September, 2012
Single Line
BUSBAR 7
34.5 kV
BUSBAR 6
0.453 kA
182.87 MVA
3.060 kA
0.000 kA
34.5 kV
BUSBAR 3
ZL1=1.086 pu
34.5 kV
0.000 kA
7
L2
L3
0.453 kA
BUSBAR 4
2.170 kA 0.651 kA
250/5
115/34.5 kV
15 MVA
Z%=10 TR1
Yy0
115kV
34.5 kV
5
34.5/13.2 kV
3 MVA
TR2
Z%=7.3
Dy1
4
BUSBAR 1
1
1 MVA
13.2 kV
2
1 MVA
1 MVA
L4
34.5 kV
1 MVA
BUSBAR 2
BUSBAR 5
Data
Calculate the following:
3. The settings of the instantaneous elements, and the TAP and DIAL
settings of the relays to guarantee a coordinated protection
arrangement, allowing a discrimination margin of 0.4 seconds
P = 100 MVA
Data
TAP = 4 A
DIAL = 5
Instantaneous = 1100 A
Data
Now, consider all the relays to be set are Beckwith M-7651, numerical
type with the characteristics indicated in the following slide. The relays
have an extremely inverse time current characteristic with the following
constants:
= 2.0,
= 80
L=0
Time Dial * 80
The TCC is defined by t MULT 2 1
Where MULT = Fault current (in secondary amps)/TAP
The following considerations have to be taken into account:
For setting of the instantaneous element a value of ten (10) times the
maximum load current is used.
The margin time for this relay can be 0.2 s since it is of numerical type.
Relay 7 is the same W CO 11 with TAP = 4 A, DIAL = 5 and Inst =
1100 A
Calculation parameters:
System frequency in Hz
Number of elements
Number of nodes
Calculation method
Kind of fault
Ik"max calculation
Interrupting times in cycles for Ib
Short circuit duration for iDC in cycles
Node voltages from loadflow (superposition method)
60.0
9
7
ANSI/IEEE
3 phase SC
Yes
3.000
0.020
No
BUSBAR5
BUSBAR4
BUSBAR7
BUSBAR7
BUSBAR7
BUSBAR1
BUSBAR1
BUSBAR4
Element
name
Type
L1
L2
L4
L3
TR1
Line
Line
Line
Line
2W Transformer
L1
TR2
Line
2W Transformer
L2
L4
G8
34,5
19,919
180
G15
34,5
19,919
180
34,5
8,281
179,94
0
0,453
0,453
179,94
0,453
0,453
8,988
180
2W Transformer
Network Feeder
0,651
0,651
13,2
TR2
8,281
Line
Synchronous
Machine
115
TR1
EQUIVALENT
2W Transformer
Ik" (RST)
[kA]
3,06
0
0
0,453
0,453
2,17
0
0
Line
Synchronous
Machine
BUSBAR2
AU L-E
(RST) []
180
34,5
L3
BUSBAR6
BUSBAR7
34,5
UL-E (RST)
[kV]
19,919
Un [kV]
Line
1
BUSBAR6
7,621
180
0
Tap setting
Iload1,2,3 = 43.74 A
Iload4 = 131,22 A
Iload5 = 50.20 A
Iload6 = 50.20 A
Iload8 = 251.02 A
Iload9 = 75.31 A
Breaker
No.
Pnom
(MVA)
Inom
(A)
Isc
(A)
9
8
7
6
5
4
1,2,3
15
15
1
3
3
3
1
75.31
251.02
16.73
50.20
50.20
131.22
43.74
4797.35
2170.40
3060.34
3060.34
1025.67
1076.06
1076.06
5/100
Isc
(A)
CT
Ratio
233.12
108.51
153.01
153.01
51.28
53.80
53.80
250/5
300/5
200/5
200/5
100/5
200/5
100/5
0.05 80
0.092s
6.6682 1
Relay 4
To coordinate with relays 1, 2 and 3 at 437.4 A ,
relay 4 requires that t4a = 0.092 0.2 = 0.292 s.
0.292
2
Time Dial
2.223 1 0.01
80
However, the dial 0.05 is the minimum that the relay has.
The operating time for a line-to-line fault is determined by taking
86% of the three-phase fault current.
MULT4b = (0.86)(1076.06)(5/200)(1/4.92) = 4.702 times.
t 4b
0.05 80
0.190s
2
4.627 1
0.390
2
Time Dial
5.475 1 0.14
80
0.14 80
0.244s
2
6.843 1
0.444
2
Time Dial
6.843 1 0.25
80
0.25 80
0.094s
2
14.628 1
0.91
2
Time Dial
2.07 1 0.04
80
However, the Time Dial 0.05 is the minimum that the relay has. No
instantaneous setting is given to relay 8 for the reasons already given. The
maximum short circuit current to be used for this relay is that which flows
from the 115 kV to the 34.5 kV busbar for a fault on the latter,
MULTb = 2170.39 (5/300) (1/6.28) = 5.76 times. At 5.76 times and Time Dial 0.05,
t
0.05 80
0.124s
2
5.76 1
0.324
2
Time Dial
5.762 1 0.13
80
Relay
No.
CT ratio
Tap
DIAL
Instantaneous
1,2,3
4
5
6
7
8
9
100/5
200/5
100/5
200/5
200/5
300/5
250/5
3.28
4.92
3.76
1.88
4
6.28
2.26
0.05
0.05
0.14
0.25
5
0.05
0.13
21.87 A
25.73 A
32.05 A
27.5 A
16.27 A
T-2
T-1
R-3
100 s
R-7
10,0 s
R-4
R-8
R-5
R-9
1,0 s
R-6
L-1
0,100 s
0,010 s
13,2 kV:0,010 kA
35 kV:
0,010 kA
0,100 kA
0,100 kA
1,0 kA
10,0 kA
1,0 kA
10,0 kA
100 kA
100 kA
1000 kA
% = (Ks(1-Ki)+1)/Ki
and
Ks = Zsource/Zelement
Ks = 6.50/12.92 = 0.50
Therefore, % = (0.50 x (1-1.25)+1)/1.25 = 0.70
This indicates that the instantaneous element covers 70% of the line.
Questions ?