Escolar Documentos
Profissional Documentos
Cultura Documentos
The overall objective of the boiler/steam generator plant protection is to ensure safe operation
and to avoid damage to the main plant components.
1.0
2.0
Flame failure and interruption of fuel or air supply or ignition energy to the burners.
Furnace pressure.
Loss of feed water and low drum water level.
Water and steam sides excessive over-pressure.
Very high drum level and failure of feed water regulating controls.
Loss of steam demand and loss of boiler circulating pumps.
2.1
Flame failure and interruption of fuel or air supply or ignition energy to the
burners.
2.2
Furnace pressure.
The boiler/steam generators for the generating units in TNB and the IPPs in Malaysia are
provided with a combination of forced draft (FD) fans for supplying the required air flow
and induced (ID) fans for regulating the gas flow to achieve balanced furnace operation.
Typically, the furnace pressure operating set-point is at 0.5 mbar. This avoids
hazardous gas and flame leaks outward from the furnace, and an excessive ingress of air
into the furnace from outside the system. Under major transient operating conditions, or
due to plant or control system failure, large excursions of furnace pressure or suction can
arise, and damage to the furnace or the ducting can occur.
In the event of complete loss of ID or FD fans, the boiler firing trip is immediately
activated. If there is uncontrolled tripping of just one ID or FD fan, the necessary
protective action depends upon the design limit of the furnace in relation to the
achievable fan head characteristics, and on the ability to maintain safe furnace
combustion.
2.3
2.4
2.5
Very high drum level and failure of feed water regulating controls.
If the level of feed flow is in excess of the prevailing steam flow, then ultimately the rise
in drum water level will result in water carryover to the boiler superheater causing tubes
overheating and failure. Very high drum water level can lead to wet steam ingress into
the steam turbine, causing rapid chilling and distortion in the turbine steam valves and
inlet stages, leaving the turbine vulnerable to major damage.
Note: Boiler protection based on high drum level is not a standard or common practice
in all major utilities.
2.6
Boiler Heat Recovery Steam Generator (HRSG) Regulations, Standards and Codes
Important and relevant regulations, standards and codes with respect to the design, construction,
installation, testing and operation of power boilers and HRSGs include the following:
1. Factories and Machinery (Steam Boiler and Unfired Pressure Vessel) Regulations 1970,
Malaysia.
a.
b.
c.
d.
e.
.....
,
OIL
TURBINE
GENERATOR
BOILER
....,_
GRID
CONNECTION
COAL
BOILER/
TURBINE
INTERTRIPS
TURBINE
PROTECTION
BURNER
IMANAGEMENT
PROTECTION
..
BOILER .
PROTECTION
-~-
ELECTRICAL
INTERTRIPS
.~
~
....
1'UM1Nt
UNIT
Flo. 3.11
,,_
s.+
-$i;t/ u;il;
to
erating pressure.
Safety valves on the reheater m.ust be sized to pass
maximum reheater flow without a rise in reheater inlet
pressure of more than 10Vo sf t6e highest set pressure.
Protection of the reheater tubes is afforded by having
the valves witb the Iowest ser pressure on the outlet
sid.e and with a capacity of not less than 2090 of
the reheat maximum flow. ,"
The types of safety valve used are:
- pressure underneath
loading due to the fluid
the valve di.sc is opposed by direct mechanical load"""tti'6
ing. The two types used are the spring type (see
Fig 3.27) and the torsion bar (see Fig 3.28).
a safety valve
5.5
SLOTTED NUT
DOME
ADJUSTING SCFEW
SPRING PLATE
SPINDLE BALL
LOCKNUT
EASING LEVEF
accessibilitY.
A typical
BODY STUD
AND NUT
constant bore.
ttt1
ALST6IM
As long as there is fire in the furnace, a suitable protection must be provided for the
superheater and the reheater elements. This is especially important when there is no
demand for steam, as when starting up, shutting down or after a turbine trip. During these
periods of no steam flow through the turbine, adequate flow through superheater and
reheater is ensured by the HP by-pass on the superheater circuit and by the LP bypass/Reheater outlet start-up vent on the Reheater circuit.
During start-up, care must be taken not to overheat the superheater or reheater eiements.
Particuiarly during ihe first stage of a cold or warm start-up, the firing rate must be
controiled to keep the maximum furnace exit gas temperature from exceeding 550 "C. A
thermocouple probe is used to measure the furnace exit gas temperatures.
Protection for unexpected over-pressure is provided by safety valves. Safeiy valves are
installed on both HP and LP cir:cuits.
On the HP circuits, safety valves are installed at the drum and at the superheater outlet.
The reheater safety valves are located on the outlet headers.
Safety Valve
HADO1 AA1O.1F
HADOl AA1O2F
HADOl AAlO3F
HADOl AA1O4F
HAH92 AAOOl F
HAH92 AAOO2F
HAJ61 AAOO,lF
HAJ61 AAOO2F
HAJ61 AAOO3F
HAJ61 AAOO4F
HAJ61 AAOOsF
HAJ62 AAOOl F
HAJ62 AAO02F
HAJ62 AAOO3F
HAJ62 AAOO4F
HAJ62 AAOO5F
LOCATION
Drum
Drum
Drum
Drum
Superheater outlet
Superheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
Reheater outlet
OPERATING CONDIT]ONS
ReliefPressure
Flow
(bar eff.)
212
212
212
210
194
194
48.5
50
50
50
48.5
50
(vh)
546.31
546.3
546.31
537.80
121.78
121
220.07
227.54
227.54
227.54
220.07
227.54
trn
227 54
48.5
220.07
50
50
227 54
227.54
LEVEF
(VALVE SPINDLE}
LOADING LEVER
BOLL ER
TORSION BAF
TOFSION BAR
BEARING SHAFT {2)
VALVE
SPINDLE
LOAOING
ROD
TOROUE ADJUSTMENT
FOR'BLOWDOWN'
WORM AND
SPINDLE
TORQUE ADJUSTN,IENT
FOFI 'SET PRESSURE'
<-
)\
loN
i.l.)
\\:;Z
VAI.VE GUIDE
SPUR WHEEL
LOCKING
VALVE
SP IAIDLE
LOCKING PIN
PLATE
VALVE GUiDE
NUT
LOCKING
PLATE
INDICATOR
POINTER
PINION'WHEEL
SPUN'WFIEEL
LOCKING
PIN NUT
VALVE
LIP
t?
{9
DISC SPRING
valve
ruction
valve