembly
4-way valve assembly
Gas valve
4-Ways valve
Accumulator tank
Compressor
Discharge temperature sensor assembly
Cover of inductance
Reactor
Copper nut
Copper nut
Compressor wire assembly
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Outdoor Units
Outdoor Units
153
154
BOM Code
202301310075
2011482G0001
201557190037
202301300111
201248300316
201257190085
201238190023
201157390007
201138090002
201248200082
201248200103
2011482A0001
2011374A0005
201100300527
202400300047
201257190071
201248200095
201248300309
201248400036
201257190115
203375390332
201157190011
201375390026
201357190085
201157190010
202301901173
203375390330
202301450042
202301450121
201257190120
201675390818
201600740706
201601300032
will to be updated
201600720398
201600600119
201400601740
202448200000
201248390003
202301000943
201148700009
201601000603
201600320003
201600320001
201245000901
Part Name
Ambient temperature sensor assembly
Rear net
Condenser assembly
Pipe temperature sensor assembly
Valve plate
Chassis assembly
Rear right clapboard assembly
Big handle
Water collector
Front right clapboard assembly
Front panel
Air outlet grille
Round sticker of air outlet grille
Axial flow fan
Brushless DC Motor
Supporter assembly of fan motor
Rear supporter
Top cover assembly
Left supporter
Partition board assembly
Electronic control box assembly
Cover of electronic control box
Outdoor main control board assembly
Inverter control board assembly
Electronic installing plate
Radiator
Terminal board assembly
Wire joint
Wire joint
Terminal board
Liquid valve assembly
Liquid valve
Electronic expansion valve
4-ways valve assembly
Gas valve
4-ways valve
Compressor
Discharge temperature sensor assembly
Cover of inductance
Reactor
Handle
Accumulator cylinder
Copper nut
Copper nut
Fix clamp of segregator
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
Outdoor Units
Outdoor Units
155
156
BOM Code
202301310075
2011482G0001
201557190037
202301300111
201248300316
201257190085
201238190023
201157390007
201138090002
201248200082
201248200103
2011482A0001
2011374A0005
201100300527
202400300047
201257190071
201248200095
201248300309
201248400036
201257190115
203375490059
201157190011
201375490032
201357190085
201157190010
202301901173
201295200010
203375390330
202301450042
202301450121
201257190120
201675390818
201600740706
201601300032
will be updated
201600720398
201600600119
201400601740
202448200000
201248390003
202301000943
201148700009
201601000603
201600320003
201600320001
Part Name
Ambient temperature sensor assembly
Rear net
Condenser assembly
Pipe temperature sensor assembly
Valve plate
Chassis assembly
Rear right clapboard assembly
Big handle
Water collector
Front right clapboard assembly
Front panel
Air outlet grille
Round sticker of air outlet grille
Axial flow fan
Asynchronous motor
Supporter assembly of fan motor
Rear supporter
Top cover assembly
Left supporter
Partition board assembly
Electronic control box assembly
Cover of electronic control box
Main control board assembly
Inverter control board assembly
Installation board for E-parts
Radiator
Installation plate of PCB
Terminal board assembly
Wire joint
Wire joint
Terminal board
Liquid valve assembly
Liquid valve
Electronic expansion valve
4-way valve assembly
Gas valve
4-Ways valve
Compressor
Discharge temperature sensor assembly
Cover of inductance
Reactor
Small Handle
Accumulator cylinder
Copper nut
Copper nut
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
Outdoor Units
Outdoor Units
157
158
BOM Code
201275590191
201248700072
2011487A0003
2011374A0005
201100320624
202400300051
201275590219
201257290010
201248700262
201557190043
201557190044
201557190045
201657290044
201657290037
2011487G0001
2012487G0011
201275590093
201248790014
201248700056
201148790000
201248700266
201157390007
203375590343
201319901145
202301450121
202301450116
201157390005
201375590213
202300500328
201275590179
201357190031
202301901085
202301300111
202301310075
202301000523
201675490388
202301820021
will be updated
202301820020
201601100168
201675591195
201600600124
201600770802
202448200000
201401500220
201245000901
201601000074
201675591192
201600740704
201601300033
201600320003
201600320001
202402220152
Part Name
Top cover assembly
Front panel
Air outlet grille
Round sticker of air outlet grille
Axial flow fan
Asynchronous motor
Supporter assembly of fan motor
Partition board assembly
Left supporter
Condenser assembly
Condenser assembly
Condenser assembly
Input pipe assembly
Fluted pipe assembly
Rear net
Rear net frame
Chassis assembly
Valve plate
Front right clapboard assembly
Water collector
Rear right clapboard assembly
Big handle
Electronic control box assembly
Outdoor Power Supply Plate Subassembly
Wire joint
Wire joint
Installing Plate
Main control board assembly
Rectifier bridge
E-part box Subassembly
Inverter control board assembly
Radiator
Pipe temperature sensor assembly
Ambient temperature sensor assembly
Electrical inductance
Suction pipe assembly
Pressure switch
Discharge pipe assembly
Pressure switch
Oil separator
4-way valve assembly
4-Ways valve
Gas valve
Discharge temperature sensor
Compressor
Fix clamp of segregator
Accumulator cylinder
liquid valve assembly
Liquid valve
Electronic expansion valve
Copper nut
Copper nut
Compressor wire assembly
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Outdoor Units
Outdoor Units
159
BOM Code
Part
Name
Quantity
1
2
201275590191
201248700072
1
1
2011487A0003
2011374A0005
1
1
4
5
201100320624
202400300051
1
1
6
7
201275590219
201275590234
1
1
8
9
201248700262
201557190043
Left supporter
Condenser assembly
1
1
9.1
9.1
201557190044
201557190045
Condenser assembly
Condenser assembly
1
1
9.2
9.3
201657290044
201657290037
1
1
10
11
2011487G0001
2012487G0011
Rear net
Rear net frame
1
1
12
13
201275490004
201248790014
Chassis assembly
Valve plate
1
1
14
15
201248700056
201148790000
1
1
16
17
201248700266
201157390007
1
1
18
18.1
203375590342
201375890118
1
1
18.2
18.3
202301310068
202300500326
1
1
18.3
18.4
202300500956
202300850043
Rectifier bridge
Contactor
1
1
18.5
18.6
201375590211
201175890008
1
1
18.7
18.8
201375590192
201175590323
1
1
18.9
18.9
202301450139
202301450121
Wire joint
Wire joint
1
1
18.10
18.11
202401000073
201200100011
Capacitor
Capacitor Clamp
1
1
18.12
18.13
202301000016
202301901144
Magnetic Loop
Radiator
2
1
18.14
18.15
201247790001
201375590172
1
1
18.16
19
201175890006
202450200331
Installation Board
Pipe temperature sensor assembly
1
1
20
22
202301300197
201675591155
1
1
160
Outdoor Units
No.
BOM Code
Part
Name
Quantity
22.1
23
202301820021
will be updated
Pressure switch
Discharge pipe assembly
1
1
23.1
23.2
202301820020
201601100168
Pressure switch
Oil separator
1
1
24
24.1
201675591194
201600600124
1
1
24.2
25
201600770802
202301300124
Gas valve
Discharge temperature sensor
1
1
26
29
201401500230
201601100060
Compressor
Accumulator cylinder
1
1
30
30.1
201675591192
201600740704
1
1
30.2
31
201601300033
201600320003
1
1
31
33
201600320001
201238090037
Copper nut
Electric inductance cover
1
1
34
35
201238090038
202301000256
1
1
36
201250200305
Inductance Holder
Outdoor Units
161
5A0-005
162
Outdoor Units
BOM Code
Part
Name
Quantity
202301390003
2
3
201175690001
201575790146
Rear net
Condenser assembly
1
1
3.1
3.1
201575790144
201575790145
Condenser assembly
Condenser assembly
1
1
3.2
3.3
201675790936
201675591150
1
1
4
5
202450200331
201248100325
1
1
6
7
201248700199
201148700009
1
2
8
9
201148790000
201248700204
Water collector
Front clapboard assembly
1
1
10
11
201248790014
201248700290
Valve plate
Chassis
1
1
12
13
201248700235
201601000636
1
1
14
15
201248700067
201275690067
1
1
16
2011487A0002
2011374A0005
2
2
17
18
201248700201
201100300045
Front panel
Axial flow fan
1
2
19
20
202400370026
201248700245
Fan motor
Supporter assembly of fan motor
2
1
21
22
201248300231
201275690066
Support Board
Supporting bar
1
1
23
24
201248300242
201401500300
1
1
25
25.1
201675890878
202301820021
1
1
26
26.1
will be updated
202301820038
1
1
26.2
27
201601100168
202301300124
Oil separator
Discharge temperature sensor assembly
1
1
28
28.1
201675790959
201600600124
1
1
28.2
29
201600770802
201675790952
Gas valve
Liquid valve assembly
1
1
29.1
29.2
201600740704
201601300022
Liquid valve
Electronic expansion valve
1
1
31
31.1
203375790126
201375790069
1
1
Outdoor Units
163
No.
BOM Code
Part
Name
Quantity
31.2
201175890009
Installation plate
31.4
31.4
202301450121
202301450139
Wire joint
Wire joint
1
1
31.5
31.7
201248700233
201375890169
1
1
31.8
31.9
201175590323
201275890158
Installing Plate
Connecting board of electronic control box
1
1
31.11
31.12
202301900140
202301900139
Radiator
Radiator
1
1
31.13
31.14
201248700234
202300500326
1
1
31.15
31.16
202301310068
202301000956
1
1
32
32
201600320001
201600320003
Copper nut
Copper nut
1
1
164
Outdoor Units
Outdoor Units
165
BOM Code
Part
Name
Quantity
1
2
202301390003
201175690001
1
1
3
3.1
201575890172
201575890174
Condenser assembly
Condenser assembly
1
1
3.1
3.2
201575890173
201675890900
Condenser assembly
Input pipe assembly
1
1
3.3
4
201675890890
202450200331
1
1
5
6
201248100325
201248700199
1
1
7
8
201148700009
201148790000
Handle
Water collector
2
1
9
10
201248700204
201248790014
1
1
11
12
201248700290
201248700235
Chassis
Partition board assembly
1
1
13
14
201601000636
201248700067
Accumulator cylinder
Fix clamp of segregator
1
1
15
16
201275690067
2011487A0002
Left clapboard
Air outlet grille
1
2
17
2011374A0005
201248700201
2
1
18
19
201100300045
202400370026
2
2
20
21
201248700245
201248300231
1
1
22
23
201275690066
201248300242
Supporting bar
Top cover assembly
1
1
24
25
201401500300
201675890878
Compressor
Suction pipe assembly
1
1
25.1
26
202301820021
will be updated
Pressure switch
Discharge pipe assembly
1
1
26.1
26.2
202301820038
201601100168
Pressure switch
Oil separator
1
1
27
28
202301300124
201675790986
1
1
28.1
28.2
201600600166
201600720684
4-way valve
Gas valve
1
1
29
29.1
201675790952
201600740704
1
1
29.2
31
201601300022
203375890209
1
1
31.1
31.2
201375890175
201175890009
1
1
166
Outdoor Units
No.
BOM Code
Part
Name
Quantity
31.4
31.4
202301450121
202301450139
Wire joint
Wire joint
1
1
31.5
31.7
201248700233
201375890169
1
1
31.8
31.9
201175590323
201275890158
Installing Plate
Connecting board of electronic control box
1
1
31.11
31.12
202301900140
202301900139
Radiator
Radiator
1
1
31.13
31.14
201248700234
202300500326
1
1
31.15
31.16
202301310068
202301000950
1
1
31.16
32
202301000956
201600320004
Reactor
Copper nut
1
1
32
201600320001
Copper nut
Outdoor Units
167
Installation
Part 4
Installation
1. Installation Procedure ................................................... 169
2. Location selection ......................................................... 170
3. Indoor unit installation .................................................. 171
4. Outdoor unit installation (Side Discharge Unit) .......... 187
5. Refrigerant pipe installation ......................................... 189
6. Drainage pipe installation ............................................. 192
7. Vacuum Drying and Leakage Checking ...................... 196
8. Additional refrigerant charge ....................................... 197
9. Engineering of insulation ............................................. 197
10. Engineering of electrical wiring ................................... 198
11. Test operation ................................................................ 199
168
Installation
Installation Procedure
1. Installation Procedure
Indoor unit installation
location selection
Refrigerant pipe
installation and insulation
Refrigerant pipe
installation and insulation
Test operation
Installation
169
Location selection
2. Location selection
2.1 Indoor unit location selection
Fe
n
ob ce o
s ta
r
cle
s
More than 60cm
More than 200cm
170
Installation
Model
JOSI-DBC024-N11
JOSI-DBC030-N11
JOSI-DBC036-N11
JOSI-DBC048-N11
A
245
245
245
287
H
>275
>275
>275
>317
Installation
171
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's
lower part should sink into the ceiling for 10~12 mm. In general, L is half of the screw length of the
installation hook.
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
172
Installation
Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifing
the grille, DO NOT make the ropes enwinded or blocked.
Installation
173
Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate
water.
174
Installation
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control
box with corresponding terminators on the body respectively.
Install the 4 corner covers back.
Installation
175
Model
176
JOSI-DCD012-N11
740
350
JOSI-DCD018-N11
960
350
JOSI-DCD024-N11
960
350
JOSI-DCD030-N11
1180
490
JOSI-DCD036-N11
1180
490
JOSI-DCD048-N11
1240
500
Installation
Installation
177
Stick the attached seal sponge as per the indicating place in the following fig, and then change the
mounting positions of air return panel and air return flange .
When install the filter mesh, please plug it into flange inclined from air return opening, and then push up.
The installation has finish, upon filter mesh which fixing blocks have been insert to the flange positional
holes.
178
Installation
JOSI-DCD060-N11
3.2.1 Service space for indoor unit
500mm or more
600mm or more
Indoor unit
Installation
179
Model
JOSI-DCD060-N11
700
1436
180
Installation
Model
JOSI-DBF018-N11
983
220
JOSI-DBF024-N11
983
220
JOSI-DBF030-N11
1200
220
JOSI-DBF036-N11
1200
220
JOSI-DBF048-N11
1565
220
Wall-mounted installation
Installation
181
Wall-mounted installation
Install the tapping screws onto the wall.(Refer to picture below)
Locate the hanging arm on the hanging screw bolt. Prepare the mounting bolts on the unit.
182
Installation
Wall-mounted installation
Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of
body can touch with floor or suspended, but the body must install vertically.)
Installation
183
184
Installation
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the
installation hooks from the height of ceiling, then cut off the unnecessary part.
If the ceiling is extremely high, please determine the length of the installation hook depending on the real
situation.
3.4.4 Install the main body
Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on
the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure
the levelness of the main body is within 1.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's
lower part should sink into the ceiling for 10~12 mm. In general, L is half of the screw length of the
installation hook.
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
Installation
185
Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate
water.
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control
box with corresponding terminators on the body respectively.
Note: The panel shall be installed after the wiring connected.
Installation
187
Air inlet
Maintain channel
Air inlet
Model
JOAU-DLY012-H11
JOAU-DLY018-H11
JOAU-DLY024-H11
JOAU-DLY030-H11
JOAU-DLY036-H11
JOAU-DLY036-H13
JOAU-DLY048-H13
JOAU-DLY060-H13
B
530
560
590
590
624
624
633.5
633.5
C
290
335
333
333
366
366
404
404
D
315
360
355
355
396
396
448
448
188
Installation
Max. Length
Max. Elevation
12,000Btu/h
25m
10m
18,000Btu/h
30m
20m
24,000Btu/h~30,000Btu/h
50m
25m
36,000Btu/h ~60,000Btu/h
65m
30m
90
Lean
Crude
Burr
Before test operation, the joint parts should not be heat insulated.
5.2.6 Flare the pipe
Insert a flare nut into the pipe before flaring the pipe
According to the following table to flare the pipe
Installation
189
1/4" (6.35)
Flare shape
Min
Max
8.3
8.7
+- 4
90
45
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
R0.4~0.8
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe
connection.
Torque
Sketch map
Pipe Diameter
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
190
Installation
Drop
Height
Pipe
Length
Note: All used branch pipe must be produced by Midea, otherwise it causes malfunction.
The indoor units should be installed equivalently at the both side of the U type branch
pipe.
Permitted Value
18K+18K
30m
24K+24K
50m
30K+30K
50m
15m
10m
Piping
L+L1+L2
L1, L2
L1-L2
20m
H1
0.5m
H2
5.3.4 The branching pipe must be installed horizontally, error angle of it should not large than 10. Otherwise,
malfunction will be caused.
Installation
191
12
2.4
18
24
30
36
42
10
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
Installation
PVC25
PVC32
Slope 1/100
20
39
27
25
70
50
PVC40
31
125
88
PVC50
40
247
175
PVC63
51
473
334
Remark
For branch pipe
PVC25
PVC32
25
410
PVC40
31
730
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
PVC pipe
Remark
220
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Drainage pipe
Water flow
Water flow
Water flow
Installation
Water flow
Drain tee
Drain tee
Drainage pipe
Water flow
Water flow
Drain tee
Water flow
Water flow
Water flow
193
Water flow
Gas
Gas
Water flow
Main pipe
Main pipe
Branch pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Indoor unit
More than 50mm
Plug
More than 25mm
Water storage pipe
Hanger
A
Installation
Indoor unit
Plug
6.2.9 The end of drainage pipe shall not contact with ground directly.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
Installation
195
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note: Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
Installation
Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the
pressure for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it
indicates that there is moisture or leak source.
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
6.35
9.52
V=15g/m(L -5)
V=30g/m(L -5)
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe insulation (except joint section) flare the pipe piping layout and connection
vacuum drying insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
Temperature of gas pipe is very high (generally 50-100) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120
According to the local law to choose insulation materials
The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Installation
197
Liquid pipe
Insulation meterial
Gas pipe
The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material.
The insulation material at the joint pipe shall be inserted into the gap of the insulation material.
The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
The linking part should be use glue to paste together
Be sure not bind the insulation material over-tight, it may extrude out the air in the material to cause bad
insulation and cause easy aging of the material.
198
Test operation
Do not use metal wire tube at the place with acid or alkali corrosion, adopt plastic wire tube to replace it.
There must be not wire connect joint in the wire tube If joint is a must, set a connection box at the place.
The wiring with different voltage should not be in one wire tube.
Ensure that the color of the wires of outdoor and the terminal No. are same as those of indoor unit
respectively.
Installation
199
Part 5
Electrical Control System
1. Electrical Control Function.........................................201
2. Troubleshooting ...........................................................214
200
T2:
T4:
T5:
201
T1-24
6.0
5.0
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
4.0
c
d
e
2.5
1.0
For DBC012
3.5
High
3.0
1.5
Medium
1.0
Low
Ts=24
For other models:
5.0
High
4.0
3.0
Medium
2.0
Low
Ts=24
1.3.2 Cooling Mode
1.3.2.1 Outdoor PMW open angle control
The unit is working in cooling mode with the EXV open 300P(For 12K, it is 220P) for 3 minutes, then
adjusting PMW open angle according to the temperature of compressor discharge every 2 minutes.
202
DC_FAN_HI_SPD_ADD
DC_FAN_MID_SPD_ADD
DC_FAN_MIN_SPD_ADD
DC_FAN_SLOW_SPD_ADD
DC_FAN_SSLOW_SPD_ADD
26
25
23
22
20
19
17
6.0
5.0
4.0
2.5
1.0
H
a
b
c
d
e
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
203
For DBC012
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low, auto and
silent.
The auto fan:
3.5
High
3.0
Medium
1.5
1.0
Low
5.0
High
4.0
3.0
Medium
2.0
Low
When T2<2 and lasts for 3 minutes, the indoor has no capacity demand and resume till T27.
When set point <17,and the T2<7, the indoor fan will be forced to run the speed RAFANC6 (1200
rpm for FWDB18, 1350rpm for FWDB24) till the T2>10
For other models: When T2<2 and lasts for 3 minutes, the indoor has no capacity demand and resume till
T27.
204
DC_FAN_SSLOW_SPD_ADD
DC_FAN_SLOW_SPD_ADD
DC_FAN_MIN_SPD_ADD
DC_FAN_MID_SPD_ADD
DC_FAN_HI_SPD_ADD
19
18
16
15
13
12
10
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Auto fan action in heating mode:
Electrical Control System
205
0.0
-1.0
L
(H+-L)*0.2+L
(H+-L)*0.4+L
-2.0
-3.0
(H+-L)*0.6+L
-4.0
(H+-L)*0.6+L
-5.0
-6.0
-6.5
(H+-L)*0.8+L
H+
For DBC012:
When the compressor is on, the indoor fan can be set to high, medium, low, auto and silent. And the
anti-cold wind function has the priority.
Auto fan action:
T1-Ts-T
Low
-3.5
-4
Medium
-4.5
-5
High
206
High
Frequency F3 FrequencyF16
on
Compressor
4-way valve
Outdoor fan
Indoor fan
off
on
off
on
off
on
off
10s
xx
10s
30s
xx=90
The other models:
Electrical Control System
207
Condition of defrosting:
T4
Time1
3
Time2
Time conditions:
time1
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T43
3. Compressor is on
4. T3TempEnterDefrost_ADD
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off.
2. T3TempEnterDefrost_ADD
Time2
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4<3
3. Compressor is on
4. T3TempEnterDefrost_ADD
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3TempEnterDefrost_ADD +2 last for 20 minutes
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time240 minutes, When defrosting is end,time1 and time2 are cleared.
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
The defrosting time achieves 10min;
T3 TempQuitDefrost_ADD;
T3 7 for 60seconds.
Defrosting action
208
Indoor fan
TimeA 10S
10S 30S
Outdoor fan
PMV running
8 mins with 300P
PMV
480P
T2
Off
TEstop
Decrease
TEdown
Hold
TEnorm
Resume
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30.
In auto mode, the machine will choose cooling, heating or fan-only mode according to T (T =T1-Ts).
For 12K models:
T=T1-Ts
Running mode
T1
Cooling
-1<T1
Fan-only
T-1
Heating
209
Running mode
T2
Cooling
-1T<2
Fan-only
T<-1
Heating
210
When heating, the setting temperature decreases 1 (be higher than 17) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesnt turns off,
but for console, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.10 Follow me
1)
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the
indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not
respond. When the unit is running with follow-me function, the PCB will control the unit according to the
temperature from follow-me signal, and the temperature collection function of room temperature sensor
will be shielded.
2)
When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.
3)
The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4)
When the unit is running with follow-me function, if the PCB doesnt receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
211
When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once.
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.
Display
Remark
00
Normal display
01
02
04
05
06
07
08
09
10
AD value of current
11
AD value of voltage
12
13
14
15
03
212
If the temp. is lower than 0 degree, the digital display tube will
show 0.If the temp. is higher than 70 degree, the digital
display tube will show 70.
If the temp. is lower than -9 degree, the digital display tube will
show -9.If the temp. is higher than 70 degree, the digital
display tube will show 70. If the indoor unit is not connected,
the digital display tube will show:
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show 13.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show 0.5,it means the compressor discharge
temp. is 105 degree. the digital display tube show 1.6,it
means the compressor discharge temp. is 116 degree)
The display value is hex number.
Frequency limit
caused by T3.
Frequency limit
caused by T5.
Frequency limit
caused by current
Frequency limit
caused by voltage
17
18
19
1# indoor unit
If the temp. is lower than 0 degree, the digital display tube will
20
2# indoor unit
21
3# indoor unit
22
23
24
213
Troubleshooting
2. Troubleshooting
2.1 Display board
2.1.1 Icon explanation on indoor display board (Super slim cassette).
PRE-DEF indicator(cooling and
heating type)
or fan only indicator(cooling only
type)
Temporary button
FUNC
Operation temp.
Timer indicator
Digital LED
Alarm indicator
Alarm indicator
Operation lamp
Temporary button
FUNC
214
Troubleshooting
2.1.4
Alarm indicator
FUNC
Temporary button
215
Troubleshooting
Malfunction
Running lamp
Timer lamp
Defrosting lamp
10
11
12
Running lamp
Timer lamp
Defrosting lamp
O(light)
(flash at 0.5Hz)
Malfunction
X(off)
(flash at 5Hz)
(flash at 0.5Hz)
Malfunction
Defrosting
lamp
Alarm
lamp
Running lamp
Timer
lamp
Display(digital
tube)
E0
E1
E2
Full-water malfunction
E3
E4
E5
E6
E7
EC
10
P0
216
Troubleshooting
11
P1
12
P2
13
P4
14
F5
O (on)
X(off)
(flash at 5Hz)
(flash at 0.5Hz)
Malfunction
Defrosting
lamp
Alarm
lamp
Running lamp
Timer
lamp
Display(digital
tube)
E1
E2
E3
E4
E7
E8
EC
Ed
Full-water malfunction
EE
10
F3
11
F4
O (on)
X(off)
(flash at 5Hz)
(flash at 0.5Hz)
217
Troubleshooting
Malfunction or Protection
E0
E2
E3
E4
E5
E6
E8
P0
P1
P2
P3
P4
P5
P6
P7
In low ambient cooling mode, the LED displaysLC or alternative displays between running frequency
and LC(each displays 0.5s)
218
Troubleshooting
No
Yes
Is it normal?
Yes
No
Replace the sensor
219
Troubleshooting
Yes
No
No
No
No
Yes
Replace the indoor PCB
220
Trouble is solved
Troubleshooting
No
Yes
Replace the indoor PCB.
No
Yes
Yes
No
Yes
Check PCB board or replace the indoor main PCB
221
Troubleshooting
No
Yes
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
No
No
Yes
Check the wires of fan
motor. Are all the
connections good?
Yes
Check whether the fan
motor is normal through
index 1?
No
If the
malfunction is
still existing,
replace the
main PCB
No
Yes
No
Replace the
main PCB.
The
malfunction is
solved?
Yes
222
Troubleshooting
Index 1:
1.Indoor DC fan motor(control chip is inside fan motor)
Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan
motor must have problems and need to be replaced.
For other models:
NO.
1
2
3
4
5
6
For console:
Color
Red
--Black
White
Yellow
Blue
5
4
6
1
2
NO.
Color
Red
---
White
Blue
Yellow
Black
Index2:
1. Indoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
For other models:
223
Troubleshooting
Signal
Vs/Vm
--GND
Vcc
Vsp
FG
Voltage
192V~380V
--0V
13.5-16.5V
0~6.5V
15V
5
4
6
1
2
DC motor voltage input and output
NO.
224
Color
Signal
Voltage
Red
VDC
310V
---
---
---
White
Vcc
15V
Blue
FG
15V
Yellow
Vsp
0-7.5V
Black
GND
0V
Troubleshooting
Yes
No
Yes
Yes
225
Troubleshooting
2.4.2 For the unit with TWINS function(For the super-slim cassette & A5 duct)
2.4.2.1 Communication malfunction between master unit and indoor unit
F3
F3 Displayed
Displayed
Communication
Communication failure
failure between
between
master
unit
and
master unit and slave
slave unit
unit
Check
Check the
the dial
dial switch
switch settings
settings of
of
master
unit
and
slave
unit,
master unit and slave unit, isis itit right?
right?
No
Correct
Correct the
the
settings
settings
Yes
Check
Check the
the PQE
PQE communication
communication wires
wires
connection,
connection, isis itit good
good enough?
enough?
No
Correct
Correct the
the wire
wire
connections
connections
Yes
One
One of
of the
the 22 indoor
indoor PCBs
PCBs isis defective.
defective.
Connect
Connect only
only one
one indoor
indoor unit
unit to
to the
the outdoor
outdoor
unit
unit separately.
separately. The
The one
one caused
caused E1
E1 error
error code
code
isis defective
defective
Problem
Problem isis solved
solved
226
Troubleshooting
No
Yes
Replace the outdoor main board
227
Troubleshooting
2.4.3.2. E2 malfunction
E2 display
Yes
Remove interference.
Increase the capacity of antiinterference
No
No
Check whether the signal wire
is shield cable or whether the
shield cable is earthing?
Yes
Check whether the wire is
correct polarity? P to P, Q to Q,
E to E?
No
Yes
No
Yes
Check whether the signal wire
is broken?
No
Check whether the signal wires
insert on PCB well?
Yes
Replace indoor PCB, is the error
distinguished?
No
Replace the outdoor PCB.
228
Troubleshooting
2.4.3.3. E3 malfunction
E3 display
No
Check the signal wire between
the IPM module and the main
board, is it connected good?
Yes
No
Yes
Reconnect and retry. Is
error still display?
No
No
Replace IPM board, and
then check whether the
system can run normally
Yes
No
Replace outdoor main
board, and then check
whether the system can run
normally
Yes
No
Replace the electric control
box
Trouble is solved
229
Troubleshooting
2.4.3.4. E4 malfunction
E4 display
Yes
No
Check whether the resistance of
condenser temp. sensorT3) is
wrong refer to the Appendix 1
Yes
No
Yes
No
Check whether the resistance of
outdoor ambient temperature
sensor (T4) is wrong refer to the
Appendix 1
Yes
No
230
Troubleshooting
Voltage protection
No
Yes
Replace the power board,
then check whether the
system can run normally
No
Check whether the voltage
of IPM board P and N is
normal? DC277-356V for
18K/24K/30KBtu/h; DC277410V for 36K/48KBtu/h
Yes
No
Yes
Yes
No
Yes
No
Trouble is solved
231
Troubleshooting
Voltage protection
No
Yes
Replace the power board,
then check whether the
system can run normally
No
Check whether the voltage
range of P-N on IPM module is
normal? DC 350-650V
Yes
No
Yes
Yes
No
Yes
No
232
Trouble is solved
Troubleshooting
Yes
No
No
Yes
No
Yes
410V
No
Check
whether
the
inductance of PFC module
is good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the PFC module
Trouble is solved
233
Troubleshooting
2.4.3.8. E8 malfunction
E8 display
No
Yes
Shut off the power supply,
rotate the fan by hand. Does
it rotate properly?
No
Yes
Check the wires of fan motor.
Are all the connections good?
No
Yes
Check the voltage between port
1 and 3 of fan motor connector,
is it within 140V~380V?
No
Yes
Replace indoor main PCB. Is it
still displaying the error code?
Color
Signal
Voltage
Red
Vs/Vm
---
---
140380V
---
Black
GND
0V
White
Vcc
13.5~16.5V
Yellow
Vsp
0~6.5V
Blue
FG
15V
234
Troubleshooting
2.4.3.8. P0 malfunction
P0 display
Temperature protection of
compressor top
Whether compressor
operates?
Yes
No
No
Yes
Whether refrigerant
circulation volume is
normal?
Whether protector is normal? If
protector is normal,resistance = 0
No
No
Charge refrigerant
Yes
Replace the outdoor main PCB
Whether abnormality is the
same after gas charging?
No
235
Troubleshooting
No
Connect it well
Yes
Judge 2: Whether
the high pressure
protector is broken
Yes
Yes
No
Check whether
the refrigerant
system is ok
Yes
No
Yes
Yes
236
Troubleshooting
No
Connect it well
Yes
Judge 2: Whether
the low pressure
protector is broken
Yes
Yes
No
Check whether
the refrigerant
system is ok
Yes
Yes
No
No
Replace outdoor main board
237
Troubleshooting
2.4.3.11. P3 malfunction
P3 display
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
238
Yes
Trouble is solved
Troubleshooting
2.4.3.12. P4 malfunction
When compressor discharge temperature is higher than 115C, the unit will stop, and unit runs again when
compressor discharge temperature is lower than 90C.
P4 display
Temperature protection of
compressor discharge
Yes
Yes
No
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
No
Yes
Judge: The
discharge temp.
sensor is broken
No
Yes
Trouble is solved
239
Troubleshooting
2.4.3.13. P5 malfunction
When condenser high temp. is more than 65C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52C.
P5 display
Yes
Yes
Yes
No
Yes
No
No
240
Yes
Troubleshooting
No
Regulate it to correct,
then check whether the
system can work
normally?
No
Yes
No
Yes
Check whether the
connecting line between main
board and the IPM module is
connected tightly
No
Connect it tightly,
check ok or not?
Connect it correctly
and tightly, check ok
or not?
No
Yes
No
No
Yes
Connect it well,
check ok or not?
No
No
Connect it tightly,
check ok or not?
Yes
No
Yes
No
No
No
Yes
Yes
Yes
No
No
Replace the compressor,
check whether the system
can work normally?
Yes
Yes
Replace the connecting line or
reactor or replace the PFC
module
Trouble is solved
241
Troubleshooting
No
Regulate it to correct,
then check whether the
system can work
normally?
No
Yes
No
Yes
Check whether the
connecting line between main
board and the IPM module is
connected tightly
No
Connect it tightly,
check ok or not?
Connect it correctly
and tightly, check ok
or not?
No
Yes
No
No
Yes
Connect it well,
check ok or not?
No
No
Connect it tightly,
check ok or not?
Yes
No
Yes
No
No
No
Yes
Yes
Yes
No
No
Yes
Trouble is solved
Yes
242
Troubleshooting
2.4.3.16. P7 malfunction
P7 display
Whether compressor
operates?
No
Whether the
connection is
good?
Yes
Yes
Check the
resistance value of
the sensor via
Appendix 1,Is it
normal?
No
No
No
Clean the heat exchanger and
the air-outlet
Yes
No
No
Check refrigerant system
(such as clogging of
capillary etc.)
243
Troubleshooting
K Ohm
K Ohm
12.6431
60
K Ohm
2.35774
100
K Ohm
0.62973
-19
115.266
108.146
20
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
-15
84.2190
25
10.000
65
1.96532
105
0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10
62.2756
30
7.97078
70
1.64691
110
0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5
46.5725
35
6.40021
75
1.38703
115
0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
35.2024
40
5.17519
80
1.17393
120
0.35982
33.3269
41
4.96392
81
1.13604
121
0.35042
31.5635
42
4.76253
82
1.09958
122
0.3413
29.9058
43
4.57050
83
1.06448
123
0.33246
28.3459
44
4.38736
84
1.03069
124
0.32390
26.8778
45
4.21263
85
0.99815
125
0.31559
25.4954
46
4.04589
86
0.96681
126
0.30754
24.1932
47
3.88673
87
0.93662
127
0.29974
22.5662
48
3.73476
88
0.90753
128
0.29216
21.8094
49
3.58962
89
0.87950
129
0.28482
10
20.7184
50
3.45097
90
0.85248
130
0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15
16.1156
55
2.84421
95
0.73119
135
0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
-20
244
(--K)
Troubleshooting
Appendix 2
Unit: ---K
-20
542.7
20
68.66
60
13.59
100
3.702
-19
511.9
21
65.62
-18
483
22
62.73
61
13.11
101
3.595
62
12.65
102
3.492
-17
455.9
23
59.98
63
12.21
103
3.392
-16
430.5
-15
406.7
24
57.37
64
11.79
104
3.296
25
54.89
65
11.38
105
3.203
-14
384.3
26
52.53
66
10.99
106
3.113
-13
363.3
27
50.28
67
10.61
107
3.025
-12
343.6
28
48.14
68
10.25
108
2.941
-11
325.1
29
46.11
69
9.902
109
2.86
-10
307.7
30
44.17
70
9.569
110
2.781
-9
291.3
31
42.33
71
9.248
111
2.704
-8
275.9
32
40.57
72
8.94
112
2.63
-7
261.4
33
38.89
73
8.643
113
2.559
-6
247.8
34
37.3
74
8.358
114
2.489
-5
234.9
35
35.78
75
8.084
115
2.422
-4
222.8
36
34.32
76
7.82
116
2.357
-3
211.4
37
32.94
77
7.566
117
2.294
-2
200.7
38
31.62
78
7.321
118
2.233
-1
190.5
39
30.36
79
7.086
119
2.174
180.9
40
29.15
80
6.859
120
2.117
171.9
41
28
81
6.641
121
2.061
163.3
42
26.9
82
6.43
122
2.007
155.2
43
25.86
83
6.228
123
1.955
147.6
44
24.85
84
6.033
124
1.905
140.4
45
23.89
85
5.844
125
1.856
133.5
46
22.89
86
5.663
126
1.808
127.1
47
22.1
87
5.488
127
1.762
121
48
21.26
88
5.32
128
1.717
115.2
49
20.46
89
5.157
129
1.674
10
109.8
50
19.69
90
130
1.632
11
104.6
51
18.96
91
4.849
12
99.69
52
18.26
92
4.703
13
95.05
53
17.58
93
4.562
14
90.66
54
16.94
94
4.426
15
86.49
55
16.32
95
4.294
16
82.54
56
15.73
96
4.167
17
78.79
57
15.16
97
4.045
18
75.24
58
14.62
98
3.927
19
71.86
59
14.09
99
3.812
B(25/50)=3950K
R(90)=5K3%
245
SERVICE MANUAL