Escolar Documentos
Profissional Documentos
Cultura Documentos
CHAPTER 7
FLAMEPROOF ENCLOSURES
Field drilling of flameproof, Ex-d, enclosures is not
allowed. To maintain the IEC or CENELEC certificate,
these enclosures can only be modified by the
manufacturer.
Flat machine joints are not allowed for Group A and B gases
with explosionproof or for IIC gases with flameproof.
Manufacturers use threaded or spigot joints for Groups A, B or
IIC certifications.
Flamepath
Gap
Flamepath
Flamepath
Flat joints (left) are used for IIA and IIB gases. Spigot joints (right) or
threaded joints (not shown) allow manufacturers to obtain Groups A, B or
IIC certifications.
Table 7.1
Summary of Differences Between Explosionproof and Flameproof
CONSIDERATION
EXPLOSIONPROOF
FLAMEPROOF
Field Drilling
Acceptable
Pressure testing
4 times maximum
Construction
Heavier
Lighter
Joints
Heat rise
Wiring room
Entries
41
Distance
IIA
10 mm
IIB
30 mm
IIC
40 mm
Covers on Ex-d enclosures must be secured so they can only be removed with
special tools. The Ex-d flameproof junction box from the Cooper CrouseHinds, Nortem facility in Spain has a hex-head cover locking screw, external
ground and thread openings for conduit or cable.
1. Temperature changes can suck gas/air mixtures into the enclosure
2. When the gas/air mixture is between the the Upper and Lower Flammable
Limits and a spark occurs, ignition and an internal explosion can occur.
3. The hot compressed gases are forced out through the flamepath, but must
not ignite any surrounding external potentially explosive atmosphere. The
flamepath cools the hot, compressed gases as they are expelled, preventing
any explosions of external atmospheres.
42
Flat joints can only be used with IIA and IIB gases. Threaded or
spigot joints are normally used for gas group IIC applications
because of the close tolerance and length of flamepath formed
by the thread. The minimum number of thread engagements is
not less than 5. The depth of engagement for up 100 cubic cm
is 5 mm and above 100 cubic cm not less than 8 mm. The
minimum width of joint and maximum gap relative to gas groups
and the enclosure volume are detailed in Table 7.2.1.
Table 7.2.1
Minimum width of joint and maximum gap for enclosures relative to Gas Groups
Gas Group
II A
IIB
IIC
Min. Joint
Width (mm)
100 cm3
0.3
9.5
0.35
0.35
12.5
0.4
0.4
0.4
0.4
25
0.5
0.5
0.5
0.5
0.3
9.5
0.3
0.3
12.5
0.3
0.3
0.3
0.2
25
0.4
0.4
0.4
0.4
0.2
9.5
0.2
0.2
12.5
0.2
0.2
0.2
0.15
25
0.2
0.2
0.2
0.2
0.1
9.5
0.1
0.1
43
Factory
sealed bushing
Ex-d gland
Sealing Fitting
Ex-e increased
safety enclosure
44
When the selected cable has spaces through which ignited gas
can travel, it is necessary to install the cable with a barrier type
cable gland. (See Fig. 7.3.2) The barrier glands are supplied
with a 2 part epoxy compound to prevent the migration of gases
and pressure piling of ignited hot gases. The only exception to
this rule is if the enclosure contains only terminals or other nonsparking devices, or if the volume of the enclosure is less than
2 liters. In these instances a standard Ex-d type cable gland
may be used.
Figure 7.32
Installing a TMCX Terminator
1. Prepare cable.
45
Conduit seals are available from Cooper Crouse-Hinds for the North
American market or from Nortem in Spain for ATEX approved seals.
46
PUMP
INJECT
SEALED
Cooper Crouse-Hinds offers the labor savings Chico A Intrapak. A twocompartment premeasured amount of Chico A sealing compound and water,
the Chico Intrapak eliminates the step of measuring before mixing. Simply
squeeze to break the water compartment, mix together, and attach the nozzle
to pour directly into the sealing fitting.
47
Chico SpeedSeal
100
=$91
90
Time (In Minutes)
80
70
60
=$56
50
40
=$44
30
20
10
=$5
=$5
=$5
0
1/2"
1"
2"
Why spend 50 minutes preparing and pouring a seal whem you can do it easier in five?
Small
explosionproof
components
eliminate the need
for seals on control
stations, breakers
and switches
48