DP820 module consists of 2 identical and independent channels for pulse and frequency
measurement.
2 channels
The counter value in channel 5 and 6 shall be the totalized flow from the pulse input.
The variable connected in the channel 5 times the unit per pulse shall be totalizer output.
The range for frequency channel can be obtained from the following formula :-
Frequency can only be scaled and hence following formula shall give us the scaled input
to which frequency can be estimated.
o Min = A1 + (A2 A1)/(F2 F1) * (Fmin F1)
Max = A2 + (A2 A1)/(F2 F1) * (Fmax F2) o
A1 = minimum value of the process unit
A2 = maximum value of the process unit
F1 = Input frequency at A1
F2 = Input frequency at A2
Fmin = Input frequency at 0% in the scaling algorithm = 0 Hz PROFIBUS
CI830 and -1.5 MHz for ModuleBus and PROFIBUS CI801 and CI840
Fmax = Input frequency at 100% in the scaling algorithm = 1.5Mhz
The Flow transmitter must be configured for the frequency input and frequency for
Kg/min. flow should be fixed.
The frequency value from the channel must be then used to totalize the flow in the logic.
For Eg.: For a flow of 1kg/min if the frequency of 10 Hz is configured in the Flow
transmitter, then The range of the frequency channel be -150000.0 to 150000.0 The
Process connections are as follows for 8 channel TB used with TU810 :-
Connect the two cables from the frequency output / pulse output of the Flow transmitter
to the 1st TB for channel 1 and 5th TB to use channel 2 of DP820 module.
Channel 1 of DP820 totalized value is obtained in the Counter value CH1 (Hardware
channel 5 in Connections [FT_83901_P])
Channel 2 of DP820 totalized value is obtained in the Counter value CH2 (Hardware
channel 6 in Connections [FT_83902_P])
Logical Expressions
The Counter value CH1 can be reset using the following set of instructions:
To reset the overflow the value of reset counter overflow [Channel 21] must be made
true.
Reference