Z23 = (0.0125 + j0.025 ) x 0.7 x 8 = 0.07 + j0.14
Z31 = (0.01 + j0.03 ) x 0.7 x 8 = 0.056 + j0.168
4.2 + j0.84
0.01 + j0.84
4.2 + j0.84
0.07 + j0.14
0.056 + j0.168
138.6 MW
256.6 MW
110.2 Mvar
45.2 Mvar
Slack Bus
V1 = 1.05 0
(a) Using the Gauss-Seidel method, determine the phasor values of the voltage at the load buses
2 & 3 (P-Q buses) accurate to four decimal places.
(b) Find the slack bus real and reactive power
(c) Determine the line flows and line losses. Construct a power flow diagram showing the
direction of line flow
y23 =
1
0.056+ j 0168 = 6.38 -63.47 = 2.85 j5.71
y31 =
1
0.08+ j 0.24 = 5.63 -71.59 = 1.78 j5.35
1.785 j3.57
256.6 MW
1.78 j5.35
2.85 j5.71
110.2 Mvar
S3
=-
(138.6+ j 45.2)
100
= -1.386 j0.452 pu
Since the actual admittances are readily available in Figure 6.10, for hand calculation, we use
(6.28). Bus 1 is taken as reference bus (slack bus). Starting from initial estimate of V 2(0) = 1.0
+ j0.0 and V3(0) = 1.0 + j0.0, V2 and V3 are computed from (6.28) as follows
sch
Psch
2 j Q2
+ y 12V 1+ y 23 V 3 (0)
V 2(0)
V2(1) =
y 12+ y 23
=
2.566+ j 1.102
+ ( 1.785 j 3.57 ) ( 1.05+ j 0 ) +( 2.85 j5.71)(1.0+ j 0)
1.0 j 0.0
4.635 j 9.28
= 0.81 j0.17
And
sch
sch
P3 j Q 3
+ y 13 V 1+ y 23 V (21 )
(1)
V
3
(
0
)
V3 =
y 12+ y 23
1.386+ j 0.452
+ (1.78 j 5.35 )( 1.05+ j0 )+(2.85 j 5.71)(0.81 j0. 17)
1.0 j0.0
3.25 j6.5
= 0.84 j0.19
For the second iteration we have
sch
Psch
2 j Q2
+ y 12V 1+ y 23 V 3 (1)
V 2(1)
V2(2) =
y 12+ y 23
=
2.566+ j 1.102
+ ( 1.785 j 3.57 ) ( 1.05+ j 0 ) +(2.85 j5.71)(0. 84 j0. 19)
0.81+ j 0.17
3.25 j 6.5
= 0.64-j0.277
And
sch
Psch
3 j Q3
+ y 13 V 1+ y 23 V (22 )
(1 )
V3
V3(2) =
y 12+ y 23
1.386+ j 0.452
+ (1.78 j 5.35 )( 1.05+ j0 )+(2.85 j 5.71)(0.64 j0.277)
0. 63+ j11.06
3.25 j 6.5
= 0.73 j0.24
The Process is continued and a solution is converged with an accuracy of 5x10 -5 per unit in
seven iterations as given below.
V2(3) = 0.4852 - j 0.2634
V3(3) = 0.6239 - j 0.2411
12
j2.008
I21 = - I12 = -0.455 + j2.008
I13 = Y13(V1 V3 )=( 1.78 j 5.35 ) ((1.05 + j0) (1.134 - j 0.008)) = -0.106+j0.463
I23 = Y23(V2 V3 )=( 2.85 j5.71 )(( 0.549 + 0.123i ) (1.134 - j 0.008)) = -0.919
+ j3.713
I32 = - I23 = 0.919 - j3.713
S32 = V3 I*32 = (1.134 - j 0.008) (0.919 + j3.713) = 1.071 + j4.203 pu = 107.1 MW + j420.3Mvar
And the line losses are
SL12 = S12 + S21 = (47.7 MW + j210.8Mvar) + (49.6 MW 104.65 Mvar) = 97.3 MW +j106.15Mvar
SL13 = S13 + S31 = (11.1 MW + 48.6Mvar) + (12.3 MW j52.4 Mvar) = 23.4MW j3.8 Mvar
SL23 = S23 + S32 = (-4.7 MW-j215.1 Mvar) + (107.1 MW + j420.3Mvar) = 102.4 MW +j205.2 Mvar
The power flow diagram is shown in figure 6.11, where real power direction is indicated by
And the reactive power direction is indicated by
. The values within parentheses are the
real and reactive losses in the line
(49.6)
(47.7)
(97.3)
(106.15)
451
(210.8)
(11.1)
(23.4)
143.9
(48.6)
(12.3)
256.6
(104.65)
(4.7)
(107.1)
(102.4)
(205.2)
(3.8)
(52.4)
138.6 MW
(420.3)
45.2 Mvar
(215.1)
110.2