Escolar Documentos
Profissional Documentos
Cultura Documentos
LSP2456-afpen.tif
7UT613
7UT612
Description
The SIPROTEC 7UT6 differential protection relays are used for fast and selective
fault clearing of short-circuits in transformers of all voltage levels and also in rotating electric machines like motors and
generators, for short lines and busbars.
The protection relay can be parameterized
for use with three-phase and single-phase
transformers.
The specific application can be chosen by
parameterization. In this way an optimal
adaptation of the relay to the protected object can be achieved.
In addition to the differential function, a
backup overcurrent protection for 1 winding/star point is integrated in the relay.
Optionally, a low or high-impedance restricted earth-fault protection, a negativesequence protection and a breaker failure
protection can be used. With external temperature monitoring boxes (thermo-boxes)
temperatures can be measured and monitored in the relay. Therefore, complete
thermal monitoring of a transformer is
possible, e.g. hot-spot calculation of the oil
temperature.
Protection functions
Differential protection with phase-segregated measurement
Sensitive measuring for low-fault currents
Fast tripping for high-fault currents
Restraint against inrush of transformer
Phase /earth overcurrent protection
Overload protection with or without
temperature measurement
Negative-sequence protection
Breaker failure protection
Low/high-impedance restricted earth
fault (REF)
Overexcitation protection (7UT613/633)
Control functions
Commands for control of circuitbreakers and isolators
7UT63x: Graphic display shows position of switching elements, local/remote
switching by key-operated switch
Control via keyboard, binary inputs,
DIGSI 4 or SCADA system
User-defined logic with CFC
Monitoring functions
Self-supervision of the relay
Trip circuit supervision
Oscillographic fault recording
Permanent differential and restraint
current measurement, extensive scope
of operational values
Communication interfaces
PC front port for setting with DIGSI 4
System interface
IEC 60870-5-103 protocol,
PROFIBUS-FMS/-DP,
MODBUS or DNP 3.0
Service interface for DIGSI 4 (modem)/
temperature monitoring (thermo-box)
Time synchronization via IRIG-B/DCF 77
8/3
Application
The numerical protection relays 7UT6 are
primarily applied as differential protection
on
transformers
7UT612:
2 windings
7UT613/633: 2 up to 3 windings
7UT635:
2 up to 5 windings,
generators
motors
short line sections
small busbars
parallel and series reactors.
8/4
Fig. 8/2
Function diagram
Application
Protection functions
ANSI No.
Three-phase
transformer
Single-phase
transformer
Autotransformer
Generator/
Motor
Busbar,
3-phase
Busbar,
1-phase
Differential protection
87T/G/M/L
Earth-fault differential
protection
87 N
Overcurrent-time
protection, phases
50/51
Overcurrent-time
protection 3I0
50/51N
Overcurrent-time
protection, earth
50/51G
Overcurrent-time
protection, single-phase
Negative-sequence
protection
46
Overload protection
IEC 60255-8
49
Overload protection
IEC 60354
49
Overexcitation protection *)
V/Hz
24
50 BF
External temperature
monitoring (thermo-box)
38
Lockout
86
Direct coupling 1
Direct coupling 2
Measured-value
supervision
Trip circuit supervision
74 TC
X Function applicable
Function not applicable in this application
*) Only 7UT613/63x
Construction
The 7UT6 is available in three housing
widths referred to a 19 module frame system. The height is 243 mm.
(7UT612),
(7UT613),
(7UT633/635) of 19
All cables can be connected with or without cable ring lugs. Plug-in terminals are
available as an option, it is thus possible to
employ prefabricated cable harnesses. In
the case of surface mounting on a panel,
the connection terminals are located above
and below in the form of screw-type terminals. The communication interfaces are located on the same sides of the housing. For
dimensions please refer to the dimension
drawings (part 16).
LSP2236F.tif
1/3
1/2
1/1
Fig. 8/3
Rear view with screw-type terminals
8/5
Protection functions
Differential protection for transformers
(ANSI 87T)
When the 7UT6 is employed as fast and selective short-circuit protection for transformers the following properties apply:
8/6
Fig. 8/4
Tripping characteristic with preset transformer parameters for three-phase faults
Fig. 8/5
3-winding transformers (1 or 3-phase)
Protection functions
Sensitive protection by measurement of
star-point current (see Fig. 8/6)
(ANSI 87N/87GD)
Apart from the current inputs for detection of the phase currents on the sides of
the protected object, the 7UT6 also contains normal sensitivity IE and high sensitivity IEE current measuring inputs.
Measurement of the star-point current of
an earthed winding via the normal sensitivity measuring input, and consideration
of this current by the differential protection, increases the sensitivity during internal single-phase faults by 33 %. If the sum
of the phase currents of a winding is compared with the star-point current measured
with the normal sensitivity input IE, a sensitive earth current differential protection
can be implemented (REF).
This function is substantially more sensitive than the differential protection during
faults to earth in a winding, detecting fault
currents as small as 10 % of the transformer rated current.
Furthermore, this relay contains a
high-impedance differential protection input. The sum of the phase currents is compared with the star-point current. A
voltage-dependent resistor (varistor) is applied in shunt (see Fig. 8/6). Via the sensitive current measuring input IEE, the
voltage across the varistor is measured; in
the milli-amp range via the external resistor. The varistor and the resistor are
mounted externally. An earth fault results
in a voltage across the varistor that is larger
than the voltage resulting from normal
current transformer errors. A prerequisite
is the application of accurate current transformers of the class 5P (TPY) which exhibit a small measuring error in the
operational and overcurrent range. These
current transformers may not be the same
as used for the differential protection, as
the varistor may cause rapid saturation of
this current transformers.
Fig. 8/6
High-impedance differential protection
Fig. 8/7
Simple busbar protection with phase-selective
configuration
7UT612: 7 feeders
7UT613/633: 9 feeders
7UT635: 12 feeders
8/7
Protection functions
n Backup protection functions
Overcurrent-time protection
(ANSI 50, 50N, 51, 51N)
Backup protection on the transformer is
achieved with a two-stage overcurrent protection for the phase currents and 3I0 for
the calculated neutral current. This function may be configured for one of the sides
or measurement locations of the protected
object. The high-set stage is implemented
as a definite-time stage, whereas the normal stage may have a definite-time or inverse-time characteristic. Optionally, IEC
or ANSI characteristics may be selected for
the inverse stage. The overcurrent protection 3I0 uses the calculated zero-sequence
current of the configured side or measurement location.
Overcurrent-time protection for earth
(ANSI 50/51G)
8/8
Lockout
(ANSI 86)
All binary outputs (alarm or trip relays)
can be stored like LEDs and reset using the
LED reset key. The lockout state is also
stored in the event of supply voltage failure. Reclosure can only occur after the
lockout state is reset.
External trip coupling
For recording and processing of external
trip information via binary inputs. They
are provided for information from the
Buchholz relay or specific commands and
act like a protective function. Each input
initiates a fault event and can be individually delayed by a timer.
Protection functions
Monitoring functions
The relay comprises high-performance
monitoring for the hardware and software.
The measuring circuits, analog-digital conversion, power supply voltages, battery,
memories and software sequence
(watch-dog) are all monitored.
LSP2376-afp.tif
Fig. 8/9
Temperature measurement and monitoring with external thermo-boxes
Measured values
Metered values
The operational measured values and statistic value registering in the 7UT6, apart
from the registration of phase currents
and voltages (7UT613/633 only) as primary and secondary values, comprises the
following:
For internal metering, the unit can calculate an energy metered value from the
measured current and voltage values.
8/9
Protection functions
Commissioning and operating aids
Fig. 8/10
Commissioning via a standard Web browser: Phasor diagram
LSP2452-afpen.tif
LSP2451-afpen.tif
Fig. 8/11
Commissioning via a standard Web browser: Operating characteristic
8/10
Protection functions
n Control and automation functions
Control
In addition to the protection functions, the
SIPROTEC 4 units also support all control
and monitoring functions that are required
for operating medium-voltage or highvoltage substations.
The main application is reliable control of
switching and other processes.
The status of primary equipment or auxiliary devices can be obtained from auxiliary
contacts and communicated via binary inputs. Therefore it is possible to detect and
indicate both the OPEN and CLOSED position or a fault or intermediate circuitbreaker or auxiliary contact position.
The switchgear or circuit-breaker can be
controlled via:
integrated operator panel
binary inputs
substation control and protection system
DIGSI 4
Command processing
All the functionality of command processing is offered. This includes the processing
of single and double commands with or
without feedback, sophisticated monitoring of the control hardware and software,
checking of the external process, control
actions using functions such as runtime
monitoring and automatic command termination after output. Here are some typical applications:
Filter time
Switching authority
Switching authority is determined according to parameters, communication or by
key-operated switch (when available).
If a source is set to LOCAL, only local
switching operations are possible. The following sequence of switching authority is
laid down: LOCAL; DIGSI PC program,
REMOTE
Every switching operation and change of
breaker position is kept in the status indication memory. The switch command
source, switching device, cause (i.e. spontaneous change or command) and result of
a switching operation are retained.
A data transmission lockout can be activated, so as to prevent transfer of information to the control center during work on
a circuit bay.
Test operation
During commissioning, all indications can
be passed to an automatic control system
for test purposes.
Chatter disable
The chatter disable feature evaluates
whether, in a configured period of time,
the number of status changes of indication
input exceeds a specified figure. If exceeded, the indication input is blocked for
a certain period, so that the event list will
not record excessive operations.
8/11
Communication
With respect to communication, particular
emphasis has been placed on high levels of
flexibility, data integrity and utilization of
standards common in energy automation.
The design of the communication modules
permits interchangeability on the one
hand, and on the other hand provides
openness for future standards (for example, Industrial Ethernet).
Local PC interface
The PC interface accessible from the front
of the unit permits quick access to all parameters and fault event data. Of particular
advantage is the use of the DIGSI 4 operating program during commissioning.
Rear-mounted interfaces
Two communication modules located on
the rear of the unit incorporate optional
equipment complements and readily permit retrofitting. They assure the ability to
comply with the requirements of different
communication interfaces.
The interfaces make provision for the following applications:
Fig. 8/12
IEC 60870-5-103 star-type RS232 copper
conductor connection or fiber-optic connection
Master control units
RS485 bus
With this data transmission via copper
conductors electromagnetic fault influences are largely eliminated by the use of
twisted-pair conductor. Upon failure of a
unit, the remaining system continues to
operate without any disturbances.
Fiber-optic double ring circuit
The fiber-optic double ring circuit is immune to electromagnetic interference.
Upon failure of a section between two
units, the communication system continues to operate without disturbance.
It is generally impossible to communicate
with a unit that has failed. If a unit were to
fail, there is no effect on the communication with the rest of the system.
Fig. 8/13
Bus structure: Fiber-optic double ring circuit
Master control units
Fig. 8/14
Bus structure: RS485 copper conductor
connection
1) Only for 7UT613/633/635
2) Under development
8/12
Communication
IEC 60870-5-103
IEC 60870-5-103 is an internationally standardized protocol for the efficient communication in the protected area.
IEC 60870-5-103 is supported by a number
of protection device manufacturers and is
used worldwide.
PROFIBUS-FMS
PROFIBUS-FMS is an internationally standardized communication system (EN
50170). PROFIBUS is supported internationally by several hundred manufacturers and has to date been used in more than
1,000,000 applications all over the world.
Connection to a SIMATIC S5/S7 programmable controller is made on the basis of
the data obtained (e.g. fault recording,
fault data, measured values and control
functionality) via SICAM energy automation system or via PROFIBUS-DP.
PROFIBUS-DP
Fig. 8/15
R232/RS485 electrical communication module
Fig. 8/16
Fiber-optic communication module
PROFIBUS-DP is an industry-recognized
standard for communications and is supported by a number of PLC and protection
device manufacturers.
MODBUS RTU
MODBUS RTU is an industry- recognized
standard for communications and is supported by a number of PLC and protection
device manufacturers.
Fig. 8/17
Communication module, optical double-ring
DNP 3.0
DNP 3.0 (Distributed Network Protocol
Version 3) is a messaging-based communication protocol. The SIPROTEC 4 units
are fully Level 1 and Level 2 compliant
with DNP 3.0.
DNP 3.0 is supported by a number of protection device manufacturers.
Ethernet / IEC 61850 1)
Ethernet IEC 61850 application-specific
profile for energy automation applications
is currently under preparation.
As soon as standardization work has been
completed, SIPROTEC 4 units will be upgraded to meet the requirements of the
new standard. Retrofitting can be carried
out simply by insertion of an Ethernet
communication module.
1) Under development.
8/13
Communication
System solution
SIPROTEC 4 is tailor-made for use in
SIMATIC-based automation systems.
Via the PROFIBUS-DP, indications
(pickup and tripping) and all relevant operational measured values are transmitted
from the protection unit.
Via modem and service interface, the protection engineer has access to the protection devices at all times. This permits
remote maintenance and diagnosis (cyclic
testing).
Parallel to this, local communication is
possible, for example, during a major inspection.
Fig. 8/18
System solution: Communications
8/14
Typical connections
Fig. 8/19
Standard connection to a transformer
without neutral current measurement
Fig. 8/20
Connection to a transformer
with neutral current measurement
8/15
Typical connections
Fig. 8/21
Connection of transformer differential protection
with high impedance REF (I7) and neutral current
measurement at I8
8/16
Typical connections
Fig. 8/22
Connection example to a single-phase power
transformer with current transformer between
starpoint and earthing point
Fig. 8/23
Connection example to a single-phase power
transformer with only one current transformer (right
side)
8/17
Typical connections
Fig. 8/24
Connection to a three-phase auto-transformer
with current transformer between starpoint
and earthing point
Fig. 8/25
Generator or motor protection
8/18
Typical connections
Fig. 8/26
Connection 7UT612 as single-phase busbar protection for 7 feeders, illustrated for phase L1
Fig. 8/27
Connection 7UT612 as busbar protection for feeders, connected via external summation current transformers (SCT)
partial illustration for feeders 1, 2 and 7
8/19
Typical connections
8
Fig. 8/28
Connection example 7UT613 for a
three-winding power transformer
8/20
Typical connections
Fig. 8/29
Connection example 7UT613 for a three-winding power transformer
with current transformers between starpoint and earthing point, additional connection
for high-impedance protection; IX3 connected as high-sensitivity input
8/21
Typical connections
Fig. 8/30
Connection example 7UT613 for a three-phase auto-transformer
with three-winding and current transformer between starpoint and earthing point
8/22
Typical connections
Fig. 8/31
Connection example 7UT635 for a three-winding power transformer
with 5 measurement locations (3-phase) and neutral current measurement
8/23
Typical connections
Fig. 8/32
Voltage transformer connection
to 3 star-connected voltage transformers
(7UT613 and 7UT633 only)
Fig. 8/33
Voltage transformer connection
to 3 star-connected voltage transformers
with additional delta winding
(e-n-winding) (7UT613 and 7UT633 only)
8/24
Technical data
General unit data
Output relay
Analog inputs
Command / indication /
alarm relay
Rated frequency
50 or 60 Hz (selectable), 16.7 Hz
Rated current
0.1 or 1 or 5 A
(selectable by jumper, 0.1 A)
Power consumption
In CT circuits
with IN = 1 A; in VA approx.
with IN = 5 A; in VA approx.
with IN = 0.1 A; in VA approx.
sensitive input; in VA approx.
7UT
612
0.02
0.2
0.001
0.05
Overload capacity
In CT circuits
Thermal (r.m.s.)
IN
Dynamic
Rated voltage (7UT613/633 only)
Power consumption per phase
at 100 V
Overload capacity
Thermal (r.m.s.)
613
0.05
0.3
0.001
0.05
633
0.05
0.3
0.001
0.05
635
0.05
0.3
0.001
0.05
100 IN for 1 s
30 IN for 10 s
4 IN continuous
250 IN (half cycle)
Quantity
each with 1 NO contact
(marshallable)
1 alarm contact, with 1 NO or
NC contact (not marshallable)
1000 W / VA
30 VA
40 W
25 W
Switching voltage
250 V
Quantity
300 A for 1 s
100 A for 10 s
15 A continuous
750 A (half cycle)
RUN (green)
ERROR (red)
LED (red), function can
be assigned
80 to 125 V
w 0.1 VA
230 V continuous
Permissible tolerance
-20 to +20 %
Superimposed AC voltage
(peak-to-peak)
w 15 %
Housing
7UT
612
5
7
24 to 48 V DC
60 to 125 V DC
110 to 250 V DC and
115 V AC (50/60 Hz), 230 V AC
633
635
6/12 6/12
20/28 20/28
7UT
612
613
633
635
1
1
7
1
1
14
1
1
14
1
1
14
IP 51
IP 51
IP 50
IP 2x with closed protection cover
7UT
612
1/3
613
1/2
633
1/1
635
1/1
Weight, in kg
Flush-mounting housing
Surface-mounting housing
5.1
9.6
8.7
13.5
13.8
22.0
14.5
22.7
Serial interfaces
Operating interface 1 for DIGSI 4 or browser
W 50 ms
Binary inputs
Connection
7UT
612
3
613
5
633
21
635
29
24 to 250 V, bipolar
Distance, max.
19 or 88 V DC (bipolar)
300 V DC
Approx. 1.8 mA
635
24
Unit design
Housing 7XP20
613
6/12
12/19
633
24
Switching capacity
Make
Break
Break (with resistive load)
Break (with L/R w 50 ms)
Degree of protection
acc. IEC 60529
For the device
in surface-mounting housing
in flush-mounting housing
front
rear
For personal safety
Quiescent; in W approx.
Energized; in W approx.
depending on design
613
8
LEDs
Auxiliary voltage
Rated voltage
7UT
612
4
Connection
Voltage levels
5, 12 or 24 V (optional)
8/25
Technical data
Service interface (operating interface 2) for DIGSI 4 / modem / service
Electrical tests
Isolated RS232/RS485/FO
Specifications
Dielectric test
Distance for RS232
Distance for RS485
Distance for FO
System interface
Baud rate
Dielectric test
Distance for RS232
Distance for RS485
For fiber-optic cable
Connector type
Optical wavelength
Permissible attenuation
Distance
PROFIBUS RS485 (-FMS/-DP)
Connector type
Baud rate
Dielectric test
Distance
ST connector
= 820 nm
Max. 8 dB, for glass-fiber 62.5/125 m
1.5 km (1 mile)
8/26
Insulation tests
Standards
IEC 60870-5-103
Isolated RS232/RS485/FO
Standards
3.5 kV DC
500 V (r.m.s.), 50 Hz / 60 Hz
Electrostatic discharge
IEC 60255-22-2 class IV
EN 61000-4-2, class IV
Irradiation with RF field, amplitude- 10 V/m; 80, 160, 450, 900 MHz,
modulated, single frequencies,
80 % AM;
IEC 60255-22-3,
duration > 10 s
IEC 61000-4-3, class III
Irradiation with RF field, pulsemodulated, single frequencies,
IEC 60255-22-3, IEC 61000-4-3/
ENV 50204, class III
Impulse: 1.2/50 s
Magnetic field with power frequency 30 A/m continuous; 300 A/m for 3 s;
IEC 61000-4-8, IEC 60255-6 class IV 50 Hz, 0.5 mT; 50 Hz
Technical data
Electrical tests (contd)
Temperatures
Damped oscillations
IEC 60894, IEC 61000-4-12
2.5 kV (peak value), polarity alternating 100 kHz, 1 MHz, 10 MHz and
50 MHz, Ri = 200
Conducted interference,
only auxiliary supply
IEC-CISPR 22
30 to 1000 MHz
Limit class B
CE conformity
During operation
Standards
Vibration
IEC 60255-21-1, class 2
IEC 60068-2-6
Sinusoidal
10 to 60 Hz: 0.075 mm amplitude;
60 to 150 Hz: 1 g acceleration
frequency sweep 1 octave/min.
20 cycles in 3 orthogonal axes
Shock
IEC 60255-21-2, class 1
IEC 60068-2-27
Half-sinusoidal
acceleration 5 g, duration 11 ms,
3 shocks each in both directions of
the 3 axes
Seismic vibration
IEC 60255-21-2, class 1
IEC 60068-3-3
Sinusoidal
1 to 8 Hz: 3.5 mm amplitude
(horizontal axis)
1 to 8 Hz: 1.5 mm amplitude
(vertical axis)
8 to 35 Hz: 1 g acceleration
(horizontal axis)
8 to 35 Hz: 0.5 g acceleration
(vertical axis)
frequency sweep 1 octave/min
1 cycle in 3 orthogonal axes
This unit conforms to the international standard IEC 60255, and the
German standard DIN 57435/Part 303 (corresponding to VDE 0435/
Part 303).
During transport
Standards
Vibration
IEC 60255-21-1, class 2
IEC 60255-2-6
Sinusoidal
5 to 8 Hz: 7.5 mm amplitude;
8 to 150 Hz: 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 orthogonal axes
Shock
IEC 60255-21-2, class 1
IEC 60068-2-27
Half-sinusoidal
acceleration 15 g, duration 11 ms,
3 shocks each in both directions of
the 3 axes
Continuous shock
IEC 60255-21-2, class 1
IEC 60068-2-29
Half-sinusoidal
acceleration 10 g, duration 16 ms,
1000 shocks on each of the 3 axes in
both directions
8/27
Technical data
Functions
Differential protection
Operating times
General
Pickup values
Differential current IDIFF > /INobj
High-current stage
0.05 to 2.00
(steps 0.01)
(steps 0.1)
IDIFF >> /INobj 0.5 to 35.0
or deactivated (stage ineffective)
1.0 to 2.0
Pickup on switch-on
(factor of IDIFF >)
(steps 0.1)
5 % of set value
5 % of set value
50 Hz
60 Hz
7UT 612
IDIFF >, min.
IDIFF >>, min.
38
19
35
17
85
25
35
30
80
7UT 613/63x
IDIFF >, min.
IDIFF >>, min.
30
11
27
11
78
20
54
46
150
16.7 Hz
0.7
Time delays
TI-DIFF>
Steady-state differential
current monitoring
IDIFF mon/INobj
0.15 to 0.80
(steps 0.01)
1 to 10 s
(steps 1 s)
Transformers
Harmonic stabilization
Trip release
Iguard/INobj
by feeder current guard
Time tolerance
1 % of set value or 10 ms
10 to 80 %
(steps 1 %)
10 to 80 %
(steps 1 %)
Crossblock function
max. action time for crossblock
50 Hz
60 Hz
16.7 Hz
7UT 612
IDIFF >, min.
IDIFF >>, min.
38
19
35
17
85
25
35
30
80
7UT 613/63x
IDIFF >, min.
IDIFF >>, min.
30
11
27
11
78
20
54
46
150
Operating times
Pickup time/dropout time with single-side infeed
Pickup time (in ms) at frequency
Operating times
50 Hz
60 Hz
16.7 Hz
25
19
25
17
50
35
30
30
70
7UT 613/63x
IDIFF >, min.
IDIFF >>, min.
11
11
11
11
18
18
54
46
150
7UT 612
0.7
0.7
0 to 11 (x 30 ) (steps 1)
Star-point conditioning
Earthed or non-earthed
(for each winding)
8/28
Technical data
Restricted earth-fault protection
Settings
Tolerances
Definite time
0.05 to 2.00
(steps 0.01)
Limit angle
REF
110 (fixed)
Time delay
TREF
Currents
Times
Inverse time
Currents
Pickup
Acc. to IEC
Times
5 % 15 ms at fN = 50/60 Hz
5 % 45 ms at fN = 16.7 Hz
for 2 w I/IP w 20
and TIP/s W 1;
or 2 w I/3I0P w 20
and T3I0P/s W 1
Acc. to ANSI
Times
5 % 15 ms at fN = 50/60 Hz
5 % 45 ms at fN = 16.7 Hz
for 2 w I/IP w 20
and DIP/s W 1;
or 2 w I/3I0P w 20
and D3I0P/s W 1
Operating times
60 Hz
16.7 Hz
7UT 612
At 1.5 setting value IREF >, approx. 40
At 2.5 setting value IREF >, approx. 37
40
Dropout time (in ms), approx.
38
32
100
80
40
80
7UT 613/63x
At 1.5 setting value IREF >, approx. 35
At 2.5 setting value IREF >, approx. 33
26
Dropout time (in ms), approx.
30
29
110
87
23
51
50 Hz
0.7
60 Hz
16.7 Hz
20
18
30
40
35
85
30
30
80
11
11
16
33
29
76
35
35
60
7UT612
IP, 3I0P
Inverse, very inverse, extremely
inverse, long-time inverse
Acc. to ANSI
16.7 Hz
40
35
100
40
35
100
30
30
80
3I0 >>
T3I0 >>
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
21
19
46
31
29
56
45
43
90
1)
0.10 to 35.00 A
(steps 0.01 A)
or deactivated (stage ineffective)
TIPh
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
3I0 >
1)
T3I0 >
Acc. to ANSI
60 Hz
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
Inverse-time stages
50 Hz
7UT 612
TIPh >>
0.05 to 35.00 A
(steps 0.01 A)
or deactivated (stage ineffective)
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
1)
IP
0.10 to 4.00 A
TIP
0.05 to 3.20 s
(steps 0.01 s)
or deactivated (no trip)
3I0P
0.05 to 4.00 A 1)
T3I0P
0.05 to 3.20 s
(steps 0.01 s)
or deactivated (no trip)
IP
0.10 to 4.00 A 1)
DIP
0.50 to 15.00 s
(steps 0.01 s)
or deactivated (no trip)
3I0P
0.05 to 4.00 A 1)
D3I0P
0.50 to 15.00 s
(steps 0.01 s)
or deactivated (no trip)
(steps 0.01 A)
Acc. to IEC
7UT613/6x
Current stages
Inverse-time stages
Dropout ratios
Current stages
Inrush blocking
Inrush blocking ratio
(2nd harmonic)
I2fN/IfN
10 to 45 %
(steps 1 %)
I > 0.2 A 1)
(steps 0.01 A)
(steps 0.01 A)
(steps 0.01 A)
1) Secondary values based on IN = 1 A;
for IN = 5 A they must be multiplied by 5.
8/29
Technical data
Overcurrent-time protection for earth current
Characteristics
Time control
IE >>, IE >
Start criterion
IEP
Inverse, very inverse, extremely
inverse, long-time inverse
CB open time
TCB open
0 to 21600 s (= 6 h)
(steps 1 s)
Active time
TActive time
1 to 21600 s (= 6 h)
(steps 1 s)
Acc. to ANSI
Current stages
High-current stage
Definite-time stage
Inverse-time stages
Acc. to IEC
Inverse-time stages
Acc. to ANSI
Tolerances
Definite time
IE >>
TIE >>
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
IE >
TIE >
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
IEP
0.05 to 4.00 A 1)
TIEP
0.05 to 3.20 s
(steps 0.01 s)
or deactivated (no trip)
IEP
0.05 to 4.00 A 1)
DIEP
0.50 to 15.00 s
(steps 0.01 s)
or deactivated (no trip)
Currents
Times
Inverse time
Acc. to IEC
Acc. to ANSI
Currents
Times
Times
TT >>
(steps 0.01 A)
Definite-time stage I >
(steps 0.01 A)
Tolerances
TI >
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
Currents
3 % of set value or
1 % of rated current at IN = 1 A or 5 A;
5 % of set value or
3 % of rated current at IN = 0.1 A
Times
1 % of set value or 10 ms
50 Hz
60 Hz
16.7 Hz
7UT612
20
18
35
Minimum
30
27
80
14
13
23
Minimum
25
22
66
50 Hz
60 Hz
16.7 Hz
7UT 612
20
40
18
35
30
85
30
30
80
11
33
11
29
16
76
35
35
60
Dropout ratios
Current stages
7UT613/63x
Without inrush restraint, min.
Dropout ratios
Current stages
Inrush blocking
Inrush blocking ratio
(2nd harmonic)
I2fN/IfN
10 to 45 %
I > 0.2 A 1)
0.30 to 25.00 A 1)
8/30
(steps 1 %)
(steps 0.01 A)
2) Secondary values for high-sensitivity current
input I8, independent of rated current.
Technical data
Unbalanced load protection (Negative-sequence protection)
Characteristics
Tripping characteristics
Definite-time stages
(DT)
I2 >>, I2 >
Inverse-time stages
Acc. to IEC
(IT)
I2P
Inverse, very inverse, extremely
inverse
(IT)
I
Ipre
k
IN
Operating range
Current stages
High-current stage
Definite-time stage
I2 >>
TI2 >>
I2 >
TI2 >
0.10 to 3.00 A 1)
(steps 0.01 A)
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
1)
0.10 to 3.00 A
(steps 0.01 A)
0.00 to 60.00 s
(steps 0.01 s)
or deactivated (no trip)
t = In
k IN
Ipre
k IN
k IN
Acc. to ANSI
Reset characteristics
Tripping characteristic
for I/(k IN) w 8
Tripping time
Heating-up time constant
Actual load current
Preload current
Setting factor IEC 60255-8
Rated current of the protected
object
Dropout ratios
/trip
Dropout at alarm
/alarm
Approx. 0.99
I/Ialarm
Approx. 0.97
Inverse-time stages
Acc. to IEC
I2P
TI2P
0.10 to 2.00 A 1)
(steps 0.01 A)
0.05 to 3.20 s
(steps 0.01 s)
or deactivated (no trip)
Tolerances
(with one 3-phase measuring location)
I2P
DI2P
0.10 to 2.00 A 1)
(steps 0.01 A)
0.50 to 15.00 s
(steps 0.01 s)
or deactivated (no trip)
Referring to k IN
Inverse-time stages
Acc. to ANSI
3 % or 10 mA 1);
class 3 % acc. IEC 60255-8
3 % or 1 s at fN = 50/60 Hz
5 % or 1 s at fN = 16.7 Hz
for I/(k IN) > 1.25
Currents
Times
Currents
Times
Tolerances
Definite-time
Inverse time
Acc. to IEC
Acc. to ANSI
Times
50 Hz
60 Hz
16.7 Hz
50
30
45
30
100
80
41
23
34
20
106
60
7UT612
Minimum
Dropout time (in ms), approx.
7UT613/63x
Dropout ratios
Current stages
Cooling
Cooling method
0.10 to 4.00
(steps 0.01)
1.0 to 10.0
(steps 0.1)
0.10 to 4.00 A 1)
Start-up recognition
(for motors)
Istart-up
0.60 to 10.00 A 1)
(steps 0.01 A)
or deactivated
(no start-up recognition)
10 to 15000 s
ON (oil natural)
OF (oil forced)
OD (oil directed)
1.6 to 2.0
(steps 0.1)
22 to 29
(steps 1)
98 to 140 C
208 to 284 F
(steps 1 C)
(steps 1 F)
98 to 140 C
208 to 284 F
(steps 1 C)
(steps 1 F)
0.125 to 128.000
(steps 0.001)
0.125 to 128.000
(steps 0.001)
From 1 thermo-box
(up to 6 temperature sensors) or
from 2 thermo-boxes
(up to 12 temperature sensors)
Oil exponent
Minimum
Dropout time (in ms), approx.
Thermo-box
(temperature monitoring box)
1 % at fN = 50/60 Hz
3 % at fN = 16.7 Hz
(steps 0.01 A)
(steps 1 s)
8/31
Technical data
Thermo-boxes for overload protection
Thermo-boxes (connectable)
1 or 2
Binary inputs
Max. 6
Measuring type
Operating time
Dropout time
Approx. 25 ms
-50 to 250 C
(steps 1 C)
-58 to 482 F
(steps 1 F)
or deactivated (no warning)
Delay time
0.00 to 60.00 s
Expiration tolerance
1 % of set value or 10 ms
-50 to 250 C
(steps 1 C)
-58 to 482 F
(steps 1 F)
or deactivated (no alarm)
Transformer annunciations
Annuciation thresholds
0.04 to 1.00 A 1)
(steps 0.01 A)
for the respective side
Pickup tolerance
Voltage symmetry
(if voltages applied)
Internal trip
External trip (via binary input)
Voltage sum
(if voltages applied)
Broken wire
Reset time
(incl. output relay), approx.
50 Hz
60 Hz
16.7 Hz
7UT612
30 ms
30 ms
60 ms
7UT613/63x
25 ms
25 ms
75 ms
Time tolerance
Times
Pickup time
Buchholz warning
Buchholz tank
Buchholz tripping
Current symmetry
(for each measurement location)
BAL. FAKT. I
BAL. I LIMIT
Starting conditions
For breaker failure protection
(steps 0.01 s)
60 Hz
16.7 Hz
31
23
90
70
0.95
Tolerances
V/f-Pickup
Time delays T
Thermal characteristic (time)
3 % of set value
1 % or 10 ms
5 % rated to V/f or 600 ms
8/32
Technical data
Additional functions
Operational measured values
Operational measured values
of currents, 3-phase for each side
and measurement location
Tolerance at IN = 1 or 5 A
Tolerance at IN = 0.1 A
cos (p.f.)
Only if voltage applied,
7UT613/633 only
Overexcitation
V/f
Only if voltage applied,
7UT613/633 only
2 % of measured value
Tolerance
3I0; I1; I2
In A primary and secondary
and % of IN
2 % of measured value or 2 % of IN
thermo-box1 to thermo-box12
In C or F relative aging rate,
load reserve
Measured values of
differential protection
Feeder
Further
High-sensitivity
I1 to I7
I1 to I9
I1 to I9
I1 to I12
I7 to I8
Ix1 to Ix3
Ix1 to Ix3
Ix1 to Ix4
I8
Ix3
Ix3
Ix3, Ix4
IDIFFREF; IRestREF
In % of operational rated current
2 % of measured value or
2 % of IN (50/60 Hz)
3 % of measured value or
3 % of IN (16.7 Hz)
1 at rated current
(I1) to (I8)
(I1) to (I9), (Ix1) to (Ix3)
(I1) to (I9), (Ix1) to (Ix4)
(I1) to (I12), (Ix1) to (Ix4)
Fault recording
Max. 8
Storage period
(start with pickup or trip)
In , referred to (I1)
1 at rated current
In kV primary and V secondary
and % of VN
VL1-E, VL2-E, VL3-E,
VL1-L2, VL2-L3, VL3-L1,
0.2 % of measured value or + 0.2 V
V1, V2, V0,
0.4 % of measured value or + 0.4 V
VEN or V4
0.2 % of measured value or + 0.2 V
Sampling rate at fN = 50 Hz
Sampling rate at fN = 60 Hz
Sampling rate at fN = 16.7 Hz
613
633
Switching statistics
Number of trip events caused by
7UT6
Total of interrupted currents caused Segregated for each pole, each side
by 7UT6
and each measurement location
Operating hours
Criterion
Up to 7 decimal digits
Excess of current threshold
f
In Hz and % of fN
10 to 75 Hz
1 % within range fN 10 % and I W IN
1 ms
Buffer battery
Time synchronization
Operating modes:
x
x
x
x
x
x
x
x
Internal
IEC 60870-5-103
S (apparent power)
P (active power)
Q (reactive power)
635
8/33
Description
Order No.
7UT612o-o-oA0
Rated current
IN = 1 A
IN = 5 A
Rated auxiliary voltage (power supply, binary inputs)
24 to 48 V DC, binary input threshold 17 V 2)
60 to 125 V DC 3), binary input threshold 17 V 2)
110 to 250 V DC, 115/230 V AC, binary input threshold 73 V 2)
Unit design
For panel surface mounting, two-tier terminals on top and bottom
For panel flush mounting, plug-in terminals (2/3-pole AMP connector)
For panel flush mounting, screw-type terminals, (direct wiring/ring lugs)
1
5
2
4
5
B
D
E
Region World, 50/60 Hz, 16.7 Hz, IEC/ANSI, language English (GB);
selectable
Region US, 60/50 Hz, 16.7 Hz, ANSI/IEC, language English (US);
selectable
Order Code
0
1
2
3
4
5
6
9
9
9
9
9
9
L
L
L
L
L
L
0A
0B
0D
0 E
0G
0H
8/34
Description
Order No.
7UT612o - o-oA0
0
1
2
3
Functions
Measured values/monitoring functions
Basic measured values
8/35
Description
Order No.
Order Code
1
5
2
4
5
B
D
E
A
B
C
E
0
1
2
3
4
5
6
9
9
9
9
9
9
L
L
L
L
L
L
0
0
0
0
0
0
A
B
D
E
G
H
8/36
Description
Order No.
7UT613o-o - oo0
Order Code
0
1
2
9
M oo
1
2
A
F
A
B
8/37
Description
Order No.
7UT63--0
Rated current
IN = 1 A
1
5
IN = 5 A
Rated auxiliary voltage (power supply, binary inputs)
24 to 48 V DC, binary input threshold 17 V2)
60 to 125 V DC3), binary input threshold 17 V2)
110 to 250 V DC1), 115/230 V AC, binary input threshold 73 V2)
Unit design
Surface-mounting with two-tier terminals
Flush-mounting with screw-type terminals
Region-specific default settings/language settings
Region DE, 50/60 Hz, 16.7 Hz, language German; selectable
Region World, 50/60 Hz, 16.7 Hz, language English (GB); selectable
Region US, 60/50 Hz, 16.7 Hz, language English (US); selectable
Region World, 50/60 Hz, 16.7 Hz, language Spanish; selectable
System interface (Port B ) on rear
No system port
IEC 60870-5-103 protocol, electrical RS232
IEC 60870-5-103 protocol, electrical RS485
IEC 60870-5-103 protocol, optical 820 nm, ST connector
PROFIBUS-FMS Slave, electrical RS485
PROFIBUS-FMS Slave, optical, single ring, ST connector4)
PROFIBUS-FMS Slave, optical, double ring, ST connector4)
PROFIBUS-DP Slave, electrical RS485
4)
2
4
5
B
D
E
Order Code
A
B
C
E
0
1
2
3
4
5
6
9
9
9
9
9
9
L
L
L
L
L
L
0
0
0
0
0
0
A
B
D
E
G
H
8/38
Description
Order No.
7UT63-o-0
Order Code
1
2
9
M oo
1
2
A
F
A
B
8/39
Accessories
Description
Order No.
DIGSI 4
Software for configuration and operation of Siemens protection relays
running under MS Windows (version Windows 95 and higher),
device templates, Comtrade Viewer, electronic manual included
as well as Getting started manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number)
7XS5400-0AA00
Demo
Demo version on CD-ROM
7XS5401-0AA00
Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default and
control displays) and DIGSI 4 Remote (remote operation)
7XS5402-0AA00
SIGRA
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format) running under MS Windows 95/98/ME/NT/2000/
XP Professional Edition.
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM.
7XS5410-0AA00
Connecting cable
Cable between PC/notebook (9-pin connector)
and protection relay (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally)
Cable between thermo-box and relay
- length 5 m / 16.4 ft
- length 25 m / 82 ft
- length 50 m / 164 ft
8/40
7XV5100-4
7XV5103-7AA05
7XV5103-7AA25
7XV5103-7AA50
3RV1611-1AG14
7XV5662-2AD10
7XV5662-5AD10
C53000-G1176-C148-1
C53000-G1176-C160-1
Accessories
LSP2089-afpen.tif
Description
LSP2091-afpen.eps
LSP2090-afpen.eps
LSP2092-afpen.eps
LSP2093-afpen.eps
Fig.
8/35
8/36
C73334-A1-C35-1
C73334-A1-C36-1
1
1
Siemens
Siemens
Crimp
connector
0-827039-1
0-827396-1
4000
1
AMP 1)
AMP 1)
0-827040-1
0-827397-1
4000
1
AMP 1)
AMP 1)
0-163083-7
0-163084-2
4000
1
AMP 1)
AMP 1)
0-539635-1
0-539668-2
0-734372-1
1-734387-1
AMP 1)
AMP 1)
AMP 1)
AMP 1)
C73165-A63-D200-1
Siemens
8/34
8/37
8/38
Crimping
tool
Fig. 8/36
3-pin connector
Fig. 8/38
Short-circuit link
for voltage
contacts
Supplier
2-pin
3-pin
Fig. 8/37
Short-circuit link
for
current contacts
Size of
package
Connector
Fig. 8/35
2-pin connector
Order No.
Short-circuit links
C73334-A1-C33-1
C73334-A1-C34-1
1
1
Siemens
Siemens
large
small
C73334-A1-C31-1
C73334-A1-C32-1
1
1
Siemens
Siemens
8/41
Connection diagram
8/42
Connection diagram
8/43
Connection diagram
8/44
Connection diagram
8/45
Connection diagram
8/46
Side view
Rear view 1
7SA610, 7SD61, 7SJ64
Rear view 2
7SJ61, 7SJ62, 7UT612,
7UM611
Panel cutout
Fig. 16/22
Housing for panel flush mounting/
cubicle mounting (1/3 x 19")
Front view
Side view
Fig. 16/23
1/3 x 19 surface-mounting housing
8/47
Side view 1
Side view 2
Panel cutout
Rear view 1
7SA61/63, 7UM621, 7SJ64
Rear view 2
7SJ63, 7UM613
Rear view 3
7SA522, 7SD52
Rear view 4
7UT613
Fig. 16/24
1/2 x 19" flush-mounting housing
8/48
Side view 1
Side view 2
Panel cutout
Rear view 1
7SA6, 7UM622, 7SJ64, 7UT633, 7UT635
Rear view 2
7SJ63, 7MD63
Rear view 3
7SA522, 7SD52
Fig. 16/26
in 1/1 x 19" flush-mounting housing
8/49
Front view
1/2 x 19" surface-mounting
housing 7XP20
Side view
Front view
1/1 x 19" surface-mounting housing 7XP20
(without sloped FO case)
Fig. 16/27
1/2 and 1/1 x 19" surface-mounting housing
8/50